2
Compact System for Level Monitoring NRGT 261 NRGT 261S For Marine Applications Issue Date: 4/06 Product Range B GESTRA Steam Systems NRGT 261 NRGT 261S Description The compact system NRGT 261 works according to the capacitance measurement principle. The NRGT 261 is designed for signalling different levels in conductive and nonconductive liquids: Water level maintained within the control band defined by two preset limits. The NRGT 261 has a level transmitter integrated in the terminal box which produces a standard output signal of 420 mA. External switchgear is not required. Function The principle of capacitance measurement is applied to determine the level. The electrode rod and the vessel wall form a capacitor. If the level of the dielectric located between the two capacitor plates changes, the current which flows through the plates changes proportionally to the level. A dielectric is defined as an insulating substance, which excludes many liquids such as water. In order to receive a useful measuring result the measuring rod, which is completely submerged in the liquid, must be completely insulated. After calibration of the zero point/measuring range (0 % 100 %) of the control unit, the level can be read off from a remote display unit. The level measuring range can be changed during operation. Design NRGT 261: Electrode with screwed connection ¾" BSP, DIN ISO 2281. NRGT 26 1S: Flanged design for marine applications DN 50, PN 40, DIN 2635. Technical Data Type approval no. NRGT 261: TÜV · WRS · 02391 NRGT 261S: LR 98/20075 RINA ELE/30298/2 GL 9924996HH BV 10617/AO BV NKK A556 DNV A8394 KR HMB 06190MS002 Service pressure 32 bar g at 238°C Connection NRGT 261: Screwed ¾“ BSP, DIN ISO 2281 NRGT 261S: Flanged DN 50, PN 40, DIN 2635 Materials Case 3.2161 G AlSi8Cu3 Stem 1.4571 CrNiMoTi17122 Flange 1.0460 P250GH Measuring electrodes 1.4571 CrNiMoTi17122 Electrode insulation PTFE Spacer disc PTFE (design for marine applications) Mains supply 230 V +/– 10 %, 50/60 Hz 115 V +/– 10 %, 50/60 Hz (optional) 24 V +/– 10 %, 50/60 Hz (optional) 24 V d.c. (optional) Overall length / measuring range See table overleaf Power consumption 5 VA Fuse Thermal fuse T max = 102 °C Sensitivity Range 1: Water 0.5 µ S/cm Range 2: Water 20 µ S/cm Range 3: Fuel oil EL ε r 2.3 Output 420 mA levelproportional. Voltfree, max. load 500 Indicators and adjustors 2 red LEDs for signalling “Level 0 %” or “Level 100 %” within the measuring range, 1 green LED for signalling “Level between 0 % and 100 %” of measuring range. 1 code switch for selecting the measuring range. 2 trimmer potentiometers for smallpercentage adjust ment of the measuring range. 2 terminal lugs for voltage metering. Cable entry Cable gland with integral cable clamp M 20 (PG 16) (2 x) Protection IP 65 to DIN EN 40050 Max. admissible ambient temperature 70 °C Weight NRGT 261: Approx. 1.8 kg NRGT 261S: Approx. 8.0 kg 1 2 3 4 5 DC Supply Wiring diagram NRGT 261 NRGT 261S 420 mA Max. load 500 PE Earthing screw in housing Thermal fuse L N Mains 24 V DC + GESTRA Steam Systems GESTRA NRGT 26-1

Gestra Nrgt 26 1 Nrgt 26 1s

  • Upload
    svoicum

  • View
    91

  • Download
    8

Embed Size (px)

Citation preview

Page 1: Gestra Nrgt 26 1 Nrgt 26 1s

Compact System for Level Monitoring NRGT 261NRGT 261S For Marine Applications

Issue Date: 4/06

Product Range BGESTRA Steam Systems

NRGT 261NRGT 261S

DescriptionThe compact system NRGT 261 works according to the capacitance measurement principle. The NRGT 261 is designed for signalling different levels in conductive and nonconductive liquids:

Water level maintained within the control band defined by two preset limits.

The NRGT 261 has a level transmitter integrated in the terminal box which produces a standard output signal of 420 mA. External switchgear is not required.

FunctionThe principle of capacitance measurement is applied to determine the level. The electrode rod and the vessel wall form a capacitor. If the level of the dielectric located between the two capacitor plates changes, the current which flows through the plates changes proportionally to the level. A dielectric is defined as an insulating substance, which excludes many liquids such as water. In order to receive a useful measuring result the measuring rod, which is completely submerged in the liquid, must be completely insulated. After calibration of the zero point/measuring range (0 % 100 %) of the control unit, the level can be read off from a remote display unit. The level measuring range can be changed during operation.

DesignNRGT 261: Electrode with screwed connection ¾" BSP, DIN ISO 2281.

NRGT 261S: Flanged design for marine applications DN 50, PN 40, DIN 2635.

Technical DataType approval no.

