Upload
cristachedinu
View
228
Download
1
Embed Size (px)
Citation preview
8/13/2019 Emerson ECM1500
1/34
ECM1500 Outdoor Cabinet
User Manual
Version V1.3
Revision date December 3, 2009
BOM 31012154
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Copyright 2009 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
8/13/2019 Emerson ECM1500
2/34
Safety Precautions
To reduce the chance of accident, please read the safety precautions very carefully before operation. The"Caution, Note, Warning, Danger" in this book and on the product do not represent all the safety points to be
observed, and are only supplement to various safety points. Therefore, the installation and operation personnel
must receive strict training and master the correct operations and all the safety points before operation.
When operating Emerson products, the operation personnel must observe the safety rules in the industry, the
general safety points and special safety instructions specified in this book.
If you purchase an outdoor power supply without SPD, you should install an SPD at the front-end of AC input,
otherwise, the power supply system will generate over-voltage.
Electrical Safety
I. Hazardous vo ltage
Danger
Some components of the outdoor cabinet system carry hazardous voltage in operation. Direct contact or indirect contact
through moist objects with these components will result in fatal injury.
Observe safety rules in the industry when installing the power supply system. The installation personnel must be
licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects, such as watches, bracelets,
bangles and rings.
When you spot the cabinet with water or moisture, turn off the power immediately. In moist environment,precautions must be taken to keep moisture out of the power supply system.
"Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during
installation.
Danger
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliancewith the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high
voltage operations.
Danger
To avoid electric shock hazard for outdoor environment and outdoor equipment, the non-professionals are prohibited tooperate or maintain the outdoor power supply system.
II. Tools
Warning
In high voltage and AC operation, specialized tools must be used.
8/13/2019 Emerson ECM1500
3/34
III. Thunderstorm
Danger
Never operate on high voltage, AC, iron tower or mast in the thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be
well earthed in time to avoid damage by lightning strikes.
IV. ESD
Note
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scaleICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from
damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.
V. Short ci rcuit
Danger
During operation, never short the positive and negative poles of the DC distribution unit of the outdoor cabinet system, orthe non-earth pole of the outdoor cabinet system and the earth. The power supply system is a constant-voltage DC power
device, short circuit will result in equipment burning and endanger human safety.
VI. Reverse connection
Warning
Never reverse-connect the AC input live line and neutral line, or else the system will be damaged.
Check the polarity of the cable and connection terminal when performing DC live operations.
As the operation space in the DC distribution unit is very tight, please carefully select the operation space.
Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.
Use insulated tools.
In live operation, keep the arm, wrist and hand tense, so that when the tool in operation slips, the movement of
the human body and tool is reduced to a minimum.
Battery
Danger
Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery
connection method.
Warning
If customers prepare batteries themselves, the battery installation and maintenance should meet relevant safety standards.
8/13/2019 Emerson ECM1500
4/34
Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent
battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs,
thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points:1. Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.
2. Use specialized insulated tools.
3. Use eye protection device, and take preventive measures.
4. Wear rubber gloves and apron to guard against electrolyte overflow.
5. In battery transportation, the electrode of the battery should always be kept facing upward. Never put the
battery upside down or slanted.
Connection And Testing Of The Outdoor Cabinet
Before installing subrack power supply in the cabinet, you should finish the connection and testing of thesubrack power supply according to the corresponding subrack power supply user manual and then testing the
outdoor cabinet.
Others
I. Sharp object
Warning
When moving equipment by hand, wear protective gloves to avoid injury by sharp object.
II. Power cable
NoticNote Please verify the cable labels before connection.
III. Signal cables
NoticNote The signal cables should be routed at least 150mm away from power cables.
8/13/2019 Emerson ECM1500
5/34
Contents
Chapter 1 Overview ....................................................... ....................................................... .............................................. 1
1.1 Model Description ...................................................... ........................................................ ................................... 1
1.2 Composition & Configuration ................................................ ........................................................ ........................ 1
1.3 Operating Theory....................................................... ........................................................ ................................... 4
1.4 Features................................................. ....................................................... ........................................................ 5
Chapter 2 Installation ..................................................... ....................................................... .............................................. 6
2.1 Safety Regulations......................... ........................................................ ............................................................... 6
2.2 Installation Preparation ............................................... ........................................................ .................................. 6
2.3 Mechanical Installation............................................... ........................................................ ................................... 72.3.1 Installing The Outdoor Cabinet ....................................................... ........................................................ ... 7
2.3.2 Opening And Closing Cabinet Door.......................................................... ................................................. 8
2.4 Electrical Installation ................................................... ....................................................... ................................... 9
2.4.1 Connecting Power Cables .................................................... ....................................................... .............. 9
2.4.2 Connecting Signal Cables ....................................................... ............................................................ .... 11
2.4.3 Sealing The Entry Holes.......................................................... ............................................................ .... 11
2.5 Battery Installation ..................................................... ........................................................ ................................. 11
2.6 Installation Check......................................................................... ....................................................................... 12
