Upload
well-lojumin
View
602
Download
37
Embed Size (px)
Citation preview
7/24/2019 Bactron Biocide
1/175
12MXMP Custom Unit
Marine Sanitation DeviceOperation & Maintenance Manual
PETRONAS
Purchase Order No.: PO/023/06/07/SE/TRD
Serial No.: 07-12MXMP-D012602
STDN Part No.: A210533PKS264
Date: October 2007
1110 Indust rial Boulevard Sugar Land, Texas 77478Telephone: 281-240-6770 Fax: 281-240-6762
http://www.severntrentdenora.com/Revision 05.4 OMSTD/Current
7/24/2019 Bactron Biocide
2/175
Preface
Preface
Construction of this Operations and Maintenance Manual
In an effort to provide a concise and informative equipment manual, Severn Trent De
Nora (STDN) has adopted the format of this particular Operations Manual based on its
past years of historical and field related experience in relation to the Omnipure Marine
Sanitation Device. Through a careful review of various customer maintenance
requirements and useful field service knowledge, this operations manual has become a
controlled standard per our ISO and Quality Assurance policies, and covers the entire
Omnipure product line.
This manual is intended to be used with the newer PLC (programmable logic controller)
controlled auto-maintenance unit. This manual addresses the most applicable
operation, maintenance and service related issues associated with the Omnipure unit. A
careful review and understanding of this manual should be achieved prior to operation
of this unit.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
3/175
Table of Contents
Table of Contents
The OmnipureMSD unit, as purchased, is described in detail throughout the following
Sections and Appendixs. This manual describes the operating, maintenance and
troubleshooting aspects of the MSD unit.
LIST OF CHARTS & TABLE DIAGRAMS ................................................................. SECTION A
MSD UNIT INSPECTION AND INSTALLATION........................................................ SECTION B
WARRANTY ............................................................................................................... SECTION C
Omnipure Performance Guaranty........................................................................................ C1
Limited Warranty.................................................................................................................. C2
WARNINGS, SYMBOLS, & SAFETY ......................................................................SECTION 1.0
Chemical Hazard..................................................................................................................1.1
Electrical Hazard..................................................................................................................1.2
Biological Hazard .................................................................................................................1.3
Fire/Explosion Hazard..........................................................................................................1.4
Warning & Safety Symbology ..............................................................................................1.5
OMNIPURE MSD UNIT ............................................................................................SECTION 2.0
General System Overview ...................................................................................................2.1
General Process Description ...............................................................................................2.2
FEATURES AND OPTIONS (IF APPLICABLE) ...................................................... SECTION 3.0
MAJOR COMPONENTS..........................................................................................SECTION 4.0
Control Panel .......................................................................................................................4.1
V-1 Surge Tank....................................................................................................................4.2
V-1 Surge Tank Level Switches...........................................................................................4.3
Macerator Pump...................................................................................................................4.4
Electrolytic Bookcell ............................................................................................................. 4.5
V-2 Effluent Tank .................................................................................................................4.6Positive Vent ........................................................................................................................ 4.7
COMMISSIONING....................................................................................................SECTION 5.0
Overboard Discharge Pump ................................................................................................5.1
Blower Option....................................................................................................................... 5.2
Water Powered Eductor Option ...........................................................................................5.3
O&M, Rev. 5.5 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
4/175
Table of Contents
COMMISSIONING (CONTINUED) ...........................................................................SECTION 5.0
Brine Option ......................................................................................................................... 5.4
Lift Station Coordination.......................................................................................................5.5
Sodium Sulfite Injection System (De-chlor)..........................................................................5.6
OPERATIONS ..........................................................................................................SECTION 6.0
Controls................................................................................................................................ 6.1
OIT Message and Alarm Index ............................................................................................6.2
Liquid Flow Paths.................................................................................................................6.3
Normal Operation.................................................................................................................6.4
Cell Flow Reversal Function ................................................................................................6.5
Manual V-2 Tank Blowdown & Auto V-2 Blowdown.............................................................6.6
Emergency V-1 and V-2 Pump Down .................................................................................. 6.7
TROUBLESHOOTING .............................................................................................SECTION 7.0
Firing Board Troubleshooting............................................................................................... 7.1
SCR and Diode Troubleshooting .........................................................................................7.2
MAINTENANCE .......................................................................................................SECTION 8.0
Macerator Pump...................................................................................................................8.1
Rectifier Firing Board ........................................................................................................... 8.2
Bookcell................................................................................................................................8.3
SPARE PARTS LISTINGS.......................................................................................SECTION 9.0
TABLES AND DIAGRAMS ....................................................................................SECTION 10.0
TEST REPORTS AND CERTIFICATIONS ............................................................SECTION 11.0
ENGINEERING DRAWINGS..................................................................................SECTION 12.0
UNIT BILL OF MATERIALS................................................................................... SECTION 13.0
EQUIPMENT DATA SHEETS ................................................................................SECTION 14.0
QA DOCUMENTS .................................................................................................. SECTION 15.0
VENDOR CUT SHEETS.........................................................................................SECTION 16.0
O&M, Rev. 5.5 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
5/175
Section A
SECTION A: LIST OF CHARTS & TABLE DIAGRAMS
Section/Figure/Table Number
Typical Liquid Flow Path for Normal Operation ......................................Figure 6-1
Manual Cell Draining ..............................................................................Figure 6-2
Manual V-2 Blowdown..........................................................................Figure 6-3A
Auto V-2 Blowdown ..............................................................................Figure 6-3B
Emergency V-1 Overboard Pumpdown................................................Figure 6-4A
Emergency V-2 Overboard Pumpdown................................................Figure 6-4B
Quick reference for Control Panel switches and alarms.......................... Table 6-1
SCR Assembly Test ...............................................................................Figure 7-2
MSD Troubleshooting Guide ................................................................... Table 7-1
Firing Board Troubleshooting Guide........................................................ Table 7-2
SCR and Diode Troubleshooting Guide .................................................. Table 7-4
Macerator Pump Parts Replacement Guide ............................................Table 8-1
Macerator Pump Mechanical Seal Replacement Guide .......................... Table 8-2
Macerator Pump Ball Bearing and Oil Seal Replacement Guide............. Table 8-3
Macerator Pump Axial Cutter Adjustment Guide ..................................... Table 8-4
Rectifier Firing Board Replacement Guide ..............................................Table 8-5
Firing Board Terminals and Signal Names ..............................................Table 7-3
Firing Board Rev. 7 and Earlier ............................................................Figure 7-1A
Firing Board Rev. 8...............................................................................Figure 7-1B
Drain, Inspect, and Clean the Bookcell.................................................... Table 8-7
Bookcell Cleaning and Electrode Replacement.......................................Table 8-8
O&M, Rev. 5.5 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
6/175
Section A
SECTION A: LIST OF CHARTS & TABLE DIAGRAMS (CONT.)
Section/Figure/Table Number
Ball Valve Replacement ..........................................................................Table 8-9
Overboard Discharge Pump Disassembly Table................................... Table 8-10
Overboard Discharge Pump Reassembly Table....................................Table 8-11
Typical Omnipure Diagram..............................................Section 10.1 Figure 10-1
Treatment Capacities Table.............................................. Section 10.1 Table 10-1
Unit Dimensions and Weights........................................... Section 10.1 Table 10-2
Unit Utility Connections and Connections......................... Section 10.1 Table 10-3
Customer Installed Piping Connections (standard unit).... Section 10.1 Table 10-4
Unit Functions at OIT Screen ........................................... Section 10.1 Table 10-5
Operating Current and Voltage chart................................ Section 10.1 Table 10-6
Daily Inspection chart ....................................................... Section 10.1 Table 10-7
Preventative Maintenance Schedule ................................ Section 10.1 Table 10-8
Bookcell Diagrams and Parts Table ................................................... Section 10.2
Macerator Pump Diagram .................................................................. Section 10.3
Macerator Pump Curve at 3450-RPM's.............................................. Section 10.3
Macerator Pump Parts........................................................................ Section 10.3
O&M, Rev. 5.5 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
7/175
Section B
SECTION B: MSD UNIT INSPECTION & INSTALLATION
Preliminary Inspection: Carefully examine the shipping crate (if applicable) or
other packaging for visible damage. If damage is noticed, DO NOT proceed with
uncrating or unpacking of the unit until the carrier is notified and an insuranceadjuster appears on the scene as a witness.
NOTE
DO NOT return the damaged goods to the factory. Severn Trent De
Nora (STDN) cannot assume responsibility for any shipping damage.
Uncrating: If no damage to the container is evident, proceed with unpacking.
