10
Datasheet of Honny Googol 260kW/325kVA Diesel Generator Guangdong Honny Power tech Co.,ltd Engine Model PTA780-G1 Engine Application: Generator set& Pump Drive No.2 North Road,Songshan Lake Industrial Park,Donguan, China Tel: 86-769-22780359, Fax: 86-769-22780357 Engine control Parts list CPL:780-4000 Chief Engineer: Jin ling. Ni Engine data sheet ( No. of Data Sheet ) DS 20140401-PTA780G1 Publication Date: 04-01-2014 Generator Model HGM358 Genset Prime Power 260kW/325kVA Engine Ratings: Engine Speed RPM1500 Generator set Frequency Hz50 Engine Standby Power (LTP) kW323 Engine Prime Power (PRP) kW295 Engine Continuous Power (COP) kW230 Single Fan Power kW14 Single Fan Consumption kW14 Quantity of Fan Sets1 All Fan Consumption kW14 Engine Net Standby Output (LTP) kW309

Googol pta780 g1 260kw 325kva

Embed Size (px)

Citation preview

Datasheet of Honny Googol 260kW/325kVA Diesel Generator

Guangdong Honny Power tech Co.,ltd Engine Model

PTA780-G1

Engine Application:

Generator set& Pump

Drive

No.2 North Road,Songshan Lake Industrial Park,Donguan, China Tel:

86-769-22780359, Fax: 86-769-22780357Engine control Parts list

CPL:780-4000

Chief Engineer:

Jin ling. Ni

Engine data sheet( No. of Data Sheet )

DS 20140401-PTA780G1Publication Date:

04-01-2014

Generator Model HGM358

Genset Prime Power 260kW/325kVA

Engine Ratings:

Engine Speed (RPM) 1500

Generator set Frequency (Hz) 50

Engine Standby Power (LTP) (kW) 323

Engine Prime Power (PRP) (kW) 295

Engine Continuous Power (COP) (kW) 230

Single Fan Power (kW) 14

Single Fan Consumption (kW) 14

Quantity of Fan (Sets) 1

All Fan Consumption (kW) 14

Engine Net Standby Output (LTP) (kW) 309

Engine Net Prime Output (PRP) (kW) 281Engine Net Continuous Output (COP) (kW) 216

BMEP for Standby Output (bar) 20.20BMEP for Prime Output (bar) 18.40

BMEP for Continuous Output (bar) 14.40Typical Generation Standby Output (kVA) 357.5Typical Generation Standby Output (kW) 286Typical Generation Prime Output (kVA) 325Typical Generation Prime Output (kW) 260

Typical Generation Continuous Output (kVA) 250Typical Generation Continuous Output (kW) 200

Typical Alternator Efficiency ≥ 92.5%Power Factor 0.8

Speed droop (static) elect. Gov. 0-5%

Governing standards to ISO 8528 Parts 1 and 5 G3

Max. step load acceptance, 1st step(% PrimeOutput)

71%

Basic Performance Datasheet

Aspiration Type Turbocharger, air-water after-cooler

Injection Type Direct Injection

Configuration In Line

No. of Cylinders 6

Displacement (liters) 12.8

Bore (mm) 128

Stroke (mm) 166

Compression Ratio 15.5:1

Piston Speed (m/s) 8.30

Rotation Direction (from flywheel) Counter Clockwise

Number of Flywheel Teeth 160

Flywheel House Size SAE1-14

Lubrication System

Lube Oil Specification AFI-CF4

Oil Capacity ( Liters) 40

Max. Permissible Oil Temperature (°C) 110

Low Oil Pressure Warning (kPa) 200

Low Oil Pressure Shutdown (kPa) 160

Oil consumption (as % of fuel consumption) ≤0.5

Cooling System

Coolant Capacity for Engine ( Liters) 18

Max. Permissible Temperature (°C) 90

Max. Coolant Warning Temperature (°C) 95

Max. Coolant Shutdown Temperature (°C) 105

Thermostat Open Temperature (°C) 71

Radiator Cooling Flow (m³/min) 410

Flow of Coolant pump (m³/h) 19.7

Heat dissipation (engine radiator) (kW) 150Heat dissipation (convection) (kW) 22

Radiator Model PSCN1000

Fuel System

Governor Type Electrical Control

Engine Output at generator set prime output (kW) 295Fuel Consumption at 25% of generator set prime

output(l/h) 21.16

Fuel Consumption at 50% of generator set prime

output(l/h) 38.97

Fuel Consumption at 75% of generator set prime

output(l/h) 54.43

Fuel Consumption at 100% of generator set prime

output(l/h) 72.25

Lowest Fuel Consumption Ratio g/kW.hr 204.66

Intake & Exhaust System(On Standby Output)

