  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    1/43

    ABB Medium Vol tage Distr ibution Components Pinetops, NC

    ABB Field Engineering Services-

    ABB GroupJune 21, 2012 | Slide 1

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    2/43

    Field Engineering Services

    ABB GroupJune 21, 2012 | Slide 2

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    3/43

    Field Engineering Services (cont.d)

    Install new units all

    sizes, all manufacturers

    Contract services

    Remove, relocate,

    units

    Retro-fit units with new

    Oil processing, oil

    dryout

    ABB GroupJune 21, 2012 | Slide 3

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    4/43

    Field Engineering Services (cont.d)

    On-site testing of Instrument

    transformers Provide training for

    maintenance and/oroperation

    coolers and pumps GEA/R&G

    Installation of transformermonitoring equipment DRMonitoring and control

    Installation of transformerprotector equipment TPCCorporation

    ABB GroupJune 21, 2012 | Slide 4

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    5/43

    On-site test capability - -

    ABB GroupJune 21, 2012 | Slide 5

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    6/43

    Generation/Transmission needs for instrument

    market

    More powerw ee ng power nee s

    Control of supply chainresources

    Requires reliable powerdelivery

    ABB GroupJune 21, 2012 | Slide 6

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    7/43

    Generation/Transmission needs for ITs (cont.d)

    GENCO to TRANSCO

    separation

    ISO activity requiresmetering

    Bottom-line focused

    Billing and current swings

    Must verify performance

    of ITs

    ABB GroupJune 21, 2012 | Slide 7

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    8/43

    On-site accuracy testing of ITs

    -

    Excitation characteristics verification

    Done on-line/no outa e

    Revenue metering (Voltage Injection) testing

    Brief outage

    Traceable to NIST (Revenue Billing)

    Each CT given RCF and PA data

    Voltage and current comparator testing

    Brief outage

    BCTs and also voltage transformers (VTs) up to 34.5 kV

    ABB GroupJune 21, 2012 | Slide 8

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    9/43

    On-site accuracy testing of ITs (cont.d)

    applications

    Bushing currentrans ormers s n

    power transformers

    BCTs in dead tank circuitrea ers

    Free standing currenttransformers (CTs)

    Specialized testing for CT

    continuous currentcapability

    VTs up to 34.5 kV

    ABB GroupJune 21, 2012 | Slide 9

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    10/43

    FES In-service CT testing

    -testing

    On-line evaluation of bushing

    generator current transformers(GCTs)

    CT excitation performance

    General CT accuracy verification CT and load problems identified

    Testin of GCTs without outa e

    Results oriented testing

    CT health and performance

    Wiring verification

    ABB GroupJune 21, 2012 | Slide 10

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    11/43

    FES In-service CT testing (cont.d)

    Secondary access only energized primary

    Variable resistance type of test

    Access needed to shorting block to replace CT burden -

    CT secondary V and I readings at each burden

    ABB GroupJune 21, 2012 | Slide 11

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    12/43

    FES In-service CT testing (cont.d)

    600

    700

    800

    900

    1000

    Voltage,

    V

    500

    600

    700

    800

    900

    1000

    lVoltage,

    V

    0

    100

    200

    300

    400

    Terminal

    0

    100

    200

    300

    400

    Termina

    Excitation curve generated for each unit tested

    0 0.2 0.4 0.6 0.8 1

    Secondary Exciting Current, A

    0 0.2 0.4 0.6 0.8 1

    Secondary Current, A

    Excitation current defined as reduction in secondarycurrent

    ABB GroupJune 21, 2012 | Slide 12

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    13/43

    Current transformer modes of failure

    600

    800

    al

    Voltage,

    V

    AB

    0

    200

    400

    Termi C

    D

    Design model of correct current transformer curve

    . . . .

    Secondary Excit ing Current, A

    Current transformer with turn to turn fault

    CT core lamination insulation failure/cores with mechanicale orma on.

    (If return points match Curve A the core was magnetized).

