Ductulator Spreadsheet to calculate rectangular air duct sizes, air pressure drop. Different materials
Citation preview
Ductulator
1000 CFM
Hold Width Constant At 12 inches
Set Mid Range Height At 8 inches
Vary Height in 2 inch increments
Ductliner? No Thickness 1 inches
Friction Loss Range 0.08 To 0.1
Velocity Range 600 To 1200
Graph Friction Loss
Width (in.) x Height (in.)Duct Velocity S.P. Loss (per 100 ft.)
Equivalent Dia. (in.)(fpm) (in. of w.c.)
- - x - - - - - - - -
- - x - - - - - - - -
- - x - - - - - - - -
- - x - - - - - - - -
- - x - - - - - - - -
- - x - - - - - - - -
- - x - - - - - - - -
12 x 2 6,000 14.118 4.9
12 x 4 3,000 2.017 7.3
12 x 6 2,000 0.672 9.1
12 x 8 1,500 0.315 10.7
12 x 10 1,200 0.177 12.0
12 x 12 1,000 0.112 13.1
12 x 14 857 0.076 14.2
12 x 16 750 0.055 15.1
12 x 18 667 0.041 16.0
12 x 20 600 0.032 16.8
12 x 22 545 0.026 17.6
12 x 24 500 0.021 18.3
12 x 26 462 0.017 19.0
12 x 28 429 0.015 19.6
Ductulator
Duct Diameter Based on Friction Loss
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
X
Rectangular Duct Size Based on Friction Loss
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
2
4
6 X X
8 X
10 X
12
14
Equivalent Dia. (in.)16 X
18
20 X
- - 22
- - 24
- - 26
- - 28 X
- - 30 X
- - 32
- - 34
4.9 36
7.3 38
9.1 40
10.7 42
12.0 44
13.1 46
14.2 48
15.1 50 X
16.0 52 X
16.8 54 X
17.6 56
18.3 58
19.0 60
19.6 62
64
Ductulator
Duct Diameter Based on Friction Loss
21 22 23 24 25 26 27 28 29 30 31 32 33 34
Rectangular Duct Size Based on Friction Loss
38 40 42 44 46 48 50 52 54 56 58 60 62 64
X X X