Combustion Air Consumption (m³/min) 24.24

Max. Intake Restriction (Kpa) 5Max. Exhaust Temperature(Before Turbo) (°C) 625Max. Exhaust Temperature(After Turbo) (°C) 485

Max. Exhaust Back Pressure (Kpa) 5

Exhaust Gas Flow (m³/min) 29.63

Exhaust Flange Diameter (mm) 1*125

Electrical System

Charging Alternator Voltage (V) 28

Charging Alternator Capacity (A) 55

Starting Voltage (V) 24

Starting Motor Capacity (kW) 1*6.6

Minimum Battery Capacity (Ah) 2*150

Minimum Temperature for Unaided Cold Start (℃) 10

Engine Dimension

Length (mm) 1745

Width (mm) 900

Height (mm) 1196

Engine Dry Weight w/o Cooling System (kg) 1025

Note:

1,All engine parameters are in accordance with ISO3046, ISO8528

2,All engine parameters are based on 25°C / 100kPa environment condition

3,No power decrease with below 40ºC environment temperature and 1500 meter altitude

4,More than 40ºCand 1500m above sea level , decrease 2% per 10ºC , and 4% per 300m

5,At calorific value 42700 kJ/kg + 5%, density 0,835 kg/dm3 , temperature 280 K

6,Above data is only the testing data in our laboratory, it can't used to be the data on all contract

Alternator

Alternator model MGA315-260-4SF

Rating Voltage(V) 400/230V,380/220V adjustable

Rating Capacity(KW/KVA) 260/325

Eff.% 95.1%

Power Factor 0.8

Exciting type Brushless self-exciter AVR

Voltage regulation ±1%

No. of Phase 3 phase 4 wire

Enclosure Class IP21

Class of Insulation H

CONTROL MODULE MAIN FEATURES. ( UK DSE)KEY FEATURES• Comprehensive synchronising & loadsharing capabilities• Built-in governor and AVR control• Base load (kW export) functionality• Mains (utility) de-coupling protection• Generator power (kW, kV Ar, kV A & pf) monitoring• Overload (kW & kV Ar) protection• Reverse power (kW & kV Ar) protection• Unbalanced load protection• Independent earth fault protection• Advanced integral PLC editor• 11 Configurable inputs• 8 Configurable outputs

Standard Accessory

Battery 2X150AH 12V

Battery Wires 1 set

Flexible Pipe 1*6 inch

Industry Silencer 1*6 inch

Optional Accessory

VCB Breaker Panel 400A

Fuel Tank 400 Liter

Fuel-water Separator

Heater Coolant & Oil Heater

• Configurable flexible sensor inputs• DSENet® expansion compatibility• User configurable RS232, RS485 and Ethernet communications• Remote SCADA monitoring via various DSE software applications• MODBUS RTU & TCP support• User configurable MODBUS pages• Advanced SMS control and fault messaging (additional GSM modem required)• Easy access diagnostic pages including modem diagnostic pages• Data logging and trending• CAN, MPU and Frequency speed sensing• Tier 4 CAN engine support• “Protections disabled” feature• Front panel editing with PIN protection• Fully configurable using DSE Configuration Suite PC software via USB• 4 Line back-lit LCD text display• LED and LCD alarm indication• Configurable display languages• USB connectivity• Customisable status screens• Five key menu navigation• 3 Configurable maintenance alarms• Multiple date and time run scheduler• Manual fuel pump control• Fuel usage monitor and low fuel level protection• Charge alternator failure protection• Load switching (load shedding and dummy load control)

• Configurable event log (250)• Backed up real time clock

OPTIONAL FEATURE

CHP or CCHP- Complete CHP or CCHP System

FUEL SYSTEM- Fuel Water Separator- Fuel Level Alarming- Auto Fuel Pump SupplyingSystem

HEATER- Coolant Heater- Lube Oil Heater- Alternator Space Heater

SWITCHGEAR- MCCB, VCB Breaker Panel- ATS Panel- Parallel Panel- LV & HV Switchgear

EXHAUST SYSTEM- Exhaust Silencer-Residential- Flexible Pipe- Installation Kits

BATTERY & CHARGER- Starting Battery- 24V /12VDC, 3A, 220V AC Input- 24V /12VDC, 5A, 220V AC Input

VOLTAGE SELECTION- Low Voltage- Middle Voltage- High Voltage

CONTROL SYSTEM- AMF Controller- Sync & Load Sharing Controller- Sync to Grid Controller- Communication Interface &software

CANOPY- Silent Canopy- Weather proof Canopy.- Moving Trailer- Weather and sound proofcontainer.

More View at : http//:honny1992.en.alibaba.com/

http://honnypower.gmc.globalmarket.com/

http://honnydg.en.made-in-china.com/