Emerson ECM1500

Embed Size (px)

Citation preview

  • 8/13/2019 Emerson ECM1500

    1/34

    ECM1500 Outdoor Cabinet

    User Manual

    Version V1.3

    Revision date December 3, 2009

    BOM 31012154

    Emerson Network Power provides customers with technical support. Users may contact the nearest

    Emerson local sales office or service center.

    Copyright 2009 by Emerson Network Power Co., Ltd.

    All rights reserved. The contents in this document are subject to change without notice.

  • 8/13/2019 Emerson ECM1500

    2/34

    Safety Precautions

    To reduce the chance of accident, please read the safety precautions very carefully before operation. The"Caution, Note, Warning, Danger" in this book and on the product do not represent all the safety points to be

    observed, and are only supplement to various safety points. Therefore, the installation and operation personnel

    must receive strict training and master the correct operations and all the safety points before operation.

    When operating Emerson products, the operation personnel must observe the safety rules in the industry, the

    general safety points and special safety instructions specified in this book.

    If you purchase an outdoor power supply without SPD, you should install an SPD at the front-end of AC input,

    otherwise, the power supply system will generate over-voltage.

    Electrical Safety

    I. Hazardous vo ltage

    Danger

    Some components of the outdoor cabinet system carry hazardous voltage in operation. Direct contact or indirect contact

    through moist objects with these components will result in fatal injury.

    Observe safety rules in the industry when installing the power supply system. The installation personnel must be

    licensed to operate high voltage and AC power.

    In operation, the installation personnel are not allowed to wear conductive objects, such as watches, bracelets,

    bangles and rings.

    When you spot the cabinet with water or moisture, turn off the power immediately. In moist environment,precautions must be taken to keep moisture out of the power supply system.

    "Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during

    installation.

    Danger

    High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliancewith the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high

    voltage operations.

    Danger

    To avoid electric shock hazard for outdoor environment and outdoor equipment, the non-professionals are prohibited tooperate or maintain the outdoor power supply system.

    II. Tools

    Warning

    In high voltage and AC operation, specialized tools must be used.

  • 8/13/2019 Emerson ECM1500

    3/34

    III. Thunderstorm

    Danger

    Never operate on high voltage, AC, iron tower or mast in the thunderstorm.

    In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be

    well earthed in time to avoid damage by lightning strikes.

    IV. ESD

    Note

    The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scaleICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from

    damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.

    V. Short ci rcuit

    Danger

    During operation, never short the positive and negative poles of the DC distribution unit of the outdoor cabinet system, orthe non-earth pole of the outdoor cabinet system and the earth. The power supply system is a constant-voltage DC power

    device, short circuit will result in equipment burning and endanger human safety.

    VI. Reverse connection

    Warning

    Never reverse-connect the AC input live line and neutral line, or else the system will be damaged.

    Check the polarity of the cable and connection terminal when performing DC live operations.

    As the operation space in the DC distribution unit is very tight, please carefully select the operation space.

    Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.

    Use insulated tools.

    In live operation, keep the arm, wrist and hand tense, so that when the tool in operation slips, the movement of

    the human body and tool is reduced to a minimum.

    Battery

    Danger

    Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery

    connection method.

    Warning

    If customers prepare batteries themselves, the battery installation and maintenance should meet relevant safety standards.

  • 8/13/2019 Emerson ECM1500

    4/34

    Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent

    battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs,

    thus causing equipment damage and short circuit of PCBs.

    Before any operation on battery, pay attention to the following points:1. Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.

    2. Use specialized insulated tools.

    3. Use eye protection device, and take preventive measures.

    4. Wear rubber gloves and apron to guard against electrolyte overflow.

    5. In battery transportation, the electrode of the battery should always be kept facing upward. Never put the

    battery upside down or slanted.

    Connection And Testing Of The Outdoor Cabinet

    Before installing subrack power supply in the cabinet, you should finish the connection and testing of thesubrack power supply according to the corresponding subrack power supply user manual and then testing the

    outdoor cabinet.

    Others

    I. Sharp object

    Warning

    When moving equipment by hand, wear protective gloves to avoid injury by sharp object.

    II. Power cable

    NoticNote Please verify the cable labels before connection.

    III. Signal cables

    NoticNote The signal cables should be routed at least 150mm away from power cables.

  • 8/13/2019 Emerson ECM1500

    5/34

    Contents

    Chapter 1 Overview ....................................................... ....................................................... .............................................. 1

    1.1 Model Description ...................................................... ........................................................ ................................... 1

    1.2 Composition & Configuration ................................................ ........................................................ ........................ 1

    1.3 Operating Theory....................................................... ........................................................ ................................... 4

    1.4 Features................................................. ....................................................... ........................................................ 5

    Chapter 2 Installation ..................................................... ....................................................... .............................................. 6

    2.1 Safety Regulations......................... ........................................................ ............................................................... 6

    2.2 Installation Preparation ............................................... ........................................................ .................................. 6

    2.3 Mechanical Installation............................................... ........................................................ ................................... 72.3.1 Installing The Outdoor Cabinet ....................................................... ........................................................ ... 7

    2.3.2 Opening And Closing Cabinet Door.......................................................... ................................................. 8

    2.4 Electrical Installation ................................................... ....................................................... ................................... 9

    2.4.1 Connecting Power Cables .................................................... ....................................................... .............. 9

    2.4.2 Connecting Signal Cables ....................................................... ............................................................ .... 11

    2.4.3 Sealing The Entry Holes.......................................................... ............................................................ .... 11

    2.5 Battery Installation ..................................................... ........................................................ ................................. 11

    2.6 Installation Check......................................................................... ....................................................................... 12

    Chapter 3 Testing....................................... ........................................................ ............................................................... 13

    3.1 Startup .................................................. ........................................................ ...................................................... 13

    3.2 Alarm Check And System Operation Status Check ............................................................ ................................ 13

