Gas Heat Pump Air Conditioner

Applicable Models

2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 U-25GEP2E5 U-30GE2E5

3WAY MULTIU-16GF2E5U-20GF2E5U-25GF2E5

Reference No. SM7110034-02

Periodic Inspections, Periodic Parts Replacement ManualApril 2012

Administrator
テキストボックス
Order No. SM7110034-11CE
Page 2: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

1. Periodic Inspections, Periodic Parts Replacement Work(1) Gas Heat Pump Air Conditioner .............................................................................. I-1(2) Periodic Inspections and Their Scheduling

Warranty Period ...................................................................................................... I-1Inspection Menu for Periodic Inspection Contract ................................................... I-1Miscellaneous ......................................................................................................... I-1

(3) Outdoor main board switch and LED arrangement diagram .................................... I-2(4) Basic Operations for Periodic Inspection Work

Backup operation during maintenance work (for W MULTI) .................................... I-3Engine Stop ............................................................................................................ I-4Canceling Engine Stop ........................................................................................... I-4Engine Oil Use Time Reset Method ........................................................................ I-5Operating the Fuel Gas Solenoid Valve Forced Off Switch .................................... I-5Coolant Circulation Operation ................................................................................. I-6Forced Rotational Speed Setting Operation ........................................................... I-7Test Run Procedure ................................................................................................ I-7

2. Periodic Inspection and Periodic Replacement Work Manual(1) Engine Oil Replenishment and Oil Filter Replacement ........................................... II-1(2) Engine oil Inspection, Replenishment, Replacement Work List .............................. II-6(3) Valve Clearance Adjustment................................................................................... II-7(4) Sparkplug Replacement ........................................................................................II-10(5) Air Cleaner Element Replacement ........................................................................II-12(6) Coolant Level Check, Replenishment ....................................................................II-14(7) Compressor Drive Belt Replacement ....................................................................II-15(8) Inspection and Replenishment of Drain Filter Filling Stones ..................................II-18(9) Generator Belt Replacement ................................................................................ II-20(10) Gas Leak Inspection ............................................................................................. II-23(11) Control program version check ............................................................................. II-23

3. Periodic Replacement Parts List ........................................................................ III-1

GHP Periodic Inspection, Periodic Replacement Checklist ............................. IV-1

CONTENTS

M2_Periodic_Wmulti.indb 1 2012/04/20 14:46:27

Page 3: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

I - 1

1. Periodic Inspections, Periodic Parts Replacement Work(1) Gas Heat Pump Air Conditioner

A gas-fueled engine drives the compressor that is the heart of the gas heat pump air conditioner (GHP) system. The use of a gas engine offers several advantages:● Because there is no defrost operation, stable heating is possible even when external temperatures are low.● As shown below, electric power consumption is relatively low (when heating with 60 Hz power source) and reduces

the load on power receiving equipment. * 45.0, 56.0, 71.0 kW types : 1.12 kW (approx.)* 85.0 kW type : 1.58 kW (approx.)However, just like a car engine, periodic inspections by a specialized serviceperson are required to ensure trouble free operation of the system. Make sure all periodic inspections are performed.

(2) Periodic Inspections and Their SchedulingWarranty PeriodThe equipment is covered by warranty for 1 year after completion of test run and delivery. However the engine itself and periodically replaceable parts are covered by warranty for one year or 2,000 hours of operation (whichever is shorter) after completion of test run and delivery.Inspection Menu for Periodic Inspection ContractSince periodic inspections are necessary to ensure long-term trouble free use of the gas heat pump air conditioner (GHP) after the warranty term ends, Panasonic has prepared the menu of inspections shown below. Please note that the service contract for periodic inspections only includes the inspections shown in the table below. Service calls for malfunctions will be charged separately.

