21
Primary Pump Unit reference Location CHW Temp WATER FLOW LENGTH in °C out °C l/s Pump-1 Secondary Floor Pump Room 6 5 42.00 1250 Pump-2 Secondary Floor Pump Room 6 5 42.00 1250 Pump-3 Secondary Floor Pump Room 6 5 42.00 1250 Pump-4 Secondary Floor Pump Room 6 5 42.00 1250 Pump-5 Secondary Floor Pump Room 6 5 42.00 1250 Secondary Pump Unit reference Location CHW Temp WATER FLOW LENGTH in °C out °C l/s Pump-1 Secondary Floor Pump Room 6 5 84.00 1600 Pump-2 Secondary Floor Pump Room 6 5 84.00 1600 Pump-3 Secondary Floor Pump Room 6 5 84.00 1600 Pump Reference Type Location Flow Static head Minimum efficiency l/s kPa % CHWP - 1 to 4 Duty pumps oof Plant Roo 53.03 175 80 Standby pumps

Final Schedule

  • View
    225

  • Download
    3

Embed Size (px)

DESCRIPTION

Final Schedule

Citation preview

Page 1: Final Schedule

Primary Pump

Unit reference LocationCHW Temp WATER FLOW

LENGTH in °C out °C l/s

Pump-1 Secondary Floor Pump Room 6 5 42.00 1250Pump-2 Secondary Floor Pump Room 6 5 42.00 1250Pump-3 Secondary Floor Pump Room 6 5 42.00 1250Pump-4 Secondary Floor Pump Room 6 5 42.00 1250Pump-5 Secondary Floor Pump Room 6 5 42.00 1250

Secondary Pump

Unit reference LocationCHW Temp WATER FLOW

LENGTH in °C out °C l/s

Pump-1 Secondary Floor Pump Room 6 5 84.00 1600Pump-2 Secondary Floor Pump Room 6 5 84.00 1600Pump-3 Secondary Floor Pump Room 6 5 84.00 1600

Pump Reference Type Location Flow Static head Minimum efficiencyl/s kPa %

CHWP - 1 to 4

Duty pumpsRoof Plant Room 53.03 175 80Standby pumps

Page 2: Final Schedule

Primary Pump

WIDTH HEIGHT

400 615400 615400 615400 615400 615

Secondary Pump

WIDTH HEIGHT

720 820720 820720 820

Maximum motor sMotor rating Speed control Electrical SupplyRPM kW Volts/Phase/Hz

1450 15.0 Constant speed 400 / 3 /50

Page 3: Final Schedule

Unit reference LocationCHW Temp WATER FLOW

LENGTH in °C out °C l/s

CHILLER ROOF FLOOR 12 6 41.83 11030

Chiller Reference Number of Duty Chillers Location Type Actual Capacity pDesign Ambient tempe

No. KW °C

CH 01 to 03 3 Roof Air Cooled 1337 46

Page 4: Final Schedule

WIDTH HEIGHT

2260 2530

Entering water te Leaving water Flow rate Pressure drop Motor RatinType of starElectrical Supply

Sound Press

°C °C I/s kPa kW Volts/Phase/Hz dB

12 6 41.8 35 285 Star - Delta 400 / 3 /50 82

Page 5: Final Schedule
Page 6: Final Schedule

Unit Ref SERVED LOCATION Range

RIGHT FCU-GF-A-049 GF.A.049_IT Rm YARDY-HP-3RRIGHT FCU-GF-B-065 GF.B.065_IT Rm 1 YARDY-HP-3RLEFT FCU-GF-B-101 GF.B.101_IT Rm 2 YARDY-HP-3R

