10/9/2013 1 Nathan J. Birmingham, P.E. SMOKE CONTROL SYSTEMS Special Inspections and the Issues That Arise Smoke Control Designs Smoke Control Special Inspections Smoke Control Equipment and Controls PRESENTATION OVERVIEW

Ashrae Presentation 10-08-13

Embed Size (px)

DESCRIPTION

dgDg

Citation preview

Page 1: Ashrae Presentation 10-08-13

10/9/2013

1

Nathan J. Birmingham, P.E.

SMOKE CONTROL SYSTEMSSpecial Inspections

and the Issues That Arise

• Smoke Control Designs

• Smoke Control Special Inspections

• Smoke Control Equipment and Controls

PRESENTATION OVERVIEW

Page 2: Ashrae Presentation 10-08-13

10/9/2013

2

• Why do they exist?

– Life Safety

• Where are they provided?

– High-rise buildings

– Underground buildings

– Windowless Prisons/Jails

– Smoke Protected Assembly Seating

– Atria

SMOKE CONTROL SYSTEMS

TYPES OF SMOKE CONTROL

Image from ASHRAE Handbook of Smoke Control Engineering, 2012

• Pressurization Method

Page 3: Ashrae Presentation 10-08-13

10/9/2013

3

• Smokeproof enclosures

– Ventilated Vestibules at each stair entrance, or

– Stairwell Pressurization

• Elevator Pressurization

– In lieu of elevator lobbies

TYPES OF SMOKE CONTROL

• Exhaust Method

– Atria

– Malls

• Keep smoke away from occupants

• Exhaust High, Supply Low

TYPES OF SMOKE CONTROL

Images from A Guide To Smoke Control in the 2006 IBC

Page 4: Ashrae Presentation 10-08-13

10/9/2013

4

• Air Flow method

– Use of opposed airflow

– Often used in combination with exhaust method

TYPES OF SMOKE CONTROL

Images from NFPA 92B, Standard for Smoke Management Systems in Malls, Atria and Large Spaces, 2009 ed.

• Special inspections are a means that an AHJ uses to determine code compliance

• Required expertise in Fire Protection Engineering Mechanical Engineering and certification as an air balancer

• Many jurisdictions require an independent Special Inspector (MA does not)

• Statement of special inspection should be submitted as part of permit documents

SMOKE CONTROL SPECIAL INSPECTIONS

Page 5: Ashrae Presentation 10-08-13

10/9/2013

5

• Test plan

– Outline of testing

– Description of types of tests

– Prerequisite states of construction required

• Duct Leakage testing

• Damper Inspection

• Sequence Testing

• Performance Testing

SPECIAL INSPECTIONS

• Final inspection test report

– Summary of Results

– Compilation of inspection reports and any issues that were identified

– Data Sheets of Equipment

– Signatures of Inspectors and EOR

SPECIAL INSPECTIONS

Page 6: Ashrae Presentation 10-08-13

10/9/2013

6

• Installation and Component verification

– Is the right equipment getting installed?

• Equipment Functional Testing

– Is the equipment working properly?

• Sequence of Operations Testing

– Are the systems properly integrated?

• System Performance Testing

– Does the system perform as designed, as required?

SPECIAL INSPECTIONS

• Listings

– Smoke Control listings ≠ Fire Alarm listings

– UUKL UL 864

• BMS or Fire Alarm

EQUIPMENT AND CONTROLS

Images from UL 864, Control Units and Accessories for Fire Alarm Systems

Page 7: Ashrae Presentation 10-08-13

10/9/2013

7

1. Fire Fighters Override Panel

2. Automatic Signal

– Smoke Detector, Waterflow Switch

3. Manual or Automatic control from other source

CONTROL PRIORITIES

• VFD Keypad not locked out

• Automatic alarm fails to override “not in auto” VFD

• VFD installed with a Bypass

• Subsequent alarms cannot alter the sequence initiated by the primary alarm.

• Control functions split between systems

– Electrical and Mechanical specs not harmonized

CONTROLS – COMMON ISSUES

Page 8: Ashrae Presentation 10-08-13

10/9/2013

8

• Electrical specifications

– Fan shuts down on fire alarm

• Mechanical specifications

– Building Controls tells fan to start

SPLIT CONTROL FUNCTIONS

Images from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

• Always use single control system (Required by NFPA 92, 2012)

CONTROL FUNCTIONS

Images from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

Page 9: Ashrae Presentation 10-08-13

10/9/2013

9

• Status Indication for all equipment

– Red � Closed/Off

– Green � Open/On

– Yellow � Fault

– White � Normal

– Blue � Duct Detector (Boston)

• Confirmation of Status

FIRE FIGHTERS OVERRIDE PANEL

• Manual Controls Switches

– Should be provided for all fans, doors, and windows.

– Manual control for dampers can often be omitted.

FIRE FIGHTERS OVERRIDE PANEL

Image from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

Page 10: Ashrae Presentation 10-08-13

10/9/2013

10

• Leak tested to 1.5 times the max design pressure

• Leakage not to exceed 5 percent of design flow

DUCTS

• 1.5x minimum number of belts

• 1.15 service factor on motor

• Power disconnects not monitored

– At the VFD

– At the Fan

FANS – POTENTIAL ISSUES

Page 11: Ashrae Presentation 10-08-13

10/9/2013

11

• Positive status of flow

– Pressure switch

– Flow switch

– CT sensor

FANS – POTENTIAL ISSUES

Image from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

• VFDs not protected with 2-hour construction

• VFDs not separated from other mechanical equipment

• Control wiring to and from room containing VFD not protected with 2-hour construction

VARIABLE FREQUENCY DRIVES (VFD)

Page 12: Ashrae Presentation 10-08-13

10/9/2013

12

• End switches

• Damper actuator

– Stroke time limited to 75s or less

DAMPERS – POTENTIAL ISSUES

Image from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

• Doors and windows are confirmed open before they are.

• Atrium Systems using natural makeup air

– Provide UPS to powered door operators

DOORS AND WINDOWS – POTENTIAL ISSUES

Page 13: Ashrae Presentation 10-08-13

10/9/2013

13

• Standby power not Emergency power

• Secondary power source or ATS in same room as normal power transformers and switch gears

POWER SYSTEMS

WEEKLY SELF - TEST

Images from Klote, Milke Turnbull, Kashef, Ferreira Handbook of Smoke Control Engineering, ASHRAE 2012,

Page 14: Ashrae Presentation 10-08-13

10/9/2013

14

• Residential buildings containing both stair and elevator pressurization

• Exit discharge doors from pressurized stairs can be a challenge to closed under pressure

WHAT TO WATCH OUT FOR

Nathan J. Birmingham, P.E.

Code Red Consultants, LLC

[email protected]

www.crcfire.com

QUESTIONS?