    3.3 Final Steps...................................................... ........................................................ ............................................ 13

    Chapter 4 Maintenance............. ........................................................ ....................................................... ......................... 14

    4.1 Routine Maintenance.................................................. ....................................................... ................................. 14

    4.2 Replacing Parts Of Forced Ventilation Model Outdoor Cabinet..................................................... ..................... 15

    4.2.1 Replacing Heat Control Board ............................................................ ..................................................... 15

    4.2.2 Replacing Fans....................................... ........................................................ ......................................... 16

    4.2.3 Replacing Door Status Sensor ........................................................... ..................................................... 18

    4.3 Replacing Parts Of Heat Exchanger Model Outdoor Cabinet ........................................................ ..................... 18

    4.3.1 Replacing Environment Climate Control Unit................................................. .......................................... 18

    4.3.2 Replacing Fans....................................... ........................................................ ......................................... 20

    4.3.3 Replacing Heater....................................................... ....................................................... ....................... 21

    4.3.4 Replacing Door Status Sensor ........................................................... ..................................................... 21

    4.4 Replaciing Parts Of Air-condition Model Outdoor Cabinet .................................................. ................................ 22

    4.4.1 Replacing air-conditioner......................................................... ............................................................ .... 22

    4.4.2 Replacing Emergent Ventilation Unit .................................................. ..................................................... 22

    4.4.3 Replacing Door Status Sensor ........................................................... ..................................................... 22

  • 8/13/2019 Emerson ECM1500

    6/34

    Appendix 1 Technical And Engineering Parameters.................................................... ..................................................... 23

    Appendix 2 Wiring Diagram........................................................................................... .................................................... 24

    Appendix 3 Schematic Diagram................................................ ........................................................ ................................ 27

  • 8/13/2019 Emerson ECM1500

    7/34

    Chapter 1 Overview 1

    Chapter 1 Overview

    ECM1500 outdoor cabinet (outdoor cabinet for short) is a power supply system used outdoors. It provides outdoor

    protection and operation environment. It contains thermal control units and AC power distribution units. The cabinetcan accommodate different Emerson subrack power supplies according to your requirement so as to form power

    supply systems with different capacities.

    This chapter introduces the model description, composition & configuration, operating theory and features of the

    outdoor cabinet.

    1.1 Model Description

    The outdoor cabinet is available in three models, configured with different models of thermal control unit (forced

    ventilation, heat exchanger and air-condition). Taking the forced ventilation model for example, the model description

    of the outdoor cabinet is given in Figure 1-1.

    EC 1500 F 1 48 300-M

    Internal power capacity: 300A, 150A, 120A

    Version No.

    Thermal control method: F (forced ventilation), H (heat exchanger), A (air-condition)

    Maximum heat productivity in cabinet:1500W

    Application: mobile network integrated cabinet

    Emerson outdoor cabinet

    Internal power voltage:48Vdc

    Figure 1-1 Model description

    1.2 Composition & Configuration

    Composition

    The outdoor cabinet is composed of thermal control units, power distribution units and related structures. Three

    models of thermal control units are available: forced ventilation, heat exchanger and air-condition.

    Configuration

    1. The configuration of the forced ventilation model outdoor cabinet is given in Table 1-1.

    Table 1-1 Configuration list of the forced ventilation model outdoor cabinet

    Component Configuration

    Fan 4 pieces

    Heat control board 1 pieceThermal controlunit Heat control extension

    board1 piece

    AC power distribution 1 route 10A single-phase AC socket; one route 25A single-phase AC input MCBPower

    distribution unit DC power distribution DC input terminals

    Power and reserved space Sharing space: 15U, you can adjust space according to requirement

    Door status sensor 1 piece

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    8/34

    2 Chapter 1 Overview

    The structure of the forced ventilation model outdoor cabinet is shown in Figure 1-2.

    Figure 1-2 Structure of the forced ventilation model outdoor cabinet

    2. The configuration of the heat exchanger model outdoor cabinet is given in Table 1-2.

    Table 1-2 Configuration list of the heat exchanger model outdoor cabinet

    Component Configuration

    Fan 4 piecesThermal control

    unitEnvironment climate

    control unit1 piece

    AC power distribution 1 route 10A single-phase AC socket; one route 25A single-phase AC input MCBPower

    distribution unit DC power distribution DC input terminals

    Power and reserved space Sharing space: 15U, you can adjust space according to requirement

    Door status sensor 1 piece

    The structure of the heat exchanger model outdoor cabinet is shown in Figure 1-3.

    Figure 1-3 Heat exchanger model outdoor cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    9/34

    Chapter 1 Overview 3

    The configuration of the air-condition model outdoor cabinet is given in Table 1-3.

    Table 1-3 Configuration list of the air-condition model outdoor cabinet

    Component Configuration

    Outdoor air-condition 1 pieceThermal control

    unit Emergent ventilation unit 1 set

    AC power distribution 1 route 10A single-phase AC socket; 1 route 25A single-phase AC input MCBPower

    distribution unit DC power distribution DC input terminals

    Power and reserved space Sharing space: 15U, you can adjust space according to requirement

    Door status sensor 1 piece

    The structure of the air-condition model outdoor cabinet is shown in Figure 1-4.

    Figure 1-4 Air-condition model outdoor cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    10/34

    4 Chapter 1 Overview

    1.3 Operating Theory

    Heat dissipation theory for forced ventilation model outdoor cabinet

    The cold air is sucked in through the front door air filter at the lower part of the outdoor cabinet. It passes through the

    battery compartment, user equipment and subrack power supply in turn. Finally, the hot air is discharged by the fans

    at the top of the outdoor cabinet. In this way, the equipment and power modules in the cabinet are cooled, as shown

    in Figure 1-5.

