72
AN-Najah National University faculty of Engineering Mechanical Engineering Departement Mohammed Itmazeh Omar Rizq-Allah Salem Rafat Basheer Osaid M. Assaf Geothermal process in Mechanical Building system Supervisor : Dr. Iyad Assaf

AN-Najah National University faculty of Engineering Mechanical Engineering Departement

  • Upload
    donnel

  • View
    51

  • Download
    2

Embed Size (px)

DESCRIPTION

AN-Najah National University faculty of Engineering Mechanical Engineering Departement. Geothermal process in Mechanical Building system. Supervisor : Dr. Iyad Assaf. Mohammed Itmazeh Omar Rizq -Allah Salem Rafat Basheer Osaid M. Assaf. Objective. - PowerPoint PPT Presentation

Citation preview

PowerPoint

AN-Najah National Universityfaculty of EngineeringMechanical Engineering DepartementMohammed ItmazehOmar Rizq-Allah SalemRafat BasheerOsaid M. AssafGeothermal process in Mechanical Building systemSupervisor : Dr. Iyad AssafObjectiveComparison between traditional system(Chiller Boiler system) and geothermal systemOutlineBuilding descriptionHeating and cooling system Geothermal systemGeothermal designPlumping and fire fighting systemCost analysis

Building description The tower is located in the suburb of basil in the city of Ramallahwhich rises from the sea 874 meters above sea level within longitude 35.20 east and 31.902 north latitude and wind speed reaches 18.5 meters per secondBuilding description cont.Inside and Outside Design condition:

ParametersTinToutinoutwin

woutTun

TgroundWinter234.750%68%93.813.8510.7Summer253050%60%101328.3335Building description cont.

Overall heat transfer coefficient Uoverall.For external wall

Ro= 0.03 m2. Co/W Ri= 0.12 m2.Co/W

U=0.8692 W/m2.k

For internal wall

Ro= Ri = 0.12 m2.Co/W

U=2.05 W/m2.k

ConstructionThickness[m]Thermal conductivity k[w/m.k)1Plaster0.021.22Cement brick0.20.95

Ceiling and floor

Windows And Doors Heating load calculation SourceThe heating load calculation begins with the determination of heat loss through a variety of building for components and situations.

WallsWindows DoorsCeiling & FloorsInfiltration Ventilation

The Heat load EquationSample calculation for room 1Boiler selectionTotal heat demand for one apartment is 13794 +8130 = 21924.7 WSo the building is Residential Building (4 floor application-2 apartments for each level) Qboiler =1.1(Qapt*4*2) = 1.1*(21924.7*4*2)= 177.84 KWThe boiler was selected from The sime company ,Boiler model no# 2R10 (180 KW)

Radiators selectionLBT radaitors were selected according to effective cost, heating demand, availabilityModel No# LBT 6/680Output /section192 W

Pump selection

Cooling load SourceHeat transfer (gain) through the building skin by conduction, as a result of the outdoor indoor temperature difference.

Solar heat gain (radiation) through glass or other transparent materials.

Heat gains from Ventilation air and/or infiltrationInternal heat gain by occupants, light, appliances, and machinery.

Cooling Load equation : For ceiling & walls :Q=U*A*(CLTD)corr(CLTD)corr = (CLTD + LM) K + (25.5 Ti )+ (To 29.4)K=1 dark colorK=0.83 medium colorK=0.5 light colorFor glass :Q=A*(SHG)*(SC)*(CLF)For people :Qs=qs*n*CLFqL=qL*nFor lighting :Qs=W*CLFFor equipments :Qs=qs*CLFQL=qLCooling calculation sample calculation for room 1Cooling calculation cont.Inside wallWest wallQW= UA (Tun-Tin)=1.05 *13.4*3.33 =46.85 WWest doorQW= UA (Tun-Tin)=5.8 *1.6*3.33=30.9 W