Inventory the ejector, seawater strainer and other loose components against the
packing list. Examine the unit for damage, such as dented cabinets, broken piping,
and the like. If there are any irregularities, notify the carrier before proceeding
further. DO NOTattempt on-site repairs, which could invalidate the claim and void
the STDN warranty.
Equipment Location: Space considerations often dictate where the MSD will be
located in the vessel/platform. If possible, install the unit above the waterline (to
eliminate the need for an overboard discharge pump), immediately below the
sewage collection header or holding tank, and in an area subject to regular
inspection. Provide ample clearance around and over the skid for maintenance andservice. The skid may be bolted or welded to the deck.
Daily Inspection: The Omnipure unit should be inspected on a daily basis to
detect impending malfunctions early and to insure the MSD unit is operating
properly. See Table 10.7 for a Daily Inspection chart.
Installation of MSD Unit: With the exception of the Model 15MX, OmnipureMSD
units are designed to pass through hatchways and standard doorways. Some
disassembly may be required. Consult Section 12.0 for skid dimensions.
Section 10.0 will detail the weights, utility requirements, and recommended pipe
sizes for particular Omnipureunits.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
8/175
Section B
7/24/2019 Bactron Biocide
9/175
Section B
Long Term Storage: To insure proper storage of the OMNIPURE MSDs for
prolonged periods of time:
1. Close all sewage, seawater feed, and air lines to the unit.
2. Flush all tanks, pumps and piping with fresh water until free of any sediment.
Completely drain the unit.
3. One of the following methods should be used to protect pump seals and
housings:
(A) Fill pumps with ethylene glycol solution (50% ethylene glycol, 50%
water) or automotive anti-freeze, which is ethylene glycol mixture.
Expected ambient temperature should not be less than temperature
rating of additive.
NOTE
Pumps should be rotated once per month.
(B) Remove rotating parts and seal sets from pumps, wrap in oilcloth
and place in anti-corrosion packing. This method offers maximum
protection.
4. Install desiccant pack in control panel, close door and then disconnect from
power.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
10/175
Section C
SECTION C: WARRANTY
The MSD Warranties and Guarantees are included in detail in the following sections.
C1: OMNIPURE PERFORMANCE GUARANTY
Severn Trent De Nora, LLC (STDN) guarantee that OmnipureSewage Treatment
Units will meet IMO and USCG Type II specifications applicable at the time of
manufacture when installed, operated and maintained in accordance with our
instructions.
C2: LIMITED WARRANTY
Severn Trent De Nora, LLC warrants the equipment of its manufacturer to be free
from defects in workmanship and materials for a period of 12 months after first
startup, or 18 months after shipment, whichever occurs first. This Warranty applies
only to the original BUYER for new and unused equipment and cannot be altered or
changed by STDN employees or its representatives. Warranty related repairs
attempted and/or executed by our authorized representatives shall only apply and is
extended when supported in writing by Severn Trent De Nora, LLC.
Where equipment sold hereunder is used with attachments and/or modifications,
which have not been recommended, or approved by STDN in writing, such use shall
not be considered normal and this Warranty shall not apply.
STDNs liability is limited to the replacement or repair of defective parts returned
freight prepaid by BUYER to a location to be specified by STDN. Repaired parts
shall be returned to BUYER F.O.B. shipping point. When circumstances permit,
STDN will invoke for the benefit of the BUYER, the Guarantee or Warranty of
STDNs vendor for equipment or materials furnished, but not manufactured by
STDN.
This Warranty does not extend to, and STDN assumes no liability for, consequentialand/or secondary damages, or loss of any kind sustained directly or indirectly as a
result of a defect in any equipment, material or installation. STDN shall in no event
be liable in an amount exceeding the purchase price on the equipment and
transportation charges thereon.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
11/175
Section C
Severn Trent De Nora, LLC makes NO Warranties regarding equipment
manufactured by it or no others (including without limitation, warranties as to
merchantability and fitness for a purpose), either expressed or implied, except as
provided herein. The foregoing shall constitute the exclusive remedies of BUYER
for any breach by STDN Corporation or its Warranties herein.
All information contained herein is based on data believed to be accurate, however,
errors and/or design changes are possible. It is the Buyers responsibility to
determine suitability for his own use of the products described.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
12/175
Section 1.0
SECTION 1.0: WARNINGS, SYMBOLS AND SAFETY
This section covers the general Warnings and Safety ideals associated with this
Omnipure Marine Sanitation Device (MSD) unit. Also, detailed in Section 1.5 is
the prescribed Warning and Safety symbology. These symbols are used throughout
this Operation and Technical manual as visual safety reminders. It must be noted
that the MSD unit is a device used in raw sewage treatment application where a
strong oxidizing agent is involved.
There are four broad groups of potential hazards that the user must be familiar with
when operating this equipment.
1.1: CHEMICAL HAZARD
This MSD unit generates a sodium hypochlorite solution through the electrolysis of
seawater during unit operation. The resultant concentration of the sodium
hypochlorite is very low at 300-ppm (maximum), as compared to 14,000-ppm for
household bleach. Although this concentration of sodium hypochlorite is fairly low,
caution must still be used due to the caustic nature of the hypochlorite product. As
detailed in Section 1.5, the user should exercise caution and wear suitable protective
safety gear when working around, or handling this sodium hypochlorite product.
Avoid prolonged exposure to the sodium hypochlorite vapors. Inhalation can result
in headaches, loss of coordination, irritation to bronchial passages and, in severe
cases, unconsciousness. Ingestion of the product can be lethal.
Muriatic Acid (dilute hydrochloric acid) is occasionally used in cleaning parts of this
MSD unit. Again, the user should exercise caution and wear suitable protective
safety gear when working around, or handling this form of acid.
DO NOT allow hydrochloric acid to come into contact with sodium
hypochlorite solution. Acid shall NEVER be allowed to enter the V-2
Effluent Tank; this would cause a chemical reaction that could generate
dangerous quantities of chlorine gas.
NOTE
Always add acid to water, NEVERwater to acid.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
13/175
Section 1.0
The following are the various associated treatment regimes for related injuries:
Treatment of Eye Burns Sodium Hypochlorite or Acid
Irrigate the eyes immediately, before moving the patient for medical
treatment. If an industry approved eyewash solution is not available, use agenerous amount of fresh water. Irrigate for at least 15 minutes, while
holding the eyelids open and rotating the eyes. Seek immediate medical
treatment.
Treatment of Skin Burns Sodium Hypochlorite or Acid
Apply generous amounts of fresh water onto the burned area. Carefully
remove the affected clothing. DO NOT neutralize acid with an alkaline
solution. Seek immediate medical treatment.
Treatment of Ingestion or Gassing Sodium Hypochlorite
Seek emergency medical assistance immediately. If the patient has been
gassed, remove him/her from the contaminated environment as quickly as
possible as soon as it is safe to do so. If NaOCl (sodium hypochlorite) has
been swallowed, DO NOT induce vomiting. Keep the patient warm and in a
restful state. If breathing stops, begin performing CPR and continue until the
patients care is taken over by trained medical personnel.
1.2: ELECTRICAL HAZARD
The MSD unit utilizes and produces electrical currents/voltages, which can be lethal.
DO NOT operate this device with the access panels removed. The user(s) must
ensure that no foreign objects are allowed to pierce the electrical interconnecting
cables or lying across the internal electrical connections, which will result in electrical
shorts.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
14/175
Section 1.0
Electrical Safety Lockout/Tagout method
STDN encourages utilization of the lockout/tagout safety procedure when servicing
any electrical circuit or any physical rotating gear associated with this equipment.
The lockout/tagout procedure will aid in the prevention of deadly electrical shock andother hazardous situations. A color-coded, industry standard, lockout and tagout kit
should be utilized for accomplishing a successful maintenance operation. Any
individuals responsible for overseeing of this equipment should be trained using the
lockout/tagout procedures.
The following is the suggested general lockout/tagout procedure:
1. Notify all affected personnel that a lockout function is to begin.
2. Initiate an equipment shutdown of the entire system per the operating
instructions of the equipment.
3. Locate the dedicated power feeder and its associated circuit breaking
protection devices.
4. Open the appropriate electrical service power feeders, removing electrical
power from the equipment.
NOTE
If the electrical power is shut down the servicing individual shall keep thepadlock key in his/her possession during the required maintenance
period. This will ensure that no person can re-apply power to the circuit.
5. Apply a lockable padlock to the lockout hasp from the lockout/tagout kit.
6. Before servicing the equipment, attach an industry tagout notification card to
the locked out service.