    Heat dissipation fan

    Subrack power supply

    Air outlet

    Air inlet

    Sharing space

    Figure 1-5 Heat dissipation access for forced ventilation model outdoor cabinet

    Heat dissipation theory for heat exchanger model ou tdoor cabinet

    A heat exchanger is fitted on the door of the outdoor cabinet. It can exchange the heat between the cold air outside

    the cabinet and the hot air inside the cabinet. In this way, the equipment and power modules in the cabinet are cooled,

    as shown in Figure 1-6.

    Internal circulation air

    inlet of heat exchanger

    Internal circulation airoutlet of heat exchanger

    Figure 1-6 Heat dissipation theory for heat exchanger model outdoor cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    11/34

    Chapter 1 Overview 5

    Heat dissipation theory for air-condition model outdoor cabinet

    An outdoor air-conditioner is fitted on the door of the outdoor cabinet to cool the cabinet. It is in this that the

    equipment and power modules in the cabinet are cooled. In case of air-conditioner fault or AC mains failure, the

    emergent ventilation units automatically startup to dissipate heat emergently, as shown in Figure 1-7.

    Top emergent ventilation fan

    Return air inlet of air-condition

    Outdoor air-condition

    Air outlet of air-condition

    Figure 1-7 Heat dissipation theory for air-condition model outdoor cabinet

    1.4 Features

    Variable subrack power supply: The outdoor cabinet can accommodate standard 19 and 23 subrack power

    supply.

    Variable space: The power space, reserved space and the battery compartment space are interchangeable. You

    can adjust the space according to the actual requirement.

    Thermal control unit: Three different models are available for your selection according to the local, environment

    and requirement.

    Safety guideline: The equipment compartment satisfies IP*5 waterproof requirement and IP5* dustproof

    requirement.

    Environment pollution level within the outdoor cabinets is 2.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    12/34

    6 Chapter 2 Installation

    Chapter 2 Installation

    This chapter introduces installation and cable connection. Strictly follow the instructions provided in this chapter to

    carry out the installation and cable connection.

    2.1 Safety Regulations

    Certain components in this power supply system have hazardous voltage and current. To ensure personnel safety,

    always follow the instructions below:

    1. Only the trained personnel with adequate knowledge of the outdoor cabinet shall carry out the installation. The

    Safety Precautions listed before the Contents of this manual and local safety rules in force shall be adhered to during

    installation.

    2. All external circuits below -48V connected to the power supply system must comply with the SELV requirement

    defined in IEC 60950.

    3. To avoid electric shock, do not conduct any operation or maintenance within the outdoor cabinet under

    thunderstorm or humid weather.

    4. Make sure that the outdoor cabinet is powered off before any operations can be carried out within the cabinet.

    5. The power cables should be routed and protected properly, so that the cables are kept away from the operation

    and maintenance personnel.

    2.2 Installation Preparation

    Unpacking inspection

    The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done

    by representatives of both the user and Emerson Network Power Co., Ltd.

    To inspect the equipment, you should open the packing case, take out the packing list and check against the packing

    list that the equipment is correct and complete. Make sure that the equipment is delivered intact.

    Preparing too ls

    The installation tools are given in Table 2-1. The tools must be insulated and ESD-proof processed before they are

    used.

    Table 2-1 Installation tools

    Tool Specification Tool Specification

    Combination wrench (hatch,

    club)

    Wrench set (10#, 13#, 16#,

    18#, 21#)Box wrench 16mm

    Adjustable wrench 200mm Cross screwdriver 100mm, 200mm

    Electrician diagonal pliers 150mm Slotted screwdriver 100mm, 200mm

    Electrician sharp nose pliers 150mm Wire cutters Maximum 300mm2

    Steel tape 5mHydraulic-pressure compaction

    pincherMaximum 300mm2

    Electric knife Normal type Digital multimeterThree and a half bit digital

    display

    Gradienter Normal type Impact electric drill With14 impact aiguille

    Blinkers To prevent splash Power socket With 5m cable

    Fireproof mud Configured in the accessories Safety shoesTo prevent puncture and for

    insulation

    Hammer

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    13/34

    Chapter 2 Installation 7

    2.3 Mechanical Installation

    2.3.1 Installing The Outdoor Cabinet

    The outdoor cabinet must be installed directly onto the cement floor.

    Step 1: Mark the specific installation position of the outdoor cabinet

    It is recommended to determine the installation position in compliance with the clearance requirements given in Table

    2-2.

    Table 2-2 Installation clearances

    Front Top Left Right Back

    Clearances 750mm 700mm 100mm 100mm 100mm

    Step 2: Install expansion bolts

    For forced ventilation model outdoor cabinet, by referring to Figure 2-1; for heat exchanger model and air-condition

    model outdoor cabinet, by referring to Figure 2-2, it is recommended to enlarge the installation size of the cabinet

    base because of the existence of the anti-toppling device (see Figure 2-3), determine the exact central points of theinstallation holes on the floor, and mark them with a pencil or oil pen. Use the electric drill (aiguille: 14) to dig holes

    (depth: 70mm) at the marked points. Clean the drilled holes off dust. Put the expansion bolts into the holes and knock

    them with a hammer till they are totally in.

    657

    700

    650

    88.5

    480

    Figure 2-1 Installation size 1 of the cabinet base (unit: mm)

    Front door

    650

    0.5

    900

    130

    Expansion bolt

    4800.5

    1100

    Figure 2-2 Installation size 2 of the cabinet base (unit: mm)

    Step 3: Fix the cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    14/34

    8 Chapter 2 Installation

    Move the cabinet to the installation position. Make the installation holes on the base coincide with those dug on the

    floor. Screw the M10 anchor bolt down into the expansion pipe in the floor.

    Pay attention to move the cabinet from the pallet in factory and install the anti-toppling device, as shown in Figure

    2-3.

    After installation, the cabinet should stand firmly no matter how it is shaken, then you can remove the anti-toppling

    device from the inside of the cabinet.