    Current transformer with windin or secondar wirin

    ABB GroupJune 21, 2012 | Slide 13

    insulation failure

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    14/43

    FES In-service CT testing (cont.d)

    Burden injection

    Done while CT is in service under normal o eration

    Secondary current and voltage from the CT is recordedwith burden changes up to saturation

    xc a on curren er ve rom e curren ec ne a eacburden) and plotted versus voltage

    Individual excitation curve developed for each CT tested

    Curve data identifies CT performance

    ABB GroupJune 21, 2012 | Slide 14

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    15/43

    Revenue metering (voltage injection) testing

    Off-line test

    Short outage for testing

    CT remains installed

    RCF and PA metering certification

    CT fundamental design parameters

    On site measurements

    Instrumentation traceable to NIST

    Metering data extracted from actual readings

    ABB GroupJune 21, 2012 | Slide 15

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    16/43

    Metering opportunities

    inside major electrical

    equipment can potentially

    capability.

    ABB GroupJune 21, 2012 | Slide 16

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    17/43

    Standard IEEE C57.13 (1993)

    Current transformers 0.3% @ rated burden

    Volta e transformers 0.3% rated burden

    Current transformers (CT)

    Error of +/-0.3% at 100% current

    (Error of +/-0.6% at 10% current) CT rated burden to meet site needs

    o age rans ormers

    Error of +/-0.3% at 90-110% volts

    ABB GroupJune 21, 2012 | Slide 17

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    18/43

    Revenue metering (voltage injection) testing

    -

    CTs remain installed inside of equipment

    Primary circuit opened somewhere

    Very clearly defined CTs tested

    Test equipment used very portable

    se vo tage n ect on

    Energizes CT secondary

    On site measurements of VA watts ex. Current

    Results are traceable for accuracy use

    RCF and PA readings provided for tested CTs

    Quick testing timing (one minute per CT)

    Test report issued on each CT

    ABB GroupJune 21, 2012 | Slide 18

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    19/43

    Injection vs. comparator method

    Field readings have NIST traceability

    Ratio error (RE)= lo x sin ( + ) / Isec (RE isproportional to core loss current)

    Phase angle (PA)= lo x cos ( + ) / Isec (PA isproportional to the magnetizing current)

    Test for accuracy using knopp tester vs. injection method

    Equivalent results

    ABB GroupJune 21, 2012 | Slide 19

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    20/43

    Site test data

    On site CT accuracy testing

    Measured components:

    Secondary winding resistance

    Exciting current into CT

    Watts into CT

    ABB GroupJune 21, 2012 | Slide 20

    rea ng

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    21/43

    Site test data (cont.d)

    =

    5 9.45 0.0068 0.00136 0.04100 0.0643 1.8 1.62 0.785 0.1 0.428 0.879 1.307 0.00131 1.2

    0.5 0.95 0.001 0.0019 0.00065 0.0009 1.8 1.62 0.785 0.1 0.428 0.813 1.241 0.00180 2.1

    5 4.95 0.0055 0.0011 0.01700 0.0273 0.9 0.81 0.392 0.1 0.407 0.897 1.304 0.00106 1.0

    Ratio Error and

    Phase Angle

    values are

    derived from. . . . . . . . . . . . . . .

    5 2.96 0.005 0.001 0.00900 0.0148 0.5 0.45 0.218 0.1 0.377 0.917 1.294 0.00096 0.9

    0.5 0.30 0.0006 0.0012 0.00013 0.0002 0.5 0.45 0.218 0.1 0.377 0.749 1.126 0.00108 1.8

    actual site

    readings

    Calculated values:

    Voltage at operating levels

    Angles between VA and watts Angle between Z and X of burden

    Ratio error

    ABB GroupJune 21, 2012 | Slide 21

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    22/43

    Transformer test information certified reports

    Date December 03 ,2003

    standards

    Actual ratio tap used for

    DATASHOWNINTHISCOLORDENOTESACTUALATSITEREADINGSOBTAINED

    GCTPosition No. G2-102

    GCTRatio 1500:5

    Burden of Connected Circuit = 0.39 Ohms .9 pf

    Isec Vo Io Io/Isec W VA Burden Rb Xb Rw f Q a=(f+Q) RE PA RCF

    5 4.8733972 0.015 0.003 0.031 0.073101 0.5 0.45 0.218 0.5 0.226 1.133 1.358 0.00293 2.2 1.00293