Chapter 3 Testing....................................... ........................................................ ............................................................... 13
3.1 Startup .................................................. ........................................................ ...................................................... 13
3.2 Alarm Check And System Operation Status Check ............................................................ ................................ 13
3.3 Final Steps...................................................... ........................................................ ............................................ 13
Chapter 4 Maintenance............. ........................................................ ....................................................... ......................... 14
4.1 Routine Maintenance.................................................. ....................................................... ................................. 14
4.2 Replacing Parts Of Forced Ventilation Model Outdoor Cabinet..................................................... ..................... 15
4.2.1 Replacing Heat Control Board ............................................................ ..................................................... 15
4.2.2 Replacing Fans....................................... ........................................................ ......................................... 16
4.2.3 Replacing Door Status Sensor ........................................................... ..................................................... 18
4.3 Replacing Parts Of Heat Exchanger Model Outdoor Cabinet ........................................................ ..................... 18
4.3.1 Replacing Environment Climate Control Unit................................................. .......................................... 18
4.3.2 Replacing Fans....................................... ........................................................ ......................................... 20
4.3.3 Replacing Heater....................................................... ....................................................... ....................... 21
4.3.4 Replacing Door Status Sensor ........................................................... ..................................................... 21
4.4 Replaciing Parts Of Air-condition Model Outdoor Cabinet .................................................. ................................ 22
4.4.1 Replacing air-conditioner......................................................... ............................................................ .... 22
4.4.2 Replacing Emergent Ventilation Unit .................................................. ..................................................... 22
4.4.3 Replacing Door Status Sensor ........................................................... ..................................................... 22
8/13/2019 Emerson ECM1500
6/34
Appendix 1 Technical And Engineering Parameters.................................................... ..................................................... 23
Appendix 2 Wiring Diagram........................................................................................... .................................................... 24
Appendix 3 Schematic Diagram................................................ ........................................................ ................................ 27
8/13/2019 Emerson ECM1500
7/34
Chapter 1 Overview 1
Chapter 1 Overview
ECM1500 outdoor cabinet (outdoor cabinet for short) is a power supply system used outdoors. It provides outdoor
protection and operation environment. It contains thermal control units and AC power distribution units. The cabinetcan accommodate different Emerson subrack power supplies according to your requirement so as to form power
supply systems with different capacities.
This chapter introduces the model description, composition & configuration, operating theory and features of the
outdoor cabinet.
1.1 Model Description
The outdoor cabinet is available in three models, configured with different models of thermal control unit (forced
ventilation, heat exchanger and air-condition). Taking the forced ventilation model for example, the model description
of the outdoor cabinet is given in Figure 1-1.
EC 1500 F 1 48 300-M
Internal power capacity: 300A, 150A, 120A
Version No.
Thermal control method: F (forced ventilation), H (heat exchanger), A (air-condition)
Maximum heat productivity in cabinet:1500W
Application: mobile network integrated cabinet
Emerson outdoor cabinet
Internal power voltage:48Vdc
Figure 1-1 Model description
1.2 Composition & Configuration
Composition
The outdoor cabinet is composed of thermal control units, power distribution units and related structures. Three
models of thermal control units are available: forced ventilation, heat exchanger and air-condition.
Configuration
1. The configuration of the forced ventilation model outdoor cabinet is given in Table 1-1.
Table 1-1 Configuration list of the forced ventilation model outdoor cabinet
Component Configuration
Fan 4 pieces
Heat control board 1 pieceThermal controlunit Heat control extension
board1 piece
AC power distribution 1 route 10A single-phase AC socket; one route 25A single-phase AC input MCBPower
distribution unit DC power distribution DC input terminals
Power and reserved space Sharing space: 15U, you can adjust space according to requirement
Door status sensor 1 piece
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
8/34
2 Chapter 1 Overview
The structure of the forced ventilation model outdoor cabinet is shown in Figure 1-2.
Figure 1-2 Structure of the forced ventilation model outdoor cabinet
2. The configuration of the heat exchanger model outdoor cabinet is given in Table 1-2.
Table 1-2 Configuration list of the heat exchanger model outdoor cabinet
Component Configuration
Fan 4 piecesThermal control
unitEnvironment climate
control unit1 piece
AC power distribution 1 route 10A single-phase AC socket; one route 25A single-phase AC input MCBPower
distribution unit DC power distribution DC input terminals
Power and reserved space Sharing space: 15U, you can adjust space according to requirement
Door status sensor 1 piece
The structure of the heat exchanger model outdoor cabinet is shown in Figure 1-3.
Figure 1-3 Heat exchanger model outdoor cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
9/34
Chapter 1 Overview 3
The configuration of the air-condition model outdoor cabinet is given in Table 1-3.
Table 1-3 Configuration list of the air-condition model outdoor cabinet
Component Configuration
Outdoor air-condition 1 pieceThermal control
unit Emergent ventilation unit 1 set
AC power distribution 1 route 10A single-phase AC socket; 1 route 25A single-phase AC input MCBPower
distribution unit DC power distribution DC input terminals
Power and reserved space Sharing space: 15U, you can adjust space according to requirement
Door status sensor 1 piece
The structure of the air-condition model outdoor cabinet is shown in Figure 1-4.
Figure 1-4 Air-condition model outdoor cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
10/34
4 Chapter 1 Overview
1.3 Operating Theory
Heat dissipation theory for forced ventilation model outdoor cabinet
The cold air is sucked in through the front door air filter at the lower part of the outdoor cabinet. It passes through the
battery compartment, user equipment and subrack power supply in turn. Finally, the hot air is discharged by the fans
at the top of the outdoor cabinet. In this way, the equipment and power modules in the cabinet are cooled, as shown
in Figure 1-5.
