ARCOsystemTheElevatedCompositeCableManagementSystemfor
RailwayUse
SystemSpecifications&InstallationInstructions
TM 2012 - 241 I. NVT 2
PAO5/06162TK135/R551dbl (Ausgabe 3-3/2012)
Approved by
banedanmarkKN239.00 Q nr. 4579
ARCOsystem 6 Metres Span Elevated Troughing
TM 2012 - 241 I. NVT 2
PAO5/06162TK135/R551dbl (Ausgabe 3-3/2012)
Approved by
banedanmarkKN239.00 Q nr. 4579
ARCOsystem 6 Metres Span Elevated Troughing
TM 2012 - 241 I. NVT 2
PAO5/06162TK135/R551dbl (Ausgabe 3-3/2012)
Approved by
banedanmarkKN239.00 Q nr. 4579
ARCOsystem 6 Metres Span Elevated Troughing
TM 2012 - 241 I. NVT 2
PAO5/06162TK135/R551dbl (Ausgabe 3-3/2012)
Approved by
banedanmarkKN239.00 Q nr. 4579
ARCOsystem 6 Metres Span Elevated Troughing
6.InstallationinstructionsfortheARCOsystemFRP-CableManagementSystem
6.1Tools
GRP-CableManagementSystemARCOsystemSize1andSize2
- ManualPileDriverforrammingSigmapost100intheground(withsuitabledrivingcap),iframming
- Longhandledspade,postholediggerand/orAuger,ifholedigging- 2piecesoftorquewrenches,SW17,SW19
- TorqueHandle
- SpiritLevel
- MitreProtractor
- File
- Knife
- String
- CuttingDisc
- VarnishSpray
- ZincSpray
- PersonalProtectiveEquipment
6.2PreparationoftheInstallation
The route works should be marked out according to the guidelines and plans of the client. Before
installationallcomponentsshouldbeexaminedforanydamage.OnlyfirstqualityGRP-profilesorsteel
partsshouldbeinstalled.Cuttingoutorrepairofdefectiveprofileareasorcomponentsisnotpermitted
andwill result in immediatecancellationofproductwarranty.AnydefectiveordamagedGRP-profiles
andsteelpartsshouldbereplacedimmediately.
6.3HandlingoftheFRP-CableManagementSystem
ShouldphysicaldamagetotheGRP-CableManagementSystemARCOsystemSize1and2beidentified,forexample,causedbymis-handlingordamageintransit,thesuppliershouldbeconsulted.
Individualprofilesshouldnotbemis-handledorsubjectedtoabuse,causingdamageby,forexample,throwingthemtothegroundwhilstunloadingorduringinstallation!
Unloadingofpalletisedcomponentsatsiteorthestorageareashouldmakeuseofsuitableforkliftor
palettetrucks,orcomponentsshouldbeunloadedindividuallybyhand.Noliabilitycanbeassumedby
thesupplierforanydamagecausedbyimpropertreatmentormis-handlingofthecomponents.
6.4DimensionalTolerancesoftheFRP-CableManagementSystem
TheARCOsystemGRP-CableManagementSystemisproducedandsuppliedaccordingtoDINEN13706.
Visibledefects,productmarkingsandacceptablequalitylevelsareaccordingtosemi-finishedPultruded
material. The dimensional tolerances of the GRP-Components are according to DIN EN 13706, the
dimensionaltolerancesofthesteelpartsareaccordingtoDIN2768-1m.
6.5InstallationoftheSupportPosts
ARCOsystemisanelevatedcabletroughingsystem,intendedtobesupported,eitherdirectlyonposts
orhungfromwallsorsimilarstructures.Whensingletroughroutesaretobepostmounted,thepostof
choiceistheSigma100(drawing#VT11-P002-1200-3000).TheSigmaPostwaschosenbecauseofits
exemplaryperformancesupportingthecentralcrashbarriersofthemotorwaysoftheworld.
