MEMORIA DE CLCULO ESTRUCTURAL
MEMORIA DE CLCULO ESTRUCTURAL
TIPOLOGIA DEL PROYECTO: CASETA DE VIGILANCIA
UBICACIN: PONIENTE 140, #720, COL. INDUSTRIAL VALLEJO
PROPIETARIO: CONDUMEX
FECHA DE CALCULO: 17 AGOSTO DE 2009.ANTECEDENTES
DESCRIPCION DE LA ESTRUCTURA
ESTRUCTURA EN 2 NIVELES, DISEADA EN BASE A UN PROYECTO ARQUITECTNICO CUYA PLANTA ES UN OCTAGONO CON EL SIGUIENTE SISTEMA CONSTRUCTIVO:
CIMENTACION: A BASE DE ZAPATA DE CONCRETO ARMADO, UNIDAS
POR UNA CONTRATRABE DE DE CONCRETO ARMADO.
F`C = 200Kg /cm2
MUROS: A BASE DE CONCRETO ARMADO TERMINADO APARENTE F`C = 200Kg / cm2
LOSA:DE ENTREPISO Y AZOTEA DE CONCRETOARMADO F`C=200Kg. /cm2
DIAGRAMA DE CUERPO LIBRE
ANALISIS DE CARGAS
AZOTEA
Teja de ladrillo 108 Kg./m2
Concreto 240 Kg./m2
Aplanado 45Kg/m2
_________
Carga muerta 393 Kg./m2
Carga viva 100 Kg./m2
_________
493 Kg./m2
= 493 Kg./m2 ( 1.4 ) Factor de Seguridad para diseo al Limite
= 690.20 Kg./m2
ENTREPISO
Loseta 120 Kg./m2
Concreto 240 Kg./m2
Apl. yeso 45 Kg./m2
__________
405 Kg./m2
= 405 Kg./m2 ( 1.4 ) FSDL
= 567 Kg./m2
MUROS
Concreto 0.20 X 1 X 1 X 1500 Kg. /cm2 = 300 Kg./m2
Aplanado resane 0.05 X 1 X 1 X 1900 = 190 Kg./m2
__________
Carga de diseo 490 Kg./cm2
DISTRIBUCION DE CARGAS
Tableros 1, 2, 3, 4, 5, 6, 7, 8
Son losas triangulares distribuyen la carga a la base del triangulo
CARGAS TRIBUTARIAS
Tomamos la Losa de Azotea por ser la ms desfavorable
AT = 1.24 X 1.50 = 0.93
W Diseo = 493 Kg./cm2
L = 1.24
B = 1.50
W Losa = AT . WD = 0.93 ( 493 Kg./cm2) = 369.75 Kg./cm2
2 1.24
CONSTANTES DE DISEO PLASTICO
F`C=300 KG/CM2
FY=4000 KG/CM2
F*C=0.80F`C = 0.80X300=240 KG/CM2
FC=0.85 F*C = 204 KG/CM2
P = 0.75FC/FY= 0.18
Q =P FY/FC =0.35
KU=Q FC 1-Q/2 FR =52.69
RU = FR FY 1-Q/2 =1650
CALCULO DE LA VIGA CIMENTACION
EJE A DE 1-2
2.910 Kg. / m
1.24
1.-Wv = 2910 Kg./m X Fsv = 1.7 = 4, 947 W TOTAL = 6,347 Kg./ cm2
Wm = 1000 Kg./m X Fsm = 1.4 = 1,400
F`C = 200 Kg./ cm2 Fy = 4000
2 Calculo del M. Max.
M. Max = WL 2 = 6347 ( 1.24 ) 2 = 6347 ( 1.53 ) = 1,213.86 Kg./cm2
8 8 8
Relacin base peralte d = 1.8 b
3 Calculamos el Area de Acero, proponemos un % = 0.01
W = fy = 0.01 (4000) = 0.20 cm2
F`c 200
4 Calculo del Momento Nomina del Concreto
Mnc = f`c w bd2 (1- 0.59 w) f `c wd d2 (1- 0.59 w)
= f `c wd3 (1- 0.59 w) Mnc (1.8) = f `c wd3 (1- 0.59)
1.8
Mnc (1.8) = f`c w (1-0.59)
d3
d 3 = f `c w ( 1- 0.59 ) =
Mnc (1.8)
d= 3 f `c w ( 1 0.59)
Mnc (1.8)
Sustituyendod = 3
f`c w ( 1- 0.59) Mnc (1.8)
d = 3
3
3
200 ( 6347) (0.41) = 520.454 = 0.23819947 = 0.69
1213.86 (1.8) 3,184.948
d = 0.69
b = d = 0.38
1.8
As Min = 0.7 F`C b d = 0.7 200 ( 0.69) (0.38) = 0.7 54.44 = 0.7 0.013
Fy
4000
4000
= 0.7 (0.11) = 0.08 cm2
4 VAR. = 4 (2.0) = 8 cm2
0.70
As = 1 cm2
0.40
Planta de Cimentacin
R t = 5 ton/m
eje
0.400.40
0.30
40
_______4 VAR
Est. 3/8 ______
VAR @ 15 cm
50
70
20
2040
20
80
ARMADO DE MUROS
VAR 3/8 @ 20 CMS
15 CMS
VAR 3/8
@20cms
En ambasVAR 3/8 @ 20cms
Caras
perfil
Alzado
VAR 3/8 @ 20cms
BAJADA DE CARGAS A CIMENTACIONTramo Azotea entrepiso plata baja aumento carga o cimentacin Losa muro losa muro muro peso 15%
Eje A 493 490 567 490 490 2,530 379.50 2,909.50 Kg./m
De 1-2
ARMADO DE LOSA
var 3/8 @ 15 cms
En ambos sentidos
ESPECIFICACIONES CONSTRUCTIVAS
Todos los elementos estructurales fueron diseados segn los siguientes coeficientes
Concreto F`C = 200 Kg./cm2
Acero F Y = 4000 Kg./cm2
Grava triturada
Agregado mximo = 10 mm en muros
20 mm en zapatas
Arena azul - grano grueso 10 en el tamiz
Revenimiento del concreto 14 cm.
Traslopes claro 1.24 = 0.31 cm.
4
Checar nivelacin de cimbra
Checar vibrado de concreto al momento del colado
Se recomienda cimbra en tableros de 1.22 X 2.44 de triplay de madera de pino de espesor, tensados con moos y cuas de acero
Checar detalles constructivos
Checar armado antes de colado