    Anti-toppling device

    Figure 2-3 Anti-toppling device

    2.3.2 Opening And Closing Cabinet Door

    You need to open and close the cabinet door during the cabinet installation, operation and maintenance. Procedures

    for opening and closing the cabinet door are as follows:

    Step 1: Insert the key into the keyhole, and turn the key clockwise until the door handle pops out.

    Step 2: Turn the handle counter-clockwise 90, as shown in Figure 2-4. Pull the handle until the door opens.

    90

    Figure 2-4 Turning the handle

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    15/34

    Chapter 2 Installation 9

    Step 3: Adjust the door stay bar to the position shown in Figure 2-5to prevent the door from closing automatically.

    Door stay bar

    Figure 2-5 Door stay bar

    Step 4: Restore the door stay bar to its original position and close the door. Finally, turn the handle to its original

    position and press it down until a click is heard.

    2.4 Electrical Installation

    All the cables must be put through metal pipes for protection. The metal pipe should be connected to the PE bar

    reliably. Plastic coated metal hoses are recommended.

    Earth cable and AC input cables enter the cabinet through the right side of the cabinet bottom. Signal cables, user

    equipment cables and DC cables enter the cabinet through the left side of the cabinet bottom.

    2.4.1 Connecting Power Cables

    Connecting earth cable

    Step 1: Cut the cable bushings covering the cabling holes (shown in Figure 2-6) on the bottom plate of the cabinet

    with an electrician knife.

    Step 2: Lead the earth cable into the cabinet through a cabling hole, and route it along the cable holders, as shown in

    Figure 2-6.

    Step 3: Connect one end of the earth cable to the earth terminal in the cabinet, and solder the other end to the earth

    metal base reliably.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    16/34

    10 Chapter 2 Installation

    Step 4: Use nylon cable ties to tie the earth cable to the cable holders.

    AC input MCB

    Earth terminal

    Cable holder

    Cabling hole

    Figure 2-6 Positions of earth terminal and cabling hole

    Connecting AC input cables

    If the outdoor cabinet has been installed Emerson matched subrack before delivery, the AC cable connection

    between subrack and cabinet should have been done by Emerson. You only need to connect the AC input cables

    according to the subrack user manual.

    If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 220V AC

    power to the AC input MCB on the right side of the cabinet (shown in Figure 2-6), so as to ensure the cabinet

    operation.

    Connecting DC cables

    If the outdoor cabinet has been installed Emerson matched subrack before delivery, the DC cable connection

    between subrack and cabinet should have been done by Emerson. You only need to connect load cables according

    to the subrack user manual.

    If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 48V DC

    power to DC input terminal on the left side of the cabinet (shown in Figure 2-7), so as to ensure the cabinet operation.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    17/34

    Chapter 2 Installation 11

    2.4.2 Connecting Signal Cables

    The cabinet provides four pairs of dry contacts for the user.

    All the dry contacts must be connected to the signal output terminal block, which is fixed on the left side of the cabinet.

    The position of the signal output terminal block is shown in Figure 2-7.

    Signal output terminal block

    DC input terminal

    Figure 2-7 Position of signal output terminal block

    Peel the signal cables and insert their ends into the corresponding terminals, then fasten the connection by tightening

    the screws on the terminals.

    The functions of the dry contact are given in Table 2-3.

    Table 2-3 Dry contact functions

    Port No. Definition Remark

    1, 2 Over temperature alarm Default value

    3, 4 Thermal control unit failure Default value

    5, 6 Door alarm Default value

    7, 8 Spare Configurable

    2.4.3 Sealing The Entry Holes

    After cable connection, use fireproof mud to seal the cabling holes (shown in Figure 2-6).

    2.5 Battery InstallationThe battery compartment can accommodate a battery string of capacity not higher than 50Ah. Batteries are classified

    into front-terminal battery and general battery.

    Note

    1. The batteries may carry dangerous current. Before connecting the battery cables, make sure all the battery input MCBs are off.

    2. Make sure that the battery cable polarities are correct. Otherwise, both the battery and the cabinet will be damaged!

    3. Insulate the installation tools. Be careful not to damage the plastic battery case or the battery terminals during installation.

    Check before installation

    1. Check that the battery shells are in good condition.

    2. Check that the polarities of the terminals are in accordance with the polarity marks on the battery shell.

    3. Check that the terminal screws are fastened.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    18/34

    12 Chapter 2 Installation

    ECM1500 Outdoor Cabinet User Manual

    Installation procedures

    Note

    1. When installing two battery strings or more, install the lower battery string first. While removing them, remove the upper

    battery string first.

    2. This chapter is applicable to Emerson subrack and battery cables. It is a reference when you configure subrack and battery

    cables for yourself.

    Step 1: Open the battery MCBs and AC input MCBs.

    Step 2: Place the batteries one by one in the battery compartment from right to left, with distance between adjacent

    batteries at least 10mm.

    Step 3: Remove the battery terminal covers, and connect the plate electrodes between the batteries in turn. Note that

    the mid-voltage sampling cable should be connected to the plate electrode between the second and the third

    batteries.

    Step 4: Connect the positive battery cables (red) in the battery compartment to the battery positive terminals. Connect

    the negative battery cables (black) in the battery compartment to the battery negative terminals. Attach the acid and

    alkali integration box (battery accessory) to the internal side of the right panel of the cabinet.

    Step 5: After installing the battery strings, use the 3M double-side adhesive tape pasted on the battery temperaturesensor to paste the sensor onto the center of the upper-layer battery string.

    Step 6: Measure the battery string voltage. If the voltage value is correct, replace the battery terminal covers.

    2.6 Installation Check

    After installation, check the installation against the list given in Table 2-4.