DependentuponthelocalgroundconditionstheSigmaPosts100fortheGRP-CableManagement
ARCOsystemcaneitherberammed,holedugorembeddedinpost-mix,paralleltotherailroadbeing
served.Sigmaposts100are1200mm,1500mm,1900mm,2500mmand3000mmlongandshouldbe
rammedorembeddedtoaminimumdepthof300mm.Rammingtendstobethemethodofchoicein
new,virgincableroutes.ApneumaticrammerfromGaykGmbH(www.gayk-baumaschinen.de)andthe
CobraPROepetroldrivenhammerfromAtlasCopcoLtd([email protected])have
beenfoundtobeparticularlysuitable.
� � �
GaykPneumaticRammerRammingSigmaPostsCobraPROePetrolHammer
Inareaswherethereisachanceofacablestrikeorthegroundisnotconsideredsuitableforarammed
solution,postsshouldbeembeddedinholeshand-dugorexcavatedbyauger,andback-filledusinga
suitablepostmix.ExamplesoftypicalembeddedSigmaPostinstallationsareshowninthefollowing
sketches,howeverifunsure,pleasereferyourparticularprojectrequirementbacktoyoursupplier.
Onoccasionsdual,ormultiplecablerunsrequirebespokesolutions.ARCOsystemSize2isdesignedto
carryaliveloadof90kg/m,butoftentheliveloadbeingcarriedismuchless.Insuchcases,itisoften
acceptabletomounttwo,oreventhreeARCOsystemtroughsonasingleSigmaPost,asshownbelow.
Insuchinstallations,careshouldbetakentoensurethattheSigmaPostsarenotoverloaded.
Consultationwithyoursupplierwillallowastructuralanalysistobeconductedwherenecessary,and
wheretheSigmaPostisdeemedtobeunsuitablebecauseoftheincreasedloading,analternativepost
willberecommended.InsuchcasesanHEAbeamwilloftenbethealternativechoice.
Sheet Size A1 594 x 841
Dra
win
g N
um
ber
Scale(s)
Drawing Number Revision
of
Sheet
Signed
Signed
Signed
Project
Status
Rev Date Description of Revisions Drawn
Designed
Drawing Title
Contractor(s)
DateSigned
Drawn
Checked
Approved
Chkd Appr
Date
Date
Date
ELR & Mileage
Alternative Reference
Suitability
Legend/Notes
3
W1005E-BCM-DRG-ECV-000003
W1005E-B
CM-D
RG-E
CV-0
00003
CONSTRUCTION
3
STANDARD TROUGH DETAILS
BCM-DRG-HVIF-083
JJF PM SH
SHEET 3
STUART HOLMES
PHILIP STATEN
PETER McDONAGH
JOSEPH FRANCIS
0 0.5 1.5 2.0 2.5m1.0
SCALE 1:25
using an approved safe method of working.
and competent contractors carrying out the work
These notes are based on the use of experienced
Construction
normally associated with this type of work:
Notes below are additional to hazards/risks
Safety, Health and Environmental Information
2
SCALE 1:25
TTS 200 SERIES TROUGH
TTS 200 TROUGH GRP TROUGH
STANDARD STRUCTURE GAUGE
IS TO BE INSTALLED CLEAR OF
OBSTRUCTED. CABLE CONTAINMENT
EXISTING REFUGES ARE NOT TO BE
SCALE 1:25
SINGLE TROUGH ON POST DOUBLE TROUGH ON POSTSCALE 1:25
SCALE 1:25
LOCATED ON A CUTTING
SINGLE TROUGH THROUGH ROUTE
SCALE 1:25
LOCATED ON A CUTTING
DOUBLE TROUGH THROUGH ROUTE
SCALE 1:25
SCALE 1:25
MASONRY WALL
TROUGH ROUTE LOCATED ON
CONCRETE WALL
TROUGH ROUTE LOCATED ON
ST4 CONCRETE SURROUND 300 DIA.
100
300
DIA.
100
330
300
DIA.
ST4 CONCRETE SURROUND 300 DIA.
FACE OF CONCRETE
FACE OF MASONRY
350
1000 H
AN
D DIG
550
ST
AN
D PIT
DIA.
300
ST4 CONCRETE SURROUND 300 DIA.