Itemization and Schedule of Periodic Inspections and Periodic Parts ReplacementRemarksNumber of years passed or total hours of operation 5 years or

10,000 hours10 years or

20,000 hoursMaintenance item Periodic

InspectionPeriodic

Inspection1 E/G oil Replace

Leak check

2 E/G systeminspection

Valve clearance adjustmentStart-up checkAbnormal noise, vibration checkHarness check

3 Coolant Check (condition, amount), replenishLeak check

4 Drain lter Replenish, clean, oil absorption sheets change

5 Inspect fuel system Check for gas leaks

6 Inspect refrig-eration system Check for gas leaks

7 Control program version check Update as required8 Collect and record operation data

9 Periodic re-placement parts

Oil lter ReplaceAir cleaner element ReplaceSpark plugs ReplaceCompressor drive belt Replace

Oil absorbent mat ReplaceOil absorbent tube Replace

Note 1: “Periodic inspection” refers to 1 entire inspection of the items marked with in the table, including replacement of periodically replaceable parts. This inspection will be performed at either 10,000 hours of operation or at 5 years, whichever comes rst.

Note 2: The periodic inspection contract is renewable as long as the parts necessary to use the equipment are available. In this case, however, if parts that are not periodically replaceable parts must be replaced, the cost of those parts and the expense of replacement will be charged separately.

Note 3: When the hours of operation reach 30,000 hours, Panasonic will arrange for “refresh maintenance.” This may be repeated for up to 13 years (if 13 years are exceeded, the equipment is replaced). Furthermore, a periodic inspec-tion is required either 10,000 hours of operation or 5 years after “refresh maintenance,” whichever comes rst. For details, contact the person responsible for inspecting the equipment.

MiscellaneousIndoor and outdoor heat exchanger cleaning is generally required once every 3 - 4 years. However, this varies ac-cording to the level of contamination, type of industry, and installation conditions. If foreign matter or dust adheres to indoor or outdoor heat exchanger ns, it will degrade performance and cause malfunctions. Cleaning must be performed to ensure proper use of the air conditioner. Cleaning costs are estimated separately.

M2_Periodic_Wmulti.indb 1 2012/04/20 14:46:27

Page 4: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

I - 2

(3) Outdoor main board switch and LED arrangement diagram

No. Name No. Name1 Terminating resistance ON/OFF switch (S010) 17 CN0752 STOP SW (S001) 18 EEPROM3 Indoor/outdoor communication monitor (D043) 19 CN037 (white)4 Fuel gas solenoid valve force close switch (S002) 20 CN049 (red) Compressor outlet/inlet pressure sensors

PS1: Inlet, PS2: outlet5 SET key (S007)6 DOWN key (S006) 21 CN029 (blue)7 UP key (S005) 22 CN014 (blue)8 LEVEL LED (D053) 23 CN016 (black)9 TEST/WARNING LED (D052) 24 CN062 (green) Hot water outlet temperature10 HOME key (S004) 25 CN060 (blue) Clutch coil temperature11 CN015 (white) 26 CN058 (white) Coolant temperature12 CN063 (yellow) 27 CN059 (black) Outdoor air temperature13 CN012 (red) 28 CN055 (blue) Heat exchanger inlet temperature14 CN011 (black) 29 CN064 (yellow) Clutch 2 coil temperature15 CN010 (white) 30 CN053 (black) Compressor inlet temperature16 CN006 (black) 31 CN054 (red) Compressor outlet temperature

31

20

81710

9

7

6

5

24

25

26

27

28

29

30

19

4

18

3

2

1

13141516

23

22

21

12

11

M2_Periodic_Wmulti.indb 2 2012/04/20 14:46:27

Page 5: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

I - 3

(4) Basic Operations for Periodic Inspection Work

All work other than when the STOP (all stop) switch (S001) is set to STOP and the VG (fuel solenoid valve forced off switch) switch (S002) is set to OFF should be performed with the HOME (S004), SET (S007), UP (S005), and DOWN (S006) keys. It is extremely dangerous if the customer performs an operation that runs the engine during a maintenance inspection or when not expected. Make sure you stop operation during work in the way described below. * Pressing the HOME (S004) key for 1 second or more forcefully returns the state to the initial state. The

value of a partially set item will be discarded, and the item number will return to “ .”* If there is no operation for 10 minutes when other than the “ ” item number is displayed, the value of

a partially set item will be discarded, and the item number will return to “ .”

Backup operation during maintenance work (for W MULTI)• What is backup operation?

In the GHP W MULTI series, multiple outdoor units are connected to the same refrigerant tube. Therefore, even during maintenance work of an outdoor unit, the other outdoor unit not required in maintenance work can be used to keep the indoor operating conditions. This is called a backup operation.

