    V4, September 2012 1/17

    ADDAD-5 Series Advanced Electronics Company, Ltd.P. O. Box 90916

    Riyadh 11623

    Kingdom of Saudi Arabia

    10 (100) A, 20(160)A, Class 1

    1.5(6)A Class 0.5S

    3 Phase 4 Wires, 3 Phase 3 Wires DirectConnection

    And

    CT, CT-VT Through Connection

    Multi Tariff Digital Energy Meter

  • 7/24/2019 ADDAD 5%2c Datasheet

    2/17

    V4, September 2012 2/17

    Revision History

    Revision Date Highlights

    - July 2011 Preliminary Electrical Parameters

    1 August 2011 Update specification

    2 September 2011 Update specification3 February 2012 Update Meter picture

    4 September 2012Connection diagram updated for CT/VT,Note update in pg.3: phase-Y as reference instead of phase-B

    Notice

    The information contained in this document is subject to change without notice. AEC makes nowarranty of any kind with regard to this material, including, but not limited to, the impliedwarranties of merchantability and fitness for a particular purpose. AEC shall not be liable forerrors contained herein or incidental consequential damages in connection with the furnishing,

    performance, or use of this material.

    This document contains proprietary information which is protected by copyright. All rights arereserved. No part of this document may be photocopied or otherwise reproduced without consentof AEC.

    Copyright (c) 2012 by AEC

    Published in a limited copyright sense, and all rights, including trade secrets, are reserved.

  • 7/24/2019 ADDAD 5%2c Datasheet

    3/17

    V4, September 2012 3/17

    1. Introduction

    The ADDAD-5 Smart Meters are designed to meet the needs of residential, commercial andindustrial energy consumers. AECLs IEC-Standard Multi Tariff Digital Energy Meters set a new

    standard for revenue-grade energy meters. It provides a highly accurate energy and demandmetering system with a comprehensive information display on an extended temperature largeLCD. It is capable of remote access via a various types of communication ports in metersinaddition it can be easily connected to SCADA system.

    The ADDAD -5 poly phase smart meter series comprises of 10(100) A, 20(160) A, 1.5(6) A, 3-Phase-4-Wires, 3-Phase-3-Wires, Direct (Whole current) connection, Transformer operated CTand CT-VT through connection meters.

    The emerging AMR technologies in the metering industry call for smart meters that haveenormous communication capabilities. The ADDAD-5 Smart Meters composite of all advancedmetering functionalities and its robust communication capabilities can easily be an integral part ofthe Automatic Meter Reading System (AMR) or Smart grid. AEC also provides state of the art

    AMR software to manage its smart meters remotely.

    Notes:

    All default values are configured based on customer request.

    For 3P3W meters phase-Y is considered as reference instead of neutral

  • 7/24/2019 ADDAD 5%2c Datasheet

    4/17

    V4, September 2012 4/17

    1.1 Meter Front Display

    Note:The above display is just a sample and the text on meter name plate shall vary accordingto meter type.

  • 7/24/2019 ADDAD 5%2c Datasheet

    5/17

    V4, September 2012 5/17

    2. Product Description

    2.1 Meter Features

    kWh, kvarh and kVAh digital metering in import and export directionsSeparate registers for import and export

    Meets international standard IEC62052-11, IEC62053-21, IEC62053-22 and IEC62053-23.

    Class 1 and Class 0.5S accuracy for kWh. Class 2 for kvarh per IEC62053-23

    -20 to +70C operational temperature

    Wide range three phase power supply built in up to 318V L-N or 550V L-L.

    Extended Temperature Large LCD display, with programmable number of digits fordisplaying the reading.

    Pulse LED for accuracy testing (Imp/kWh and Imp/kvarh)

    SO and EOI electrical output pulse per IEC62053-31.

    Internal Real Time Clock with battery backup. Per IEC62054-21 (2004-05).

    Storing reading in EEPROM that does not require any battery backup with minimum dataretention of 20 years

    Measure and display the following: kWh, kvarh, kVAh in all tariffs, import and export directions. PF for total system power factor and per phase, Voltage per phase, Current per phase, Total three-phase active power. Total three-phase reactive power, Total three-phase apparent power, Line frequency, Demand kW, kvar and kVA total import and export directions Maximum Demand kW, kvar and kVA import and export directions (Basic &TOU)

    Configurable to select block method or sliding window method for demand calculation 8 Multiple Tariffs registers for kWh, kvarh and kVAh (Time of Use) import and export

    directionso Up to 8 TOUo Up to 620 Special days.

