    Split Air Conditioning System

    Course Code: Split AC-01

    Engineer M Rouf Khan

  • 7/29/2019 BTS AC SYSTEM

    3/40

    AIM

    . SCOPE

    . Safety Points

    Introduction to HVAC

    . International Standards

    Designing Parameters

    . System Design

    General Points for Mobiserve Sites

    Installation at Mobiserve Sites

    Use of AC Tools

    Working of Split AC

    Precautions

    Most Common Problems

    Inspection & Maintenance

    Contents

    3

  • 7/29/2019 BTS AC SYSTEM

    4/40

    4

    AIM

    Provide Thermal Comfort

    To Increase:

    Technical Knowledge & Professional Skills,

    To Reduce:

    Human Errors at sites,Trouble shooting time,

    Number of Repeated Alarms

    Maintenance Cost.

  • 7/29/2019 BTS AC SYSTEM

    5/40

    5

    SCOPE

    Build a project team

    aware to use method(s) & technique(s) to form a

    CoolingSystem by locally available resources i.e.

    materials & manufacturing techniques and be

    able to run & maintain it.

  • 7/29/2019 BTS AC SYSTEM

    6/40

    6

    Safety Points

    Always follow instructions.

    Keep the work area clean.

    Keep flammable and combustible items away

    from spark producing activities.

    Know where the emergency stop buttons are positioned in the

    workshop.

    Always be patient, never rush in the working area.

    Keep hands away from moving/rotating machinery.

  • 7/29/2019 BTS AC SYSTEM

    7/40

    7

    H- Heating

    V- Ventilation

    AC- Air Conditioning

    1. Room Temperature2. Humidity

    3. Air Quality

    4. Air Flow

    Factors

    Introduction to HVAC System

  • 7/29/2019 BTS AC SYSTEM

    8/40

    8

    ASHRAE American Society of Heating,Refrigerating and Air-Conditioning

    Engineers

    National Fire Protection AssociationNFPA

    International Standards

  • 7/29/2019 BTS AC SYSTEM

    9/409

    Room cooling requirements

    Temperature and Humidity range

    Placement of IDU & ODU

    Space considerations

    Effect on Equipment performance

    Efficiency

    Environmental Impact

    Designing Parameters

  • 7/29/2019 BTS AC SYSTEM

    10/4010

    Designing Parameters

    Heat Load Calculations:

    Outside temp -5 C to +50 C

    Room size 15 X 10

    Heat due to opaque surfaces = 1866.2 W

    Heat due to fenestration = 732 W

    Internal Loads ( equipment ) = 2689.66 W

    Total Load = 5.287 kW

  • 7/29/2019 BTS AC SYSTEM

    11/4011

    Designing Parameters

    Heat Load = 5.287 kW

    Cabin Relative Humidity = 40%

    Evaporator Temperature = 4C

    Refrigerant Used = R22

    Refrigeration Cycle : Vapor Compression

  • 7/29/2019 BTS AC SYSTEM

    12/4012

    Result

    Evaporator Pressure = 3 bar

    Condenser Pressure = 12 bar

    Heat Load = 5.287 KW

    Condenser Cooling Load= 6.308 KW

    Compressor Work = 1.02 KW

    Mass Flow Rate = 1.94 l/min

  • 7/29/2019 BTS AC SYSTEM

    13/4013

    System Design

  • 7/29/2019 BTS AC SYSTEM

    14/4014

    System Design

    OD unit

    ID unit

  • 7/29/2019 BTS AC SYSTEM

    15/4015

    System Design

  • 7/29/2019 BTS AC SYSTEM

    16/4016

    System Design

    Split Air Conditioner

  • 7/29/2019 BTS AC SYSTEM

    17/4017

    System Design

    Split Air Conditioner

  • 7/29/2019 BTS AC SYSTEM

    18/40

    18

    General Points for Mobiserve Sites

    Zones

    1-Inside Shelter

    2- Outside Shelter

    Thermostat

  • 7/29/2019 BTS AC SYSTEM

    19/40

    19

    General Points for Mobiserve Sites

    Coil

    NC NO

    27 Thermostat

    Fuse

    2

    Amp 2

    From A/C1 C.B From A/C2 C.B

    L

    F

    A2 A2

    24 Hrs Timer

    A/C1 Contactor A/C2 Contactor

    C 1

    A1 A1

    N

    To A/C1 To A/C2

    To control the time

    of working for each

    A/C and it consistsof:

    24 Hrs timer + 2

    contactors + fuse

    base with fuse 2

    Amp + thermostat

    Time Control circuit

  • 7/29/2019 BTS AC SYSTEM

    20/40

    20

    Central Station

    General Points for Mobiserve Sites

  • 7/29/2019 BTS AC SYSTEM

    21/40

    21

    Indoor Unit

    Installation at Mobiserve Sites

    Thermostat

    Remote

  • 7/29/2019 BTS AC SYSTEM

    22/40

    Outdoor Unit

    Condenser

    Compressor

    Installation at Mobiserve Sites

    22

  • 7/29/2019 BTS AC SYSTEM

    23/40

    23

    Thermostat

    Indoor Items Outdoor Items

    Indoor Bracket & Hole Outdoor Bracket

    Pipe Connection Outdoor UnitPipe Connection Indoor Unit

    Electric Connection Outdoor door Unit

    Installation

  • 7/29/2019 BTS AC SYSTEM

    24/40

    Use of AC Tools

    Swaging & Flaring Tool 2 way Valve for liquid

    3 way Valve for Gas

    Refrigerant 22

    Mani Fold Valve Piping & Accessories

    24

  • 7/29/2019 BTS AC SYSTEM

    25/40

    25

    Thermostat

    Installation at Mobiserve Sites

  • 7/29/2019 BTS AC SYSTEM

    26/40

    Working of Split AC

    26

  • 7/29/2019 BTS AC SYSTEM

    27/40

    Routing of Cable.

    Routing of Pipes.

    Should be routed through areas oflow risk

    Angle of pipe and cable hole should be proper

    If Cables are installed less than 2.25m above the

    floor should they normally be protected.

    Precautions

  • 7/29/2019 BTS AC SYSTEM

    28/40

    Most Common Problems

    Remote Control

    Wall Thermostat

    Dirty Air Filter

    Coils Blockage

    Capacitor

    Fuses

    Refrigerant Leakage

  • 7/29/2019 BTS AC SYSTEM

    29/40

    Most Common Problems

    Thermostat

    Remote

    Air Filter

  • 7/29/2019 BTS AC SYSTEM

    30/40

    Most Common Problems

    Capacitor

    In case of LG system we

    have a combine capacitor for

    motor and fan

    30

    Compressor

  • 7/29/2019 BTS AC SYSTEM

    31/40

    Most Common Problems

    Fuse on PCB Assembly

    31

  • 7/29/2019 BTS AC SYSTEM

    32/40

    Most Common Problems

    Out Door Unit

    Flare Nut

  • 7/29/2019 BTS AC SYSTEM

    33/40

    Inspection and Maintenance

    Leak check by Soapy water

    33

  • 7/29/2019 BTS AC SYSTEM

    34/40

    Inspection and Maintenance

    Proper Purging of Air

    34

  • 7/29/2019 BTS AC SYSTEM

    35/40

    Inspection and Maintenance

    Proper charging of gas through low pressure side

    35

  • 7/29/2019 BTS AC SYSTEM

    36/40

    Inspection and Maintenance

    Indoor & Outdoor Unit

    DAILY

    WEEKLY

    Monthly

    inspections and issue a certificate after each inspection. It is

    normal practice to be cleaned and checked on each monthly visit

    so that the entire system has been properly maintained after the

    fourth visit.

  • 7/29/2019 BTS AC SYSTEM

    37/40

    Inspection and Maintenance

    Proper cleaning of Condenser and Evaporator.

    Keep the air filters clean

    Keep the indoor evaporator & outdoor condensercoils clean

    Every yearLubricate Indoor blower motor and outdoor unit fan

    motor bearings.

    Finally, a record should be kept of all maintenance and repairsmade to the system. It is always helpful to have a history of the

    system.