• Backup operation procedureTo perform backup operation, the outdoor unit for maintenance work (hereafter referred to as "target outdoor unit") must be cut off from the system using the following procedure. Review content of the maintenance work and then select the most suitable method.Also, after the maintenance work is nished, always refer to [System recovery procedure] and then return the system to its normal state.

[Backup operation procedure]To turn off power of target outdoor unit and then perform maintenance work (basic operation during inspection of outdoor unit)

« Important »This is the basic operation performed during inspection work. If this operation is not performed and the power of the outdoor unit is turned off, this will cause system fault and prevent backup operation to be car-ried out, and serious malfunction will occur. If this happens, see [System recovery procedure] to recover the system, and then once again use the following procedure to perform setup. Automatic backup operation will kick in.

* 1) Sometimes all outdoor units may stop. If there is operation input, outdoor units other than the target one will start operation again after approximately ve minutes. (For details on the settings, see the next

item.)

* 2) Always carry out the following three tasks.

Check to make sure « Step 2 » is nished. If the shut-off valve is opened, refrigerant will ow from the other outdoor unit to the target outdoor unit, causing serious malfunction.

After 3 minutes has elapsed from completion of « Step 1 », check to make sure the outdoor main board displays " " and then perform this operation. If you turn off the power immediately after performing "STOP" setting, the entire system will stop. (Backup operation cannot be performed.) If this happens, see [System recovery procedure], recover the system, and then start over again starting from « Step 1 ».

There will not be any problem whether the circuit break-er of the outdoor unit in « Step 3 » is ON or OFF. Select one of them according to the work required.

On the outdoor main board of the target outdoor unit, set the STOP switch (S001) to "STOP". *1

(After con rming that the engine of the target outdoor unit is stopped) close the valves of re-frigerant gas tube, refrigerant gas liquid tube, and balance tube.

On the outdoor main board of the target outdoor unit, set the STOP switch (S001) to "STOP". Wait for three minutes or more and then turn off the circuit breaker of the target outdoor unit. *2

Start maintenance work.

« Step 1 »

« Step 2 »

« Step 3 »

M2_Periodic_Wmulti.indb 3 2012/04/20 14:46:27

Page 6: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

I - 4

[Work example] Perform maintenance on W MULTI outdoor unit 2 in refrigerant system 1.

a) For the W MULTI outdoor unit 2 indicated in the left diagram, perform « Step 1 » to « Step 3 » in [Backup operation procedure] in that order. Then, perform maintenance work on W MULTI outdoor unit 2.

b) When « Step 3 » is nished, W MULTI outdoor unit 1 is reset. (It'll stop even if it is operating.)

c) After approximately ve minutes, if there is operation input (indoor remote controller is "Run" or test run setting on outdoor main board), W MULTI outdoor unit 1 starts up. (Backup operation starts.)

d) If test run is set from outdoor main board, W MULTI outdoor unit 1 continues to run. However, if normal operation is started by the indoor remote controller, depending on the load, all outdoor units may stop due to thermostat off.

[System recovery procedure]If backup operation has been performed, by all means check the following items after the maintenance work, and then perform settings again to return the system to its normal state.1) Check to make sure all shutoff valves of refrigerant gas tube, refrigerant liquid tube, and balance tube of the outdoor

unit are opened.2) Check to make sure the STOP switch (S001) on the outdoor main board is set to "NORM".3) If the power of the outdoor unit has been turned off, turn on the circuit breaker.4) If "Test run" (No.4 - / ) is set, cancel it.* When adjusting to No.4 - / , if TEST/WARNING LED (D052) lights, this means

"Test run" is being set. In this state, press the SET (S007) key for one second or more. The setting will be canceled (TEST/WARNING LED (D052) goes off.)

Engine StopForcibly turns off the thermostat of all operating indoor units, and stops outdoor units.(STOP SW (S001) is normally set to “NORMAL.”)

1) Move STOP SW (S001) from “NORMAL” to “STOP” (Figure 1). “ ” will appear on the 7- seg-ment LED display (Figure 2).On a W MULTI, the 7-segment LED display shown in Figure 3 (“ “) replaces that shown in Fig-ure 2 (“ “) when 3 minutes have elapsed.

2) The all stop operation starts.Note: During all stop, the outdoor unit will not start

even when directed to do so by the indoor unit.3) Turn off the power supply circuit breaker for the out-

door unit.