LEFT FCU-GF-C-002GF.C.001_Security

YARDY-HP-3RGF.C.002_Entry

GF.C.003_Information

LEFT FCU-GF-C-017 GF.C.017_IT Rm 1 YARDY-HP-4RLEFT FCU-GF-C-067 GF.C.067_IT Rm 2 YARDY-HP-3R

RIGHT FCU-GF-D-019 GF.D.019_IT Rm/ICT Office YARDY-HP-3RRIGHT FCU-FF-B-062 FF.B.062_IT Rm 1 YARDY-HP-3RRIGHT FCU-FF-B-095 FF.B.095_IT Rm 2 YARDY-HP-3RLEFT FCU-FF-C-009 YARDY-HP-4RLEFT FCU-FF-C-070 FF_C-070_IT Rm2 YARDY-HP-3RLEFT FCU-FF-D-012

FF_D-012_IT Rm/ICT YARDY-HP-3R

LEFT FCU-FF-D-012-1 YARDY-HP-3RRIGHT FCU-FF-E-003 CONTROL ROOM YARDY-HP-3RLEFT FCU-SF-C-007 SF.C.007_IT Room 1 YARDY-HP-3RLEFT FCU-SF-C-072 SF.C.072_IT Rm 2 YARDY-HP-3RLEFT FCU-SF-D-014

SF.D.014_IT Rm/ICT OfficeYARDY-HP-3R

LEFT FCU-SF-D-014-1 YARDY-HP-3RLEFT FCU-SF-D-027

SF.D.027_GSM RoomYARDY-HP-3R

RIGHT FCU-SF-D-027-1 YARDY-HP-3RLEFT FCU-SF-MCC ROOM SF_MCC Room YARDY-HP-3R

RIGHT FCU-SF-CHILLER ROOMSF_Chiller Room

YARDY-EVRIGHT FCU-SF-CHILLER ROOM-1 YARDY-EVRIGHT FCU-SF-CHILLER ROOM-2 YARDY-EV

PIPE CONECTION

SIDE

 FF.C.009_IT Rm 1

Page 7: Final Schedule

ModelAIR FLOW CHW Temp WATER FLOW

LENGTH WIDTH HEIGHT

L/S in °C out °C L/S

300 854 6.3 11.8 0.31 720 1,295 335250 608 6.3 11.8 0.24 720 1,295 335250 608 6.3 11.8 0.24 720 1,295 335

100 380.55559 6.3 11.8 0.28 555 1295 250

300 836 6.3 11.8 0.37 720 1295 335100 381 6.3 11.8 0.15 555 1295 250300 854 6.3 11.8 0.31 720 1,295 335250 608 6.3 11.8 0.24 720 1,295 335250 608 6.3 11.8 0.24 720 1,295 335300 836 6.3 11.8 0.37 720 1295 335100 381 6.3 11.8 0.15 555 1295 250250 608 6.3 11.8 0.24 720 1,295 335250 608 6.3 11.8 0.24 720 1,295 335100 340 6.3 11.8 0.16 555 1295 250300 854 6.3 11.8 0.31 720 1,295 335100 381 6.3 11.8 0.15 555 1295 250250 608 6.3 11.8 0.24 720 1,295 335250 608 6.3 11.8 0.24 720 1,295 335200 477 6.3 11.8 0.18 670 1295 285200 477 6.3 11.8 0.18 670 1295 285250 608 6.3 11.8 0.40 720 1,295 33580 386 6.3 11.8 0.41 1500 570 22080 386 6.3 11.8 0.41 1500 570 22080 386 6.3 11.8 0.41 1500 570 220