Heat dissipation fan
Subrack power supply
Air outlet
Air inlet
Sharing space
Figure 1-5 Heat dissipation access for forced ventilation model outdoor cabinet
Heat dissipation theory for heat exchanger model ou tdoor cabinet
A heat exchanger is fitted on the door of the outdoor cabinet. It can exchange the heat between the cold air outside
the cabinet and the hot air inside the cabinet. In this way, the equipment and power modules in the cabinet are cooled,
as shown in Figure 1-6.
Internal circulation air
inlet of heat exchanger
Internal circulation airoutlet of heat exchanger
Figure 1-6 Heat dissipation theory for heat exchanger model outdoor cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
11/34
Chapter 1 Overview 5
Heat dissipation theory for air-condition model outdoor cabinet
An outdoor air-conditioner is fitted on the door of the outdoor cabinet to cool the cabinet. It is in this that the
equipment and power modules in the cabinet are cooled. In case of air-conditioner fault or AC mains failure, the
emergent ventilation units automatically startup to dissipate heat emergently, as shown in Figure 1-7.
Top emergent ventilation fan
Return air inlet of air-condition
Outdoor air-condition
Air outlet of air-condition
Figure 1-7 Heat dissipation theory for air-condition model outdoor cabinet
1.4 Features
Variable subrack power supply: The outdoor cabinet can accommodate standard 19 and 23 subrack power
supply.
Variable space: The power space, reserved space and the battery compartment space are interchangeable. You
can adjust the space according to the actual requirement.
Thermal control unit: Three different models are available for your selection according to the local, environment
and requirement.
Safety guideline: The equipment compartment satisfies IP*5 waterproof requirement and IP5* dustproof
requirement.
Environment pollution level within the outdoor cabinets is 2.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
12/34
6 Chapter 2 Installation
Chapter 2 Installation
This chapter introduces installation and cable connection. Strictly follow the instructions provided in this chapter to
carry out the installation and cable connection.
2.1 Safety Regulations
Certain components in this power supply system have hazardous voltage and current. To ensure personnel safety,
always follow the instructions below:
1. Only the trained personnel with adequate knowledge of the outdoor cabinet shall carry out the installation. The
Safety Precautions listed before the Contents of this manual and local safety rules in force shall be adhered to during
installation.
2. All external circuits below -48V connected to the power supply system must comply with the SELV requirement
defined in IEC 60950.
3. To avoid electric shock, do not conduct any operation or maintenance within the outdoor cabinet under
thunderstorm or humid weather.
4. Make sure that the outdoor cabinet is powered off before any operations can be carried out within the cabinet.
5. The power cables should be routed and protected properly, so that the cables are kept away from the operation
and maintenance personnel.
2.2 Installation Preparation
Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done
by representatives of both the user and Emerson Network Power Co., Ltd.
To inspect the equipment, you should open the packing case, take out the packing list and check against the packing
list that the equipment is correct and complete. Make sure that the equipment is delivered intact.
Preparing too ls
The installation tools are given in Table 2-1. The tools must be insulated and ESD-proof processed before they are
used.
Table 2-1 Installation tools
Tool Specification Tool Specification
Combination wrench (hatch,
club)
Wrench set (10#, 13#, 16#,
18#, 21#)Box wrench 16mm
Adjustable wrench 200mm Cross screwdriver 100mm, 200mm
Electrician diagonal pliers 150mm Slotted screwdriver 100mm, 200mm
Electrician sharp nose pliers 150mm Wire cutters Maximum 300mm2
Steel tape 5mHydraulic-pressure compaction
pincherMaximum 300mm2
Electric knife Normal type Digital multimeterThree and a half bit digital
display
Gradienter Normal type Impact electric drill With14 impact aiguille
Blinkers To prevent splash Power socket With 5m cable
Fireproof mud Configured in the accessories Safety shoesTo prevent puncture and for
insulation
Hammer
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
13/34
Chapter 2 Installation 7
2.3 Mechanical Installation
2.3.1 Installing The Outdoor Cabinet
The outdoor cabinet must be installed directly onto the cement floor.
Step 1: Mark the specific installation position of the outdoor cabinet
It is recommended to determine the installation position in compliance with the clearance requirements given in Table
2-2.
Table 2-2 Installation clearances
Front Top Left Right Back
Clearances 750mm 700mm 100mm 100mm 100mm
Step 2: Install expansion bolts
For forced ventilation model outdoor cabinet, by referring to Figure 2-1; for heat exchanger model and air-condition
model outdoor cabinet, by referring to Figure 2-2, it is recommended to enlarge the installation size of the cabinet
base because of the existence of the anti-toppling device (see Figure 2-3), determine the exact central points of theinstallation holes on the floor, and mark them with a pencil or oil pen. Use the electric drill (aiguille: 14) to dig holes
(depth: 70mm) at the marked points. Clean the drilled holes off dust. Put the expansion bolts into the holes and knock
them with a hammer till they are totally in.
657
700
650
88.5
480
Figure 2-1 Installation size 1 of the cabinet base (unit: mm)
Front door
650
0.5
900
130
Expansion bolt
4800.5
1100
Figure 2-2 Installation size 2 of the cabinet base (unit: mm)
Step 3: Fix the cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
14/34
8 Chapter 2 Installation
Move the cabinet to the installation position. Make the installation holes on the base coincide with those dug on the
floor. Screw the M10 anchor bolt down into the expansion pipe in the floor.