NRGT 261: TÜV · WRS · 02391NRGT 261S: LR 98/20075 RINA ELE/30298/2 GL 9924996HH BV 10617/AO BV NKK A556 DNV A8394 KR HMB 06190MS002 Service pressure 32 bar g at 238°C

Connection NRGT 261: Screwed ¾“ BSP, DIN ISO 2281 NRGT 261S: Flanged DN 50, PN 40, DIN 2635

Materials Case 3.2161 G AlSi8Cu3 Stem 1.4571 CrNiMoTi17122 Flange 1.0460 P250GH Measuring electrodes 1.4571 CrNiMoTi17122 Electrode insulation PTFE Spacer disc PTFE (design for marine applications)

Mains supply 230 V +/– 10 %, 50/60 Hz 115 V +/– 10 %, 50/60 Hz (optional) 24 V +/– 10 %, 50/60 Hz (optional) 24 V d.c. (optional)

Overall length / measuring range See table overleaf

Power consumption 5 VA

Fuse Thermal fuse Tmax = 102 °C

Sensitivity Range 1: Water ≥ 0.5 µS/cm Range 2: Water ≥ 20 µS/cm Range 3: Fuel oil EL εr 2.3

Output 420 mA levelproportional. Voltfree, max. load 500 ΩIndicators and adjustors 2 red LEDs for signalling “Level 0 %” or “Level 100 %” within the measuring range, 1 green LED for signalling “Level between 0 % and 100 %” of measuring range. 1 code switch for selecting the measuring range. 2 trimmer potentiometers for smallpercentage adjustment of the measuring range. 2 terminal lugs for voltage metering.

Cable entry Cable gland with integral cable clamp M 20 (PG 16) (2 x)

Protection IP 65 to DIN EN 40050

Max. admissible ambient temperature 70 °C

Weight NRGT 261: Approx. 1.8 kg NRGT 261S: Approx. 8.0 kg

1 2 3 4 5

DC

Supply

Wiring diagram

NRGT 261NRGT 261S

420 mA Max. load

500 Ω

PE

Earthing screw in housing

Thermal fuse L N

Mains

24 V DC+ –

GESTRA Steam Systems

GESTRANRGT 26-1

Page 2: Gestra Nrgt 26 1 Nrgt 26 1s

GESTRA Steam Systems

GESTRANRGT 26-1S

GESTRA Steam Systems

GESTRANRGT 26-1

¾“ BSP to EN ISO 2281

26∅ 42

337.

5

339

173

140

173

62

140

Flange DN 50, PN 40

37

b = 70

3 41 2

Compact System for Level Monitoring NRGT 261NRGT 261S For Marine Applications

Dimensions

GESTRA AGP. O. Box 10 54 60, D28054 BremenMünchener Str. 77, D28215 Bremen

Telephone +49 (0) 421 35 03 0, Fax +49 (0) 421 35 03393

EMail [email protected], Internet www.gestra.de

81019404/406cm · © 1998 GESTRA AG · Bremen · Printed in Germany

Supply in accordance with our general terms of business.

Fig. 2 NRGT 261 SFig. 1 NRGT 261

373 477 583 688 794 89910041110121413191423152816362156

300 400 500 600 700 800 9001000110012001300140015002000

316 420 526 631 737 842 9471053115712621366147115792099

275 375 475 575 675 775 875 975107511751275137514751975

Fig. 3 Protection tube for installation of electrode inside the boiler

Fig. 4 External measuring pot

ATEX (Atmosphère Explosible)According the the European Directive 94/9/EC the equipment must not be used in potentially explosive areas.

Important NotesCable required for wiring: flexible multicore control cable, min. conductor size 1.5 mm2.

Order and Enquiry Specification GESTRA Level electrode NRGT 261, PN 40

Mains supply...............................................................Connection.............................................................Inspection.............................................................Length supplied...................................................... mmFluid.....................................................................

GESTRA Level electrode NRGT 261 S, PN 40 for marine applications

Mains supply...............................................................Connection.............................................................Inspection.............................................................Length supplied...................................................... mmFluid.....................................................................

The following test certificates can be issued on request, at extra cost: In accordance with DIN EN 102042.1, 2.2 and 3.1B.

All inspection requirements have to be stated with the order. After supply of the equipment certification cannot be established. For tests and inspection charges please consult us.

Key1 NRGT 261: Max. length of installation at 238 °C

2 NRGT 261: Measuring range

3 NRGT 261S: Max. length of installation at 238 °C

4 NRGT 261S: Measuring range

1 Flange PN 40, DN 50, DIN 2527 Flange PN 40, DN 100, DIN 2527

2 For the approval of the boiler standpipe with connecting flange the relevant regulations must be considered.

3 Vent hole

4 High water (HW)

5 Electrode rod d = 15 mm

6 Protection tube DN 80

0 Low water (LW)

! Reducer DIN 2616, part 2 K 88.9 x 3.2 42.4 x 2.6 W

1 2 3 4

∅ 48.5

∅ 42.5

b = 70

∅ 42

Examples of Installation

DN 20

≤ 20

¾“ BSP

Cent

re d

ista

nce

1

5

4

0

2

DN 20

1

∅20

20

DN 50

¾“ BSP

≥10

∅ 20

≤ 90°

2

34

6

0

!

5