    Table 2-4 Installation check list

    Check item No. Description

    1 Check that the cabinet is level, upright and steadily fixed

    2Check that all bolts are tightened, especially those in electrical connections, that all bolts have plain

    washers and spring washers, and that the washers are not reversed3 Check that there are no irrelevant materials in the cabinet, and clear them away if any

    4Check that the cabinet paint is intact. If there are scratches, paint them immediately with antirust paint to

    prevent corrosion

    5 Clean up the cabinet

    6 Check that the door can move freely, the locks are in good condition and the door stay bar is fixed

    Cabinet

    installation

    7Check that the dummy plates are installed at the reserved space where no customer device is installed.

    Check that the burglarproof components (if configured) and battery baffles (if configured) are installed

    1 Verify the specifications of all MCBs and cables

    2Check the correctness of bus bar connections, input and output cable connection, and connection

    between the power system and the system grounding

    3 Check the correctness of the batteries number and connection, and battery strings polarities

    4 Make sure all the cable connections are firm and reliable

    5

    Check the connection point, line sequence and polarities of DC cables. Check the connection polarities of

    the batteries. Check that the connection points are fixed and the cable connections are correct and

    reliable

    Electrical

    connection

    6 Check that the cables are tidy, and the cable binding is normative

  • 8/13/2019 Emerson ECM1500

    19/34

    Chapter 3 Testing 13

    Chapter 3 Testing

    This chapter introduces the testing after installation. The corresponding safety rules shall be adhered to in the testing.

    This testing should be done after the subracks in the cabinet are tested.

    3.1 Startup

    Note

    Before the test, inform the chief manufacturer representative. Only the trained electrical engineer can maintain and operate this

    equipment. In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets, bangles

    and rings.

    During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries

    and property damage. Before the test, check the equipment to ensure the proper earthing.

    Make sure that the AC input and DC input are normal.

    Forced ventilation check

    After power-on, the heat control board enters self testing and the fans accelerate to full speed gradually. After a few

    minutes, the fans stop. If the environmental temperature is about 35C, the fans will operate at low speed.

    Heat exchanger check

    After power-on, the simple control unit enters self testing and the fans accelerate to full speed gradually. After a few

    minutes, the fans stop. If the environmental temperature is about 35C, the internal fans will operate at low speed and

    the external fans will stop.

    Air-condition check

    After power-on, the air-condition starts to operate. If the environmental temperature is about 35C, the internal fans of

    the air-condition will operate at low speed and the compressors of the external fans will stop.

    3.2 Alarm Check And System Operation Status Check

    Alarm check

    Disconnect the thermal control units, so as to check that if the thermal control units can trigger thermal control unit

    alarm.

    System operation status check

    There should be no alarms during normal system operation.

    3.3 Final Steps

    OK Comments

    Disconnect all test equipment from the outdoor cabinet and make sure that materials irrelevant to the

    equipment have been all removed.

    Restore the outdoor cabinet to its original condition and close the cabinet door.

    Check and handover the equipment that the user has purchased.

    Note down all the operations taken, including time of the operation and name of the operator.

    If any defect is found in this equipment, inform the personnel responsible for the contract.

    If repairing is needed, please fill in the FAILURE REPORT and send the report together with the faulty unit to the

    repairing center for fault analysis.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    20/34

  • 8/13/2019 Emerson ECM1500

    21/34

    Chapter 4 Maintenance 15

    4.2 Replacing Parts Of Forced Ventilation Model Outdoor Cabinet

    4.2.1 Replacing Heat Control Board

    Replace the heat control board using the following procedures:

    Step 1: Loosen the two fixing screws to remove the cover (shown in Figure 4-2), and then you can see the heat

    control board. The appearance of the heat control board is shown in Figure 4-3.

    Fixing screw of cover

    Cover

    Figure 4-2 Cover position

    SW2

    SW1

    Alarm indicator

    Figure 4-3 Appearance of the heat control board

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    22/34

    16 Chapter 4 Maintenance

    ECM1500 Outdoor Cabinet User Manual

    Step 2: Disconnect J11, J12 and J2 terminals (shown in Figure 4-4) in sequence, and then disconnect the rest

    connection terminals on the heat control board.

    B

    H1 H2

    H4

    H3

    ON

    J3

    J11

    J2

    J12

    J10

    J7

    J6

    SW1

    SW2

    Figure 4-4 Heat control board terminals layout

    Step 3: Loosen the fixing screws on the heat control board. Replace the heat control board with a new one.

    Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the indicators show correctly

    when fan fails. In normal condition, no alarm indicators will be on.

    Step 5: Set the SW2 switch according to Table 4-2.

    Table 4-2 Setting description of the SW2

    Name Label on thecorresponding cover

    Silk print on the

    corresponding fan control

    board

    Setting description

    Bit 1 Put the switch to the ON position (default), see Figure 4-3

    Bit 2Switch SW2 (shown in Figure 4-3)

    Put the switch to the OFF position (default), see Figure 4-3

    Step 6: Press the SW1 self-test button (shown in Figure 4-3) to ensure that the fan can start normally.

    Step 7: Replace the cover of the heat control board.

    4.2.2 Replacing Fans

    Fan alarm circu it

    The fan-cooling unit of the outdoor cabinet is mainly composed of 2 ~ 4 axial flow fans. The fan alarm circuit is shownin Figure 4-5, where the blue line is the alarm line.

    MOTORDRIVER IC VCE

    (Red) Ic

    VCC

    VFG

    R

    FG SIGNAL

    GROUND

    (Blue)

    (Black)

    (Yellow)

    Figure 4-5 Illustration of the fan alarm circuit

  • 8/13/2019 Emerson ECM1500

    23/34

    Chapter 4 Maintenance 17

    Fan alarm indicators

    The position of the alarm indicators is shown in Figure 4-3.

    The alarm indicators 1 ~ 4 on the heat control board correspond to fans 1 ~ 4 (alarm indicator 5 is the temperature

    sensor alarm indicator).