    20 days regular (repeated every year e.g. national day) 600 irregular days for 30 years (each year 20 days)

    o Up to 10 seasonso Up to 10 weekso Up to 31 dayso Each day up to 10 Scripts

    Simple Meter installation at site, with date and time stamp recording:

    o Catch reverse run caused by cable swapping.o Catch phase and neutral swapping.o Catch unconnected phases.o Catch Phase sequence revisal

    Tamper detection with date and time stamp recording:o Detect top cover openo Detect terminal cover openo Detect external CT short for CT operated Meters (requires CT on neutral line).

  • 7/24/2019 ADDAD 5%2c Datasheet

    6/17

    V4, September 2012 6/17

    o Detect Outage.

    Event detection with date and time stamp: Over Current/Under Voltage limit violation Detect low total system power factor Auto demand reset.

    Manual demand reset. Meter Configuration. Battery failure Clock Initialization Memory Error Meter Initialization Time change (Before/After) Demand Reset Manual Demand Reset Auto-Reset Meter Configuration Change Communication Port log Output Relay Control

    Support Demand integration periods of 5, 15, 30 and 60 minutes.

    Store the maximum demand for the below registers:1. Max Demand kW Import2. Max Demand kW Export3. Max Demand kvar Import4. Max Demand kvar Export5. Max Demand kvar Q16. Max Demand kvar Q47. Max Demand kVA Import8. Max Demand kVA Export

    Load Profile storage for 4320 points (enough for 90 days at 30 minutes interval)

    Load Profile storage for (9 channels) + (Temperature, Status, Date/Time stamp)The 9 channels are selected from the below channel options:

    1. Demand kW Import2. Demand kW Export3. Demand kvar Import4. Demand kvar Export5. Demand kvar Q16. Demand kvar Q47. Demand kVA Import8. Demand kVA Export9. Average PF10. Voltage Phase 111. Voltage Phase 2

    12. Voltage Phase 313. Current Phase 114. Current Phase 215. Current Phase 316. Power Factor Phase 117. Power Factor Phase 218. Power Factor Phase 319. Frequency

  • 7/24/2019 ADDAD 5%2c Datasheet

    7/17

    V4, September 2012 7/17

    Support 12 programmable EOB (End Of Billing).

    Daily Energy profile provide reading for the last previous 4 days

    Utility Sealed battery door and reset switch.

    Communication Features Optical Communication port complies with IEC62056-21 Mode E, 9600bps.

    RS485, 9600bps.

  • 7/24/2019 ADDAD 5%2c Datasheet

    8/17

    V4, September 2012 8/17

    2.2 Electrical Specifications

    Meter Type 10(100) 20(160) 1.5(6)

    Accuracy Class

    kWhkVARhkVAh

    121

    121

    0.5s21

    Standard IEC62053-21,IEC62053-23

    IEC62053-21,IEC62053-23

    IEC62053-22,IEC62053-23

    Connection 3 Ph 4 Wire 3 Ph 4 Wire 3 Ph 4 Wire,3 Ph 3 Wire

    Operating Frequency 60Hz 60Hz 60Hz

    Input Voltage Range formeasurements (L-to-N)

    Range, VAC

    Nominal, VAC

    100 to 318

    3x127/220,3x133/230,3x220/380,3x 230/400,3x 277/480

    100 to 318

    3x127/220,3x133/230,3x220/380,3x 230/400,3x 277/480

    100 to 318 3P4W86 to 120 3P3W

    3P4W:3x127/220,3x133/230,3x220/380,3x 230/400,3x 277/480

    3P3W:3x100,3x110,3x120

    Maximum Power SupplyOperating Voltages

    L-N VACL-L VAC

    318550

    318550

    318550

    Current and Voltage Connection Direct(Whole current)

    Direct(Whole current)