NOTE
A typical card will include areas for the servicemans name, department
and date of expected completion. This notification tag is to be solely
removed by the responsible serviceman who initiated the lockout
procedure.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
15/175
Section 1.0
7. After all service has been performed, the initiating service person shall
remove the notification tag and file it accordingly into the maintenance
records.
8. Remove padlock from the safety hasp.
9. Remove hasp from the opened circuit protection device.
NOTE
The padlock, padlock key and safety hasp should be returned to the
lockout/tagout kit for future use.
10. Close electrical power feeding circuit to the serviced equipment.
11. Perform equipment system startup per operating procedure.
1.3: BIOLOGICAL HAZARD
The MSD unit collects and processes untreated sewage, which may be
contaminated with viral and organic parasites. These parasites are transmitted
orally, through mucus membranes, and through open wounds. Extreme caution
must be exercised to avoid direct contact with the sewage. Upon coming into
contact with sewage, immediately wash the contact area with a disinfectant soap,
shower and change into clean clothing. DO NOTeat, smoke, or perform any hand-
to-mouth activity until thoroughly decontaminated. Seek immediate medical
attention for cuts, abrasions and any puncture wounds that may have been exposed
to the sewage.
Clean up any spills that may have occurred and immediately disinfect the entire
MSD area.
1.4: FIRE/EXPLOSION HAZARD
A small quantity of hydrogen gas is produced as a byproduct of theelectrochlorination process of the MSD unit. The ventilation system must remain
functional at all times to ensure that the concentration of byproduct gas is kept below
the hydrogens explosive limit.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
16/175
Section 1.0
In the event of a suspected vent gas leak, shut down all electrical equipment in the
immediate area and any other possible ignition sources. Thoroughly vent all
overhead spaces to dissipate the suspected gas.
1.5: WARNING AND SAFETY SYMBOLOGY
A group of visual safety reminders are found throughout this operating manual. The
safety symbols are incorporated in this manner so as to afford the user or operator a
quick visual representation of a notable hazard or safety advisory.
The individual warning/safety symbols are shown in this section with a helpful
description of each symbol.
Due to the sensitive nature and potential hazards of the electrical
circuits involved in specific trouble shooting tasks, only knowledgeable
individuals should perform the electrical checks. If for any reason an
electrical component of this equipment is in question, or is not operating
properly, seek a qualified Electrician to perform any checks and/or
repairs.
The STOP symbol is used to denote an operational or functional task
that requires very explicit instructions and/or user qualification. Upon
any section of this manual where this symbol is noted. All instructions
should be fully read prior to performing any task.
The WARNING symbol is used throughout this manual to inform the
user(s) that the task to be performed may cause bodily harm or death, if
specific instructions and guidelines are not followed accordingly.
User (s) should understand that the particular chemical or chemical
combination is highly corrosive and can cause serious injury.
Appropriate personal safety precautions should be taken to ensure
user(s) safety.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
17/175
Section 1.0
First Aid required or seek professional medical assistance
-or-
Render specific medical aid.
The CAUTION symbol is used throughout this manual to inform the
user(s) that the task to be performed may cause equipment damage, if
specific instructions and guidelines are not followed accordingly.
Prior to working on equipment, place all switches, and circuit breakers
in their open (off) position, close valves lockout and tag them
DANGER, SHOCK HAZARD or DO NOT OPERATE. DO NOT
change position of any tagged switch.
ec an ndv dua
7/24/2019 Bactron Biocide
18/175
Section 2.0
SECTION 2.0: OMNIPURE MSD UNIT
The Omnipure System manufactured by Severn Trent De Nora, LLC is a self
contained, Marine Sanitation Device (MSD) that meets the United States Coast
Guard (USCG) requirements of 33 CFR 159. This MSD is USCG Type II certified
and IMO (International Maritime Organization) approved for overboard discharge in
territorial and international waters. Copies of the applicable Certificates of
Compliance are contained in Section 11.0 of this manual.
All numerical data included in this manual and are in English and Metric units.
2.1: GENERAL SYSTEM OVERVIEW
The following is a MSD general description of the operating process. STDN also
produces a Process Module (PM) Omnipureunit where the V-1, Collection Tank
and V-2, Residence Tank are supplied by the customer and not provided on the
Omnipure skid unit. Process Modules are identical in function to standard skid
units with tanks. Process Modules use customer-constructed tanks or preexisting
tanks in the vessel to save space and/or simplify installation. The MSD unit is
versatile and may be installed on ocean going vessels, and fixed or mobile offshore
platforms. The complete skid mounted system consists of pre-assembled Schedule
80 PVC piping and valve works, mounting skid, tanks, control panel/power supply,
bookcell, and macerator pump. The process piping on the unit is divided into
replaceable sections via unions or union type ball valves. The piping and valves
included in this MSD unit meets ASTM D-1784 industry standards.
The following description is for an Omnipureunit, not a Process Module although
the general operation is the same. This generic overview does not specifically detail
every operating component of the system. The various components are described
in detail in Section 4.0 of this manual.
Process Modules CANNOT be factory calibrated for the proper
flowrate. Others supply the tanks and some piping, so the system
flowrates must be field set at the time of start-up.
See Section 3.0 for Custom features and operating notes.
NOTE
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
19/175
Section 2.0
2.2: GENERAL PROCESS DESCRIPTION
Raw sewage is collected from toilets, sinks, showers, urinals, and associated
sanitary waste systems and is introduced into the MSDs V-1 Collection Tank. The
V-1 tank incorporates a float type level switch assembly. This level assembly
initiates the start and stop sequences of the MSD unit when the unit is in the Auto
mode. When V-1 tank level rises, the level switches are actuated and the treatment
unit starts. The raw sewage contained in the V-1 tank is finely ground, or
macerated, through a specially designed macerator pump. From macerator pump
discharge, a portion of the macerated sewage is returned to the V-1 tank through a
calibrated orifice plate. The remainder of the macerated sewage is then mixed with
a controlled amount of seawater as it is pumped through a second calibrated orifice
plate to the Omnipure Bookcell. Seawater enters the MSD unit between the
bookcell and the discharge of the macerator pump via a strainer and flow controller.
This flow controller limits the seawater flow to a predetermined value based on
specific treatment capacities of the various MSD units. The use of calibrated orifice
plates and the seawater flow controller allows liquid flow to the bookcell to be
maintained at the correct rate for each specific unit.
In locations where the ambient seawater salinity is low, an optional SALT ADD unit
can be supplied to allow proper operation.
The MSD unit oxidizes and disinfects raw sewage by means of an electrochemical
reaction in the bookcell. The electrochemical reaction is the result of D.C. voltage
applied to specially designed anode and cathode plates (electrodes) within the
bookcell. The sewage and seawater slurry from the macerator pump flows between
the charged electrodes. The seawater acts as an electrolyte for DC current flow
between the anode and cathode plates. The chloride salts of the seawater are
decomposed by electrolysis to form sodium hypochlorite. The electrochemicalreaction and the resulting production of sodium hypochlorite kills harmful coliform
bacteria and oxidizes the organic compounds in the sewage stream. One pass
through the bookcell kills nearly 100% of resident bacteria and oxidizes between 90
to 95% of the organic compounds found in normal sewage.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
20/175
Section 2.0
The electrical power required to operate the bookcell is derived from the treatment
units internal D.C. power supply. Each MSD model has a specific, fixed current
associated with its bookcell. The amount of D.C. current applied to the bookcell
determines the amount of sodium hypochlorite produced.
After the slurry of sewage and seawater has been electrolyzed in the bookcell, the
stream is routed into the MSDs V-2, Residence Tank. The stream enters the top of
V-2 tank through a vertical downcomer pipe. This pipe is internal to the V-2 tank.
The downcomer pipe outlet is near the bottom of the V-2 tank. The downcomer
reduces velocity of incoming process stream and encourages degasification. During
the electrolysis process, small amounts of hydrogen and other gases are produced
as byproducts. The downcomer works in conjunction with a positive vent system to
extract gases from the process and send them to the atmosphere.
The V-2 tank is sized to provide a minimum 30-minute retention time between the
entry of treated sewage (effluent) at the bottom of the V-2 tank and subsequent
discharge from the top of V-2 tank to the sea.
This 30-minute retention time assures that any remaining bacteria will be killed and
allows any partially oxidized particles to settle. These particles (consisting mostly of
cellulose) are recirculated into the V-1 tank for re-treatment through the blowdown
line during the backflush and blowdown maintenance procedure.
After retention time, the effluent overflows from the top of V-2 tank. It is normally
gravity drained overboard through customer piping. During installations where V-2
tank discharge is below the waterline, an optional stainless steel centrifugal
overboard pump can be supplied to discharge the treated effluent.