    Fan replacing procedures

    If the fan is faulty, the corresponding indicator will be on. Follow the following procedures to replace the fan.

    Step 1: Make sure that the fan-control terminals (J11 and J12 are hot pluggable) on the heat control board are

    inserted firmly. The fan-control terminals are shown in Figure 4-4.

    Step 2: Ensure that Bit 2 of SW2 switch is put to the OFF position.

    Step 3: Press the SW1 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cables

    are perfect.

    Step 4: Loosen the fixing screws at the cabinet top cover to open the top cover. (Opening the top cover, pull it forward

    and then lift up its front not more than 30. Otherwise the top cover will be fallen.)

    Step 5: Disconnect the fan power terminals at the top of the cabinet. Use a multimeter to measure the voltage

    between the positive power cable and the negative power cable. Check if the voltage is close to the DC output

    voltage (54.0V).

    If the fan power voltage is normal, the fans are damaged. Carry out the next step.

    Step 6: Loosen the fixing screws of the fans and replace the fans, as shown in Figure 4-6.

    Fan

    Figure 4-6 Fan position

    Step 7: Reconnect the fan power terminals, and press SW1 self-test button (shown in Figure 4-3) to ensure that the

    fan can startup normally.

    Step 8: Replace the cabinet top cover.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    24/34

    18 Chapter 4 Maintenance

    4.2.3 Replacing Door Status Sensor

    There is a door status sensor installed in the cabinet for detecting the close or open status of the cabinet door. The

    alarm will be eliminated only when the cabinet door is closed.

    The door status sensor requires no particular maintenance; just replace it when it is damaged. If the door is closed,

    while the door status sensor alarm occurs, the sensor must have been damaged. The position of the sensor is shownin Figure 4-7.

    Remove the sensor top cover and then the two screws. Replace the old sensor with a new one and finally fix the

    sensor and the signal cables with the screws.

    Door status sensor

    Figure 4-7 Position of the door status sensor

    4.3 Replacing Parts Of Heat Exchanger Model Outdoor Cabinet

    4.3.1 Replacing Environment Climate Control Unit

    Appearance and terminal layout

    The appearance of the environment climate control unit is shown in Figure 4-8, and the terminal layout is shown in

    Figure 4-9.

    Earth nut

    DIP switch

    Figure 4-8 Environment climate control unit

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    25/34

    Chapter 4 Maintenance 19

    J15

    J13

    J9

    J11

    J10

    J12

    J8J14J4J3J2J1

    J7

    J6

    J5

    SW101

    SW100

    CAN

    LED_ALM

    RS232

    P

    OWER

    LED_RUN

    LED_FAULT

    AL

    MOUT

    FAN1 FAN2 FAN3 FAN4

    AC_OFF

    TEMP.

    TEMP.&HUM.

    WATER

    INFRARED

    SMOKE

    DOOR

    Figure 4-9 Terminal layout of the environment climate control unit

    DIP switch description

    DIP switch function description and setting method:

    1. Bit 1 ~ 4 are used to set addresses of the environment climate control unit. OFF: 0, ON: 1. Default address: 16.

    The setting method of the environment climate control unit (ECCU for short) is given in Table 4-3.

    Table 4-3 Setting method of ECCU address

    Bit 4 Bit 3 Bit 21 Bit 1 Address

    0 0 0 0 16

    0 0 0 1 10 0 1 0 2

    1 1 1 1 15

    Bit 1 ~ Bit 4 have been set in factory. You can change the settings according to your communication requirement.

    2. The function description and setting method of Bit 5 ~ Bit 8 are given in Table 4-4.

    Table 4-4 Function sescription and setting method of Bit 5 ~ 8

    Bit No. Function Setting method Default value

    5 Choose cabinet modelOFF: heat exchanger model

    ON: forced ventilationOFF

    6 Choose dry contact alarm modeOFF: normal when open; alarm when closed

    ON: normal when closed; alarm when open ON

    7* Choose sensorOFF: serial port termperature & humidity sensor

    ON: temperature sensorON

    8Choose whether stopping fans

    when AC mains fails

    OFF: No

    ON: YesOFF

    Note*: When Bit 7 is placed to ON position, ECCU has no humidity acquisition function

    Replacing procedures of the ECCU

    Step 1: Loosen the two fixing screws to remove the cover, and then you can see the ECCU. The position of cover is

    shown in Figure 4-10.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    26/34

    20 Chapter 4 Maintenance

    Fixing screw of cover

    Cover

    Figure 4-10 Cover position

    Step 2: Disconnect J15 terminal (shown in Figure 4-9), and then disconnect the rest connection terminals on the

    ECCU.

    Step 3: Loosen the fixing screws on the ECCU. Replace the ECCU with a new one.

    Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the LED_FAULT (shown in

    Figure 4-9) indicator show correctly. Under normal instance, the LED_FAULT indicator is power-off.

    Step 5: Place the DIP switch to the correct position according to Table 4-3and Table 4-4.

    Step 6: Press the SW1 self-test button (shown in Figure 4-9) to ensure that the fan can start normally.

    Step 7: Replace the cover of the ECCU.

    4.3.2 Replacing Fans

    The heat exchanger of the outdoor cabinet is mainly composed of four centrifugal fans and a heat-exchanging core.

    If the fan is faulty, follow the following procedures to replace the fan.

    Step 1: Make sure that the fan-control terminals (J1, J2, J3 and J4 are hot pluggable) on the ECCU are inserted firmly.

    The fan-control terminals are shown in Figure 4-9.

    Step 2: Place the DIP switch to the correct position according to Table 4-3and Table 4-4.

    Step 3: Press the SW1 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cablesare perfect.

    Step 4: Disconnect the fan power terminals on the right side of the cabinet. Use a multimeter to measure the voltage

    between the positive power terminal and the negative power terminal. Check if the voltage is close to the DC output

    voltage (54.0V).