400
1000 H
AN
D DIG
1100
ST4 CONCRETE SURROUND 300 DIA.
300
DIA.
ST
AN
D PIT
NO
M.
NO
M.
EQUIPMENT SHOULD BE CONSIDERED
MAY OCCUR USE OF SAFETY HARNESS
STEEP GRADIENTS, RISK OF FALL
WORK TO BE CARRIED OUT ONHAZARD
HAZ
HAZ
IN PLACE
PERMIT TO DIG PROCEDURE TO BE
CUTTINGS HOWEVER APPROPRIATE
BURIED SERVICES/UTILITIES INHAZARD
Cii
Civ
GP POST ROUTE INSTALLATION
Civ PERSONNEL SAFETY DURING
INSTALLATION OF POST
Ciii. SLOPE STABILITY DURING
Cii. BURIED SERVICES
WITHIN WASTE
Ci. UNKNOWN POTENTIAL HAZARDS
XX/02/17C01
18/03/16
18/03/16
XX/02/17
18/03/16
C01
VARIOUS
Cii Cii
Cii Cii
750
750
900
1000
1:25
OR SIMILAR APPROVED
(VT1011-P002-1500) AT 6.0m CENTRES
CASTIONI SIGMA POST 1500mm LONG
AT 6.0m CENTRES OR SIMILAR APPROVED
CONNECTION BRACKETS (VT12-P002-A008)
(VT122596000PGK) ON STRAIGHT PLATE
CASTIONI GRP CABLE TROUGH & LID
1900 O/A
LL P
OS
T
1500 O/A
LL P
OS
T
AT 6.0m CENTRES OR SIMILAR APPROVED
CONNECTION BRACKETS (VT12-P002-A008)
(VT122596000PGK) ON STRAIGHT PLATE
CASTIONI GRP CABLE TROUGH & LID
OR SIMILAR APPROVED
CASTIONI SIGMA POST
OR SIMILAR APPROVED
CASTIONI SIGMA POST
OR SIMILAR APPROVED
(VT1011-P002-1900) AT 6.0m CENTRES
CASTIONI SIGMA POST 1900mm LONG
AT 6.0m CENTRES OR SIMILAR APPROVED
POST (VT1011-P002-A018-300mm x 300mm)
CASTIONI GRP CABLE TROUGH & LID
AT 6.0m CENTRES OR SIMILAR APPROVED
POST (VT1011-P002-A018-300mm x 300mm)
CASTIONI GRP CABLE TROUGH & LID
AT 6.0m CENTRES OR SIMILAR APPROVED
CONNECTION BRACKETS (VT12-P002-A008)
(VT122596000PGK) ON STRAIGHT PLATE
CASTIONI GRP CABLE TROUGH & LID
AT 6.0m CENTRES OR SIMILAR APPROVED
POST FIXING BRACKETS (VT1011-P002-A028)
(VT122596000PGK) ON OUT-HANGING
CASTIONI GRP CABLE TROUGH & LID
1900 O/A
LL P
OS
T
2500 O/A
LL P
OS
T
AT 6.0m CENTRES OR SIMILAR APPROVED
CONNECTION BRACKETS (VT12-P002-A008)
(VT122596000PGK) ON STRAIGHT PLATE
CASTIONI GRP CABLE TROUGH & LID
AT 6.0m CENTRES OR SIMILAR APPROVED
POST FIXING BRACKETS (VT1011-P002-A028)
(VT122596000PGK) ON OUT-HANGING
CASTIONI GRP CABLE TROUGH & LID
AT 6.0m CENTRES OR SIMILAR APPROVED
CONNECTION BRACKETS (VT12-P002-A008)
(VT122596000PGK) ON STRAIGHT PLATE
CASTIONI GRP CABLE TROUGH & LID
TO SUIT
& LID (VT122596000PGK) CUT
CASTIONI GRP CABLE TROUGH
6000mm MAX. POST CENTRES
1:2 MAX. SLOPE GRADIENT FOR POST ROUTES
SIMILAR APPROVED
ANCHOR BOLTS BY 'HILTI' OR
M8 GRADE 3.3 GALVANISED
SIMILAR APPROVED
ANCHOR BOLTS BY 'HILTI' OR
M8 GRADE 3.3 GALVANISED
330
2500 O/A
LL P
OS
T
300
DIA.