    CT, CT-VT

    Reference Current, (In) (Amps) 10 20 1.5

    Maximum Current, (Imax) (Amps) 100 160 6

    Short Circuit Current, (Amps)30xImax for Direct for 10ms20xImax for CT for 500ms

    3000 4800 120

    Minimum Current, (Amps)(0.05 In) A for (DIRECT)(0.01 In) A for (CT, CT-VT)

    0.5 1 0.015

    Starting Current, (Amps)(0.004 In) A (DIRECT)(0.001 In) A (CT, CT-VT)

    0.04 0.08 0.0015

    Power consumption in voltagecircuit per phase

    At 3x133/230At 3x230/400At 3x277/480

    0.5 W, 0.65 VA0.6 W, 1.0 VA0.65 W, 1.2 VA

    0.5 W, 0.65 VA0.6 W, 1.0 VA0.65 W, 1.2 VA

    0.5 W, 0.65 VA0.6 W, 1.0 VA0.65 W, 1.2 VA

  • 7/24/2019 ADDAD 5%2c Datasheet

    9/17

    V4, September 2012 9/17

    Power consumption in Currentcircuit per phase

    At 10 AAt 100 AAt 1.5 A

    At 6 A

    0.05 VA5 VA

    0.05 VA5 VA

    0.06 VA

    0.4VAOutput Pulse Ratioimp / kWhimp / kVARh

    10001000

    10001000

    1000010000

    Output Pulse LEDColorPeak emissionwavelengthSpectral Line Half-width

    Red635nm40nm

    Red635nm40nm

    Red635nm40nm

    SO & EOI Output PulseSwitching Power

    - - 30V / 30mA

    No. of Measuring Element:

    3Phase 4WireEnergyVoltageCurrent

    3Phase 3WireEnergyVoltageCurrent

    333

    333

    333 + Neutral

    222

    Conductor bore diameter 9.2mm 9.2mm 5mm

    2.3 Electromagnetic Compatibi lity Specifications

    Electrostatic dischargePer IEC61000-4-2

    Test severity level 4.

    Contact Discharge: Test Voltage 8kV.

    Air Discharge: Test voltage 15kV.

    Electromagnetic HF fieldPer IEC61000-4-3

    Test severity level 3.

    Frequency band 80MHz to 2000MHz.

    Test field strength 10V/m. with current

    Test field strength 30V/m. without current

    Fast transient burstPer IEC61000-4-4 (5/50nSwaveform)

    Test severity level 4.

    Test voltage at current and voltage circuit: 4kV.

    Test duration 60 seconds.

    Conducted EMC Per CISPR 22 class B

  • 7/24/2019 ADDAD 5%2c Datasheet

    10/17

    V4, September 2012 10/17

    Frequency band 150kHz to 30MHz.

    Radiated EMCPer CISPR 22 class B

    Frequency band 30MHz to 1000MHz.

    Surge immunity Test

    Per IEC61000-4-5 (1.2/50us)

    Test severity level 4.

    Test Voltage 4kV.

    Damped Oscillatory waveimmunityPer IEC61000-4-12

    Test Voltage

    Common mode, 2.5kV

    Differential mode, 1kV

    Test frequency

    100kHz, repetition rate, 40Hz

    1MHz, repetition rate, 400Hz

    Immunity to conducteddisturbances

    Frequency band 150kHz to 80MHz.

    Per IEC61000-4-6

    Power Frequency withstandvoltage

    2kV

    2.4 Electrical Compatibil ity Specifications

    Static meters for active energy

    (classes 1 and 2)Per IEC62053-21

    Static meters for active energy

    (classes 0,2 S and 0,5 S)Per IEC62053-22

    Static meters for reactive

    energy (classes 2 and 3)

    Per IEC62053-23

    2.5 Communication Interface

    OPTICAL Port

    Optical Link Infrared, 860nm - 950nm

    Optical Port Per IEC62056-21

    Max. Baud rate 9600 bps

    RS485 9600 bps

    2.6 Backed up Battery for the RTC

    Back up type Lithium Battery

    LifeMeter operates in normal conditions: 10 years.

    With AC power off: 1 year.

  • 7/24/2019 ADDAD 5%2c Datasheet

    11/17

    V4, September 2012 11/17

    2.7 Back up for readings and Data

    Back up type EEPROMLife With AC power off: 20 years.