The United States Coast Guard (USCG) Certification, which STDN holds for each
Omnipure
model, strictly dictates the parameters for operation and quality ofeffluent discharged from the MSD system. The USCG Certificate in effect when this
Omnipuremodel was manufactured can be found in Section 11.0 of this manual.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
21/175
Section 3.0 Custom Features and Options
SECTION 3.0: CUSTOM FEATURES AND OPTIONS
This Omnipure MSD unit configuration incorporates the following Custom
Features. These additional features allow the MSD unit to perform in a manner
different from the standard MSD unit.
Chart on the next page lists specific information concerning purchased equipment.
The part number printed on the front cover of this manual can be broken down to
detail the equipment model and size, development level, supply power requirements,
standard options, and special customer requirements or features.
The part number below is an example only. This is to illustrate how the number can
be broken down for specific information.
Example: A150554AFTVS030
The part number is arranged as follows:
(A) = Omnipure Unit
(15) = Model 15MX
(05) = STDN Product Development Level
(5) = Voltage Designation(440-480VAC)
(4) = Ph/Hz Designation(3 Ph. / 60Hz)
(A) = Overboard Pump Option
(F) = Custom Skid
(T) = Dual Macerator Pumps
(V) = Ultrasonic Level Control System
(S030) = Description of Special Features and Options
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
22/175
Sectio
PRODUCT LINEEX: (A)
MODEL IDENTIFIER(15)
PRODUCT DEV. LEVEL(05)
POWERREQUIREMENTS
(54)
UNIT SIZE
NUMBER 5=VOLTAGE DESTINATION
1 = 110V2 = 220V3 = 380V4 = 415V5 = 440-480V6 = 575-600V7 = 460V
NUMBER 6=Ph/Hz DESIGNATION
A
=OMNIPUREPRODUCT
PRODUCTDE
VELOPMENTLEVEL
Anydesign/componentchangewillincreasethe
developmentleveltothenextnumericalincrement.
01 = 4MS02 = 6MC03 = 6MPM04 = 6MS05 = 7ME06 = 8MC07 = 8MPM08 = 8MS09 = 12MC10 = 12MPM11 = 12M12 = 12MS13 = 12MX Unit14 = 12MXPM15 = 15MX Unit
16 = 15MXPM17 = 15MX Compact (Left)18 = 15MX Compact (Right)19 = 12MXPM w/Multi-Pass Cell20 = 15MXPM w/Multi-Pass Cell21 = 12MX Unit Multi-Pass Cell22 = 15MX Unit Multi-Pass Cell23 = 6MV24 = Next Available Std.
1 = 1 Phase, 50 Hz2 = 1 Phase, 60 Hz
3 = 3 Phase, 50 Hz4 = 3 Phase, 60 Hz5 = 1 Phase, 50/60 Hz6 = 3 Phase, 50/60 Hz
A =B =
D =H =M =P =E =F =G =I =
J =K =L =N =Q =
R =
T =U =V =W =X =Y =Z =Z1 =Z2 =Z3 =Z4 =Z5 =Z6 =
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
23/175
Section 3.0 Custom Features and Options
SPECIAL FEATURES AND OPTIONS
This OmnipureMSD unit configuration includes CPVC piping as opposed to PVC.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
24/175
Section 4.0 Major Components
SECTION 4.0: MAJOR COMPONENTS
This MSD unit as purchased is fitted with the standard major components listed on
the following pages. Please also see Section 3.0 if this MSD unit was constructed in
a custom configuration.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
25/175
Section 4.1 Control Panel
SECTION 4.1: CONTROL PANEL
Refer to system drawings in Section 12.0of this manual for control panel details and
electrical schematics.
The standard OmnipureControl Panel is a NEMA 4X rated enclosure located on
the MSD unit skid. The Control Panel is pre-wired to all components located on the
MSD skid and controls all MSD functions. All control logic elements, whether relay
or microprocessor based, are housed in the panel. Also contained in the panel are
the bookcell DC power supply, control voltage transformer, and motor-starters. Unit
status indicators including the bookcell voltage and current meters are located on
the control panel door along with the OIT required for operator control of the MSD.
The power rectification circuits (D.C. power supply) housed in the Control Panel,
changes the main unit supply power into usable high current, low voltage DC power
for the bookcell electrolysis process. The rectification circuits consist of SCR/diode
block(s) (Power Modules) controlled by a printed circuit Rectifier Firing Board. This
firing board drives the Power Module(s) to maintain a constant DC current to the
bookcell. Should variations occur in the salt content of the sewage slurry stream in
the bookcell, the conductivity of the sewage slurry will change. The Firing Board
compensates by increasing or decreasing the D.C. voltage to maintain the bookcell
current at the correct setting. If the salinity falls below minimum requirements
(approximately 1%), an over-voltage circuit activates to shut down the MSD. This
alarm condition actuates a set of relay contacts in the customer remote alarm circuit,
which can be used to notify operator that the MSD unit has shutdown. Other alarm
conditions include but are not limited to:
V-1 tank high level
Motor over-current
Bookcell high temperature
Vent high pressure on 12MX and 15MX units
Other alarms may be added when options are purchased
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
26/175
Section 4.1 Control Panel
The MSD unit is operated via controls on the panels door front. The operator
selects a mode of operation at the OIT. When in the Hand mode, the systems
components run continuously without regard to the V-1 tank level. This mode is
used during the Manual Blowdown maintenance procedure. In the Auto mode, the
unit runs on demand as required by V-1 tank level. The Auto-Override function,
when installed, provides the operator with limited control of the bookcell. The
Override mode turns bookcell power off at all times, without affecting the other MSD
components. In Auto mode, the bookcell power is energized and de-energized as
the MSD starts and stops.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
27/175
Section 4.2 V-1 Surge Tank
SECTION 4.2: V-1 SURGE TANK
Refer to system drawings in Section 12.0 of this manual for Omnipure unit
mechanical details.
The standard Omnipure unit incorporates a V-1 Sewage Collection Tank to
accommodate the normal raw sewage flow into the MSD unit. During peak periods
of use it acts as a reservoir to contain surge flow. This permits the MSD unit to
operate at the correct treatment rate without regarding the incoming flow rate. The
tank allows the MSD unit to operate on demand, via the tanks level switches (see
Section 4.3). The surge tank has a "coal-tar" epoxy internal coating to prevent tank
corrosion.
The V-1 Surge Tank includes a clear site tube for visual indication of the liquid level.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
28/175
Section 4.3 V-1 Surge Tank Level Switches
SECTION 4.3: V-1 SURGE TANK LEVEL SWITCHES
Refer to the system drawings in Section 12.0 of this manual for Omnipure unit
mechanical and electrical details.
As detailed in Section 4.2, the standard V-1 Collection Tank includes a level switch
assembly. This assembly contains three float type level switches. The switches are
comprised of a mercury switch connected to a length of 2 conductor #16 AWG type
SO cable. The switch and connected end of the cable are encapsulated in a hard
urethane ball for flotation. The switches are commonly noted on the Engineering
drawings as LSL-1 (Off), LSH-1 (On) and LSH-2 (High level alarm). The switches
are secured to a flange and stainless steel rod arrangement, which holds in place at
the correct levels. Electrical terminations are made in a junction box on top of the
flange. The three switches are in closed or made condition when liquid level in the
V-1 tank is low. The Level Switch Assembly is constructed to allow the three float
switches to be replaced individually in the event of failure.
If the MSD unit is in the Auto mode, it will start automatically when the level in V-1
tank rises above the ON level switch (LSH-1). The MSDs macerator pump will
begin to pump the V-1 tank down until the low-level point is reached and the
corresponding low-level switch (LSL-1) closes. This action will cause the MSD unit
to stop. In normal operation, the Omnipure unit starts and stops between these
two level switches.
In the event of an unusually high surge rate to V-1 tank, the high-level alarm level
switch (LSH-2) opens, and an alarm indication on the MSDs front panel is activated.
In addition, redundant start signal is sent to the macerator pump to ensure pumping
has started in the event the On switch LSH-1 has failed". This action also actuates
contacts in the customer remote alarm circuit to provide a remote alarm signal.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
29/175
Section 4.4 Macerator Pump
SECTION 4.4: MACERATOR PUMP
All Omnipure MSD units require a macerator pump as the prime mover for fluid
through the treatment system. Standard Omnipure MSD units use a specially
designed macerator, or grinder, pump produced by Severn Trent De Nora. This
Omnipure macerator pump takes suction from the V-1 tank. When the macerator
is in operation one stationary and two rotating cutter blades inside the macerator
reduce the solids in the sewage stream to between 1/8 and 1/16 particle size prior
to discharge. The reduction in the particle size is the first step in treatment process
and allows the bookcell to more effectively treating solids. The macerator pump
discharge is piped to both the V-1 tank return line and to the bookcell. The pumps
discharge flow is regulated by predetermined flow orifices installed in the process
piping.