Page 8: Final Schedule

Unit reference LocationAIR FLOW CHW Temp WATER FLOW

LENGTH L/S in °C out °C l/s

CCU INDOOR FIRST FLOOR 6300 6.3 11.8 0.91 1236

Unit Ref. Location Quantity

Fan Data

Supply Air Motor

l/s Pa TypeCCU-1 First Level Server Room1 2,014 75 Constant

External Static Pressure

Page 9: Final Schedule

WIDTH HEIGHT

870 1980

Fan Data

Motor Total Sensible EAT (db/wb) Total Sensible

kW kW kW l/s kPa kW kW10.0 17.2 17.2 20.5/14.2 13.5/11.3 0.68 14.0 20.3 20.3

Cooling CoilChilled Water Mode

Cooling CoilDX Mode

LAT-oC (db/wb)Chilled Water Flow

Coil Pressure

DropoC oC

Page 10: Final Schedule

Heating Coil Humidifier Filter

EAT (db/wb) Sensible EAT (db/wb) Capacity Power Type Grade

kW kg/hr kW20.5/14.2 12.1/10.8 7.5 12.1/10.8 15.1/12.1 9.0 6 Panel Merv 8

Cooling CoilDX Mode

LAT-oC (db/wb) LAT-oC (db/wb)

oC oC oC oC

Page 11: Final Schedule

PIPE CONECTION SIDE Unit reference Location Unit ModelSupply airflow Return airflow Fresh airflow Ehaust airflow CHW Temp WATER FLOW

LENGTH WIDTH HEIGHTl/s l/s l/s l/s in °C out °C l/s

R RIGHT AHU-EL-1 SECOND FLOOR ROOF ADV-A 5250-6046 4743 3926 817 6.3 11.8 5.94 3930 2110 1570L RIGHT AHU-AD-1 SECOND FLOOR ROOF ADV-A 6060-6046 5929 4360 3482 1913 6.3 11.8 6.79 4020 2290 1630L LEFT AHU-K-1 ROOF FLOOR ADV-A 3600-6046 3372 2616 756 6.3 11.8 4.58 3570 1640 1550R RIGHT MAHU-01 ROOF FLOOR ADV-A 3270-6046 3015 3015 6.3 11.8 4.54 2640 1640 1390L RIGHT AHU-S-1 ROOF FLOOR ADV-A 11400-6046 10937 9606 5050 3722 6.3 11.8 19.07 5545 3000 4160R LEFT AHU-S-2 ROOF FLOOR ADV-A 11400-6046 10982 9310 4778 3106 6.3 11.8 18.46 5545 3000 4160L LEFT AHU-S-3 ROOF FLOOR ADV-A 12600-6046 11398 9634 4770 3006 6.3 11.8 19.64 5545 3200 4280R RIGHT AHU-S-4 ROOF FLOOR ADV-A 11400-6046 10181 7830 6355 4004 6.3 11.8 19.24 5675 3000 4160L LEFT AHU-S-5 ROOF FLOOR ADV-A 8480-6046 7952 7111 2274 1433 6.3 11.8 12.20 5445 2850 3450L RIGHT AHU-S-6 ROOF FLOOR ADV-A 7500-6046 6803 6603 1514 1314 6.3 11.8 11.56 5295 2720 3160L RIGHT AHU-P-3 SECOND FLOOR ROOF ADV-A 11400-6046 9498 8207 3490 2199 6.3 11.8 16.84 5145 3000 3640L RIGHT AHU-P-2 SECOND FLOOR ROOF ADV-A 12600-6046 11398 10258 3610 2470 6.3 11.8 20.23 5545 3200 4280L RIGHT AHU-P-1 SECOND FLOOR ROOF ADV-A 9750-6046 10312 8902 3810 2400 6.3 11.8 18.69 5545 3000 4160L LEFT AHU-KG-1 FIRST FLOOR ROOF ADV-A 9750-6046 8957 7956 2705 1704 6.3 11.8 14.72 5145 3000 3640L RIGHT AHU-D-1 SECOND FLOOR ROOF ADV-A 7500-6046 6408 5767 2114 1473 6.3 11.8 9.72 5295 2720 3160L LEFT AHU-SH-1 SECOND FLOOR ROOF ADV-A 8480-6046 8387 7749 1725 1087 6.3 11.8 10.83 5445 2850 3450L LEFT AHU-S-7 ROOF FLOOR ADV-A 1720-6046 1566 1436 1566 1436 6.3 11.8 2.33 3720 1470 1880