Canceling Engine Stop1) Move the STOP SW (S001) from “STOP” to “NOR-

MAL.”2) Turn on the power supply circuit breaker for the out-

door unit. The all stop will be canceled, and the engine will start.

Figure 3

Figure 2

Figure 1

Refrigerant system 1R

efrig

eran

t tub

e(m

ain

tube

) Refrigerant tube(outdoor branch tube)

Balance tube

W MULTIoutdoor unit 1

W MULTIoutdoor unit 2In

door

/out

door

con

trol w

ire

«Step 1»«Step 2»«Step 3»

M2_Periodic_Wmulti.indb 4 2012/04/20 14:46:28

Page 7: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

I - 5

Engine Oil Use Time Reset MethodMake sure to perform this procedure after checking (re-plenishing, changing) the engine oil.

1) Press the HOME (S004) key for one second or more. The menu display will show item number “ ”

2) Next, press the UP (S005) and DOWN (S006) key, displaying the menu item numbers. Go to menu item “ ”

3) After menu item number “ ” appears, the oil use time will be displayed. Press the SET (S007) key.

4) When the SET (S007) key is pressed with the oil use time displayed (Figure 3), the next display appears. By pressing the UP (S005) key or DOWN (S006) key in this mode, the oil use time display clear setting or the forced oil replenishment setting can be selected. Select the setting to clear oil use time display (“ ” on the 7-segment LED display).

Display Function

↑DOWN

↓UP

Oil use time display clear setting

Forcible oil replenishment setting

5) Clearing the Oil Use Time DisplayWhen the SET (S007) key is pressed for 1 second or more while the oil use time display is selected, “ ” will appear on the 7-segment LED display (Figure 4).

6) Release the SET (S007) key once “ ” is dis-played, then quickly hold it down again. “ ” will be displayed (Figure 5), and the oil use time will be reset to 0 hours. Next the oil use time will be dis-played and can be checked.Note: If the oil use time does not return to 0 hours,

perform the procedure again.

Operating the Fuel Gas Solenoid Valve Forced Off Switch

This VG switch (S002) is used to forcibly close the gas solenoid valve (Figure 6).

«This switch should normally be set to “NORMAL”. »

Figure 6

Figure 5

Figure 4

Figure 3

Oil use time (10,100 hours)

“o” is displayed, indicating oil use time

M2_Periodic_Wmulti.indb 5 2012/04/20 14:46:28

Page 8: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

I - 6

Coolant Circulation OperationThis operation forcibly drives the coolant pump and the coolant electric three-way valve. It is used for re lling cool-ant and for removing air from the coolant circuit.Note: Check that the coolant circuit contains some coolant before performing this operation. The pump may be dam-

aged if forced operation is started without any coolant. 1) Press the HOME (S004) key for 1 second or more. The menu item number “ ” will be displayed.2) Next press the UP (S005), DOWN (S006) keys to display menu item number “ ”3) After “ ” the test run/forced setting display

“ ” will appear (Figure 7). Press the SET (S007) key while “ ” is displayed.

4) Press the SET (S007) key in the forced cooling test run setting mode to select one of the displays shown in the table below. Press the UP (S005) or DOWN (S006) key to select “ “ (forced coolant circulation setting). (Figure 8)

Display Function Remarks

↑DOWN

↓UP

Forced cooling test run setting <No power generation mode>Forced heating test run setting <No power generation mode>Forced valve opening settingForced coolant circulation settingForced bypass valve closingCoolant air bleed modeForced engine distributor modeForced engine feedbackForced engine adjustment valve closingForced compressor oil replenish W MULTI onlyForced compressor oil supply W MULTI onlyForced defrosting operation setting• W MULTI and 3WAY cannot be set.• May not be displayed depending on the micro-computer

version.Forced defrosting operations (indoor defrosting for gas-engine coolers.)• May not be displayed depending on the micro-computer

version.Ignore pressure sensorForce fuel gas solenoid valve offForced cranking mode• May not be displayed depending on the micro-computer

version.