The SCP-1000 macerator pump is cast of Silicone Bronze. The rotating elements
are stainless steel and other corrosion resistant materials. The cutter blades are on
the suction side of the centrifugal pump impeller and discharge directly into the inlet
of the impeller. The pump shaft is sealed by a forced oil lubricated mechanical seal
and driven by a flexible coupled motor.
NOTE
NEVERoperate the pump(s) without the coupling guard in place.
A radial sleeve bearing, lubricated by oil, is located behind the seal and supports the
radial load from the pump impeller and cutter blades.
The oil lubricated duplex ball thrust bearing is held in an adjustable cap so that the
axial cutter and cutter ring axial clearance can be adjusted from the outside without
the use of shims.
A 2 H.P. (3450 RPM) motor is used on the 12MX, 15MX, and 18MX size units.
Although there is a flexible coupling between the two shafts, the mating surfaces of
the motor and pump are C" face configuration so no alignment is required.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
30/175
Section 4.4 Macerator Pump
All macerator pumps installed on MSD units manufactured after September 1999
incorporate a seawater seal flush system. This system allows pressurized
seawater to flush the pump seal cavity via a solenoid valve during operation. The
seawater flows around the mechanical seal to keeps debris away from seal faces
and also, keeps seal cool in the event the pump is run dry.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
31/175
Section 4.5 12MX Multi-Pass Electrolytic Bookcell
SECTION 4.5: THE MULTI-PASS BOOKCELL ASSEMBLY
The OMNIPURE 12MX multi-pass Bookcell consists of two machined PVC
sections that are hinged to open like a book. When the "Bookcell" is closed, the
front section or Door mates to the rear section or Base. The sections are sealed
with an O-ring around the perimeter that forms a watertight barrier. The primary
anodes, made of titanium and coated with a dimensionally stable anode (DSA)
coating, are mounted at the bottom of the bookcell. The terminal anodes connect to
the positive side of the DC power supply. The Hastelloy primary cathodes are
mounted at the top of the bookcell. The cathodes connect to the negative side of the
DC power supply. Eighteen (18) titanium bipolar plates are included in the assembly;
ten are on the inner Door face, and eight are on the inner Base face of the
bookcell. Half of each bipolar plate is coated with a DSA coating and acts as an
anode. The other half is uncoated bare titanium that serves as a cathode. The 18
bipolar plates are interchangeable.
The proprietary DSA coating on the bipolar plate and the terminal anodes extends
their life, reduces current consumption, and increases the efficiency of the
conversion process. Efficiency is further increased by use of the Hastelloy
cathode.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
32/175
Section 4.5 12MX Multi-Pass Electrolytic Bookcell
The four primary electrodes and eighteen bipolar plates form two identical parallel
electrical circuits, which are side by side in the Bookcell. For simplicity, only one of
the circuits is described. Each circuit is a series of ten separate electrolytic
"CELLS". The primary anode is paired with cathode section of the highest bipolar
plate on the Door to form the first cell. Opposing anode and cathode halves of the
following staggered bipolar plates form eight additional cells. The anode half of the
lowermost bipolar plate on the Door and the primary cathode on the Base form
the tenth cell. The current path terminates at the upper cathode at the rear of the
bookcell body. The two identical electrical circuits are connected in parallel so that
they conduct an equal amount of current (25 ADC each, 50 ADC total) at an equal
voltage (50-100 VDC). This balance of current is monitored by the control panel to
prevent bookcell damage if there is a fault in one of the circuits.
When the bookcell is closed, a liquid flow path is formed between the plates on the
front, back, and middle sections. The sewage and saltwater slurry flowing in the
channel between the plates provides the conductive path to complete the electrical
circuit for sodium hypochlorite production. The flow path is approximately 96 in.
(2438 mm) long and 0.25 in. (6 mm) thick and 10 in. (254 mm) wide. This flow path
is made up of two sections between the Door and Base of the bookcell. These
sections are connected in series and the flow through the bookcell may be in either
direction. The flow direction is reversed to reduce the buildup of seawater deposits
on the electrodes. Flow reversal is accomplished by the actuation of a pair of three-
way valves. These valves are mounted at the top rear of the Bookcell. They actuate
to change flow direction each time the treatment system completes a cycle and
shuts down.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
33/175
Section 4.5 12MX Multi-Pass Electrolytic Bookcell
BOOKCELL ALARMS
There are three bookcell safeguards provided that will alarm and shut down the
individual treatment units. The alarms are:
Bookcell High Temperature: When fluid temperature in bookcell exceeds 103 F
(113 F for special high temp locations)
Bookcell DC Current Unbalanced: Each bookcell has two parallel current paths
across the electrodes. If the current of the two paths is not equal, within 20% a
shutdown alarm occurs.
Bookcell Valve Position Incorrect: If the Bookcell flow reversing valves are out of
position for more than 20 seconds during flow reversal transition, a shutdown alarm
will occur.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
34/175
Section 4.6 V-2 Effluent Tank
SECTION 4.6: V-2 EFFLUENT TANK
Refer to the system drawings in Section 12.0 of this manual for the Omnipure
MSD unit mechanical details.
All MSD units require a V-2 Effluent Tank to retain the treated sewage during
residence time. The standard unit V-2 tank has a special coal-tar epoxy internal
coating, like the V-1 tank, to resist corrosion and provide long operational life of the
tank.
The V-2 Effluent Tank is sized to provide a 30 minute retention time between the
entry of effluent into the bottom of the tank via the downcomer pipe and the
subsequent discharge through the overboard overflow. The retention time ensures
contact with the sodium hypochlorite, so that any remaining bacteria will be killed.
The tank low internal velocity allows partially oxidized particles to settle. The
particles, consisting mostly of cellulose, are recirculated to the V-1 Surge Tank
through the blowdown line located at the bottom of the tank during a daily blowdown
operation.
The V-2 Effluent Tank includes an internal downcomer which encourages
degasification and stabilizes the incoming process flow stream. The V-2 tank is
operated in the flooded state so that the overflow discharge is continuously removed
from tank while the MSD is in operation. The downcomer works in conjunction with
the air ejector vent system to extract gases from the MSD unit and send them to the
atmosphere.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
35/175
Section 4.7 Positive Vent Blower Option (P)
SECTION 4.7: POSITIVE VENT BLOWER OPTION (P)
Refer to the system drawings in Section 12.0of this manual for OmnipureMSD
unit mechanical vent details.
All MSD units generate small amounts of gases during operation, primarily hydrogen
(H2) with some carbon dioxide (CO2). These gasses must be vented to atmosphere.
This venting is accomplished by maintaining a vacuum on the positive vent pipe
connected to the V-2 tank down comer pipe. On this unit the vacuum is generated
by use of an optional regenerative air blower. A blower is used when sufficient air
supply is not available to operate the standard air ejector as the vacuum source.
The vacuum is only used to evacuate gases from the unit and not to assist in effluent
treatment.
The blower suction is connected to the positive vent pipeline to maintain 2 W.C.
(water column) of vacuum during operation. The blower discharge is vented to
atmosphere. Two 3/8 vacuum break holes are drilled in the positive vent line
immediately adjacent to the suction of the blower. These holes allow dilution air to
be drawn into the vent line to be mixed with vent gasses.
A pressure switch is included with 12MX and 15MX units and serves as a vent high-
pressure alarm device for the positive vent pipe.
DO NOT TRAP OR POCKET VENT LINES. The positive vent
pipeline from the unit must be installed in such a way as to prevent any
section of piping from holding water without draining. A pocketed
portion of any vent line may form a liquid seal and prevent proper
evacuation of flammable gases. This could cause damage to the unit
and a condition hazardous to personnel.
A continuous upward slope must be maintained throughout the venting
system, to allow any condensation or liquids that may have formed in
the vents, to flow back into the system.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
36/175
Section 4.7 Positive Vent Blower Option (P)
The blower must be mounted at least 20 feet (6M) above the V-2 Effluent Tank. A
motor starter in the MSD controls panel controls the blower.