1000
1200 H
AN
D DIG
300
ST
AN
D PIT
Cii
AT 6.0m CENTRES OR SIMILAR APPROVED
CONNECTION BRACKETS (VT12-P002-A008)
(VT122596000PGK) ON STRAIGHT PLATE
CASTIONI GRP CABLE TROUGH & LID
ST4 CONCRETE SURROUND 300 DIA.
200
MIN.
350mm DEPTH TO MINIMISE EXCAVATION
OR SIMILAR APPROVED DRIVE FINAL
(VT1011-P002-1900) AT 6.0m CENTRES
CASTIONI SIGMA POST 1900mm LONG
400mm DEPTH TO MINIMISE EXCAVATION
OR SIMILAR APPROVED DRIVE FINAL
(VT1011-P002-2500) AT 6.0m CENTRES
CASTIONI SIGMA POST 2500mm LONG
300mm DEPTH TO MINIMISE EXCAVATION
OR SIMILAR APPROVED DRIVE FINAL
(VT1011-P002-2500) AT 6.0m CENTRES
CASTIONI SIGMA POST 2500mm LONG
1000 M
IN.
CL RAIL FOR HV ROUTE.
TROUGH ROUTE TO BE MARKED IN AGREEMENT WITH NETWORK 16.
BS 8500-1.
CONCRETE GRADE TO BE ST4 IN ACCORDANCE WITH 15.
DRAWINGS.
DRAWINGS TO BE READ IN CONJUNCTION WITH FEEDER ROUTE14.
AND PERMITS TO DIG.
WORK FOR EXCAVATIONS WHICH SHALL INCLUDE CAT SCANNING
CONTRACTOR TO HAVE IN PLACE APPROPRIATE SAFE SYSTEM OF13.
A FLUSH JOINT.
ALL TROUGHS TO BE MITRED WHERE REQUIRED TO PROVIDE 12.
ALL STEEL TO BE S275JR IN ACCORDANCE WITH BS EN 10025-2.11.
AS PER MANUFACTURERS INSTRUCTIONS.
CASTIONI GRP TROUGHS ERECTED AND FIXED TO SUPPORT POSTS10.
COPPER CABLE IS 1500mm.
MINIMUM ALLOWABLE BEND RADIUS FOR 630mm SINGLE CORE9.
DESIGNERS RISK ASSESSMENT No. WE1005-BCM-RAR-MPM-000013.
THIS DRAWING SHALL BE READ IN CONJUNCTION WITH THE 8.
NOTED OTHERWISE.
BRACKETS TO BE M8 GRADE 3.3 GALVANISED BOLTS UNLESS
ALL BOLTS SECURING GRP TROUGHS TO CASTIONI 'VT12 & VT1011'7.
PRODUCTS.
TREATED WITH ZINC RICH SPRAY OR SIMILAR APPROVED
ALL SITE DRILLED HOLES IN GALVANISED STEELWORK SHOULD BE 6.
6000mm c/c.
MAXIMUM SPACING OF GRP TROUGH SUPPORT POSTS IS 5.
MANUFACTURERS INSTRUCTIONS.
ALL PROPRIETARY PRODUCTS INSTALLED IN ACCORDANCE WITH4.
NR/L3/CIV/140 MODEL CLAUSES FOR CIVIL ENGINEERING WORKS.
ALL MATERIALS AND WORKMANSHIP IN ACCORDANCE WITH 3.
SYSTEM.
CABLE ROUTES FORMING PART OF THE TRACTION DISTRIBUTION
WITH NR/SP/ELP/27224 SPECIFICATION FOR INSTALLATION OF
ALL TROUGH ROUTES FORMING PART OF A CABLE ROUTE COMPLY2.
ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE STATED.1.