    If the fan power voltage is normal, the fans are damaged. Carry out the next step.

    Step 5: Loosen the fixing screws to remove cover of heat exchanger (shown in Figure 4-11), and then you can see

    the fans. Loosen the fixing screws of the fans to replace the fans.

    Step 6: Reconnect the fan power terminals, and press SW101 self-test button (shown in Figure 4-9) to ensure that the

    fan can startup normally.

    Step 7: Replace the heat exchanger cover.

    Fixing screw of heatexchanger cover

    Figure 4-11 Fixing screws of heat exchanger cover

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    27/34

  • 8/13/2019 Emerson ECM1500

    28/34

    22 Chapter 4 Maintenance

    4.4 Replaciing Parts Of Air-condition Model Outdoor Cabinet

    4.4.1 Replacing air-conditioner

    Step 1: Switch off the AC input MCB, as shown in Figure 4-14. Disconnect all the cable connectors.

    AC input MCB

    Figure 4-14 AC input MCB position

    Step 2: Loosen the fixing screws of air-condition to remove and replace air-condition.

    4.4.2 Replacing Emergent Ventilation Unit

    The emergent ventilation unit is composed of heat control board and fans. The replacing procedures of heat control

    board and fans are the same as that of the forced ventilation model outdoor cabinet. You can refer to 4.2.1

    Replacing Heat Control Boardand 4.2.2 Replacing Fans.

    4.4.3 Replacing Door Status Sensor

    Refer to 4.2.3 Replacing Door Status Sensor.

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    29/34

    Appendix 1 Technical And Engineering Parameters 23

    Appendix 1 Technical And Engineering Parameters

    Table 1 Technical parameters

    Parametercategory

    Parameter Description

    Operating temperature-10C ~ +45C (forced ventilation model), -40C ~ +45C (heat exchanger

    model), -40C ~ +50C (air-condition model)

    Storage temperature -40C ~ +70C

    Relative humidity 5%RH ~ 100%RH

    Altitude 2,000m (derating is required above 2,000m)

    Environmental

    Others No conductive dust or erosive gases. No possibility of explosion

    Conducted emission

    Radiated emissionClass A EN55022

    Immunity to EFT Level 3 EN61000-4-4

    Immunity to ESD Level 3 EN61000-4-2

    Immunity to Surges Level 4 EN61000-4-5

    Immunity to radiation Level 3 EN61000-4-3

    EMC

    Immunity to conduction Level 3 EN61000-4-6

    Safety regulation Compliant with IEC60950-1, IEC60950-22

    Insulation resistance

    At temperature of 15C ~ 35C and relative humidity not bigger than 90%RH,

    apply a test voltage of 500Vdc. The insulation resistances between AC circuit

    and earth, DC circuit and earth, and AC and DC circuits are all not less than

    10M

    Insulation strength

    (Remove the SPD, monitoring module and rectifiers from the system before the

    test.)

    AC circuit to earth: 50Hz, 2,500Vac

    DC circuit to earth: 50Hz, 1,000Vac

    Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac

    AC to DC circuits: 50Hz, 3,000VacFor all the three tests above, there should be no breakdown or flashover within

    1min, with leakage current not bigger than 10mA

    MTBF 100,000hr

    Others

    ROHS Compliant with R5 requirement

    Cabinet 700 (W) 700 (D) 1800 (H)

    Dimensions (mm) Internal space of

    battery compartment613 (W) 570 (D) 350 (H)

    Forced ventilation

    model cabinet125 (excluding subrack and battery string)

    Heat exchanger

    model cabinet180 (excluding subrack and battery string)

    Mechanical

    Weight (kg)

    Air-condition model

    cabinet 175 (excluding subrack and battery string)

    Table 2 Spart part list

    Part Specification or model BOM

    Fan DC axial flow fan 32010191

    Fan DC centrifugal fan 32010261

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    30/34

    Appendix 2 Wiring Diagram

    Mains Input

    QFA1

    3

    N

    11

    L

    42

    NLPE

    5

    6

    2

    3

    4

    PE Bar

    1

    7

    PEBUS

    3

    2

    X1

    4

    MS

    PE

    W02

    N L

    NOTE:

    W02_A for Europen standard socket.

    W02_B for American standard socket.

    W02_C for Chinese and British standard socket.

    1 3 5

    2 4 6

    W01

    W01

    U1

    6

    1

    2

    2

    1

    3

    2

    1

    W20

    68 7 5 4 3 2 1

    W04

    P344309U1

    J6

    J7

    J10J2

    J3

    61 2 3 4 554321

    W05

    J12J11

    Temperature sensor I

    W1234578 6

    1234578 6

    1 2

    W07

    14-7

    14-5 U2

    7

    7-J2

    J3

    J1J2

    6-J3

    7-J1

    6-J10

    1 3

    2 4+ -

    5

    X2

    1

    14-3

    14-1 3

    5

    7

    9

    11

    13

    15

    17

    1921

    23

    2

    46

    8

    10

    12

    14

    16

    18

    2022

    24

    7-J3-7

    7-J3-8

    7-J3-2

    8-1

    8-2

    7-J3-1

    X3

    14

    P345314X1

    AC Input

    DC Input

    FAN2FAN1

    RedYellowBlue Black

    Blue Yellow Red Black Blue

    Blue Yellow

    Yellow Red

    Red Black

    Black

    FAN1 FAN2

    9 10

    FAN3

    RedYellowBlue Black

    Blue Yellow Red Black

    FAN3

    11

    solder solder solder

    W03

    W05 W05

    W06

    W06

    W06

    W06

    W07

    W08

    W07

    Figure 1 Wiring diagram of forced ventilation model outdoor cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    31/34

    Mains Input

    QFA1

    3

    N

    11

    L

    42

    NLPE

    5

    6

    2

    3

    4

    PE Bar1

    7

    3

    2

    X1

    4

    MS

    PE

    W02

    N L

    NOTE:

    W02_A for Europen standard socket.

