32
1 | Technical Seminar | HVACR Indonesia | October 2014 Electronics Controller

05 controller erc & ak rc 10x optyma controller

Embed Size (px)

Citation preview

1 | Technical Seminar | HVACR Indonesia | October 2014

Electronics Controller

2 | Technical Seminar | HVACR Indonesia | October 2014

Controller

3 | Technical Seminar | HVACR Indonesia | October 2014

Cold room Control – Single & Three Phase

Cold Room control can Be donein a number of ways from simple Mechanical Thermostat to high end Electronic controls.

Danfoss offers all of the above,But today we will focus on theElectronic Controls for Single andThree Phase systems.

4 | Technical Seminar | HVACR Indonesia | October 2014

ERC 21x

5 | Technical Seminar | HVACR Indonesia | October 2014

ERC 21x Project Scope

• Introduce a new low-mid end product range to gain market share in the Commercial Refrigeration segment with focus on the following applications:

5│

• Replacing existing EKC102 with a product range having additional features, an

improved usability and more competitive price level

6 | Technical Seminar | HVACR Indonesia | October 2014

Single Phase Solution for Medium & Low Temperature Applications – ERC 21x

Type Description S-PackCode no.

ERC 211 Red LED, 230 V, 1 relay, 1 sensor 080G3263

ERC 213 Red LED, 230 V, 3 relay, 2 sensors 080G3265

A7 Booklet

6 languages(EN, RU, PL, ES, PT, FR)

NTC Sensor10kOhm at 25°C

1,5m cable

ERC 21X

&

Mounting Clip

Kit placed in existing box

Box with

accessory

7 | Technical Seminar | HVACR Indonesia | October 2014

Display Icon and Button Description

Press and hold: Factory reset

Press once : BackPress & hold : Pull down

Press once : Temp set point/OKPress & hold : Menu

Press once : UPPress & hold : ON/OFF

Press once : DOWNPress & hold : Defrost

8 | Technical Seminar | HVACR Indonesia | October 2014

Display Icon

9 | Technical Seminar | HVACR Indonesia | October 2014

Technical SpecificationsPower Supply

Input

UL60730 EN60730

DO1 (Compressor relay)120 V a.c.: 16 A resistive/FLA16/LRA72240 V a.c.: 10 A resistive/FLA10/LRA60

16 (16) A

DO2 (Defrost/Alarm) 8A resistive, FLA 2 / LRA 12 2 (2) ADO3 (Fan) 3A resistive, FLA 2 / LRA 12 2 (2) ADO4 (Light / Alarm) 2A 2A

Probes

Connectors

Mounting

Display

Keypad

Operating Conditions

Storage conditions

Range of Measurement

Protection

Envirnomental

Resistance to heat & fire Category D (UL94-V0)

Output

4 buttons (integrated IP65 design), user programmable

-10°C to 55°C

-40°C to 105°C, 93% RH

-40°C to 70°C

Front: IP65, Rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00

Pollution degree II, non-condensing

LED display, 3 digit, decimal point and multi functionality icons; °C/°F scale

115VAC/230VAC 50-60Hz Galvanic isolated low voltage regulated power supply.

4 inputs: 2 analogue, 1 analogue/digital, 1 digital

Compatable with below SensorsNTC 5000 ohm @ 25 °CNTC 10000 ohm @ 25 °CPTC (990 ohm @ 25°C)Pt 1000 (1000 ohm @ 0 °C)

Screw terminal connetors for both input and output connections.

Rear mounting (Insert the controller from front and lock with clips from rear)

10 | Technical Seminar | HVACR Indonesia | October 2014

Easy Menu Structure

- The parameters are structured in

groupswhich makes finding the right

parameter a lot faster.

- We introduced quick installation and

service menus to make installation

and service faster.

- Alphanumeric codes for easy

recognizability

11 | Technical Seminar | HVACR Indonesia | October 2014

Patented

Largest Display in Product ClassERC 21x has a display size of 29X17 cm which is largest among our competitors

Support widest range of sensorsNone of the main competitors support 4 types of Sensors. This gives ERC 21x maximum flexibility in replacement sales

No compromise on accuracy with deviation of+/- 0.5K Between -35 to +25˚C+/- 1K Between -40 to -35˚C +/- 1K Between +25 to 105˚C

Flat Front Design Most of our competitors do not have Flat front Design with clear feedback on button click and no grooves around buttons, which makes it easy to clean and also avoid filth

EU Design

Registration

Longest LifeWith Zero Cross Technology on all relays, ERC 21x’s life increases up to 33% (2 years) longer as compared to competitors

ReliabilityNone of the main competitors protects the compressor by monitoring:- the power supply voltage level- the condenser temperature with 2

levels of alarms

Application Based setupERC 21x has pre configured applications making setup quick and easy

Single Phase Solution for Medium & Low Temperature Applications – ERC 21x

12 | Technical Seminar | HVACR Indonesia | October 2014

AK-RC 101/103Optyma Controller

13 | Technical Seminar | HVACR Indonesia | October 2014

14 | Technical Seminar | HVACR Indonesia | October 2014

AK-RC 101/103 OPTYMA Controller

Single-phase

Three-phase

Three-phase

15 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – single-phase

Transparent cover allows access to the protections

(IP65 rating)

Innovative design

.