SCALE 1:25
AT EXISTING S&T TROUGH LOCATION
SINGLE TROUGH ON POST
EXISTING S&T TROUGH
A01 12/01/16 FIRST ISSUE JJF PM SH
138920 HV INDEPENDENT FEEDERS
BRACKET (VT1011-P002-A01A037)
TO GROUND MOUNTED
CASTIONI TRANSITION ELEVATED
15°
TO NEW GRP POST ROUTE
DETAIL C - ELEVATION ON TRANSITION FROM NEW SURFACE TROUGH
B01 17/02/16 ISSUED FOR IDC JJF PM SH
LOCATED ON A CUTTING
TRIPLE TROUGH THROUGH ROUTE
SCALE 1:25
2500
1100
1000
400
AFIT FOR CONSTRUCTION
ISSUED FOR CONSTRUCTION
B02 18/03/16 JJF PM SHISSUED FOR FORM 3 REVIEW
BCM
!
!
!!
! !
!
DRIVE FINAL 350mm TO MINIMISE EXCAVATION
Regardlessofsoiltype,SupportPostshavebeenusedsuccessfullyinflatandembankmentlocations.
Themid-railtracktopostdistanceshouldbeconstant,andasspecifiedbytheclient.Inhillsidelocations
withlimitedaccess,customlengthscanbeprovidedinordertomaintaintherecommendedcantilever
lengthof100to350mmabovegroundlevel.Theminimumrecommendedburialdepthmustbe
maintainedotherwisetheperformanceguaranteewillbenullified.
6.6InstallationofStandardHead
Thepre-assembledstandardheadsareavailableintwosizestosuitARCOsystemSizes1and2(Drawing
#1313-0010-00&1313-0012-00).Theseheadsorstraightconnectionplatesexhibitthestandardfeature
common to all ARCOsystem bracketry; the upturned edges that guide and align the troughs. The
standardheadsareusedwithGRP-troughsizes 1and2 (DrawingNr.A1011-P002-C001a&C003a).The
headsshouldbeinstalledatoptheSigmaPost100.Theheadallowsheightadjustmentofupto70mm,
usingM12screwsatatorqueof86Nm,ensuringrapidinstallationofstraightruns.
StandardHeadSize1StandardHeadSize2
6.7AssemblyoftheFRP-Trough
Theprofiled lowersectionoftheGRPtroughsmirrortheup-turnedsoleplatesofthesteelbrackets .
The GRP-Troughs, Sizes 1 and 2 (Drawing Nr. A1011-P002-C001a & C003a) are inserted into the pre-
assembledstandardheadssize1+2,slidingthebaseofthetroughintotheupturnedsidesofthesole
plate.AttheotherendoftheGRP-trough,anotherstandardheadsize1or2(Drawing#1313-0010-00&
1313-0012-00)shouldbeinsertedintothesoleplateofthebracketandfixedtotheSigmapost(torque
momentoftheM12screwis86Nm).TheGRP-Troughsshouldbefixedinthemiddleofthesoleplateof
thestandardheadwitha3mmgapbetweenthetwolengths.Avarianceof20mmfromthemiddleis
acceptable.Traditionalmethodsareusedtolevelthetroughrunusingastoutcordandaspiritlevelin
theGRP-trough.
! �
InstallationofSize2GRPTroughduringinstallation
CareneedstobetakentoallowforthethermalexpansionoftheGRP-troughSize1or2(DrawingNr.
A1011-P002-B001/002)byleavinga3mmgapbetweeneachindividuallengthofGRP-trough.
Theheightofthestandardheads,sizes1and2,isadjustedbytighteningtheM12screwstoamaximum
torqueof86Nm.ThescrewsareprotectedbyusingflatwasherstoA12DIN9021andspringwashersto
12DIN127.TheGRPtroughsareinstalledbetweenthesupportsandlevelledwiththeaidofaspiritlevel.