Figure 8

Figure 7

M2_Periodic_Wmulti.indb 6 2012/04/20 14:46:29

Page 9: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

I - 7

5) Setting and Canceling Forced Coolant Circulation OperationPress the SET (S007) key for 1 second or more while forced coolant circulation setting is selected. The coolant pump will operate and the coolant electric three-way valve will cycle repeatedly through closing completely for 3 minutes, then opening completely for 1 minute and 15 seconds. During this time, the forced setting in progress display will appear (the TEST/WARNING LED (D052) will light). To cancel the forced coolant circulation set-ting, press the SET (S007) key for 1 second or more. The forced setting in progress display will be cleared (the TEST/WARNING LED (D052) will go out) and the display will return to the forced setting selection operation.

Forced Rotational Speed Setting OperationThis setting is used to forcibly x the revolution of en-gine when doing test runs.1) Press the HOME (S004) key for one second or more.

The menu item number “ ” will be dis-played.

2) Next press the UP (S005) and DOWN (S006) keys to display menu item number “ ”

3) Press the SET (S007) key while “ ” is dis-played. The forced engine revolution setting display “ ” will appear (Figure 9).

4) When the SET (S007) key is pressed in this mode, the following displays will cycle in sequence at 1-second intervals.

Display Function

Forced engine revolutions (example: 1400 min-1)

Engine revolutions (example: 1400 min-1)

Compressor inlet pressure (example: 0.56 Mpa)

Compressor outlet pressure (example: 0.56 Mpa)

Compressor outlet temperature (example: 85.0ºC)

5) Setting and Canceling Forced Rotational SpeedSelect forced engine revolutions using the UP (S005) and DOWN (S006) keys.The speed can be set within the range from the minimum speed to the maximum speed of the engine, in units of 100 revolutions. With the speed selected, press the SET (S007) key for 1 second or more. The selected speed will be xed as the forced engine revolutions. During this time, the forced setting in progress display will appear (the TEST/WARNING LED (D052) will light).To cancel the forced engine revolution setting, press the SET (S007) key for 1 second or more. The forced setting in progress display will be cleared (the TEST/WARNING LED (D052) will go out) and the display will return to the forced setting selection operation.

Test Run ProcedureThis setting is used to perform a test run from the outdoor unit.1) Set all remote controller switches to “Stop”.2) Select “ “ (forced cooling test run) or “ “ (forced heating test run). For details see steps 1) to 4)

on page I-7.3) Setting and Canceling a Forced Test Run

When “ “ (forced cooling test run) or “ “ (forced heating test run) is selected, holding down the SET (S007) key 1 second or longer causes the forced setting to appear (TEST/WARNING LED (D052) before a test run starts. To cancel forced test run operation, hold down the SET (S007) key for 1 second or longer. This clears the forced setting (TEST/WARNING LED (D052) goes off) and the forced setting selection reappears.

Figure 9

M2_Periodic_Wmulti.indb 7 2012/04/20 14:46:29

Page 10: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 1

2. Periodic Inspection and Periodic Replacement Work ManualPeriodic inspections and replacements are very important for ensuring that users can enjoy long and trouble-free service from Panasonic gas heat pump air conditioners.

(1) Engine Oil Replenishment and Oil Filter Replacement

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit side. Before carrying out work on the inside of the outdoor unit, make sure you turn off the power supply circuit breaker of the outdoor unit.(However, if a system controller or other centralized control device is being used, an abnormal communications error may be generated.) Alternatively, perform the STOP operation for the outdoor unit.

Model No.

K25 (Nissan engine)

Chapter [2 (2)].

Use Panasonic genuine oil for the engine oil.

Name Q’ty

Engine oil---------------

45.0~ 43liters

50liters

45.0~

1

needed

needed1 each

Closed wrench 19mm 11

Filter wrench 1

spout 5 liters 1

1Pliers 1

Figure 1 Genuine gas engine oil

Page 11: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 2

For models with a K25 engine(45.0, 56.0, 71.0KW Types) (85.0KW Type)

Page 12: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 3

c) Use a rag to wipe up spilled oil.

For models with a K25 engine(45.0, 56.0, 71.0KW Types)

Caution

damaged, resulting in oil leaks.

Figure 3 Applying Panasonic genuine oil

(85.0KW Type)

Page 13: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 4

Models 45.0 to 71.0KW type

4) Use an oil pump to remove the oil.

old oil that adheres to the front end of the hose used to re-

hose used for removing the oil to its original location.

6) Use an oil can to measure the oil and gently pour 40 liters of

Figure 5

Figure 6

Fill hole A

Divider

Fill hole B

Page 14: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 5

Model 85.0KW Type

4) Use an oil pump to remove the oil.

