Upload
mariusz
View
212
Download
0
Embed Size (px)
Citation preview
Control algorithm of a DC/AC converter
applied in a small wind turbine
Pawel Mlodzikowski, Adam Milczarek, Mariusz Malinowski
Warsaw University of Technology, Institute of Control & Industrial Electronics, Warsaw, Poland
[email protected], [email protected], [email protected]
Abstract-Paper in detail presents control algorithm of a DC/AC converter applied in a small wind turbine (SWT), which has grid
connected and a stand-alone operation mode. Common problems encountered SWT’s transient between modes are described. Algorithm was implemented using a digital signal processor (DSP)
control platform and tested using a lab setup with a 2.2 kW permanent magnet synchronous generator (PMSG). That type of generator is popular among SWTs. Results obtained from
experimental verification are included.
I. INTRODUCTION
Wind power plants are playing an important role in
a modern electrical grid. According to IEC 61400-02 [1]
SWT must fulfill requirement of area swept by rotor blades
higher than 2m2, but less than 200m
2. These kind of wind
turbines are a very promising supplement to full scale
commercial applications [10]. Moreover there are simple in
construction and could be more efficient supplying local
loads near SWT. Therefore many governments are
encouraging private sector to broaden the SWT market.
In Poland 95% of SWT is working in stand-alone mode.
Number of installations is growing, and according to many
SWT producers this growth is estimated between 15-30% this
year.
Fig. 1 illustrates a block scheme of a small wind turbine
suited for working in grid connected or stand-alone mode.
The SWT basically consists of:
� A wind turbine and PMSG connected directly with
each other (without a gearbox) [8],
� AC/DC converter which is mostly a six-pulse diode
rectifier with a DC/DC boost converter for
utilization of Maximum Power Point Tracking
(MPPT) [9],
� DC/AC converter for transferring energy to the grid
or local load (converter should be able to operate
with non-symmetrical load), what is discussed in this
paper
Many DC/AC converter topologies are considered in
SWT. Their prices, efficiency, functionality and control
methods of energy conversion are varying between types.
One of most simple, is a three-phase converter with ∆-Y
transformer (Fig. 1), which helps to control power
independently in every phase during stand-alone operation.
Additionally exist plenty of control methods for this kind of
converters which can be applied in low-cost micro-controller.
Fig. 1 Block scheme of a small wind turbine with three-phase DC/AC converter with ∆-Y transformer
A universal control algorithm for two modes of operation
is in detail explained and the transition process between grid
connected and stand-alone mode are analyzed (section II).
Proposed control method applied in DSP platform is verified
by experiment (section III).
II. CONTROL SCHEME FOR DC/AC CONVERTER
APPLIED IN SMALL WIND TURBINES
Control scheme for DC/AC converter for SWT must ensure
proper work in stand-alone and grid connected mode, also it
has to be able to fast switch between them without delays. In
scheme shown in Fig. 3 we can distinguish three control
blocks:
� Direct Power Control – Space Vector Modulated
(DPC-SVM) in grid connected mode of operation,
� Voltage control in stand-alone mode,
� Monitoring.
A. DIRECT POWER CONTROL IN GRID CONNECTED MODE
DPC-SVM method bases on controlling instantaneous
values of active and reactive powers [7],[2]. Fig. 2 (red
dashed line) illustrates a block scheme of DPC-SVM.
978-1-4244-9312-8/11/$26.00 ©2011 IEEE 1006
Given active (pref) set by outer dc-link controller and
reactive (qref=0 for unity power factor) powers are compared
with their estimated values described as:
�� = � ∙ ���� + ����� (1)
�� = � ∙ ����� − ���� (2)
where:
udc - dc link voltage; iLα, iLβ - phase currents in α-β coordinate
system; uLα, uLβ - phase voltages in α-β coordinate system.
Instantaneous active and reactive power errors are input
values of PI controllers. Their outputs generate signals in d-q
coordinate system that represent given voltages for SVM.
B. VOLTAGE CONTROL IN STAND-ALONE MODE
The most important criterion taken into consideration
while choosing a control method in stand-alone mode was
simplicity. A simple algorithm can be easily implemented
using a cost effective microcontroller. Subsystem shown in
Fig. 2 (blue dashed line) contains inner ac voltage control
loops in d-q coordinate system and outer dc voltage control
loop [4],[5]. Outer control loop is in charge for keeping udc
voltage at constant, given level.
Reference values ud_ref and uq_ref compared with uLd and
uLq become input for PI regulators. Signal uq_ref is equal to
zero, therefore vector of converter voltage is aligned with
d-axis and amplitude of AC voltage depend on ud_ref only,
what allows to simplify the control.
Output signals from inner PI regulators after
transformation:
������� = �cos (�) −sin (�)sin (�) cos (�) � ∙ �������� (3)
are given values for Space Vector Modulator (SVM).
Important part of the control algorithm in this mode of
operation is energy dissipation. When local load will be lower
than power generated by turbine this circuit should be
activated, what helps maintain dc voltage at a constant level.