Custom installations around obstacles and incorporating changes in height can be readily
accommodatedwithcarefulplanning.Bypassingsignals,catenarymastsandthelikeisreadilymanaged
on-site because of the ease of cutting of the GRP toughs and lids, as well as the range of readily
availablebracketrysolutions.Thetroughsandlidscanbecutandmitredasnecessarytoaccommodate
directionalchangesintherailtrackortoavoidobstacles.Thecutandmitredtroughsandlidscanthen
beinsertedintoSinglePlaneSwivelbrackets(1313-0014-00&1313-0015-00) fordirectionalchangeson
one level. Where height and directional changes are necessary, Hinged Swivel Riser Brackets
(1313-0061-00&1313-0066-00)shouldbeused.
!!
Gap of 3 mm
�
HeightandDirectionalChanges
ItisimportantthattheGRPcabletroughandlidsmustnotbeundertensionwhen
installedontheSigmaPostsupports.
ThemaximumspanoftheGRPtroughsandlidsbetweentwoSigmapostsis6000mm.Thetroughsand
lidsmustnotbeextendedoverthislength.TroughandlidrunsshouldbeterminatedwithaSigmaPost
100.
6.8FasteningoftheFRPLids
Once the runof cableshasbeen laid inplace according to the client’s instructions, theGRPLids are
placedontheGRPtroughsusingalittledownwardpressuretoensureasnap-fit.Takecarehowever,to
ensurethatnodirtorgritorothercontaminationinterfereswiththeconnection.
!
!
�
Leave a 3mm gap between lid lengths to allow for thermal expansion of the lids. It ismore
common to fix lids onto troughs in a ‘stretcher bond’ rather than ‘stack bond’ pattern. The overlap
offersalittlemorestability.
ARCOsystemisreadilyinstalledonopenstretchesoftrack,enablingstraightrunsandsweeping
curvedlengthstobeputinplace,ensuringrapidinstallationprogresstobeachieved.
�
6.9AreaAdaptationsandHeightChanges
ArangeofARCOsystembracketryhasbeendesignedtoenablechangesinheightordirectionto
be accommodated with ease. Height changes in the cable runs are managed by the use of pre-
assembledhingedswivel riserbrackets(drawing#1313-0061-00&1313-0066-00).Thesebracketshave
theaddedbenefitofhorizontalswivel,toenabledirectionaswellasheightchanges.Theriserbracketis
deliveredpreassembled,andwillbemountedontheSigma100post.
OntherammedorembeddedSigmapost100theriserbracket is
mounted in the sameway as the standard head. The horizontal
GRP-troughs,aswellasthetroughstobelowered,mustbemitre
cut(GRP-troughsmustbecutalwaysonbothsideswithhalfthe
angleoftheheightchange,e.g.:15°equal15°/2=7.5°).Notethat
mitring troughs shortens their length, therefore post centres
needtobeadjustedtoaccommodateforthereducedlength.
In order to accommodate for longitudinal thermal expansion
theremustbeagapof3mm.TheGRP-lidsshouldbecutbefore
closing on to the GRP-troughs, mitred and cut to length if
necessary.Theraisedorloweredangleshouldnotexceed30°.
Alwaysensurethatthemaximumallowedbendingradiusofthecables
beinglaidisstrictlyfollowed!Laycablesintothecabletroughs.Donot
imposeexcessivehorizontalloadsontheARCOsysteminstallationwhenfeedingcablesfromdrums.Use
guidancesystemstoensuretrouble-freecablelaying.
6.10AvoidingObstaclesandUnevenGround
ObstaclescanbeavoidedusingtheSwivelBracket,whichallowsupto30odirectionchange.
As already stated in point 6.9 (Area Adaptions and Height Changes) the GRP-troughs and GRP-lids
shouldbecutandmitredwhen there isadirectionchange,andshortened ifnecessary (GRP-troughs
mustbecutalwaysonbothsideswithhalftheangleoftheheightchange,e.g.:15°equal15°/2=7.5°).It
isofteneasiermanagetheonsitefabricationoncethelidsareinplaceonthetroughs.
A typical maximum bending radius of 30° should not be exceeded, but always check the
recommendationsofthecablemanufacturer.AftertheassemblyoftheSwivelbracket,undo
thescrewsoftherotatingsupportmetalheadandinserttheshortenedmitredcabletroughs
into the steel support shoe. Theunit shouldbeadjusted inheight andfixedonto theSigma
post 100, (aspreviouslydescribed).Following this thecableductsshouldbeadjustedbefore
the loosened screws are tightened again. Whenever bypassing obstacles, it is essential to
maintaintheagreedworkingdistancebetweentherailtrackandthecableroute.