Ventilation and Infiltration Calculation.Vinf = 16.1 L/s Vvent = 60 L/sQs)vent,inf = 1.2 * Vvent,inf * (Ti To) = 1.2*60*5 = 270 WQL)vent,inf = 3 * Vvent,inf * (wi wo) = 3*60*3 = 540 W

PeopleQL= n q = 10*30 =300 WQs= n q (CLF)=10*70*0.33= 532 WEquipment(TV, Laptops)Qs= n q (CLF)=2*100*0.65= 130 WQs= n q (CLF)=1*150*0.65=97.5WLightingQs= n q (CLF)=4*35*0.77=107.8

Total cooling load for room1 is 2804.17 W

Chiller selectionTotal cooling load is 131.05 KW chiller capacity = 131.05*1.1 =144.11Kw = 41.17 T.R The Chiller was selected from Carrier companyModel No. 30RAPAQUASNAP unit 050 with capacity of 43.1 T.R

Pump selection

Geothermal systemIntroduction:

Heat from the earth can be used as an energy source in many ways form large and complex power station to small and relatively simple pumping system .This heat energy known as geothermal energy, Then thermal energy is generated and stored in the Earth and determines the temperature that converted to an energy that used for cooling and heating.

Type of Geothermal Exchange Systems:Open loop Geothermal Exchange System.

Closed loop Geothermal Exchange System.

Open loop Geothermal Exchange System:An open loop system is quite uncommon due to the fact that it relies on a nearby body of water.

The water from the body of water flows (underground) to the heat exchanger in the heat pump and then back out again.

More efficient than a closed loop system.

Closed loop Geothermal Exchange System:A closed loop system is the most common type of geothermal exchange system simply because it does not require a nearby body of water to pull from.

Has two different types.1. Vertical loop system:

This type is ideal for area is limited and the depth of drilled holes between 46 to 138 m.

More expensive than the horizontal type, due to more depth of the well holes.

2. Horizontal loop system:

This type is the most Popular and most cost effective Of all geothermal exchange System, and require the Depth at least 2.5m.

Geothermal in heating and coolingUsing the geothermal in heating and cooling is more possible to implement due to the low cost, in comparison with using it in producing energy.

The cooling and heating geothermal system does not need very high temperature so that the wells is not as deep as the depth in the producing energy(about 150m underground).

Geothermal designSteps GSHP design 1- Building load: heating load = 104 KWcooling load = 131 KW

2- GSHP system: The available land for this project will be considered to suit the vertical system only (because is not enough for the horizontal system).

3- Selection Pump:

The selection of heat pump needs the following parameter:1- Type of the system(open, close, etc)2- Building load3- The required of a Coefficient of Performance(COP)4- Pump characteristics(water to air, water to water)In this project, we select water to air heat pump.

For our building (131KW cooling & 104KW heating) EKW130 is enough to cover the building

4- pipe properties:Equivalent Diameters and Thermal Resistances for Polyethylene U-Tubes

this table show the thermal resistance and pipe size the flow rate should be at least 2.0 gpm for through 1 pipe, and at least 3.0 gpm pipe.

5- Estimation of pipe length:We have two methods to estimate pipe length:Method 1: The required GHX length based on heating requirements, Lh is:

Wehre qheat : the load liquid flow for the heating COPh: the design heating coefficient of performance (COP) of the heat pump system. Rp: the pipe thermal resistance. Rs: the soil/field thermal resistance. Fh: the GHX part load factor for heating. Tg,min: the minimum undisturbed ground temperature. Tewt,min: the minimum design entering water temperature (EWT) at the heat pump.

The required GHX length based on cooling requirements, Lc is:

Where qcool : the load liquid flow for the cooling COPc: the design cooling coefficient of performance (COP) of the heat pump system. Rp: the pipe thermal resistance. Rs: the soil/field thermal resistance. Fc: the part load factor for cooling. Tg,min: the maximum undisturbed ground temperature. Tewt,min: the maximum design entering water temperature at the heat pump

Method 2:For horizontal and vertical systems given the following:Vertical, all configurations: L= 21m/KW (73m/ton)Horizontal, all configuration: L= 37m/KW(130m/ton) Results:Tg = 19oC (on the depth of hole is 110m)Tewt,min = -6.7 oCTewt,max = 92.2 oCRp = 0.4 m2.oC/WRs = 1 m2.oC/WFrom the heat pump catalogue we have :For heatingCOP = 4.9Flow rate = 6.8 L/sFor coolingCOP = 5.4Flow rate = 8.5 L/s

This table show the results of the two method:

6- land required: Each borehole needs to be 2 meters away from the other, This distance will be enough to diffuse the heat from the ground.

