Upload
sisproint
View
84
Download
7
Embed Size (px)
DESCRIPTION
manual tvss
Citation preview
Commercial in Confidence Document: 36 TD PV140 Range.pub Version: 2.11 14/04/2011 Copyright 2010 LPI 1
LPI® Photovoltaic Shunt Protector - PV140
Product Description The LPI PV140 is a surge protection device rated for 40kA 8/20μs single shot surge capacity (Imax). The unit is designed for protection of positive and negative busbars of photovoltaic systems against the surge effects according to EN 61643-11 and IEC 61643-1. It is also designed for easy mounting on standard 35mm DIN rail. The unit comes with fast, responsive Metal Oxide Varistors (MOV) to provide effective surge protection with low let-through voltage to protect sensitive electronics and electrical circuits. The PV140 is fitted with thermal disconnects which will respond should the varistors be overloaded. In this case, the indicator changes status to red, and alarm contacts change over. The unit comes as a two part item. The base is hardwired into the circuit to be protected, and the protection module is plugged into this
base. This enables easy replacement of protection modules should they be degraded or damaged by excessive transient activity.
Features
• High performance surge protector • Nominal impulse discharge current 40kA, 8/20µs / Single Mode • 35mm DIN rail mount
Ordering Code PV140-60 PV140-240 PV140-400
Application: Single Mode Protector, 40kA 8/20µs
Surge Rating Imax: 40kA 8/20µs single shot surge capacity
Nominal discharge In: 15kA
Max. Continuous Operating Volt-age, Uc:
200V 600V 1000V
Let through voltage at In <950V <2.5kV <3.5kV
Response time, tA: <25ns <25ns <25ns
Protection Status Indication: Green/Red display showing operational condition
Dimensions: 18(W) x 90(L) x 63(H) mm
Mounting: Standard 35 mm – DIN43880 Din rail
Weight: Approx. 100 grams
IP rating: IP 20
Colour: Blue
Conductor size: 25mm² (Max)
Operating temperatures: -40 to +80°C, 0 – 95% humidity
Standards: IEC 61643-1
Application: Positive and Negative Busbar of Photovoltaic System
Configuration: Hardwired base and pluggable module with built-in changeover alarm contacts.
Warranty: 5 Years
20kA
Commercial in Confidence Document: 36 TD PV140 Range.pub Version: 2.11 14/04/2011 Copyright 2010 LPI 2
A set of voltage-free contacts integral to each of the PV140 protection mod-ules provides the facility to monitor the protection status. With the protec-tion module fully operational, the status indicator will be green and terminals 1 & 2 on the remote monitoring terminals will be connected. When the PV140 protection module MOV material degrades to a point where replace-ment is necessary, the status indicator will change to red and the voltage free contacts will change state so that terminals 2 & 3 are connected (see Figure 2)
Installation:
Remote Status Indication
1. Fix the PV140 modules onto the DIN rail.
2. Connect the positive terminal to one side and the negative to the other side.
3. Series connect the normally closed alarm contacts (1 and 2) for remote monitoring.
4. The PV140 is a pluggable module and the pluggable unit can be replaced (when the indicator turns red`) without disconnecting the power supply.
5. Modules marked with an asterisk in Figure 1. are only necessary if neither the +ve or the –ve wires are locally grounded.
Figure 2. Remote Status Monitoring voltage-free contacts on protection module
PV140 in IP66 enclosure:
Figure 3. Connection for IP66 Version
The PV140 is also available in an IP66 enclosure for outdoor applications. For applications where either positive or negative is grounded at both supply end and equipment end, the connections as per figure 3 can be used.
Model Dimension
1XPV140-60-IP66 171x121x80mm
1XPV140-60-IP66-MKII
171x121x80mm
Cable
10-14mmΦ Gland, one on each side
10-14mmΦ Gland, two on each side