    0.5 0.4873397 0.0041 0.0082 0.001 0.0017983 0.5 0.45 0.218 0.5 0.226 0.981 1.207 0.00766 10.0 1.00766

    GCTPosition No. G2-106

    GCTRatio 1500:5

    At important current levels (10%and 100%) or user defined levels

    At a licable burden to su ort

    Burden of Connected Circuit = 0.51 Ohms .9 pf

    Isec Vo Io Io/Isec W VA Burden Rb Xb Rw f Q a=(f+Q) RE PA RCF

    5 4.8733972 0.019 0.0038 0.041 0.0925945 0.5 0.45 0.218 0.5 0.226 1.112 1.338 0.00370 3.0 1.00370

    0.5 0.4873397 0.0047 0.0094 0.001 0.0020614 0.5 0.45 0.218 0.5 0.226 1.064 1.290 0.00903 9.0 1.00903

    Readingstakenabovearecertifiedto betraceabletoNational Instituteof Standards andTechnology(NIST) byusing

    instrumentationcalibratedandwithinactivecertifi cationdates. Icertify that theresults shownareaccurate andhave

    uncertaintyreadingswell withintheallowablerangedefinedbystandards.

    Items in red do not comply with 0.3% accuracy class

    definition per IEEE C57.13 industry standard.

    Certified By

    Date Certified:

    14.0

    actual burden measured on site

    Certified report issued

    Within two weeks of test

    Kuhlman Field Engineering ServicesGroup

    Can be used for revenue capture

    Any unit not meeting 0.3%highlighted in red

    ABB GroupJune 21, 2012 | Slide 22

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    23/43

    Injection metering accuracy testing summary

    period)

    100 generator CTs

    stat on serv ce s

    39 oil circuit breaker CTs

    200:5 to 35000:5

    GCTs, BCTs, and wound

    ABB GroupJune 21, 2012 | Slide 23

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    24/43

    Injection metering accuracy testing summary (cont.d)

    Generator CTs = 87 of 100CTs (87% in 0.3% class)

    9000:5 ratio CTs 0.6% (9cores not annealed)

    1200:5 ratio CTs 0.6%

    Station service CTs = 176 of233 CTs (75.6% in 0.3%classes)

    - : ra o s0.6%

    OCB CTs = 18 of 39 CTs.

    800:5 tap ratio CTs 0.6%

    ABB GroupJune 21, 2012 | Slide 24

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    25/43

    CT design information

    Revenue 0.3% demands

    0.3% maximum error at 100% rated current

    0.6% maximum error at 10% rated current

    Can be turns compensated (biased to achieve best

    Relaying CTs

    Core sized to develo a s ecified volta e at fault leveloperation

    Generally good metering accuracy at high ampere-turns/lar e core cross-section

    Non-compensated design (actual turns count equalnameplate ratio information)

    ABB GroupJune 21, 2012 | Slide 25

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    26/43

    CT design information (cont.d)

    C400/C800 rated 600:5 ratios and higher

    Lar e core cross-section = low o eratin flux densities

    No supporting test certifications

    Not all relay CTs with ratios above 1000:5 are accurate

    Non-annealed relay cores Cores that have experienced mechanical tension

    Turn-to-turn problems with CTs windings

    ABB GroupJune 21, 2012 | Slide 26

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    27/43

    True comparator CT accuracy test

    Off-line test for BCTs in OCBs

    Outage for testing

    Isolated from primary circuit

    RCF/PA certification - comparator method

    Highly accuracy comparator & standard transformer

    Driver transformer

    Accurate burdens

    NIST trace-ability

    Standard and comparator traceable to NIST

    RCF and PA readings recorded

    ABB GroupJune 21, 2012 | Slide 27

    O

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    28/43

    On site VT accuracy testing

    .