5) Use an oil can to measure the oil and gently pour 42 liters of

(Figure 6)

Canceling

drain hose.

Figure 7

Figure 5

Figure 6

Oil tank

Fill hole A Fill hole B

Oil tank Divider

Fill hole C

Page 15: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 6

(2) Engine oil Inspection, Replenishment, Replacement Work List

Maintenance item

1 2 3 4 5 6 7 8 9 10 11 12 13

2 4 6 8 10 12 14 16 18 20 22 24

Periodic inspection

3 liters 40 liters 43 liters

3 liters 42 liters 5 liters 50 liters

Page 16: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 7

(3) Valve Clearance Adjustment

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit side. Before carrying out work on the inside of the outdoor unit, make sure you turn off the power supply circuit breaker of the outdoor unit.(However, if a system controller or other centralized control device is being used, an abnormal communications error may be generated.) Alternatively, perform the STOP operation for the outdoor unit.

or other reason.3) Perform the valve clearance adjustment when the engine is warm.

Caution

Name Q’ty0.45mm 1 each1/2 inch drive (12.7 mm) 1 each

1 each

1 each

1 each

pressing on it (Figure 2).

Figure 2Figure 1

Cap nuts

Page 17: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 8

(Figure 3).

-ley is aligned with the timing pointer (Figure 5).

-

cylinder is at compression top dead center. Perform the

below (Figure 7).

and discharge side pushrods for the fourth cylinder with

compression top dead center. Perform the valve clearance

Cylinder Number 4 3 2 1Valve Discharge Discharge Discharge Discharge

Figure 3

Figure 6 Check the compressor top dead point

Intake sideDischarge side

First cylinder

Figure 4 Timing mark

Figure 5

Timing pointer

Top mark (orange)

Timing indicator details

Top mark (orange)

(white)(white)

(white)

(white)

Page 18: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 9

-

with the timing pointer. If the valves were -

adjust the clearance of the remaining valves

-

Discharge valvesK21 0.38 mmK25 0.45 mm

clearances must be readjusted.

Figure 7 Location of each valve

discharge inlet inlet discharge discharge inlet inlet discharge

Page 19: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 10

(4) Sparkplug Replacement

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit side. Before carrying out work on the inside of the outdoor unit, make sure you turn off the power supply circuit breaker of the outdoor unit.(However, if a system controller or other centralized control device is being used, an abnormal communications error may be generated.) Alternatively, perform the STOP operation for the outdoor unit.

-pare them before starting.

Name Q’ty11

1 each14

Figure 1

Page 20: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 11

Figure 5 Removing the wire harness plugs

Installation to ).

Figure 6 Removing the sparkplug coils

Page 21: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 12

(5) Air Cleaner Element Replacement

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit side. Before carrying out work on the inside of the outdoor unit, make sure you turn off the power supply circuit breaker of the outdoor unit.(However, if a system controller or other centralized control device is being used, an abnormal communications error may be generated.) Alternatively, perform the STOP operation for the outdoor unit.

«Mounted on K21 and K25 engines»

-ments.

Preparations

Name Q’ty

Parts 1 Figure 1

Nut driver

Figure 1

Page 22: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 13

-move the dust cap. (Figure 2)

2) Clean the inside of the dust cap. (Figure 3)

Caution

Caution

Figure 3 Dust CapFigure 2

Page 23: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 14

(6) Coolant Level Check, Replenishment

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit side. Before carrying out work on the inside of the outdoor unit, make sure you turn off the power supply circuit breaker of the outdoor unit.(However, if a system controller or other centralized control device is being used, an abnormal communications error may be generated.) Alternatively, perform the STOP operation for the outdoor unit.

Use Panasonic Genuine Coolant solution (Figure 1).

Caution

mouth during work.

Preparations

Name Q’ty

Materials

Panasonic genuine coolant

------------------- -------------------------------------------------- ---------------------------

Dispensing container 2 liters 1 For coolant (free from oil)Gauges For ethylene glycol

Figure 1

Figure 2

H level

L level

Figure 3

Cap

hole cover

Page 24: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 15

(7) Compressor Drive Belt Replacement

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit side. Before carrying out work on the inside of the outdoor unit, make sure you turn off the power supply circuit breaker of the outdoor unit.(However, if a system controller or other centralized control device is being used, an abnormal communications error may be generated.) Alternatively, perform the STOP operation for the outdoor unit.