    2.8 Output Relay Specif ications

    ContactThe contact is change over, form C,NO/NC

    Rated Voltage 250VAC/ 30VDC

    Continuous rated current 2A

    Max. Operating Voltage 250VAC/ 30VDC

    2.9 Mechanical Specifications

    Terminal insulation Per IEC 62052-11

    Impulse Voltage Withstand 6KV (1.2/50uS impulse) 62053-11

    Terminal heat resist Per IEC62052-11, IEC60095-2-11

    Dust & water Per IEC62052-11, IEC529; IP54

    Solar Radiation

    Per IEC 62052-11, IEC 60068-2-5,

    procedure A, 55C, 3 days

    Vibration 10-150Hz @ 1g, 75 min.

    Per IEC 62052-11, IEC60068-2-6

    Shock Half sine @ 30g impulse for 18ms

    Per IEC 62052-11, IEC68-2-27

    Weight(Direct) Whole current meter is 2.4 kg,(CT, CT-VT) Transformer Operated Meteris 1.6 kg.

    Overall Dimensions (mm)Direct: W= 189, H= 270, D= 107.3CT and CT/VT: W= 189, H= 270, D= 87.3

    LCD Viewing area Dimensions (mm) 73 x 31.5

    LCD main digit size Dimensions (mm) 9.0x4.5

    Case Material Polycarbonate.

    Spring hammerIEC 62052-11, IEC 60068-2-75.

    Apply kinetic energy of 0.2J

    2.10 Climatic Specifications

  • 7/24/2019 ADDAD 5%2c Datasheet

    12/17

    V4, September 2012 12/17

    Dry heat Per IEC 62052-11, IEC 60068-2-2

    Cold Per IEC 62052-11, IEC 60068-2-1

    Damp heat cyclicPer IEC 62052-11, IEC 60068-2-30 foroutdoor meter

    2.11 Environmental Specifications

    Operating Temperature -20 to +70 degree C

    Storage Temperature -30 to +85 degree C

    Humidity 95 % non-condensing

    2.12 LCD Appearance

  • 7/24/2019 ADDAD 5%2c Datasheet

    13/17

    V4, September 2012 13/17

    2.13 Dimension and appearance

    Direct Meters:

    CT and CT/VT Meters:

  • 7/24/2019 ADDAD 5%2c Datasheet

    14/17

    V4, September 2012 14/17

    3.2 Connection Diagram:

    DIRECT (WHOLE CURRENT) 3-PHASE 4-WIRES (3P4W) TYPE METERS

    1 2 3 4 5 6 7 8 9 10 11

    2221

    RJ45-left RJ45-Right

    15 16 17

    COM NO NC

    Output Relay

    R

    Y

    B

    N

    R

    Y

    B

    N

    R

    LoadSource Power Flow

  • 7/24/2019 ADDAD 5%2c Datasheet

    15/17

    V4, September 2012 15/17

    CT, CT-VT 3-PHASE 4-WIRES (3P4W) TYPE METERS

  • 7/24/2019 ADDAD 5%2c Datasheet

    16/17

    V4, September 2012 16/17

    CT-VT 3-PHASE 3-WIRES (3P3W) TYPE METERS

  • 7/24/2019 ADDAD 5%2c Datasheet

    17/17

    17/17

    6. Ordering Information

    The meter can be ordered using below format.

    1 2 3 4 5 6 7 8

    Model #

    ADDAD5 A 5

    Meter Type

    Direct D

    CT-VT V

    CT C

    Meter Connection

    3P3W 3

    3P4W 4

    Meter Accuracy

    Class 2 A

    Class 1 B

    Class 0.5 C

    Class 0.2 D

    Voltage Range

    (3x 133/230 and 3x 230/400 VAC) 1

    (3x 110 120 VAC) 2

    (3x 57.7/100 ~ 69.3/120) 3

    (3x 57.7/100 ~ 3x 230/400 VAC) 4

    3x 277/480 VAC 5

    (3x 127/220 ~ 3x 277/480 VAC) 6

    Current Range

    10(100) A 1

    20(160) A 2

    1.5(6) A 3

    1(6) A 4

    5(6) A 5

    1(1.2)A 6

    Additional Communication Port

    RS485 Port R