Pay attention to move the cabinet from the pallet in factory and install the anti-toppling device, as shown in Figure
2-3.
After installation, the cabinet should stand firmly no matter how it is shaken, then you can remove the anti-toppling
device from the inside of the cabinet.
Anti-toppling device
Figure 2-3 Anti-toppling device
2.3.2 Opening And Closing Cabinet Door
You need to open and close the cabinet door during the cabinet installation, operation and maintenance. Procedures
for opening and closing the cabinet door are as follows:
Step 1: Insert the key into the keyhole, and turn the key clockwise until the door handle pops out.
Step 2: Turn the handle counter-clockwise 90, as shown in Figure 2-4. Pull the handle until the door opens.
90
Figure 2-4 Turning the handle
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
15/34
Chapter 2 Installation 9
Step 3: Adjust the door stay bar to the position shown in Figure 2-5to prevent the door from closing automatically.
Door stay bar
Figure 2-5 Door stay bar
Step 4: Restore the door stay bar to its original position and close the door. Finally, turn the handle to its original
position and press it down until a click is heard.
2.4 Electrical Installation
All the cables must be put through metal pipes for protection. The metal pipe should be connected to the PE bar
reliably. Plastic coated metal hoses are recommended.
Earth cable and AC input cables enter the cabinet through the right side of the cabinet bottom. Signal cables, user
equipment cables and DC cables enter the cabinet through the left side of the cabinet bottom.
2.4.1 Connecting Power Cables
Connecting earth cable
Step 1: Cut the cable bushings covering the cabling holes (shown in Figure 2-6) on the bottom plate of the cabinet
with an electrician knife.
Step 2: Lead the earth cable into the cabinet through a cabling hole, and route it along the cable holders, as shown in
Figure 2-6.
Step 3: Connect one end of the earth cable to the earth terminal in the cabinet, and solder the other end to the earth
metal base reliably.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
16/34
10 Chapter 2 Installation
Step 4: Use nylon cable ties to tie the earth cable to the cable holders.
AC input MCB
Earth terminal
Cable holder
Cabling hole
Figure 2-6 Positions of earth terminal and cabling hole
Connecting AC input cables
If the outdoor cabinet has been installed Emerson matched subrack before delivery, the AC cable connection
between subrack and cabinet should have been done by Emerson. You only need to connect the AC input cables
according to the subrack user manual.
If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 220V AC
power to the AC input MCB on the right side of the cabinet (shown in Figure 2-6), so as to ensure the cabinet
operation.
Connecting DC cables
If the outdoor cabinet has been installed Emerson matched subrack before delivery, the DC cable connection
between subrack and cabinet should have been done by Emerson. You only need to connect load cables according
to the subrack user manual.
If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 48V DC
power to DC input terminal on the left side of the cabinet (shown in Figure 2-7), so as to ensure the cabinet operation.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
17/34
Chapter 2 Installation 11
2.4.2 Connecting Signal Cables
The cabinet provides four pairs of dry contacts for the user.
All the dry contacts must be connected to the signal output terminal block, which is fixed on the left side of the cabinet.
The position of the signal output terminal block is shown in Figure 2-7.
Signal output terminal block
DC input terminal
Figure 2-7 Position of signal output terminal block
Peel the signal cables and insert their ends into the corresponding terminals, then fasten the connection by tightening
the screws on the terminals.
The functions of the dry contact are given in Table 2-3.
Table 2-3 Dry contact functions
Port No. Definition Remark
1, 2 Over temperature alarm Default value
3, 4 Thermal control unit failure Default value
5, 6 Door alarm Default value
7, 8 Spare Configurable
2.4.3 Sealing The Entry Holes
After cable connection, use fireproof mud to seal the cabling holes (shown in Figure 2-6).
2.5 Battery InstallationThe battery compartment can accommodate a battery string of capacity not higher than 50Ah. Batteries are classified
into front-terminal battery and general battery.
Note
1. The batteries may carry dangerous current. Before connecting the battery cables, make sure all the battery input MCBs are off.
2. Make sure that the battery cable polarities are correct. Otherwise, both the battery and the cabinet will be damaged!
3. Insulate the installation tools. Be careful not to damage the plastic battery case or the battery terminals during installation.
Check before installation
1. Check that the battery shells are in good condition.
2. Check that the polarities of the terminals are in accordance with the polarity marks on the battery shell.
3. Check that the terminal screws are fastened.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
18/34
12 Chapter 2 Installation
ECM1500 Outdoor Cabinet User Manual
Installation procedures
Note
1. When installing two battery strings or more, install the lower battery string first. While removing them, remove the upper
battery string first.
2. This chapter is applicable to Emerson subrack and battery cables. It is a reference when you configure subrack and battery
cables for yourself.
Step 1: Open the battery MCBs and AC input MCBs.
Step 2: Place the batteries one by one in the battery compartment from right to left, with distance between adjacent
batteries at least 10mm.
Step 3: Remove the battery terminal covers, and connect the plate electrodes between the batteries in turn. Note that
the mid-voltage sampling cable should be connected to the plate electrode between the second and the third
batteries.
Step 4: Connect the positive battery cables (red) in the battery compartment to the battery positive terminals. Connect
the negative battery cables (black) in the battery compartment to the battery negative terminals. Attach the acid and
alkali integration box (battery accessory) to the internal side of the right panel of the cabinet.
Step 5: After installing the battery strings, use the 3M double-side adhesive tape pasted on the battery temperaturesensor to paste the sensor onto the center of the upper-layer battery string.