�
Pivot brackets (1313-0106 & 0107) enable gradual slopes to be tackled,whilst tilting brackets enable
ARCOsystemtroughstobemaintainedlevelonslopingground.
!
Tiltingbracketsonslopingground
6.11Out-hangingandWallBracketry.
Often elevated troughing needs to be installed in difficult, space limited or confined areas where
installationatopaSigmaPost isnotpossible. InordertoaccommodatetheseneedsarangeofOut-
hangingandWallMountedBracketsareavailable,offeringthesameheightanddirectionalcontrolas
SigmaPostmountedbracketry. This enables situations suchasbridge crossings, stationby-passesor
underpasses(dive-unders)tobetackledwithconfidence.
Outhangingorbridgehungbracketsaredesignedwithtoclamparoundthepostorbridgestructure,
with 4 x 12mm coach bolts passing through the front plate and bolted onto the backing plate, to
provideasecurefixing.
! !
Whenfixingtowalls,thebracketscaneitherbemounteddirectlyagainstthewallandfixedwithfour
anchorbolts,ormounteda90˚SigmaPost,againfixedwithanchorboltstothewall.Theselectionof
appropriateanchorboltswilldependuponthequalityofthesubstrate. Ifnecessary,additionalplates
canbeusedtospreadtheload.Anchorboltselectionandtheneedforloadspreadingplatesshouldbe
discussedwiththestructuralengineerresponsiblefortheinstallation
6.12BespokeSolutions
Veryoccasionally thestandardrangeofARCOsystembracketrywillnotaddressspecificcable routing
needs. In these circumstances, bespoke solutions can often be provided. Examples of such bespoke
solutionsareshownbelow.
SuchbespokesolutionsoftendemandtheuseofanalternativetoSigmaPosts,ifthebracketryistobe
postmounted. In such cases, depending upon the load and service requirements C channels orHEA
beamswilloftenbeused.ThesizeofCchannelorHEAbeamusedwilldependupontheanticipatedlive
loads in theparticular installation.Advice shouldbe sought fromyour supplier toensure the correct
selectionofsupportbeam.
Wheninstallingmulti-heightbespokesolutions,ensuresufficientclearancetoenablelidopening.
Size1
Size2
ca
.228
ca
.248
45°
ca
.293
ca
.183
NormGepr.Bearb.
(Toleranz)
Zust. Änderung Datum Name
(Oberfl.)
(Werkstoff)
Kabelkanal +geöffneten Deckel
Gr.1
26.08.16Datum
HinzName
Blätter
Blatt
1:5Maßstab entgraten
Kd.-Zg.-Nr.Kunde
DIN2768-m
Prg-Nr.
ca
.193
ca
.358
ca
.354
45°
ca
.443
NormGepr.Bearb.
(Toleranz)
Zust. Änderung Datum Name
(Oberfl.)
(Werkstoff)
Kabelkanal +geöffneten Deckel
Gr.2
26.08.16Datum
HinzName
Blätter
Blatt
1:5Maßstab entgraten
Kd.-Zg.-Nr.Kunde
DIN2768-m
Prg-Nr.
6.13TerminationsandTransitionstoGround-basedTroughs
For operational or topographical reasons a terminating run of elevated troughing may need to
transitionintoagroundbasedtroughsystem.MouldedFRPtransitionsforroutedevelopmentfroman
ARCOsystemSize1toSize2,aswellasfromanARCOsystemtroughtoavarietyofstandardconcrete
sizesareavailable,thatprovideaclean,faultlessroutecontinuation.
� �
ARCOsystemTransitions:Size1toSize2&ARCOsystemtoGroundBasedConcreteTrough
Also,whereacablerouteends,FRPtroughendcapsarealsoavailabletoprovideacleantermination.
