Datasheet of Honny Googol 260kW/325kVA Diesel Generator
Guangdong Honny Power tech Co.,ltd Engine Model
PTA780-G1
Engine Application:
Generator set& Pump
Drive
No.2 North Road,Songshan Lake Industrial Park,Donguan, China Tel:
86-769-22780359, Fax: 86-769-22780357Engine control Parts list
CPL:780-4000
Chief Engineer:
Jin ling. Ni
Engine data sheet( No. of Data Sheet )
DS 20140401-PTA780G1Publication Date:
04-01-2014
Generator Model HGM358
Genset Prime Power 260kW/325kVA
Engine Ratings:
Engine Speed (RPM) 1500
Generator set Frequency (Hz) 50
Engine Standby Power (LTP) (kW) 323
Engine Prime Power (PRP) (kW) 295
Engine Continuous Power (COP) (kW) 230
Single Fan Power (kW) 14
Single Fan Consumption (kW) 14
Quantity of Fan (Sets) 1
All Fan Consumption (kW) 14
Engine Net Standby Output (LTP) (kW) 309
Engine Net Prime Output (PRP) (kW) 281Engine Net Continuous Output (COP) (kW) 216
BMEP for Standby Output (bar) 20.20BMEP for Prime Output (bar) 18.40
BMEP for Continuous Output (bar) 14.40Typical Generation Standby Output (kVA) 357.5Typical Generation Standby Output (kW) 286Typical Generation Prime Output (kVA) 325Typical Generation Prime Output (kW) 260
Typical Generation Continuous Output (kVA) 250Typical Generation Continuous Output (kW) 200
Typical Alternator Efficiency ≥ 92.5%Power Factor 0.8
Speed droop (static) elect. Gov. 0-5%
Governing standards to ISO 8528 Parts 1 and 5 G3
Max. step load acceptance, 1st step(% PrimeOutput)
71%
Basic Performance Datasheet
Aspiration Type Turbocharger, air-water after-cooler
Injection Type Direct Injection
Configuration In Line
No. of Cylinders 6
Displacement (liters) 12.8
Bore (mm) 128
Stroke (mm) 166
Compression Ratio 15.5:1
Piston Speed (m/s) 8.30
Rotation Direction (from flywheel) Counter Clockwise
Number of Flywheel Teeth 160
Flywheel House Size SAE1-14
Lubrication System
Lube Oil Specification AFI-CF4
Oil Capacity ( Liters) 40
Max. Permissible Oil Temperature (°C) 110
Low Oil Pressure Warning (kPa) 200
Low Oil Pressure Shutdown (kPa) 160
Oil consumption (as % of fuel consumption) ≤0.5
Cooling System
Coolant Capacity for Engine ( Liters) 18
Max. Permissible Temperature (°C) 90
Max. Coolant Warning Temperature (°C) 95
Max. Coolant Shutdown Temperature (°C) 105
Thermostat Open Temperature (°C) 71
Radiator Cooling Flow (m³/min) 410
Flow of Coolant pump (m³/h) 19.7
Heat dissipation (engine radiator) (kW) 150Heat dissipation (convection) (kW) 22
Radiator Model PSCN1000
Fuel System
Governor Type Electrical Control
Engine Output at generator set prime output (kW) 295Fuel Consumption at 25% of generator set prime
output(l/h) 21.16
Fuel Consumption at 50% of generator set prime
output(l/h) 38.97
Fuel Consumption at 75% of generator set prime
output(l/h) 54.43
Fuel Consumption at 100% of generator set prime
output(l/h) 72.25
Lowest Fuel Consumption Ratio g/kW.hr 204.66
Intake & Exhaust System(On Standby Output)
Combustion Air Consumption (m³/min) 24.24
Max. Intake Restriction (Kpa) 5Max. Exhaust Temperature(Before Turbo) (°C) 625Max. Exhaust Temperature(After Turbo) (°C) 485
Max. Exhaust Back Pressure (Kpa) 5
Exhaust Gas Flow (m³/min) 29.63
Exhaust Flange Diameter (mm) 1*125
Electrical System
Charging Alternator Voltage (V) 28
Charging Alternator Capacity (A) 55
Starting Voltage (V) 24
Starting Motor Capacity (kW) 1*6.6
Minimum Battery Capacity (Ah) 2*150
Minimum Temperature for Unaided Cold Start (℃) 10
Engine Dimension
Length (mm) 1745
Width (mm) 900
Height (mm) 1196