    Primary and secondary access needed

    Off-line test Outage for testing

    Isolated from primary circuit

    -

    Highly accurate comparator and standard VT

    Driver transformer

    NIST trace-ability

    Comparator and standard VT traceable to NIST

    Actual readings on RCF and PA taken

    ABB GroupJune 21, 2012 | Slide 28

    C t t f t t

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    29/43

    Current transformer test

    apparatus use at higher currents)

    Off-line test-secondary access only

    u age or es ng

    Primary circuit opened

    Define application

    Bushing size/voltage rating

    Distance from terminal block to CT

    Wire size of secondary leads

    Ratio of CT tested

    Define exact winding resistance

    Perform excitation test

    Develops the core size

    ABB GroupJune 21, 2012 | Slide 29

    oss c arac er s cs

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    30/43

    C t t f t t ( t d)

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    31/43

    Current transformer test (cont.d)

    Record

    CT ratio

    CT accuracy (if known)

    Bushing kV application/type bushing

    CT to terminal block dimension and wire size

    Site conditions

    -

    Demagnetize CTs

    Measurements DC resistance (on each tap)

    Excitation test

    ABB GroupJune 21, 2012 | Slide 31

    Current transformer test (cont d)

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    32/43

    Current transformer test (cont.d)

    Measure DC Resistance and IEX Current

    Rw

    Voltage

    Injection

    and

    Measurement

    Secondary ExcitationVoltage

    Secondary Voltage Injected - Measure Excitation Current

    ABB GroupJune 21, 2012 | Slide 32

    Current transformer test (cont d)

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    33/43

    Current transformer test (cont. d)

    us ng ze=

    MakeMake

    CT ApproximateGCT # 123456789Size(optional) = 1010--14 ID14 ID

    CT to Terminal Block

    Dynamic secondary excitation curve for each CT

    Distance= 20 of #10AWG20 of #10AWG

    Installation details- bushing kV, lead run

    DC resistance of winding

    DC resistance = 0.565 ohms @ 20C

    ABB GroupJune 21, 2012 | Slide 33

    Current transformer test (cont d)

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    34/43

    Current transformer test (cont. d)

    na yze s e a a s an

    GCTs)

    Calculate RF on each CTtested

    Winding resistance

    Wire cross-sectioncalculated

    Result tolerance

    +/- 15% of true value on

    RF

    Rating factor categorized

    RF=1.0, 1.5, 2.0, 3.0, 4.0

    ABB GroupJune 21, 2012 | Slide 34

    On site Kuhlman FES testing

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    35/43

    On site Kuhlman FES testing

    In-service energized testing: in place and energized-

    excitation performance (patented) Injection accuracy method: in place and de-energized-

    metering (RCF & PA) error (patented)

    -

    standard CT/ comparator (IEEE test) Rating factor definition: in place and de-energized-

    Voltage transformers

    True com arator method: in lace and de-ener ized-standard VT with comparator (IEEE test)

    ABB GroupJune 21, 2012 | Slide 35

    Benefit to user

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    36/43

    Benefit to user

    In place provides needed data

    -

    Saves real estate

    No purchase costs

    No installation costs

    Already wired out for connections

    Eliminates need for hi h volta e oil-filled/ as-filled CTs

    No maintenance reduces overall maintenance

    Safer inherently safe LV CTs on HV circuit

    On site accuracy test failures what next?

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    37/43

    On site accuracy test failures what next?

    -

    0.3% and 0.15% high

    accuracy rating Rating factors of 4.0

    Window sizes 6 to 42

    Help in sizing applications

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    38/43

    Help in sizing applications

    ee goo mens ons o

    ensure fit

    -

    Help in sizing applications (cont d)

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    39/43

    Help in sizing applications (cont. d)

    On site accuracy test failures what next?

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    40/43

    On site accuracy test failures what next? - .

    w e range per ormance

    0.15% B0.5 (0.3%B0.9)

    1% to 400% accuracy range (e.g.400:5 4A to 1600A)

    400:5 to 1200:5 ratios

    0.15% Accuracy0.15% Accuracy0%1% Current Range 400%

    On site accuracy test failures what next?

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)

    41/43

    On site accuracy test failures what next? -

    ype me er ng w

    auxiliary power extended range

    0.15% from 0.5% to 400%

    = .

    Designed for IPP use

    High short-circuit strength CT

    No burden restriction B1.8

    0.15% Accuracy0.15% Accuracy

    0 0.5% Current Range 400%

  • 8/13/2019 ABB Onsite Testing (NXPowerLite)