ACESS DOOR SIDE

Page 12: Final Schedule

Unit reference LocationEhaust airflow

LENGTH WIDTH HEIGHTl/s

ECU-1 ROOF FLOOR 5427 4110 2050 1560

UNIT NO. QUANTITY FAN LOCATION FLOWRATE, (l/s)EXTERNAL STATIC PRESSURE, (Pa)MOTOR RATING, (kW)ECU-1 1 Roof Level 3,547 700 15

Page 13: Final Schedule

ELECTRICAL DATA, (V/PH/HZ)415/3/50

Page 14: Final Schedule

UNIT NO. QUANTITY FAN LOCATION Model CONFIGURATION LENGTH OUTER DIA INER DIA

TEF-S.1 1 ROOF FLOOR 1907 408 2.2 400/3/50 Duty 500 530 450EF-S.1 1 ROOF FLOOR 901 420 1.1 400/3/50 Duty 450 480 400KEF-S.1 1 ROOF FLOOR MUB/T 025 355E4 350 300 0.315 230/1/50 Duty 500 500 378TEF-S.2 1 ROOF FLOOR 4046 407 4 400/3/50 Duty 750 660 560EF-AD.1 1 SECOND FLOOR ROOF 1912 406 2.2 400/3/50 Duty 500 530 450TEF-S.3 1 ROOF FLOOR 1390 406 1.5 400/3/50 Duty 500 530 450TEF-P.1 1 SECOND FLOOR ROOF 441 289 0.75 400/3/50 Duty 375 435 355TEF-P.2 1 SECOND FLOOR ROOF 753 302 0.75 400/3/50 Duty 375 435 355TEF-P.3 1 SECOND FLOOR ROOF 801 301 0.75 400/3/50 Duty 375 435 355TEF-KG.1 1 FIRST FLOOR ROOF KVO 250 271 351 0.301 230/1/50 Duty 612 558 x 558TEF-KG.2 1 FIRST FLOOR ROOF KVO 315 367 451 0.549 230/1/50 Duty 700 615 x 615

UNIT NO. QUANTITY FAN LOCATION Model CONFIGURATION LENGTH OUTER DIA INER DIA

PF-01 & 02 2 Auditorium Roof Level 21954 600 30 415/3/50 1 Duty + 1 Standby 1170 1390 1250

SEF-01 & 02 2 Auditorium Roof Level 22083 600 30 415/3/50 1 Duty + 1 Standby 1000 1364 1120

FLOWRATE, (l/s)

EXTERNAL STATIC PRESSURE, (Pa)

MOTOR RATING, (kW)

ELECTRICAL DATA, (V/PH/HZ)

AXC 450-10/17°-2AXC 400-10/16°-3

AXC 560-6/16°-2AXC 450-10/17°-2AXC 450-10/12°-2AXC 355-10/10°-2AXC 355-10/16°-2AXC 355-10/17°-2

FLOWRATE, (l/s)

EXTERNAL STATIC PRESSURE, (Pa)

MOTOR RATING, (kW)

ELECTRICAL DATA, (V/PH/HZ)

AXC(A) 1250-9/26°-4

AXC 1250-5/27°-4(F)

Page 15: Final Schedule

Unit Ref Location

1 IDU-LV.1/ODU-LV.1 LV Room - 1A Roof Level2 IDU-LV.2/ODU-LV.2 LV Room - 1A Roof Level3 IDU-LV.3/ODU-LV.3 LV Room - 1A Roof Level4 IDU-TR.1/ODU-TR.1 Telecom Room Roof5 IDU-TR.2/ODU-TR.2 Telecom Room Roof6 IDU-LV.4/ODU-LV.4 LV Room7 IDU-LV.5/ODU-LV.5 LV Room8 IDU-GH.1/ODU-GH.1 Gate House 19 IDU-GH.2/ODU-GH.2 Gate House 210 IDU-PR.1/ODU-PR.1 Makeup Plant room11 IDU-PR.2/ODU-PR.2 Makeup Plant room12 IDU-PR.3/ODU-PR.3 Domestic Water Pump13 IDU-PR.4/ODU-PR.4 Domestic Water Pump