Area = 2(m)* number of hole =2*25=50m2

Duct Design and Fan-coil unit system Sample of calculation for number of diffusers: For the room 1

Fan coil unit selection.For multipurpose room (Room 1) in the ground floor:

Table (5.2): The equal pressure method for sizingRoom 1Ductv' m3/s)v(m/s)A(m2)D (m)p/L(pa/m)H (mm)W (mm)AB0.3950.0960.350.9200280BC0.1340.0490.250.9200280BE0.1340.0490.250.9200280BD0.1340.0490.250.9200280Table (5.9): The equal pressure method for sizingBath 1Ductv' m3/s)vA(m2)D (m)p/L(pa/m)H (mm)W (mm)AB0.16650.03140.201.7200219BC0.08334.50.0200.161.7150170BD0.08334.50.0200.161.7150170Bath rooms duct dsign

For bath room1 Bath rooms and kitchen Exhaust fan selection.

1 SPEEDTYPE=CentrifugalCFM =162 406VOLTAGE= 115WEIGHT (lbs)= 30SONES @SP =2.2 - 10.4MAX BHp=.95HP =100 WATTSIZE =6RPM=1250-2700PHASE= 1MOTOR =TERPMRANGE=DRIVE =Direct DrivedB(A)=-WARRANTY =1 Year MotorTable (5.15): Exhaust fan electrical and mechanical data.

Exhaust Fan modelSP-SQD601AS Plumping & Fire fighting System.

1 - potable water system

Plumbing also refers to a system of pipes and fixtures installed in a building for the distribution of potable water and the removal of waterborne wastes.

In our project the design of the pipes based on the flash tank type.

PVC were used for cold water services pipes in the building, and CPVC were used for hot water services pipes.

Sample of calculation :

Supply hot water pipes design:

Branch nameFixture unitFlow(l/s)P/L(pa/m)Diameter(in)A-B8.50.84900B-C4.750.57450C-D3.250.44800Supply hot water stack design:

Branch nameFixture unitFlow(l/s)p(pa/m)Diameter(in)1-2682.25501 2-3341.551501 3-425.51.3630014-5171.1632015-A8.50.847002-6341.551501 6-725.51.3630017-8171.1632018-A8.50.84700pump calculation. for hot water .(P)pump = (P)head + (P) friction ,fitting + (P) flow(P)head = 15*9.81 = 147.15 Kpa.(P) flow = 5 psi * 6.89 = 34.45 Kpa.(P) friction = (P/L)*L = 77* 0.350 = 26.95 Kpa.(P) friction ,fitting = 26.95 *1.8 = 48.5 Kpa .(P)pump = (P)head + (P) friction ,fitting + (P) flow(P)pump = 147.15 + 48.5 + 34.45 = 230 Kpa.(P)pump = (230/101.125) *14.7 = 33.5 psi.Q pump = 2.2 (L/s)

Hot water pump selections: for cold water .

(P)pump = (P)head + (P) friction ,fitting + (P) flow(P)pump = -39.24 + 28.8 + 34.45 = 24 Kpa.(P)pump = (24/101.125) *14.7 = 3.5 psi.Q pump = 3.7 (L/s)The size of the cold water tank = 3.7 * 30 min,*60 = 6660 = 6.66 m3. litre for a one day. But tank size for a three days = 6.66 * 3 = 19.98 m3 , so select 20 m3.

for return hot water .