Size1&Size2ARCOsystemEnd-caps
6.14CableOutlets
CableexitsfromthetroughruncanbemanagedwithadedicatedCableOutlet.CableOutlets,designed
to exit the trough fromeither the sideor base, are available for both Size 1 and Size 2, each in two
diameters,70mmand115mm,tosuitavarietyofcables.
BaseExitCableOutlets
SideExitCableOutlets
Thepositionforaslottedholeshouldbemarkedinthemiddleofthetroughbaseorsidewall,wherethecableexitisrequired,atleast500mmfromthenearestSigmapost100.Theslottedholecanbeeasilycuton-siteusingaholesawandjigsaw.Beforeputtingthecableexitinplaceandfixingittothetrough,theslottedholeshouldbede-burredandanycutedgessealedusingasprayresinseal.Withthecableexitinplace,thedivertedcableruncanbelaidtoearththroughaflexiblesteelorplasticpipe
Cable Exit 30° Size 1 Ø 70 mmItem No. VT1011-P002-A019
!
Kabelauslass seitlich Ø 70 mmArt.-Nr. VT11-P002-1085
Kabelauslass seitlich Ø 115 mmArt.-Nr. VT-11-P002-1086
6.15ColourCodedLidsandWarningMessages
Colourcodedlids,withimprintedmessagesifrequired,areavailable
when particular areas of cable route need to be highlighted. The
messagesareprintedontosurfaceveilsthatarepultrudedontothe
top layer of the lid, ensuring an encapsulated, long lasting, hard
wearingmessageasopposed toaprinted-onmessage that canbe
easilywornoff.
6.16AdditionalSecurity
In areaswhere additional security is preferred Stainless Steel Lid Closer Security Straps are available
witheithersideorbasefastening.
6.17SpecialComponentFloorBrackets
Althoughdesignedasanelevatedcabletroughsystem,ARCOsystemoccasionallyneedstobemountedat
groundleveltocompleteacablerun.Toaccommodatetheseneeds,specialbracketryisavailable.
GroundlevelARCOsystemInstallations
7InstallationVideo
ARCOsystem is a development of Castioni Kabelführungssysteme GmbH. An installation video,
demonstratingtheeasewithwhichARCOsystemcanbeinstalledcanbefoundatthefollowinglink…
https://tinyurl.com/ya335nnu
8Maintenance
ARCOsystem composite troughs and lids are manufactured from glass reinforced unsaturated
polyester. Contained within the resin is a UV inhibitor, which prevents sunlight yellowing and
degradationof the resin.Also, encasing theglass reinforcementwithin theprofile is a synthetic veil,
whichadds furtherprotection to theprofile. The result is aUVprotected,water resistant composite
troughandlidthatismaintenancefree,andwillprovideover50yearsservice.
Duringthe layingofthecablesortheclosingoftheGRP-lid it isrecommendedtochecktroughs, lids,
headsandSigmaPosts 100 foranyvisibledamage.Screwconnectionsshouldnotbeover tightened.
Theexactmaintenanceregimeshouldconformtotheclient’sspecificrequirements.
9ProductMarkingandNomenclature
Themarkingsystemisbaseduponthefollowingconvention…
! !
Nomenclature
Item Product Reference Product Category Commodity Group
Dimension Material Colour Component
ARCOsystem Size 1 Trough VT111006000PGT VT=Traffic Engineering 11 width=100mm length=6000mm P=Polyester G=Grey T=Trough
Lid VT111006000PGD VT=Traffic Engineering 11 width=100mm length=6000mm P=Polyester G=Grey D=Lid
Cable Duct VT111006000PGK VT=Traffic Engineering 11 width=100mm length=6000mm P=Polyester G=Grey K=Trough & Lid
ARCOsystem Size 2 Trough VT122506000PGT VT=Traffic Engineering 11 width=250mm length=6000mm P=Polyester G=Grey T=Trough
Lid VT122506000PGD VT=Traffic Engineering 11 width=250mm length=6000mm P=Polyester G=Grey D=Lid
Cable Duct VT122506000PGK VT=Traffic Engineering 11 width=250mm length=6000mm P=Polyester G=Grey K=Trough & Lid