.

Circuit breaker accessible from the front panel,

which cuts the general power supply

Control for complete management of refrigeration systems with single-phase compressor up to 1,5 kW (2 HP) and defrost heaters 3 KW

16 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – single-phase

.

Electronic control with wide LED display and easy to use

buttons

Easy installation and opening with new hinged cover

17 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – single-phase

.

..

.

Easy wiring on the internal terminal block with voltage

(230V) outputs

Protection cover for the controller PCB

Sticker for connectionLarge internal space

18 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – three-phase

.

Adjustable motor circuit breaker for compressor protection

accessible from the front panel

Magnetothermic circuit breaker for auxiliary circuits

..

Magnetothermic circuit breaker accessible from the front panel,which cuts the general power

supply

Three-phase systems series for 5,5 kW (7,5HP):Total control of three-phase refrigeration plant up to 5.5 kW, static or ventilated, with off-cycle or electrical defrosting.

• 11 to 16A• 14 to 20A

Three-phase systems series for 3 kW (4 HP):Total control of three-phase refrigeration plant up to 3 kW, static or ventilated, with off-cycle or electrical defrosting.

• 4,5 to 6,3A• 7 to 10A

19 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – three-phase

Contactors for:• Compressor• Defrost• Fan• Light

20 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – spare parts NTC sensor

EKS 221 NTC sensor 3,5m

code no. : 084N3210

IP 67

Tolerance 1%

Ohmic check : 10Kohm / 25 °C

e

EKS 211 NTC sensor 3,5m

code no. : 084B4404

IP 67

Tolerance 1%

Ohmic check : 5Kohm / 25 °C

WARNING !! EKS 211 for EKC 102,202 can not be used !!

21 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – programming

Level 1 – Programming (User Level)To gain access to the Level 1 configuration menu proceed as follows:

1.Press the UP (▲) and DOWN (▼) keys simultaneous and keep them pressed for a few seconds until the first program variable appears on the display.

2.Release the UP (▲) and DOWN (▼) keys.

3.Select the variable to be modified using the UP (▲) and DOWN (▼) keys.

4.When the variable has been selected it is possible to:•display the settings by pressing the SET key •modify the setting by pressing the SET key together with the UP (▲) and DOWN (▼) keys.

When configuration values have been set, you can exit the menu by pressing the UP (▲) and DOWN (▼) keys simultaneous for a few seconds until the cold room temperature appears.

5.The new settings are saved automatically when you exit the configuration menu.

22 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – programming

23 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – programming

Level 2 – Programming (Installer Level)To access to the second level press the UP (▲) and DOWN (▼) keys and the LIGHT key simultaneous for a few seconds.

When the first programming variable appears thesystem automatically goes to stand-by.

1.Select the variable to be modified by pressing the UP (▲) and DOWN (▼) keys. When the parameter has been selected it is possible to:

2.View the setting by pressing the SET key.

3.Modify the setting by holding the SET key down and press the UP (▲) and DOWN (▼) keys.

4.When configuration settings have been completed you can exit the menu by pressing the UP (▲) and DOWN (▼) keys simultaneous and keeping them pressed until the room temperature reappears.

5.Changes are saved automatically when you exit the configuration menu.

6.Press the STAND-BY key to enable electronic control.

24 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – programming

25 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – programming

26 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – trouble shooting

27 | Technical Seminar | HVACR Indonesia | October 2014

28 | Technical Seminar | HVACR Indonesia | October 2014

29 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control – programming

30 | Technical Seminar | HVACR Indonesia | October 2014

OPTYMA Control on test application

This nice photo of a test application with OPTYMA Controller and OPTYMA PLUS Condensing unit

This also Clearly shows the OPTYMA controller and Condensing are a Perfect match…!

31 | Technical Seminar | HVACR Indonesia | October 2014

Smart Store Product Portfolio

3rd Party HVAC, Light, Controllers

Evaporator Control

Customized SolutionsBasic Control

Pack Control HVAC, Light, Aux. Control

System Manager StoreViewDesktop

SiteService App Remote Management Tool

Web Browser

Basic

High-End

OPTYMA Controller Mid-RangeHFC

High EndHFC/CO2

I/O ModulesHumidity Sensor

Light Sensor

Energy MeterGas Sensor

Sto

re L

evel

Sto

re L

evel

Chain

Level

Chain

Level

Applic

ation L

evel

Applic

ation L

evel

Act

uato

r/se

nso

rAct

uato

r/se

nso

r

Enterprise ManagerDanfoss Electronically Delivered Services

CO2 Valves

Aux. Components

TXV EEV Sensors Drives

Heat Exchangers

Open XML interface for 3rd party integration

Balancing Valves Condensing Units

Compressors

32 | Technical Seminar | HVACR Indonesia | October 2014

Thank you