The blower stops and starts with the unit operation. The blower is shipped loose
and the installer must make all pipe and wiring connections between the blower and
control panel.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
37/175
Section 4.7.1 Sprayhead Assembly Unit
SECTION 4.7.1: SPRAYHEAD ASSEMBLY UNIT (12MX & 15MX SIZE UNITS)
The sprayhead assembly is shipped loose for installation on top of the V-2 Tank
down comer in the field. The Sprayhead Assembly Unit performs two functions:
The first function of the device is to take a measured amount of seawater (2.56
gpm) and pass it through an electronically controlled solenoid valve to an internal
sprayer (cone type). This seawater sprayer aids in keeping any foam, generated
by the electrolytic process, from migrating up the positive vent pipe.
The sprayhead solenoid valve is controlled via logic in the Main Control Panel.
This valve is energized only when the Macerator pump is energized.
The secondary function is to allow a sensing port for a vent high-pressure switch.
A vent high-pressure switch is shipped loose with the sprayhead assembly for
installation in the field. This pressure switch continuously monitors the pressure
inside the positive vent pipe. On increasing vent pressure, this switch will
activate, causing the Omnipure unit to shut down.
Refer to Section 10 for sprayhead assembly details.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
38/175
Section 5.0 Commissioning
SECTION 5.0: COMMISSIONING
All MSD units are individually tested and calibrated per testing procedures at the
factory. However, vibration and shock during shipment and installation can damage
piping and sensitive electrical components. Flow rates for process modules cannot
be factory set. Flow rate adjustments MUST be made at time of commissioning.
Failure to do so will result in improper MSD unit operation.
Mechanical and electrical connections should be verified with engineering drawings
in Section 12.0.
Electrical Test
1) Inspect and verify all mechanical and electrical connections have been
made according to engineering drawings in Section 12.0.
2) Locate main electrical disconnect switch/breaker for MSD.
3) Lockout/Tagout disconnect.
NOTE
Section 1.2 of this manual should be used as a guide for this
procedure if one does not exist in your organization. This safety
procedure should be followed each time you see Lockout/Tagout
in the commissioning procedure.
4) Open control panel and remove all fuses.
5) Note location of each fuse or refer to their position on control panel layout
drawing as they are removed.
6) Press "OFF" button.
7) Energize power to MSD unit.
8) Verify voltage is available at incoming supply terminals and correct to +/- ten
percent (10%) of voltage required.
9) Lockout/Tagout main power.
10) Replace main transformer T-1 primary fuses, control voltage transformer
primary fuses, firing board transformer, primary fuses and pump motor-
starter fuses.
11) Energize main power.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
39/175
Section 5.0 Commissioning
12) Verify secondary voltage of transformers and voltage on load side of pump
fuses.
13) Remove lockout/tagout device.
14) Turn power "ON" to unit via users main circuit breaker.
15) Verify (using a voltmeter) voltage at T-1 isolation transformer is within 20%
of the no load reading.
NOTE
If voltage does not meet these specifications, shut the unit down,
reapply the lockout device, and contact STDN for instructions.
Leave the prescribed Lockout/Tagout procedure in place until
resolution has been made on this matter.
16) Lockout/Tagout main power.
17) Replace remaining fuses.
Hydraulic Test
1) Rotate all pumps and motors by hand for a minimum of 5 revolutions. The
pump(s) and motor(s) should turn smoothly with no binding or noise.
NOTE
The macerator pump-coupling sleeve, which connects the pump and
motor shafts, must NOTbe installed for the next step.
STDN supplied pumps have counter-clockwise rotation direction as
viewed from the suction end of the pump. To prevent reverse
rotation damage to the Macerator, it has been shipped with the
motor coupling removed. When Counter-clockwise rotation has
been verified, insert the coupling between the pump and motor unit.
2) Energize main power.
3) Press "Hand" key then quickly press "OFF" button to manually actuatepump motor(s) by.
4) Verify motor(s) turns clock-wise when viewed from fan end.
5) Correct rotation, if required, by reversing two phases of motor leads.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
40/175
Section 5.0 Commissioning
Setting Unit Parameters
NOTE
If an optional blower or water-powered eductor is used in place of
the standard air ejector, read the special instructions at the end of
this section before continuing.
1) Turn on air supply to filter/regulator for ejector.
2) Close needle valve connected to regulator discharge.
3) Set regulator pressure to 6 psi.
4) Open needle valve two full turns as an initial setting.
NOTE
The final setting will be made during operation. The regulator is
adjusted by pulling up on the yellow top knob and twisting.
5) Open seawater inlet supply valve to MSD unit.
6) Verify water is available at pump seal flush solenoid(s).
7) Press "AUTO" button.
RESULT: The V-1 tank will fill with seawater from the seawater flow
control valve (FCV). Adding water from an alternate source
may decrease the V-1 tank fill time.
8) Fill V-1 tank until unit starts automatically, (about 1/3 full).9) Press "AUTO" button.
10) Allow tank to continue filling until High Level Alarm message is displayed.
11) Turn Auto-Off-Hand switch to "AUTO" position or press "AUTO" button.
12) Measure each motors current phase with a clamp on ammeter after unit
starts.
13) Verify current readings do not exceed full load current listed on motor tag(s)
for rated voltage.
14) Select "AUTO" at Auto-Override Function and observe bookcell current and
voltage rise and stabilize at correct values.
REFERENCE: Section 10.0 for bookcell current/voltage chart).
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
41/175
Section 5.0 Commissioning
15) Verify air ejector maintains 2 W.C. (water column) vacuum on positive vent
pipe while cell is in operation.
NOTE
This vacuum does not assist in treating the sewage but is for the
evacuation of the by-product gasses of the Bookcell electrolysis.
16) Adjust needle valve to set vacuum to 2 W.C.
NOTE
Too much vacuum can cause vent pipe blockage, too little
vacuum can cause gas build up in the vent.
The next step is to check the unit flow rate, which will begin as
soon as the MSD unit shuts down on low level. This test is for
MSD units, with tanks that have been factory calibrated.
Process modules cannot be factory calibrated. Process module
flow rates must be set during commissioning.
17) Isolate sewage inlet valve and any other sources of water to V-1 tank except
for seawater entering through flow control valve (FCV).
18) Begin timing when MSD unit shuts down, at V-1 tank low level.
NOTE
When the unit starts it automatically records the tank fill time and
begins measuring the pump down time.
19) Compare fill time and pump down time after MSD unit is shutdown on V-1
tank low level:
If they are equal the flow rate is correct.
If pump down time is longer than fill time, then flow rate is too slow.
If pump down time is shorter than fill time, then flow rate is too fast.
If flow rate is incorrect by more than ten percent (10%), contact STDN
for instructions.
NOTE
The MSD unit is now ready to be put into service.
20) Open sewage inlet valve and remove all test connections.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
42/175
Section 5.0 Commissioning
Optional Equipment:
5.1: OVERBOARD DISCHARGE PUMP
If an overboard pump is fitted to your MSD unit it is very important that seal flush
water is available to the solenoid and the solenoid is operational. In new
commissioning and startups after the V-2 tank has been drained the overboard
pump will run dry for 30 minutes before the V-2 tank is filled and overflows to the
pump suction. To prevent damage to the mechanical seal the seawater solenoid
must provide flush water to the pump when it is operating.
5.2: BLOWER OPTION
If an electric blower option is installed, the operation is very similar to the standardair ejector. The difference is a regenerative fan (blower) generates vacuum on the
powered vent pipe. The blower starts and stops with the MSD unit operation.
Vacuum in the vent line is adjusted by drilling air bleed holes in the suction of the
blower manifold. (See engineering drawings for specific details).
5.3: WATER POWERED EDUCTOR OPTION
If water powered eductor is installed to provide vacuum for the positive vent line, the
principal of operation is very similar to the standard air ejector with a few exceptions:
Water is used as the motive force in place of compressed air.
The powered vent discharge is below the waterline, instead of the
atmosphere.
NOTE
Dilution air is drawn into the powered vent pipe from the atmosphere
vent pipe through a vacuum control valve.
When adjusting vacuum, a 1 valve is used to control water flow in the same
manner the needle valve is used to control airflow to the standard ejector.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
43/175
Section 5.0 Commissioning
Installations where a water-powered eductor is used are usually customized to the
particular vessel. For this reason initial set-up of the eductor will be slightly more
difficult than the standard air ejector.
1) Prior to starting the MSD unit, all overboard discharge valves must be
opened and seawater should be turned on to the eductor.
2) Slowly open eductor seawater inlet valve to establish and maintain a
vacuum reading of 2 W.C.
5.4: BRINE OPTION
Prior to beginning commissioning the brine add system, the brine tank connection
must be verified with the engineering drawings (Section 12.0). Clean pressurized
seawater or potable water must be available at the level control valve connection
and the tank should be filled with salt (40lbs. minimum) several hours prior to
commissioning.