Step 6: Measure the battery string voltage. If the voltage value is correct, replace the battery terminal covers.
2.6 Installation Check
After installation, check the installation against the list given in Table 2-4.
Table 2-4 Installation check list
Check item No. Description
1 Check that the cabinet is level, upright and steadily fixed
2Check that all bolts are tightened, especially those in electrical connections, that all bolts have plain
washers and spring washers, and that the washers are not reversed3 Check that there are no irrelevant materials in the cabinet, and clear them away if any
4Check that the cabinet paint is intact. If there are scratches, paint them immediately with antirust paint to
prevent corrosion
5 Clean up the cabinet
6 Check that the door can move freely, the locks are in good condition and the door stay bar is fixed
Cabinet
installation
7Check that the dummy plates are installed at the reserved space where no customer device is installed.
Check that the burglarproof components (if configured) and battery baffles (if configured) are installed
1 Verify the specifications of all MCBs and cables
2Check the correctness of bus bar connections, input and output cable connection, and connection
between the power system and the system grounding
3 Check the correctness of the batteries number and connection, and battery strings polarities
4 Make sure all the cable connections are firm and reliable
5
Check the connection point, line sequence and polarities of DC cables. Check the connection polarities of
the batteries. Check that the connection points are fixed and the cable connections are correct and
reliable
Electrical
connection
6 Check that the cables are tidy, and the cable binding is normative
8/13/2019 Emerson ECM1500
19/34
Chapter 3 Testing 13
Chapter 3 Testing
This chapter introduces the testing after installation. The corresponding safety rules shall be adhered to in the testing.
This testing should be done after the subracks in the cabinet are tested.
3.1 Startup
Note
Before the test, inform the chief manufacturer representative. Only the trained electrical engineer can maintain and operate this
equipment. In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets, bangles
and rings.
During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries
and property damage. Before the test, check the equipment to ensure the proper earthing.
Make sure that the AC input and DC input are normal.
Forced ventilation check
After power-on, the heat control board enters self testing and the fans accelerate to full speed gradually. After a few
minutes, the fans stop. If the environmental temperature is about 35C, the fans will operate at low speed.
Heat exchanger check
After power-on, the simple control unit enters self testing and the fans accelerate to full speed gradually. After a few
minutes, the fans stop. If the environmental temperature is about 35C, the internal fans will operate at low speed and
the external fans will stop.
Air-condition check
After power-on, the air-condition starts to operate. If the environmental temperature is about 35C, the internal fans of
the air-condition will operate at low speed and the compressors of the external fans will stop.
3.2 Alarm Check And System Operation Status Check
Alarm check
Disconnect the thermal control units, so as to check that if the thermal control units can trigger thermal control unit
alarm.
System operation status check
There should be no alarms during normal system operation.
3.3 Final Steps
OK Comments
Disconnect all test equipment from the outdoor cabinet and make sure that materials irrelevant to the
equipment have been all removed.
Restore the outdoor cabinet to its original condition and close the cabinet door.
Check and handover the equipment that the user has purchased.
Note down all the operations taken, including time of the operation and name of the operator.
If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the faulty unit to the
repairing center for fault analysis.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
20/34
8/13/2019 Emerson ECM1500
21/34
Chapter 4 Maintenance 15
4.2 Replacing Parts Of Forced Ventilation Model Outdoor Cabinet
4.2.1 Replacing Heat Control Board
Replace the heat control board using the following procedures:
Step 1: Loosen the two fixing screws to remove the cover (shown in Figure 4-2), and then you can see the heat
control board. The appearance of the heat control board is shown in Figure 4-3.
Fixing screw of cover
Cover
Figure 4-2 Cover position
SW2
SW1
Alarm indicator
Figure 4-3 Appearance of the heat control board
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
22/34
16 Chapter 4 Maintenance
ECM1500 Outdoor Cabinet User Manual
Step 2: Disconnect J11, J12 and J2 terminals (shown in Figure 4-4) in sequence, and then disconnect the rest
connection terminals on the heat control board.
B
H1 H2
H4
H3
ON
J3
J11
J2
J12
J10
J7
J6
SW1
SW2
Figure 4-4 Heat control board terminals layout
Step 3: Loosen the fixing screws on the heat control board. Replace the heat control board with a new one.
Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the indicators show correctly
when fan fails. In normal condition, no alarm indicators will be on.
Step 5: Set the SW2 switch according to Table 4-2.
Table 4-2 Setting description of the SW2
Name Label on thecorresponding cover
Silk print on the
corresponding fan control
board
Setting description
Bit 1 Put the switch to the ON position (default), see Figure 4-3
Bit 2Switch SW2 (shown in Figure 4-3)
Put the switch to the OFF position (default), see Figure 4-3
Step 6: Press the SW1 self-test button (shown in Figure 4-3) to ensure that the fan can start normally.
Step 7: Replace the cover of the heat control board.
4.2.2 Replacing Fans
Fan alarm circu it
The fan-cooling unit of the outdoor cabinet is mainly composed of 2 ~ 4 axial flow fans. The fan alarm circuit is shownin Figure 4-5, where the blue line is the alarm line.
