8
CONDAIR MK5 Resistive steam humidifier with patented scale management system Humidification and Evaporative Cooling

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

CONDAIR MK5Resistive steam humidifierwith patented scale management system

Humidification and Evaporative Cooling

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:52 Page 1

Page 2: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

Condair MK5Resistive steam humidifier with scale management

The Condair MK5 can operate on anywater quality. When used with ademineralised water supply thehumidifier can offer ±1%RH control andrequires very little maintenance.

Due to the system’s patented scalemanagement system, even when thehumidifier is operating with hardwater, the scale can easily be removedquickly and efficiently.

Resistive heating elements offer close controlConsistent and accurate humiditycontrol is offered with resistance heatertechnology. Unlike electrode boilerhumidifiers, the water level inside theheating chamber remains constant andthe heating elements continue tooperate even during mineral dilutioncycles. This provides a consistent steamoutput and accurate humidity control.

Incoloy heating elements with stagedoperation prevent current peaks on startup. Scale detaches from the elementsduring operation and falls into the scalecollection tank at the bottom of thehumidifier for easy removal.

Innovative pumped drainThe drain is located above the scalecollector tank so that scale collects inthe tank rather than blocking drainpipework.

Mains, softened or demineralised water

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:52 Page 3

Page 3: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

Durable casingSteel powder-coated case withstainless steel option.

Stainless steel boiling cylinder The Condair MK5 eliminates theexpense of disposable plastic boilingcylinders, significantly reducingoperating costs.

Electronic float level sensorProvides reliable water level control.

Easy to controlAn ergonomic keypad and backlitdisplay make the Condair MK5 easy touse. Operational status, fault andservice requirements are visuallyindicated.

Continuous control of steam outputfrom 0-100% of its range provides closehumidity control.

Scale collector tankAn externally located tank at thebottom of the boiling chamber collectsthe scale that detaches from theheating elements. It can be drained,removed, emptied of scale andreattached within minutes makingessential maintenance quick andsimple.

Protection brackets for scalecollector tank

The Condair MK5 resistive steamhumidifier provides reliable andaccurate humidity control with minimalmaintenance and without the expenseof replaceable boiling cylinders.

Patented scale managementtechnology allows scale deposits to beeasily removed from the system quicklyand efficiently.

A control accuracy of ±2%RH can be

achieved with mains water or ±1%RH with a demineralised water supply.The system is easy to install withquality, compact construction. The CrNistainless steel cylinder and Incoloyheating elements are extremely robustand provide a long operational lifetime.

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:52 Page 4

Page 4: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

When operated on mains water allsteam humidifiers build up limescale inthe boiling chamber as waterevaporates. How a humidifier managesthis scale determines how easy thesystem is to use and service. TheCondair MK5’s patented scalemanagement system makes it theeasiest and most user-friendly steamhumidifier in the world, ensuring longoperational periods and shortmaintenance intervals.

Quick and easy to serviceScale that forms on the heatingelements cracks off as they expandduring operation. The scale then fallsinto a scale collector tank located at thebottom of the system.

The externally located scale collectortank allows servicing to take placewithout having to open thehumidifier’s casing. To remove thescale, the system is drained, then thescale collector tank is unlocked andlowered with its ergonomic handles.The tank is then emptied andreattached allowing the system to beoperational again within minutes.

Innovative pumped drainAs scale falls down into the scalecollector tank, the drain pump, which islocated above the tank, is kept free ofscale. Unlike other humidifiers, thisavoids blockage of the pump anddrainage pipework.

Patented scale management

Scale is dislodged from the elements and falls into the scale collector tank

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:52 Page 5

Page 5: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

Boiling chamber

Scale collector tank

Drain pump

Collected scale is easily removed from the system in minutes

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 6

Page 6: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

An optional feature enablesthe linking of the Condair MK5 to abuilding management system. Controland monitoring of the humidificationsystem can then be carried out from aPC.

The card allows eachhumidifier in the system to beindividually addressed. The interface iscompatible with Modbus, BACnet/IPand LonWorks protocols.

Remote monitoring and control with

Can connect to a building management system

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7

Page 7: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

The Condair MK5 can operate onmains, softened or demineralisedwater. When used with mains waterthe humidifier will provide up to±2%RH humidity control and up to±1%RH when used with ademineralised supply.

A demineralised supply will alsovirtually eliminate scale build-upwithin the system, reducingmaintenance time and operating costs.It also reduces the overall energy

consumption of the humidifier, as thesystem isn’t running dilution cycles tocontrol the water’s mineral content,which avoids sending expensive hotwater to drain.

Condair manufactures and supplies awide range of water treatmentsolutions specifically designed for usewith humidification systems.

Flexible water options

PureFlo Reverse Osmosis Water FilterDesigned for use with humidificationsystems such as the Condair MK5

Operates on mains, softened or demineralised water

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 8

Page 8: i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp Layout 1 · i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 7. The Condair MK5 can operate on mains,

Condair plc - the new name for JS HumidifiersArtex Avenue, Rustington, Littlehampton, West Sussex, BN16 3LN, UKTel: +44 (0)1903 850200 - [email protected] - www.condair.co.uk

10/2014

Technical data

12

3

4

5

Standard system

Stainless steel steam cylinderSteel powder-coated caseExternal scale collector tankControl panel Self-diagnostic systemHours run timer

Options

Stainless steel casingOptiSorp short evaporation steamdistribution system

connection to BMSHumidity sensors for in-duct/direct roomHygrostatsPureFlo reverse osmosis water filter

Accesssories

1 Steam lance (in-duct)2 Steam hose3 Condensate hose4 Water filter5 Fan distribution system (in-room)

MK5 Visual/Process 5 8 10 16 20 24 30 40 50 60 80

Heating voltage Maximum steam output in kg/h

400 VAC / 3Ph / 50..60Hz kg/h 5.0 8.0 10.0 16.0 20.0 24.0 30.0 40.0 50.0 60.0 80.0

230 VAC / 1Ph / 50..60Hz kg/h 5.0 8.0 10.0 - - - - - - - -

Control voltage 230 VAC/ 1 Ph / 50..60Hz

Dimensions (WxHxD) mm 500 x 1087 x 437 594 x 1087 x 382 2x594 x 1087 x 382

Operating weight kg 51 51 52 53 71 73 73 74 144 146 148

Conformities CE, VDE, SVE

Subject to technical changes

i0522-80 JS Condair MK5 8pp Brochure AW 08/14.qxp_Layout 1 07/10/2014 10:53 Page 9