MEMORIA DE CÁLCULO ESTRUCTURAL TIPOLOGIA DEL PROYECTO: CASETA DE VIGILANCIA UBICACIÓN: PONIENTE 140, #720, COL. INDUSTRIAL VALLEJO PROPIETARIO: CONDUMEX FECHA DE CALCULO: 17 AGOSTO DE 2009. ANTECEDENTES DESCRIPCION DE LA ESTRUCTURA ESTRUCTURA EN 2 NIVELES, DISEÑADA EN BASE A UN PROYECTO ARQUITECTÓNICO CUYA PLANTA ES UN OCTAGONO CON EL SIGUIENTE SISTEMA CONSTRUCTIVO: CIMENTACION: A BASE DE ZAPATA DE CONCRETO ARMADO, UNIDAS POR UNA CONTRATRABE DE DE CONCRETO ARMADO. F`C = 200Kg /cm2 MUROS: A BASE DE CONCRETO ARMADO TERMINADO APARENTE F`C = 200Kg / cm2 LOSA:DE ENTREPISO Y AZOTEA DE CONCRETOARMADO F`C=200Kg. /cm2 DIAGRAMA DE CUERPO LIBRE

09 Condu MemoriaCalculo CasetaVigilancia

Embed Size (px)

Citation preview

MEMORIA DE CLCULO ESTRUCTURAL

MEMORIA DE CLCULO ESTRUCTURAL

TIPOLOGIA DEL PROYECTO: CASETA DE VIGILANCIA

UBICACIN: PONIENTE 140, #720, COL. INDUSTRIAL VALLEJO

PROPIETARIO: CONDUMEX

FECHA DE CALCULO: 17 AGOSTO DE 2009.ANTECEDENTES

DESCRIPCION DE LA ESTRUCTURA

ESTRUCTURA EN 2 NIVELES, DISEADA EN BASE A UN PROYECTO ARQUITECTNICO CUYA PLANTA ES UN OCTAGONO CON EL SIGUIENTE SISTEMA CONSTRUCTIVO:

CIMENTACION: A BASE DE ZAPATA DE CONCRETO ARMADO, UNIDAS

POR UNA CONTRATRABE DE DE CONCRETO ARMADO.