MOTORDRIVER IC VCE
(Red) Ic
VCC
VFG
R
FG SIGNAL
GROUND
(Blue)
(Black)
(Yellow)
Figure 4-5 Illustration of the fan alarm circuit
8/13/2019 Emerson ECM1500
23/34
Chapter 4 Maintenance 17
Fan alarm indicators
The position of the alarm indicators is shown in Figure 4-3.
The alarm indicators 1 ~ 4 on the heat control board correspond to fans 1 ~ 4 (alarm indicator 5 is the temperature
sensor alarm indicator).
Fan replacing procedures
If the fan is faulty, the corresponding indicator will be on. Follow the following procedures to replace the fan.
Step 1: Make sure that the fan-control terminals (J11 and J12 are hot pluggable) on the heat control board are
inserted firmly. The fan-control terminals are shown in Figure 4-4.
Step 2: Ensure that Bit 2 of SW2 switch is put to the OFF position.
Step 3: Press the SW1 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cables
are perfect.
Step 4: Loosen the fixing screws at the cabinet top cover to open the top cover. (Opening the top cover, pull it forward
and then lift up its front not more than 30. Otherwise the top cover will be fallen.)
Step 5: Disconnect the fan power terminals at the top of the cabinet. Use a multimeter to measure the voltage
between the positive power cable and the negative power cable. Check if the voltage is close to the DC output
voltage (54.0V).
If the fan power voltage is normal, the fans are damaged. Carry out the next step.
Step 6: Loosen the fixing screws of the fans and replace the fans, as shown in Figure 4-6.
Fan
Figure 4-6 Fan position
Step 7: Reconnect the fan power terminals, and press SW1 self-test button (shown in Figure 4-3) to ensure that the
fan can startup normally.
Step 8: Replace the cabinet top cover.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
24/34
18 Chapter 4 Maintenance
4.2.3 Replacing Door Status Sensor
There is a door status sensor installed in the cabinet for detecting the close or open status of the cabinet door. The
alarm will be eliminated only when the cabinet door is closed.
The door status sensor requires no particular maintenance; just replace it when it is damaged. If the door is closed,
while the door status sensor alarm occurs, the sensor must have been damaged. The position of the sensor is shownin Figure 4-7.
Remove the sensor top cover and then the two screws. Replace the old sensor with a new one and finally fix the
sensor and the signal cables with the screws.
Door status sensor
Figure 4-7 Position of the door status sensor
4.3 Replacing Parts Of Heat Exchanger Model Outdoor Cabinet
4.3.1 Replacing Environment Climate Control Unit
Appearance and terminal layout
The appearance of the environment climate control unit is shown in Figure 4-8, and the terminal layout is shown in
Figure 4-9.
Earth nut
DIP switch
Figure 4-8 Environment climate control unit
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
25/34
Chapter 4 Maintenance 19
J15
J13
J9
J11
J10
J12
J8J14J4J3J2J1
J7
J6
J5
SW101
SW100
CAN
LED_ALM
RS232
P
OWER
LED_RUN
LED_FAULT
AL
MOUT
FAN1 FAN2 FAN3 FAN4
AC_OFF
TEMP.
TEMP.&HUM.
WATER
INFRARED
SMOKE
DOOR
Figure 4-9 Terminal layout of the environment climate control unit
DIP switch description
DIP switch function description and setting method:
1. Bit 1 ~ 4 are used to set addresses of the environment climate control unit. OFF: 0, ON: 1. Default address: 16.
The setting method of the environment climate control unit (ECCU for short) is given in Table 4-3.
Table 4-3 Setting method of ECCU address
Bit 4 Bit 3 Bit 21 Bit 1 Address
0 0 0 0 16
0 0 0 1 10 0 1 0 2
1 1 1 1 15
Bit 1 ~ Bit 4 have been set in factory. You can change the settings according to your communication requirement.
2. The function description and setting method of Bit 5 ~ Bit 8 are given in Table 4-4.
Table 4-4 Function sescription and setting method of Bit 5 ~ 8
Bit No. Function Setting method Default value
5 Choose cabinet modelOFF: heat exchanger model
ON: forced ventilationOFF
6 Choose dry contact alarm modeOFF: normal when open; alarm when closed
ON: normal when closed; alarm when open ON
7* Choose sensorOFF: serial port termperature & humidity sensor
ON: temperature sensorON
8Choose whether stopping fans
when AC mains fails
OFF: No
ON: YesOFF
Note*: When Bit 7 is placed to ON position, ECCU has no humidity acquisition function
Replacing procedures of the ECCU
Step 1: Loosen the two fixing screws to remove the cover, and then you can see the ECCU. The position of cover is
shown in Figure 4-10.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
26/34
20 Chapter 4 Maintenance
Fixing screw of cover
Cover
Figure 4-10 Cover position
Step 2: Disconnect J15 terminal (shown in Figure 4-9), and then disconnect the rest connection terminals on the
ECCU.
Step 3: Loosen the fixing screws on the ECCU. Replace the ECCU with a new one.
Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the LED_FAULT (shown in
Figure 4-9) indicator show correctly. Under normal instance, the LED_FAULT indicator is power-off.
Step 5: Place the DIP switch to the correct position according to Table 4-3and Table 4-4.
Step 6: Press the SW1 self-test button (shown in Figure 4-9) to ensure that the fan can start normally.
Step 7: Replace the cover of the ECCU.
4.3.2 Replacing Fans
The heat exchanger of the outdoor cabinet is mainly composed of four centrifugal fans and a heat-exchanging core.
If the fan is faulty, follow the following procedures to replace the fan.