REU-GR.1/RCU-GR.1 Garbage Room LHSREU-GR.2/RCU-GR.2 Garbage Room RHS

PIPE CONECTION

SIDE

Page 16: Final Schedule

Unit Ref. LocationREU-GR.1/RCU-GR.1 Garbage Room LHSREU-GR.2/RCU-GR.2 Garbage Room RHS

Page 17: Final Schedule

ModelQuantity

Supply Air Actual Total CoolingLENGTH

INDOOR OUTDOOR l/s kWUBMY-118 MCAEY-118 1 733 10.55 1225UBMY-118 MCAEY-118 1 733 10.55 1225UBMY-118 MCAEY-118 1 733 10.55 1225UBMY-112 MCAEY-112 1 415 7.06 1225UBMY-112 MCAEY-112 1 415 7.06 1225UBMY-118 MCAEY-118 1 733 10.55 1225UBMY-118 MCAEY-118 1 733 10.55 1225UBMY-107 MCAEY-107 1 221 4.38 940UBMY-107 MCAEY-107 1 221 4.38 940UDHY-126 NCAEY-126 1 1216 15.25 1225UDHY-126 NCAEY-126 1 1216 15.25 1225UBMY-111 MCAEY-118 1 879 5.9 940UBMY-118 MCAEY-118 1 733 10.55 1225

13

Page 18: Final Schedule

Quantity Inside Temperature, Condenser/Compressor Electrical LoadCondensor Rating Evaporator Load1 10oC 2.5 kW 400V/3-Phase/50Hz 0.45 kW1 10oC 3.0 kW 400V/3-Phase/50Hz 0.45 kW

Page 19: Final Schedule

WIDTH HEIGHT

245 330245 330245 330245 330245 330245 330245 330180 270180 270245 330245 330180 270245 330

Page 20: Final Schedule

Defrost Heater Evaporator Rating1.5 kW 400V/3-Phase/50Hz1.5 kW 400V/3-Phase/50Hz

Page 21: Final Schedule

AHU-S.1 AHU-S.2 AHU-S.3 AHU-S.4 AHU-S.5 AHU-S.6 MAHU-1 ECU-1 AHU-K.1 AHU-S.7SA RA SA RA SA RA SA RA SA RA SA RA SA RA SA RA SA RA

R.F 23174 20354 23269 19727 24151 20413 21573 16591 16849 15068 14415 13991 6388 7145 3318 3043S.F 8120 8120 8908 8908 16917 16917 8632 8632F.F 4547 4547 9145 9145 4979 4979 14792 14792 6348 6348 4161 4161 3335 3335G.F 8374 8374 9588 9588 4708 4708 9332 9332 11984 11984

21041 21041 27641 27641 26604 26604 24124 24124 14980 14980 16145 16145 0 0 0 0 3335 3335

AHU-SH.1 AHU-D.1 AHU-AD.1 AHU-EL.1SA RA SA RA SA RA SA RA

S.F 17771 16419 13578 12219 12563 10050S.F 1640 1640F.F 1750 1750G.F 1401 1401G.F 5265

0 0 0 0 0 0 10056 4791

AHU-P.3 AHU-P.2 AHU-P.1SA RA SA RA SA RA

S.F 20125 17390 24151 21736 21850 18862F.F 11607 11607 14347 14347 11164 11164G.F 9654 9654 11692 11692 10645 10645

21261 21261 26039 26039 21809 21809

AHU-KG.1SA RA

F.F 18979 16858G.F 17174 17174

17174 17174