    W02_B for American standard socket.

    W02_C for Chinese and British standard socket.

    1 3 5

    2 4 6

    W01

    W01

    U1

    6

    14-9

    21

    Door alarm

    MJ

    8W08

    1 3

    2 4+ -

    5

    X2

    6-J8

    W05

    T1

    13

    Temperature sensor I

    14-11

    6-J5-1

    6-J5-2

    6-J5-48-1

    8-2

    6-J5-3

    POWER

    J5

    J1 J2 J3 J4 J8

    J15

    AC Input

    DC Input

    FAN2FAN1

    Blue Yellow Red Black

    FAN1 FAN2

    9 10

    Heater1

    H1

    22

    23

    H2

    Heater2

    21

    12

    Black

    Red

    1 2

    KT1

    21

    Black

    solder

    solderBlack

    Red

    Black

    Black

    BlueBlue

    Blue

    1 2 3 4 5 1 2 3 4 51 2 3 4 1 2 3 4

    W05Temperature sensor I

    2

    1

    5-4

    5-2

    6-J15-1

    6-J15-2+- PWM ALARM

    5-25-4

    ECCU11U1

    W03

    W03

    W03

    W04

    W04

    W06

    W07

    W08

    1

    2345

    78

    6

    W07

    14-114-314-514-7

    XT

    19

    Bottom cross

    1

    2

    3

    4

    J11

    1

    2

    J13

    1 2 1 2 3

    J14

    W07

    W07

    W07

    YellowBlue Red Black

    solder

    FAN1

    FAN1* Blue Ye llow

    - PW

    5-4

    YellowBlue

    so

    FAN3

    FAN3*Blue Yellow Red Black

    +- PWM ALARM

    5-25-4

    YellowBlue Red Black

    solder

    FAN2

    FAN2*

    Figure 2 Wiring diagram of heat exchanger model outdoor cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    32/34

    Mains Input

    QFA1

    3

    N

    11

    L

    42

    NLPE

    5

    6

    2

    3

    4

    PE Bar

    1

    7

    3

    2

    X1

    4

    MS

    PE

    W02

    N L

    NOTE:

    W02_A for Europen standard socket.

    W02_B for American standard socket.

    W02_C for Chinese and British s tandard socket.

    1 3 5

    2 4 6

    W01

    W01

    AC Input

    1

    2

    2

    1

    3

    2

    1

    68 7 5 4 3 2 1

    P344309U1

    J6

    J7

    J10J2

    J3

    61 2 3 4 554321

    W06

    J12J11

    16

    W08

    XT

    15

    XT

    14-9

    21

    Door alarm

    MJ

    8W17

    7-J2

    7-J1

    1 3

    2 4+ -

    5

    X2

    6-J6

    W05

    T1

    13

    Temperature sensor I

    1

    3

    5

    7

    9

    1113

    15

    17

    19

    21

    23

    2

    4

    6

    8

    10

    1214

    16

    18

    20

    22

    24

    14-11

    7-J3-7

    7-J3-8

    8-1

    8-2

    DC Input

    Blu

    Blu

    AC

    19

    Air-condition

    321

    J2J1

    PENL

    J3

    Temperature sensor II

    Cable from Air-condition

    54

    18

    W08

    XT

    17

    XT

    W03

    W04

    W07

    W

    Bottom cross front door line

    Bottom cross back door line

    9101112131415

    12345678

    14-5

    14-7

    6-J12-3

    FAN2

    6-J12-3

    FAN1

    19-

    19-

    19-

    19-

    20

    W09

    XT

    19

    XT

    Bottom cross control board door line

    X3

    14

    19-J2-919-J2-10

    W06

    W06

    W17

    W08

    Figure 3 Wiring diagram of air-condition model outdoor cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    33/34

    Appendix 3 Schematic Diagram 27

    Appendix 3 Schematic Diagram

    L

    N

    QFA1

    L

    N

    ALARM

    +-

    A

    V-

    V+

    FanC

    CONTROL

    Forced Ventilation Unit

    FCU

    A

    V-

    V+

    FanC

    ALARM

    +- CONTROL

    FCUX

    Over Temperature

    Dry Contact Terminal

    Spare

    Climate unit fault

    Door Alarm

    PE

    to PE bar

    0V

    -48V

    to Dry Contact TerminalDoor Alarm

    X1

    X2

    X3

    XS

    AC Input

    DC Input

    Figure 4 Schematic diagram of forced ventilation model outdoor cabinet

    L

    N

    L

    N

    ALARM

    +

    A

    V-

    V+

    Internal fan

    C

    CONTROL

    Heat Exchanger Unit

    ECCU

    A

    V-

    V+

    External fan

    C

    ALARM

    +- CONTROL

    Over Temperature

    Dry Contact Terminal

    Spare

    Climate unit fault

    Door AlarmAC

    PE

    to PE bar

    0V

    -48V

    to Dry Contact TerminalDoor AlarmX1

    X3

    AC Input

    DC Input

    Heater

    -

    QFA1 XS

    KT1

    X2

    Figure 5 Schematic diagram of heat exchanger model outdoor cabinet

    ECM1500 Outdoor Cabinet User Manual

  • 8/13/2019 Emerson ECM1500

    34/34

    28 Appendix 3 Schematic Diagram

    L

    N

    QFA1

    Air-condition Unit

    Over Temperature

    Dry Contact Terminal

    Spare

    Climate unit fault

    Door Alarm

    PE

    to PE bar

    AlarmFan contral

    0V

    -48V

    V+

    V-Fan

    Emergent Ventilation Unit

    FCU FCUX

    to Dry Contact TerminalDoor Alarm

    X1

    X2

    X3

    AC Input

    DC Input

    XS

    LN

    Figure 6 Schematic diagram of air-condition model outdoor cabinet