1) Verify V-1 tank is partially filled with freshwater or seawater with a low salt
content (>1%).
2) Start MSD unit.
3) Open brine flow control valve FI-1 completely.
4) Observe book cell voltage.
NOTE
When the voltage exceeds 90 VDC (180 for 15MX) the brine
solenoid should open to allow brine to be drawn into the process
stream. After a delay of 10 15 seconds the voltage should begin
to fall. When voltage falls below 70 VDC (160 VDC for 15 MX) the
brine solenoid will close to stop the flow of brine.
The control logic has an overvoltage alarm delay, which is actuated
when the brine solenoid is actuated. The unit may activate the
alarm and have to be reset several times before the brine line from
the tank is purged of air and brine flows to the unit properly.
Once high and low voltage setpoints have been verified, the brine
flow control valve must be adjusted.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
44/175
Section 5.0 Commissioning
5) Turn MSD unit on and wait for brine solenoid to actuate.
6) Adjust FI-1 valve until Bookcell voltage stabilizes at 80 85 VDC. (170-180
VDC for 15MX).
NOTE
The brine system is now operational. Its actuation is automatic. Ifthe Briner is to be used the tank should be filled to the top with salt.
5.5: LIFT STATION COORDINATION
If the sewage collection system contains a lift station or remote collection tank that
pumps to the MSD unit, the coordination between the two systems is important. The
lift station must pump to the MSD unit only then the MSD is shut down with the V-1
tank at low level.
When the MSD unit pumps down to the low level point and stops, permissive
contacts for lift station transfer actuate. If sewage is available in the lift station
tank the transfer pump should start.
When the level in V-1 tank reaches the " ON" level point and the MSD unit
starts, transfer from the lift station must stop.
This cycle will repeat until available sewage has been processed and the
MSD unit stops at low level.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
45/175
Section 5.0 Commissioning
5.6: SODIUM SULFITE INJECTION SYSTEM (DE-CHLOR)
When properly installed, the De-chlor system operation is automatic. The injection
pump starts and stops as the treatment unit starts and stops. To properly adjust the
injection system, chlorine residual samples must be taken and the output of the
injection pump adjusted until the residual is within the required limits. These limits
are set by the governing authority where the vessel or platform is operating.
Initial adjustment may be estimated by assuming a 10 mg/l residual. A table is
shown below as a guideline for initial pump set-up. During operation, the residual
will typically fluctuate. Use the table below for initial set-up of the injection pump and
Sodium Sulfite consumption reference for your particular installation.
Initial Injection Pump Settings(Stroke Rate at 50% Stroke Length)
Unit Size: 12MX 15MX 18MX
Unit Discharge Rate (L/min): 38.6 77.3 85.03
PPM
1 4.32 2.16 4.75
2 8.65 4.32 9.52
3 12.97 6.48 14.27
4 17.30 8.64 19.03
5 21.62 10.80 23.78
6 25.95 12.96 28.55
7 30.27 15.12 33.30
8 34.60 17.28 38.06
9 38.92 19.43 42.81InitialChlorineRe
sidual
10 43.24 21.59 47.56
NOTE
For pump dial settings, round desired number up to next whole number.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
46/175
Section 5.0 Commissioning
Helpful Notes:
PPM (parts per million) = mg/l (milligrams per liter) Metric measurement will
be used to simplify calculations.
2 parts of Sodium Sulfite (Na 2SO3) are required to neutralize 1 part ofchlorine.
A saturated solution of Na 2SO3and water @ 20 C is 269 g/l (grams per liter)
The injection pump capacity is 0.265 ml/stroke and 100 strokes/min max
The treatment rates for individual Omnipure units are shown below.
The following is an example of an Omnipure unit with a treatment flowrate of 4l/min.
Residual concentration multiplied by flow rate.
10 mg/l x 4 l/min = 40 mg/min chlorine
Saturated Na2SO3solution multiplied by volume per stroke.
0.269g/ml x .265ml/st roke = 71.3mg/stroke
Residual mg/min divided by pump mg/stroke.
40mg/min .71.3 mg/stroke = .56 stroke/min .
Amount of chlorine multiplied by two equals the amount of Na2SO3 required to
neutralize.
0.56 stroke/min x 2 = 1.12 strokes per minute.
Per the pump manufacturers recommendation, a faster stroke rate is desirable, so
the stroke length should be reduced from 100% to 50 %. This will double the
required number of strokes per minute to 2.24.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
47/175
Section 6: Operations
SECTION 6.0 OPERATIONS
All Omnipure units must function in accordance with the USCG Certificate
requirements under which the MSD units are designed. The process operation and
specific functionality of any Omnipure unit may not be changed from that which is
declared in the USCG Certificate.
The general process operation for every MSD unit is essentially the same.
NOTE
Field modifications and/or changes to the treatment unit that are not
Authorized by STDN will void the equipment warranty!
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
48/175
Section 6: Operations
7/24/2019 Bactron Biocide
49/175
Section 6: Operations
AUTO MODE
When F2 is pressed, the unit will go into AUTO MODE. AUTO IDLE or AUTO
MODE OPERATING will be displayed in the Mode Message box. BOOKCELL INAUTO will be displayed in the Display Message box directly below the Mode
Message Box.
If the unit has a high tank level in the V1 tank, it will display HIGH TANK LEVEL
on the main screen in the message box. The PLC will initiate a redundant start
signal and if the high level goes away the unit will automatically clear the internal
PLC latch within 10 seconds, and the appropriate message will be displayed. A
high level alarm will not shut the unit down.
HOURMETER SCREEN
Displays the following:
Macerator pump hours of operation
Max time is 32,767 hours. After this timer reaches 32,767 hours it rolls to
00000 hours.
Bookcell hours of operation
Max time is 32,767 hours. After this timer reaches 32,767 hours it rolls to
00000 hours.
Displays current time and date.
Also, while in the OFF MODE, the user can cycle the cell flow reversal valves by
pressing F4while in the HOURMETER SCREEN. The CELL VALVES will cycle.
When the CELL VALVES CYCLE the following message will be displayed in the
MODE Message Box, on the main screen. CELL VALVE CYCLING
The following text is scrolling at the bottom of the HOURMETER screen.
F1 = MAIN MENU, F2= CELL OVERRIDE, F3= BLOWDOWN, F4 = VALVE
CYCLE
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
50/175
Section 6: Operations
See chart below for Function Key modes.
Function
Key
Function
OFF Turns MSD off when pressed
AUTO Enables MSD to operate automatically when pressed
RESET Resets all MSD alarms
HAND Operates macerator pump for 30 seconds each time button is pressed
ESD Turns MSD off in Emergency stop condition
Blowdown Causes blowdown cycle to occur as soon as MSD stops in Auto Idlemode when pressed. Also causes 24 hour timer to be reset so that the
next blowdown cycle will occur 24 hours from the time the button ispressed
Valvecycle
Causes bookcell valves to manually cycle and reverse flow throughbookcell
NOTE
Function Keys are OIT Screen Dependent. Each specific OIT screen
incorporates its own set of particular Function Keys.
ALARM HISTORY
If the unit has an alarm, the alarm will immediately be indicated at the OITscreen. By pressing F4 from the main screen, the alarm can be acknowledged.
By pressing F4 again, this will release the latching logic internal in the logic
controllers (CPU). If the alarm was not cleared then ALM LATCHED PRESS F4
will be displayed in the Mode Message box. The operator needs to clear the
alarm and then press F4again.
The last 50 alarms (date, time, and description) will be stored in the OIT. From
the Main Menu press the DWN ARROW= ALARM HISTORY. By using the UP
and Dwn keys the alarms can be scrolled through. When the 51st alarm occurs
the oldest alarm will be erased and all of the alarms will be pushed down one.
The following is scrolling at the bottom of the ALARM HISTORY screen:
F1= MAIN SCREEN, F2 = STATUS, F4= ALARM ACK
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
51/175
Section 6: Operations
7/24/2019 Bactron Biocide
52/175
Section 6: Operations
CELL VALVE LIMIT SWITCH FAILURE
The cell has dual water paths and these cell valves will cycle when the unit stops.
This helps to keep the cell clean by reversing the cell flow. This shutdown has a20 second delay. Determine problem and then press F4 to clear alarm. Report
problem to STDN Service Manager to avoid damage to the cell. Manually cycle
the cell by putting the unit in OFF MODE and cycling the cell valve.
VENT HIGH PRESSURE
If the vent high-pressure switch opens for 5 consecutive seconds the PLC will
display this alarm, this is not a shutdown it is strictly an alarm. If the unit is
getting vent high-pressure alarms, report the problem to the STDN Service
Manager to avoid damage to the unit.