F`C = 200Kg /cm2

MUROS: A BASE DE CONCRETO ARMADO TERMINADO APARENTE F`C = 200Kg / cm2

LOSA:DE ENTREPISO Y AZOTEA DE CONCRETOARMADO F`C=200Kg. /cm2

DIAGRAMA DE CUERPO LIBRE

ANALISIS DE CARGAS

AZOTEA

Teja de ladrillo 108 Kg./m2

Concreto 240 Kg./m2

Aplanado 45Kg/m2

_________

Carga muerta 393 Kg./m2

Carga viva 100 Kg./m2

_________

493 Kg./m2

= 493 Kg./m2 ( 1.4 ) Factor de Seguridad para diseo al Limite

= 690.20 Kg./m2

ENTREPISO

Loseta 120 Kg./m2

Concreto 240 Kg./m2

Apl. yeso 45 Kg./m2

__________

405 Kg./m2

= 405 Kg./m2 ( 1.4 ) FSDL

= 567 Kg./m2

MUROS

Concreto 0.20 X 1 X 1 X 1500 Kg. /cm2 = 300 Kg./m2

Aplanado resane 0.05 X 1 X 1 X 1900 = 190 Kg./m2

__________

Carga de diseo 490 Kg./cm2

DISTRIBUCION DE CARGAS

Tableros 1, 2, 3, 4, 5, 6, 7, 8

Son losas triangulares distribuyen la carga a la base del triangulo

CARGAS TRIBUTARIAS

Tomamos la Losa de Azotea por ser la ms desfavorable

AT = 1.24 X 1.50 = 0.93

W Diseo = 493 Kg./cm2

L = 1.24

B = 1.50

W Losa = AT . WD = 0.93 ( 493 Kg./cm2) = 369.75 Kg./cm2

2 1.24

CONSTANTES DE DISEO PLASTICO

F`C=300 KG/CM2

FY=4000 KG/CM2

F*C=0.80F`C = 0.80X300=240 KG/CM2

FC=0.85 F*C = 204 KG/CM2

P = 0.75FC/FY= 0.18

Q =P FY/FC =0.35

KU=Q FC 1-Q/2 FR =52.69

RU = FR FY 1-Q/2 =1650

CALCULO DE LA VIGA CIMENTACION

EJE A DE 1-2

2.910 Kg. / m

1.24

1.-Wv = 2910 Kg./m X Fsv = 1.7 = 4, 947 W TOTAL = 6,347 Kg./ cm2

Wm = 1000 Kg./m X Fsm = 1.4 = 1,400

F`C = 200 Kg./ cm2 Fy = 4000

2 Calculo del M. Max.

M. Max = WL 2 = 6347 ( 1.24 ) 2 = 6347 ( 1.53 ) = 1,213.86 Kg./cm2

8 8 8

Relacin base peralte d = 1.8 b

3 Calculamos el Area de Acero, proponemos un % = 0.01

W = fy = 0.01 (4000) = 0.20 cm2

F`c 200

4 Calculo del Momento Nomina del Concreto

Mnc = f`c w bd2 (1- 0.59 w) f `c wd d2 (1- 0.59 w)

= f `c wd3 (1- 0.59 w) Mnc (1.8) = f `c wd3 (1- 0.59)

1.8

Mnc (1.8) = f`c w (1-0.59)

d3

d 3 = f `c w ( 1- 0.59 ) =

Mnc (1.8)

d= 3 f `c w ( 1 0.59)

Mnc (1.8)

Sustituyendod = 3

f`c w ( 1- 0.59) Mnc (1.8)

d = 3

3

3

200 ( 6347) (0.41) = 520.454 = 0.23819947 = 0.69

1213.86 (1.8) 3,184.948

d = 0.69

b = d = 0.38

1.8

As Min = 0.7 F`C b d = 0.7 200 ( 0.69) (0.38) = 0.7 54.44 = 0.7 0.013

Fy

4000

4000

= 0.7 (0.11) = 0.08 cm2

4 VAR. = 4 (2.0) = 8 cm2

0.70

As = 1 cm2

0.40

Planta de Cimentacin

R t = 5 ton/m

eje

0.400.40

0.30

40

_______4 VAR

Est. 3/8 ______

VAR @ 15 cm

50

70

20

2040

20

80

ARMADO DE MUROS

VAR 3/8 @ 20 CMS

15 CMS

VAR 3/8

@20cms

En ambasVAR 3/8 @ 20cms

Caras

perfil

Alzado

VAR 3/8 @ 20cms

BAJADA DE CARGAS A CIMENTACIONTramo Azotea entrepiso plata baja aumento carga o cimentacin Losa muro losa muro muro peso 15%

Eje A 493 490 567 490 490 2,530 379.50 2,909.50 Kg./m

De 1-2

ARMADO DE LOSA

var 3/8 @ 15 cms

En ambos sentidos

ESPECIFICACIONES CONSTRUCTIVAS

Todos los elementos estructurales fueron diseados segn los siguientes coeficientes

Concreto F`C = 200 Kg./cm2

Acero F Y = 4000 Kg./cm2

Grava triturada

Agregado mximo = 10 mm en muros

20 mm en zapatas

Arena azul - grano grueso 10 en el tamiz

Revenimiento del concreto 14 cm.

Traslopes claro 1.24 = 0.31 cm.

4

Checar nivelacin de cimbra

Checar vibrado de concreto al momento del colado

Se recomienda cimbra en tableros de 1.22 X 2.44 de triplay de madera de pino de espesor, tensados con moos y cuas de acero

Checar detalles constructivos

Checar armado antes de colado