(P)pump = (P)head + (P) friction ,fitting + (P) flow(P)pump = 0 + 22+ 0 = 22 Kpa.(P)pump = (22/101.125) *14.7 = 3.2 psi.Q pump = 1.32 (L/s).

2- Sanitary Drainage system.

Sanitary Drainage system is that system in which waste and soil are transferred to main sewer line or other sewage system.

Used fixture.BathtubLavatoryWater closet (wc).Kitchen sink.

Drainage pipe sizing. To determine drainage pipe size tow factor govern the size. 1-Number of fixture unit. 2-Self clean velocity.

Used fixtureEquivalentFixture unitBranch line to floor drain (in)Floor drain to stack(in)Vent size(in)Stack size(in)Kitchen sink22444Dish washer22floor drain6- Table (6.7): kitchen.3 - fire fighting system

Fire protection is the study and practice of managing the unwanted effects of fires.

Standpipe system A standpipe is a type of rigid water piping which is built into multi-story buildings in a vertical position.the diameter of the risers is usually (4), and for the line which goes to the landing valve is (2.5) .

Fire fighting pump calculation.

The total pressure drop due to friction = 14.8 psiThe total pressure drop in pipes and fittings = 1.8 *14.8 = 26.6 psi p due to head = 12*9.81 = 117.72 Kpa = 17 psi. p due to flow = 100 psi Total head for the pump = 26.6 + 17 + 100 = 144 psi . The jockey pump pressure is 149 psi, and its flow rate is 7. 5 gpm.Tank capacity:Total demand=750 gallon/min = 750* 3.8*90*10-3 = 257 m3standard size of tank by calculation the tank size should be 260 m3

firefighting pump selection: Total head for the pump = 144 psi . flow rate = 750 gpm.

Cost AnalysisCost analysisNormal System:1. Initial cost:The mechanical room that needed for (104.43)KW heating will has a 1300 $ initial cost.The chiller required for (131.05)KW cooling has a 44000 $ cost.

Initial cost = (1300) + (44000) = (45300)$

Cost AnalysisCost AnalysisCost AnalysisMonth12345101112Mean temp.10.210.411.71720.721.317.712.7DD value251221205400018174Cost AnalysisCooling cost:

Power consumed each hour:

Time Hr.1112131415161718Hour ratio0.70.730.750.780.810.80.85MonthMonth ratioJune1Power (KW)91.895.798.325102.12107.5131.1107.1112.47July0.8476.880.0482.2585.5689.7109.789.6493.84August0.7871.5874.5276.7380.0483.83102.1283.5687.77September0.7568.8671.7673.147780.049880.0484.18Total PowerKW309322330.45344.72361.1440.92360.34378.26Cost AnalysisWe can estimate the total power of needed to be (2847 KW).

From which we have the power input to be (2847*60/2.9) = 58903 KWh.

If the 1 KWh cost is 0.3 $, then the annual cost will be Rc=17670 $.Cost AnalysisGeothermal System:1. Initial cost:High initial cost due to the holes drilling and pipe system. The cost of finishing one borehole will be about 5000 $ (we need 25 holes).The price of the water to water heat pump for 131 KW cooling and 104 KW heating is about 40000 $.Then:The initial cost will be about (40000) + (5000*25) = 165000$.Cost Analysis2. Running cost:The input power will be about 8441.25 Kwh. From which the running cost is determined by multiplying the power with 0.3 $ and will be about 2533 $.The input heat pump power to be (2847*60/5.7) = 29970Kwh (29970*0.3) = 8990 $.

Then:The annual running cost will be Rc =(2533+8990) = 11523$.

Cost AnalysisFinal Result:High initial cost for the geothermal system (165000 $).Low initial cost for the normal system (45300 $).The running cost for normal system will be about (8601+17670) = 26271 $.The running cost for geothermal system is about (2533+8990)= 11523 $.

The running cost of the geothermal system is almost 43% of the running cost for the normal system.

Cost AnalysisWe can see that after about 10 years, geothermal system is less cost than the normal system.Then, geothermal system is more economic than the normal system.

Thank youany question??