POWER LOSS OCCURRED
When the unit initially starts or if there is a power interruption to the unit, this
alarm will be displayed. Determine problem and then press F4to clear alarm.
BLOWDOWN VALVE FAILED TO OPEN
If the blowdown valve fails to fully go to the right or left and if the PLC was telling
it to not do a blowdown this alarm will be displayed. This shutdown has a 10second delay. Correct valve position or repair valve and then press F4 to clear
the alarm.
BLOWDOWN VALVE FAILED TO CLOSE
If the blowdown valve fails to fully go to the right or left and if the PLC was telling
it to do a blowdown this alarm will be displayed. This shutdown has a 10 second
delay. Correct valve position or repair valve and then press F4to clear alarm.
BLOWER MOTOR STARTER TROUBLE
When the logic controllers CPU tries to either open or close the blower motor
starter, and if the motor starter does not respond in a specified time (1 sec.), the
above alarm will occur. Determine problem and then press F4to clear alarm.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
53/175
Section 6: Operations
OVERBOARD MOTOR STARTER TROUBLE
When the logic controllers CPU tries to either open or close the overboard-motor
starter, and if the motor starter does not respond in a specified time (1 sec.), the
above alarm will occur. Determine problem and then press F4to clear alarm.
6.3: LIQUID FLOW PATHS
Liquid is routed through the MSD unit by manually operated valves. There are four
possible modes of operation.
Normal operation
Sewage flows to V-1 tank, then to the macerator. From the macerator, it mixes
with incoming seawater and goes through the cell and to effluent V-2 tank for
subsequent discharge. Some of the sewage is recycled through the orifice plate
to V-1 tank. When the unit is not operating, the seawater flows into V-1 tank.
See Sheet 3 of the Flow Diagram for Normal Operation.
Cell Flow Reversal Function
This enhanced Bookcell incorporates two (2) 3-way actuated valves at the top of
the cell. These valves are piped to allow the process flow through the Bookcell to
be automatically reversed after each treatment cycle. This change of flow
direction at each treatment cycle aides in the breakdown of any sizable mineral
deposits from the electrode plates in the cell. The internal PLC controller initiates
this valve cycling sequence as needed. These cell reversal valves may also be
cycled if the user is in the HAND mode of the units control.
NOTE
This cell flow reversal function is meant to aide in the prolonging of the
Bookcell operational life. It is not intended to replace the need for
manual, periodic opening and cleaning of the Bookcell electrode plates.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
54/175
Section 6: Operations
V-2 Blowdown Modes
Untreated solids in V-2 tank are recycled back to V-1 tank for treatment. Since
this MSD is equipped with the Automatic blowdown feature, no manual
manipulations of hand valves are required during normal operation. This system
uses an automatic actuated valve to divert the macerator pump flow through a
liquid eductor (venturi), which draws untreated solids from the V-2 tank and
returns the flow to the V-1 tank for retreatment. This Automatic Blowdown
function occurs once every 24 hrs for a timed period of one (1) minute. See
Sheet 3 of the Flow Diagram. It is also possible for the user to perform a Manual
Blowdown of the V-2 tank. In the Manual blowdown operation, the macerator
pump takes suction from the bottom of V-2 tank back to and discharges through
the return orifice to V-1 tank. This manual function requires the user to stop the
treatment system for handvalve repositioning, and then run the Macerator pump
in HAND mode. See Sheet 3 of the Flow Diagram for manual handvalve
operations.
Emergency Pump Down
Allows liquid in the V-1 and V-2 tanks to be directly discharged overboard by the
macerator pump. See Sheet 3 of Flow Diagram.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
55/175
Section 6: Operations
6.4: NORMAL OPERATION
To operate the MSD unit in Normal Treatment Mode:
1. Align unit hand valves as shown for Normal Operation on Sheet 3 of the Flow
Diagram. Note: All Automated actuated valves are controlled via the internal
PLC controller.
2. Open compressed air supply to vent air ejector.
3. Open pressurized seawater inlet valve to unit (customer supplied).
4. PressAUTO button. The MSD unit will start if required by the liquid level in
V-1 tank or pressAUTO button.
5. Clear any alarms by pressingALARM RESETpush-button if necessary.
RESULT: The MSD unit will start and stop automatically as required by the
liquid level in V-1 tank.
NOTE
When the unit starts, bookcell operation will be indicated after a short
delay by the voltage and amperage meters. See Section 10.0 for the
bookcell operating currents and voltages.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
56/175
Section 6: Operations
6.5: CELL FLOW REVERSAL FUNCTION
This enhanced Bookcell incorporates two (2) 3-way actuated valves at the top of the
cell. These valves are piped to allow the process flow through the Bookcell to be
automatically reversed after each treatment cycle. This change of flow direction at
each treatment cycle aides in the breakdown of any sizable mineral deposits from
the electrode plates in the cell. The internal PLC controller initiates this valve cycling
sequence as needed. These cell reversal valves may also be cycled if the user is in
the HAND mode of the units control.
NOTE
This cell flow reversal function is meant to aide in the prolonging of the
Bookcell operational life. It is not intended to replace the need for
manual, periodic opening of the bookcell and cleaning of the internal
electrode plates.
6.6: MANUAL V-2 TANK BLOWDOWN & AUTO V-2 BLOWDOWN
Untreated solids in V-2 tank should be recirculated back to V-1 tank for treatment
upon completion of the daily bookcell backflush procedure. The purpose is to
provide a flow path from the V-2 tank to the V-1 tank. Follow the steps below:
1. Press OFFbutton.2. Set manual valves as shown in Sheet 3 of Flow Diagram.
3. Ensure following valves are in the proper position:
4. Go to OVERRIDEMode.
5. Press HAND button.
RESULT: The macerator pump will start.
6. Press OFFbutton after 30 seconds.
7. Re-Set MSD valves for normal operation (Flow Diagram, Sheet3).8. PressAUTO button.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
57/175
Section 6: Operations
6.7: EMERGENCY V-1 AND V-2 PUMP DOWN
Situations may arise when it is necessary to pump untreated sewage from V-1 tank
overboard or to a shore connection. The same procedure can be used to pump
down the V-2 effluent tank if the situation arises. Follow the steps below:
1. Press OFFbutton.
2. Position valves as shown in Sheet 3 of Flow Diagram.
NOTE
A direct path from V-1 and V-2 to the emergency bypass line is
provided through the macerator pump.
3. Go to OVERRIDE Mode.
4. Press HAND button.
5. Observe liquid level in V-1 tank sight glass.
6. Press OFFbutton.
NOTE
When macerator pump suction inlet is no longer flooded, then the
last few inches of liquid below pump suction must be removed
manually through the clean out.
If the MSD unit is to be used in the bypass configuration for an
extended period, press "AUTO" button.
When the unit is used in the bypass mode, the overboard pump
motor fuses should be removed if overboard pump is installed
without seal flush water connections. This will prevent damage to
the overboard pump mechanical seal.
O&M, Rev. 5.4 Severn Trent De Nora, LLC
7/24/2019 Bactron Biocide
58/175
Section 7: Troubleshooting
SECTION 7.0 TROUBLESHOOTING
PPE
Table 7-1 MSD Troubleshoot ing Guide
SYMPTOM PROBABLE CAUSE REQUIRED ACTION
Low seawater salinity Suspend system operation untilship moves into area of highersalinity
Or
Add salt to the Briner tank (ifinstalled)
No seawater entering thesystem at flow controller
Verify seawater supply at skid.
Clean seawater strainer
Bookcell electrodes dirty Open and clean bookcell (seeSection 8.0)
Bookcell electrode damagedor out of place
Replace electrodes (see Section8.0)
Bookcell power wireconnection loose
Clean and tighten connection
CELL OVER-VOLTAGE/OVERCURRENTmessage displayed
and
Rectifier Firing Board OVLED is lit
SCR firing board malfunction Troubleshoot Firing Board (seeSection 7.0)
Bookcell power wire loose Clean the wire and tightenconnection
Current signal wire to RectifierFiring Board loose
Clean the wire and tightenconnection
SCR shorted Troubleshoot SCR (see Section7.0)
CELL OVER-VOLTAGE/OVERCURRENTmessage displayed
And
Rectifier Firing Board OCLED is lit
SCR firing board malfunction Troubleshoot SCR firing board(see Section 7.0)
Low flow through the Bookcell See Low Treatment Flow Rate CELL HIGH TEMP message isdisplayed
Bookcell electrodes are dirty Open and clean Bookcell