Preparations

Name Q’ty

Parts Compressor drive belt 1

Gauges

19mm 1

1

1

1

1

Preparation

Page 25: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 16

CAUTION

not forget to remove that plate.

Figure 2

Bolts

Bolts

Page 26: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 17

Compression drive belt tension adjustment has been raised.

-

tension has been obtained.

CAUTION

Adjust belt tension by applying pressure to it without grasping it.

Be sure to check that there is no slippage at these important places

290 mm tension measurement location

Density

Number of ribs 10

--

-dure until desired tension is achieved.

).

Page 27: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 18

(8) Inspection and Replenishment of Drain Filter Filling Stones

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit. When working on internal parts of the outdoor unit, make sure to cut the power to the outdoor unit at the circuit breaker before starting work. (However, if a centralized control device such as system controller is used, an abnormal communications error may occur.) Or, perform a STOP opera-tion on the outdoor unit.

Inspection and replenishing

Name Quantity

Materials · tools

CV638-011-9356 (inside plastic bag)

Nut driver 1141

* Note that water may drain from the unit.

the outdoor unit. (Figure 1) (Figure 2)

Figure 1

Bolts A

Hose A

Bolts B

Hose B

Figure 2

Cover anchor

Bolts C

Bolts C

Page 28: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 19

height of the rib).

4) Place the tray in the case.

could become lodged in the grooves of the case.

Figure 3

Cover

Tray

Case

Packing

Oil

mats

Figure 4

Add neutralizer

Page 29: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 20

(9) Generator Belt Replacement

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit. When working on internal parts of the outdoor unit, make sure to cut the power to the outdoor unit at the circuit breaker before starting work. (However, if a centralized control device such as system controller is used, an abnormal communications error may occur.) Or, perform a STOP opera-tion on the outdoor unit.

For models with the K21 and K25 engine generator

before you start.Name Quantity

Parts Vee belt 1

measuring instruments

1111

Figure 1

(2)

(1)

(4)

(3)

Figure 2

(1)

(5)

Page 30: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 21

Installing the new belt

Figure 3

(7)

(6)

Figure 4

(8)

Figure 5

(8)

Page 31: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 22

295 mm tension measurement position

Density

Number of ribs 5

-

-justment bolt (6). (Figure 7)

Caution

Figure 6

(6)

(1)

(8)

(5)

Figure 7

(8)

(7)(6)

Page 32: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

II - 23

Panel installationInstall the front and rear panels on the outdoor unit and turn on the outdoor unit.

(10) Gas Leak Inspection

Safety PrecautionsStopping only the indoor unit is extremely dangerous because the engine may suddenly start if the customer operates the remote controller on the indoor unit side. Before carrying out work on the inside of the outdoor unit, make sure you turn off the power supply circuit breaker of the outdoor unit.(However, if a system controller or other centralized control device is being used, an abnormal communications error may be generated.) Alternatively, perform the STOP operation for the outdoor unit.

-tions or inside the unit. (Figure 2)

(11) Control program version check

Figure 1 Figure 2

Openings through which gas will escape in the event of a gas leak

Fuel line connection

Page 33: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

III - 1

3. Periodic Replacement Parts List U-16GE2E5 · U-20GE2E5 · U-25GE2E5 · U-16GF2E5 · U-20GF2E5 · U-25GF2E5

Replacement rank (Replacement time) Part code Part name Quantity

C-5(10,000 hours or5 years)

CZ-PSLF3 Oil filter 1

CZ-PSAF1 Air cleaner element 1

CZ-PSPG1 Spark plugs 4

CZ-PSVB5 Compressor operation belt 1

CZ-PSLS5 Oil absorbent mat 14

CZ-PSDF1 Drain filter packing 1

C-10(20,000 hours or10 years)

CZ-PSLF3 Oil filter 1

CZ-PSAF1 Air cleaner element 1

CZ-PSPG1 Spark plugs 4

CZ-PSVB5 Compressor operation belt 1

CZ-PSLS5 Oil absorbent mat 14

CZ-PSDF1 Drain filter packing 1

U-16GEP2E5 · U-20GEP2E5 · U-25GEP2E5Replacement rank

(Replacement time) Part code Part name Quantity

C-5(10,000 hours or5 years)