Step 1: Make sure that the fan-control terminals (J1, J2, J3 and J4 are hot pluggable) on the ECCU are inserted firmly.
The fan-control terminals are shown in Figure 4-9.
Step 2: Place the DIP switch to the correct position according to Table 4-3and Table 4-4.
Step 3: Press the SW1 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cablesare perfect.
Step 4: Disconnect the fan power terminals on the right side of the cabinet. Use a multimeter to measure the voltage
between the positive power terminal and the negative power terminal. Check if the voltage is close to the DC output
voltage (54.0V).
If the fan power voltage is normal, the fans are damaged. Carry out the next step.
Step 5: Loosen the fixing screws to remove cover of heat exchanger (shown in Figure 4-11), and then you can see
the fans. Loosen the fixing screws of the fans to replace the fans.
Step 6: Reconnect the fan power terminals, and press SW101 self-test button (shown in Figure 4-9) to ensure that the
fan can startup normally.
Step 7: Replace the heat exchanger cover.
Fixing screw of heatexchanger cover
Figure 4-11 Fixing screws of heat exchanger cover
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
27/34
8/13/2019 Emerson ECM1500
28/34
22 Chapter 4 Maintenance
4.4 Replaciing Parts Of Air-condition Model Outdoor Cabinet
4.4.1 Replacing air-conditioner
Step 1: Switch off the AC input MCB, as shown in Figure 4-14. Disconnect all the cable connectors.
AC input MCB
Figure 4-14 AC input MCB position
Step 2: Loosen the fixing screws of air-condition to remove and replace air-condition.
4.4.2 Replacing Emergent Ventilation Unit
The emergent ventilation unit is composed of heat control board and fans. The replacing procedures of heat control
board and fans are the same as that of the forced ventilation model outdoor cabinet. You can refer to 4.2.1
Replacing Heat Control Boardand 4.2.2 Replacing Fans.
4.4.3 Replacing Door Status Sensor
Refer to 4.2.3 Replacing Door Status Sensor.
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
29/34
Appendix 1 Technical And Engineering Parameters 23
Appendix 1 Technical And Engineering Parameters
Table 1 Technical parameters
Parametercategory
Parameter Description
Operating temperature-10C ~ +45C (forced ventilation model), -40C ~ +45C (heat exchanger
model), -40C ~ +50C (air-condition model)
Storage temperature -40C ~ +70C
Relative humidity 5%RH ~ 100%RH
Altitude 2,000m (derating is required above 2,000m)
Environmental
Others No conductive dust or erosive gases. No possibility of explosion
Conducted emission
Radiated emissionClass A EN55022
Immunity to EFT Level 3 EN61000-4-4
Immunity to ESD Level 3 EN61000-4-2
Immunity to Surges Level 4 EN61000-4-5
Immunity to radiation Level 3 EN61000-4-3
EMC
Immunity to conduction Level 3 EN61000-4-6
Safety regulation Compliant with IEC60950-1, IEC60950-22
Insulation resistance
At temperature of 15C ~ 35C and relative humidity not bigger than 90%RH,
apply a test voltage of 500Vdc. The insulation resistances between AC circuit
and earth, DC circuit and earth, and AC and DC circuits are all not less than
10M
Insulation strength
(Remove the SPD, monitoring module and rectifiers from the system before the
test.)
AC circuit to earth: 50Hz, 2,500Vac
DC circuit to earth: 50Hz, 1,000Vac
Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac
AC to DC circuits: 50Hz, 3,000VacFor all the three tests above, there should be no breakdown or flashover within
1min, with leakage current not bigger than 10mA
MTBF 100,000hr
Others
ROHS Compliant with R5 requirement
Cabinet 700 (W) 700 (D) 1800 (H)
Dimensions (mm) Internal space of
battery compartment613 (W) 570 (D) 350 (H)
Forced ventilation
model cabinet125 (excluding subrack and battery string)
Heat exchanger
model cabinet180 (excluding subrack and battery string)
Mechanical
Weight (kg)
Air-condition model
cabinet 175 (excluding subrack and battery string)
Table 2 Spart part list
Part Specification or model BOM
Fan DC axial flow fan 32010191
Fan DC centrifugal fan 32010261
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
30/34
Appendix 2 Wiring Diagram
Mains Input
QFA1
3
N
11
L
42
NLPE
5
6
2
3
4
PE Bar
1
7
PEBUS
3
2
X1
4
MS
PE
W02
N L
NOTE:
W02_A for Europen standard socket.
W02_B for American standard socket.
W02_C for Chinese and British standard socket.
1 3 5
2 4 6
W01
W01
U1
6
1
2
2
1
3
2
1
W20
68 7 5 4 3 2 1
W04
P344309U1
J6
J7
J10J2
J3
61 2 3 4 554321
W05
J12J11
Temperature sensor I
W1234578 6
1234578 6
1 2
W07
14-7
14-5 U2
7
7-J2
J3
J1J2
6-J3
7-J1
6-J10
1 3
2 4+ -
5
X2
1
14-3
14-1 3
5
7
9
11
13
15
17
1921
23
2
46
8
10
12
14
16
18
2022
24
7-J3-7
7-J3-8
7-J3-2
8-1
8-2
7-J3-1
X3
14
P345314X1
AC Input
DC Input
FAN2FAN1
RedYellowBlue Black
Blue Yellow Red Black Blue
Blue Yellow
Yellow Red
Red Black
Black
FAN1 FAN2
9 10
FAN3
RedYellowBlue Black
Blue Yellow Red Black
FAN3
11
solder solder solder
W03
W05 W05
W06
W06
W06
W06
W07
W08
W07
Figure 1 Wiring diagram of forced ventilation model outdoor cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
31/34
Mains Input
QFA1
3
N
11
L
42
NLPE
5
6
2
3
4
PE Bar1
7
3
2
X1
4
MS
PE
W02
N L
NOTE:
W02_A for Europen standard socket.