Engine Dry Weight w/o Cooling System (kg) 1025
Note:
1,All engine parameters are in accordance with ISO3046, ISO8528
2,All engine parameters are based on 25°C / 100kPa environment condition
3,No power decrease with below 40ºC environment temperature and 1500 meter altitude
4,More than 40ºCand 1500m above sea level , decrease 2% per 10ºC , and 4% per 300m
5,At calorific value 42700 kJ/kg + 5%, density 0,835 kg/dm3 , temperature 280 K
6,Above data is only the testing data in our laboratory, it can't used to be the data on all contract
Alternator
Alternator model MGA315-260-4SF
Rating Voltage(V) 400/230V,380/220V adjustable
Rating Capacity(KW/KVA) 260/325
Eff.% 95.1%
Power Factor 0.8
Exciting type Brushless self-exciter AVR
Voltage regulation ±1%
No. of Phase 3 phase 4 wire
Enclosure Class IP21
Class of Insulation H
CONTROL MODULE MAIN FEATURES. ( UK DSE)KEY FEATURES• Comprehensive synchronising & loadsharing capabilities• Built-in governor and AVR control• Base load (kW export) functionality• Mains (utility) de-coupling protection• Generator power (kW, kV Ar, kV A & pf) monitoring• Overload (kW & kV Ar) protection• Reverse power (kW & kV Ar) protection• Unbalanced load protection• Independent earth fault protection• Advanced integral PLC editor• 11 Configurable inputs• 8 Configurable outputs
Standard Accessory
Battery 2X150AH 12V
Battery Wires 1 set
Flexible Pipe 1*6 inch
Industry Silencer 1*6 inch
Optional Accessory
VCB Breaker Panel 400A
Fuel Tank 400 Liter
Fuel-water Separator
Heater Coolant & Oil Heater
• Configurable flexible sensor inputs• DSENet® expansion compatibility• User configurable RS232, RS485 and Ethernet communications• Remote SCADA monitoring via various DSE software applications• MODBUS RTU & TCP support• User configurable MODBUS pages• Advanced SMS control and fault messaging (additional GSM modem required)• Easy access diagnostic pages including modem diagnostic pages• Data logging and trending• CAN, MPU and Frequency speed sensing• Tier 4 CAN engine support• “Protections disabled” feature• Front panel editing with PIN protection• Fully configurable using DSE Configuration Suite PC software via USB• 4 Line back-lit LCD text display• LED and LCD alarm indication• Configurable display languages• USB connectivity• Customisable status screens• Five key menu navigation• 3 Configurable maintenance alarms• Multiple date and time run scheduler• Manual fuel pump control• Fuel usage monitor and low fuel level protection• Charge alternator failure protection• Load switching (load shedding and dummy load control)
• Configurable event log (250)• Backed up real time clock
OPTIONAL FEATURE
CHP or CCHP- Complete CHP or CCHP System
FUEL SYSTEM- Fuel Water Separator- Fuel Level Alarming- Auto Fuel Pump SupplyingSystem
HEATER- Coolant Heater- Lube Oil Heater- Alternator Space Heater
SWITCHGEAR- MCCB, VCB Breaker Panel- ATS Panel- Parallel Panel- LV & HV Switchgear
EXHAUST SYSTEM- Exhaust Silencer-Residential- Flexible Pipe- Installation Kits
BATTERY & CHARGER- Starting Battery- 24V /12VDC, 3A, 220V AC Input- 24V /12VDC, 5A, 220V AC Input
VOLTAGE SELECTION- Low Voltage- Middle Voltage- High Voltage
CONTROL SYSTEM- AMF Controller- Sync & Load Sharing Controller- Sync to Grid Controller- Communication Interface &software
CANOPY- Silent Canopy- Weather proof Canopy.- Moving Trailer- Weather and sound proofcontainer.
More View at : http//:honny1992.en.alibaba.com/
http://honnypower.gmc.globalmarket.com/
http://honnydg.en.made-in-china.com/