CZ-PSLF3 Oil filter 1

CZ-PSAF1 Air cleaner element 1

CZ-PSPG1 Spark plugs 4

CZ-PSVB5 Compressor operation belt 1

CZ-PSLS5 Oil absorbent mat 14

CZ-PSDF1 Drain filter packing 1

CZ-PSGB1 Generator operation belt 1

C-10(20,000 hours or10 years)

CZ-PSLF3 Oil filter 1

CZ-PSAF1 Air cleaner element 1

CZ-PSPG1 Spark plugs 4

CZ-PSVB5 Compressor operation belt 1

CZ-PSLS5 Oil absorbent mat 14

CZ-PSDF1 Drain filter packing 1

CZ-PSGB1 Generator operation belt 1

Page 34: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

III - 2

U-30GE2E5Replacement rank

(Replacement time) Part code Part name Quantity

C-5(10,000 hours or5 years)

CZ-PSLF5 Oil filter 1

CZ-PSAF1 Air cleaner element 1

CZ-PSPG1 Spark plugs 4

CZ-PSVB3 Compressor operation belt 1

CZ-PSLS5 Oil absorbent mat 14

CZ-PSDF1 Drain filter packing 1

C-10(20,000 hours or10 years)

CZ-PSLF5 Oil filter 1

CZ-PSAF1 Air cleaner element 1

CZ-PSPG1 Spark plugs 4

CZ-PSVB3 Compressor operation belt 1

CZ-PSLS5 Oil absorbent mat 14

CZ-PSDF1 Drain filter packing 1

Page 35: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

IV - 1

GHP Periodic Inspection, Periodic Replacement ChecklistDelivery

Destination · ( ) - Inspection, Replacement

Company name · ( ) -

DeliveryAddress Address

Part

No.

Outdoor U- (No. )

Indoor

S- S- S- S- · S-S- S- S- S- · S-S- S- S- S- · S-S- S- S- S- · S-S- S- S- S-

Gas company name Inspection date ( / / )

Gas type used

Check items Work Conclusion

1. Operating hours Hours2. No. of times ON/OFF Times3. Check, replace

Coolant level check, replenishment Drain lter lling stone check, replenishment Sparkplug replacement Engine oil change Oil lter replacement Air cleaner element replacement Compressor drive belt replacement Valve clearance adjustment Oil absorbent mat Oil absorbent tube

Intake valve Exhaust valveBefore adjustment After adjustment Before adjustment After adjustment

1st cylinder2nd cylinder3rd cylinder4th cylinder

4. Replacement parts Q’ty Remarks

(Code) :Ok C:Cleaned :Dismantled A:Adjusted L:Replenish X:Changed T:Tightened -:Not applicable

M2_Periodic_Wmulti.indb 1 2012/04/20 14:46:40

Page 36: Gas Heat Pump Air Conditioner - Kälte Bast · PDF fileGas Heat Pump Air Conditioner Applicable Models 2WAY MULTI/W MULTI U-16GE2E5 U-16GEP2E5 U-20GE2E5 U-20GEP2E5 U-25GE2E5 ... Valve

IV - 2

Check items Measurement Conclusion5. Engine system checks

6. Control program version Version update available? Yes Version No

7. Operation data collection Data collection time (Time after starting operation)

Note: Operate all indoor units and measure. Min.

Abnormal vibration, noise checks OK/ not Ok

Out

door

uni

t ope

ratio

nal d

ata

Data Code Measurement item (sensor name) Unit Measurement Conclusion

11 Engine revolution speed min-1

12 Compressor inlet pressure MPa13 Compressor outlet pressure MPa14 Compressor inlet temperature °C15 Compressor outlet temperature °C19 External air temperature °C31 Outdoor fan output %34 Outdoor unit electrical valve 1 output Step- Compressor intake superheat/2 outputs Deg /

Indo

or u

nit o

pera

ting

data

Operation mode (cool, heat)

TypeElectric valve

degree ofopening

Intaketemperature

Discharge temperature Coil input temp. Coil output

temp.

123456789101112131415161718192021222324

Special comments

M2_Periodic_Wmulti.indb 2 2012/04/20 14:46:40