W02_B for American standard socket.
W02_C for Chinese and British standard socket.
1 3 5
2 4 6
W01
W01
U1
6
14-9
21
Door alarm
MJ
8W08
1 3
2 4+ -
5
X2
6-J8
W05
T1
13
Temperature sensor I
14-11
6-J5-1
6-J5-2
6-J5-48-1
8-2
6-J5-3
POWER
J5
J1 J2 J3 J4 J8
J15
AC Input
DC Input
FAN2FAN1
Blue Yellow Red Black
FAN1 FAN2
9 10
Heater1
H1
22
23
H2
Heater2
21
12
Black
Red
1 2
KT1
21
Black
solder
solderBlack
Red
Black
Black
BlueBlue
Blue
1 2 3 4 5 1 2 3 4 51 2 3 4 1 2 3 4
W05Temperature sensor I
2
1
5-4
5-2
6-J15-1
6-J15-2+- PWM ALARM
5-25-4
ECCU11U1
W03
W03
W03
W04
W04
W06
W07
W08
1
2345
78
6
W07
14-114-314-514-7
XT
19
Bottom cross
1
2
3
4
J11
1
2
J13
1 2 1 2 3
J14
W07
W07
W07
YellowBlue Red Black
solder
FAN1
FAN1* Blue Ye llow
- PW
5-4
YellowBlue
so
FAN3
FAN3*Blue Yellow Red Black
+- PWM ALARM
5-25-4
YellowBlue Red Black
solder
FAN2
FAN2*
Figure 2 Wiring diagram of heat exchanger model outdoor cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
32/34
Mains Input
QFA1
3
N
11
L
42
NLPE
5
6
2
3
4
PE Bar
1
7
3
2
X1
4
MS
PE
W02
N L
NOTE:
W02_A for Europen standard socket.
W02_B for American standard socket.
W02_C for Chinese and British s tandard socket.
1 3 5
2 4 6
W01
W01
AC Input
1
2
2
1
3
2
1
68 7 5 4 3 2 1
P344309U1
J6
J7
J10J2
J3
61 2 3 4 554321
W06
J12J11
16
W08
XT
15
XT
14-9
21
Door alarm
MJ
8W17
7-J2
7-J1
1 3
2 4+ -
5
X2
6-J6
W05
T1
13
Temperature sensor I
1
3
5
7
9
1113
15
17
19
21
23
2
4
6
8
10
1214
16
18
20
22
24
14-11
7-J3-7
7-J3-8
8-1
8-2
DC Input
Blu
Blu
AC
19
Air-condition
321
J2J1
PENL
J3
Temperature sensor II
Cable from Air-condition
54
18
W08
XT
17
XT
W03
W04
W07
W
Bottom cross front door line
Bottom cross back door line
9101112131415
12345678
14-5
14-7
6-J12-3
FAN2
6-J12-3
FAN1
19-
19-
19-
19-
20
W09
XT
19
XT
Bottom cross control board door line
X3
14
19-J2-919-J2-10
W06
W06
W17
W08
Figure 3 Wiring diagram of air-condition model outdoor cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
33/34
Appendix 3 Schematic Diagram 27
Appendix 3 Schematic Diagram
L
N
QFA1
L
N
ALARM
+-
A
V-
V+
FanC
CONTROL
Forced Ventilation Unit
FCU
A
V-
V+
FanC
ALARM
+- CONTROL
FCUX
Over Temperature
Dry Contact Terminal
Spare
Climate unit fault
Door Alarm
PE
to PE bar
0V
-48V
to Dry Contact TerminalDoor Alarm
X1
X2
X3
XS
AC Input
DC Input
Figure 4 Schematic diagram of forced ventilation model outdoor cabinet
L
N
L
N
ALARM
+
A
V-
V+
Internal fan
C
CONTROL
Heat Exchanger Unit
ECCU
A
V-
V+
External fan
C
ALARM
+- CONTROL
Over Temperature
Dry Contact Terminal
Spare
Climate unit fault
Door AlarmAC
PE
to PE bar
0V
-48V
to Dry Contact TerminalDoor AlarmX1
X3
AC Input
DC Input
Heater
-
QFA1 XS
KT1
X2
Figure 5 Schematic diagram of heat exchanger model outdoor cabinet
ECM1500 Outdoor Cabinet User Manual
8/13/2019 Emerson ECM1500
34/34
28 Appendix 3 Schematic Diagram
L
N
QFA1
Air-condition Unit
Over Temperature
Dry Contact Terminal
Spare
Climate unit fault
Door Alarm
PE
to PE bar
AlarmFan contral
0V
-48V
V+
V-Fan
Emergent Ventilation Unit
FCU FCUX
to Dry Contact TerminalDoor Alarm
X1
X2
X3
AC Input
DC Input
XS
LN
Figure 6 Schematic diagram of air-condition model outdoor cabinet