May 11 TH - 12TH 2010, Maribor,Slovenia 

ELIMINATION OFELECTROMAGNETICINTERFERENCE IN

TRANSFORMER STATION 

Dr.sc.Hidajet Salkić dipl.ing.el.

Page 2: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 2/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

According to IEC 61000-4-8 standard, the environment of low frequency magnetic field

( 50 -60 Hz ) can be grouped into 5 levels, according to the amounts of magnetic field intensity:

Level 1: Environment in which the CRT monitors can normaly operate, as well aselectronic microscopes and other devices that operate on the principle of

electronic beam.Level 2: Well-protected environment. Refers to the special offices and facilities with

hospital devices.Level 3: Protected environment. Examples include smaller industrial facilities and

management and control of major plant rooms.Level 4: Industrial environment. Examples include heavy industrial facilities, power

plants, control rooms of transformer stations.

Level 5: Heavy industrial environment. Examples include switchgears andtransformer stations.

Level  Magnetic fieldintensity (A/m)  Magnetic induction in air

(μT) 1  1  1.26 2  3  3.77 3  10  12.56 4  30  37.68 5  100  125.60 

Page 3: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 3/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Protective measures:

Avoiding of spaces with the levels of magnetic fields over 5 μT,  Lowering the value of magnetic field by reconstructing, distancing or removing the

source of magnetic field,

Protection from influence of magnetic fields by placing protective armors andfloors.

Page 4: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 4/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Calculations of the magnetic and electric fields for TS 10(20)/0.4 kV, 3x1250 kVAm which islocated in the basement part of the building, were done with software package EFC-400,which provides simulation and modeling in three-dimensional space.

In substation TS 10(20)/0.4 kV transformation 10(20)/0.4 kV is performing on three separatepower transformers 1250 kVA, of which, two are in operation, TR1 and TR3.

It is adopted a maximum possible current load of transformers HV/MV.

Transformers 10/0.4 kV, 1250 kVA, 4%, Dyn5 and belonging MV switchgear rated voltage 12kV are modeled, with a current load of 75 A.

LV cells rated voltage 0.4 kV are modeled as well, with a total load current of 1804 A, so thecalculation was on the side of safety.

Substation is modeled with ceiling height of 3.5 m.

The visual overview of the obtained results of magnetic flow density and intensity of theelectric field is done in the computer program “Matlab“, using “Runal.B“ and “Runal.E“ programs, while subprograms “Crtajgraf .B“ and “Crtajgraf .E“ are used for opening , load anddisplaying the results of the calculation of the magnetic flow density and intensity of theelectric field.

Page 5: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 5/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Two-dimensional and three-dimensional view of substation disposition in program EFC 400

Page 6: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 6/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Distribution of electric field intensity in X-Y plane at height of 4.5m  – continuous distribution

Page 7: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 7/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Distribution of magnetic flow density in X-Y plane at height of 4.5m – continuous distribution

Page 8: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 8/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

The results of electric field intensity and magnetic flow density in 3D view at heigh of 4.5m

Page 9: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 9/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Two-dimensional and three-dimensional view of reconstructed substation in EFC 400

Page 10: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 10/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Distribution of electric field intensity in X-Y plane at height of 4.5m  – reconstructed substation

Page 11: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 11/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Distribution of magnetic field density in X-Y plane at height of 4.5m – reconstructed substation

Page 12: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 12/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

The results of electric field intensity and magnetic flow density in 3D view at heigh of 4.5m

Page 13: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 13/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Magnetic fields at height of 4.5m with metal plates installed above transformer T3

Page 14: Em Interference

8/3/2019 Em Interference

http://slidepdf.com/reader/full/em-interference 14/14

ELIMINATION OF ELECTROMAGNETIC INTERFERENCE IN TRANSFORMER

STATION

Magnetic flow density even on greater distances from the transformer and other equipmenthas a value above 100 μT, which is greatly above the value of 40 μT as it is prescribed by thedirectives and recommendations of the European Union for a people staying.

Values above 40 μT occurs almost on a larger part of the floor in the upper rooms. First of all it is necessary to dismount the copper rails with which the low voltage from the

transformer leads to LV cells. The same rails are the largest source of unfavorable magneticfields. It is necessary to replace them with cable connection according to the technicaldescription of the project.

From the calculation results of reconstructed substation it is visable that the values ofmagnetic flow density, after the reconstruction, already in the immediate vicinity of the

transformers are less than the prescribed values for the professional exposure. Regarding of the influence to the devices, most devices in the room belongs to the upper class

in accordance with international standard IEC 61000-4-8. This however does not refer tomonitors with cathode tubes, which in some cases may show a reduced immunity to magneticflow density up to 5 μT.

The recommendation is using of LCD monitors in the offices located above transformer TR3