Energy dissipation circuit consists of a transistor and
a resistor (or a water boiler so that dissipated heat can be
utilized) which power rating should be not less than generator
nominal power. Control is very simple because generated
power (pdc) described as:
�� = !� ∙ � (4)
is compared with instantaneous power of the three-phase load
pload, which can be calculated with help of
�"#$� = ��$�$ + ��%�% + �� � (5)
where:
uLa, uLb and uLc are estimated values based on duty cycles of
converter’s control pulses and dc link voltage describe as
��$ = &'() (2+, − +- − +.) (6)
��% = &'() (2+- − +, − +. ) (7)
Fig. 2 Chosen control scheme involving voltage control, monitoring and DPC-SVM
1007
Fig. 4 Phase synchronization process: a) converter not-synchronized,
b) converter synchronized
22
βα
β
LL
L
UU
U
+
22
βα
α
LL
L
UU
U
+
Fig. 3. Implemented PLL’s scheme
�� = &'() (2+. − +, − +-) (8)
After calculations, control signals are introduced to
a proportional controller, with gain given by:
/0 = 123
(9)
where:
PN – nominal generator power.
Output signal from this proportional controller is compare
with carrier signal, which amplitude is equal to PN.
In results, there is calculated duty cycle of gate signal for Td.
C. MONITORING
Monitoring contains two main blocks:
� voltage and frequency verification
� phase locked loop (PLL)
When the grid faults appears, control algorithm is switched
to stand-alone mode of operation as well as PLL is working
in open loop (∆Θ=0) (Fig. 3).
If voltage recover, firstly the algorithm is testing if grid
voltage and frequency fulfils standards PN-EN 50160:2008,
what means that phase voltage can vary ±10% and frequency
±1%. Moreover, monitoring is checking if zero sequence
component of grid voltages described as:
��4 = 15 (��$ + ��% + �� ) (10)
is not higher than ±3% (selected experimentally) by
comparison to phase voltage. Then system make decision to
continue stand-alone mode or switch to grid connected mode
of operation.
If system decides about grid connected mode, then PLL is
applied to phase synchronization of converter and grid
voltages, what provide smooth transition between two modes
of operation (Fig. 3). Idea based on assumption, that
converter can be connected to the grid if ∆Θ described as [5]:
For (6 − �)>π:
∆Θ ≅ 9:(6 − �) = 9: 6 ∙ ;<9 � − ;<9 6 ∙ 9: � (11)
For (6 − �)<π:
∆Θ ≅ sin(� − 6) = ;<9 6 ∙ 9: � − sin 6 ∙ cos � (12)
is equal zero (Fig. 4).
Unfortunately it can happens, when sine argument (6 − �)
is equal “0” (correctly) as well as “π” (incorrectly). Therefore
if (6 − �)=π, small value is added to ∆Θ, to protect against
this undesirable situation.
III. EXPERIMENTAL VERIFICATION
View of laboratory setup is presented in Fig.5 and the particular parts of system are shown in block scheme (Fig. 6).
Tests includes:
� steady state operation of grid connected converter with
DPC-SVM (Fig. 7),
� steady state operation of stand-alone mode with one
and two-phase load (Fig. 8 and 9),
� step change of the load in stand-alone mode (Fig. 10),
� transient from stand-alone to grid connected and from
grid connected to stand-alone mode (Fig. 11 and 12).
Fig. 5 View of a experimental laboratory setup
1008
Fig. 6 Laboratory setup
Fig. 7 Steady state of converter working in grid connected mode
(DPC-SVM algorithm). From the top: phase voltage uLa, phase current iLa, active power p, reactive power q
Fig. 8 Steady state of converter working in stand-alone mode and supplying
single-phase load. From the top: measured phase voltage uLa, phase currents iLa, iLb,, iLc
Fig. 9 Steady state of converter working in stand-alone mode and supplying
two-phase load. From the top: phase voltage uLa, phase currents iLa, iLb, iL
Fig. 10 Step change of the load for converter working in stand-alone mode.
From the top: phase voltage uLa, phase current iLa, voltage in dc link UDC
YPMSGDCM
Danfoss 5.5 kW
3-ph converter
Danfoss 5.5 kW
3-ph converter
used as diode rectifier
P=2.2 kW,
n=1750 rev/min,
T=12 Nm,
U=3x220V,
pp=3
Grid simulator
California Instr.
15003iX
P=15 kW
U=3x400 V
Transformer
3x400/3x400
P=5kW per phase
PC
3x L=5 mH
3xC=3µF
Digital
Aquisition & ControlCard
1103
Master: PowerPC 604e
Slave: DSP TMS320F240
PCI RS-232
LEM
voltage & current
converters
with conditoning circuits
thyristor based
controled rectifier
direct
current
motor
control
Control
I. II. III. IV. V.
VI. VII.
Load
1009
Fig. 11 Transient from stand-alone to grid connected mode. From the top:
signal of switching command, phase voltage uLa, phase current iLa, voltage in
dc link UDC
Fig. 12 Transient from grid connected to stand-alone mode. From the top:
signal of switching command, phase voltage uLa, phase current iLa, voltage in
dc link UDC
CONCLUSIONS
This paper focus on control algorithm of a DC/AC
converter applied in a small wind turbine. Main control
blocks and monitoring are described in detail. Shown
experimental results prove, that converter is working
correctly in grid connected as well as stand-alone mode of
operation. Presented method of monitoring and converter
synchronization to the grid provides a smooth transient
between modes without affecting continuity of power supply
to local loads.
ACKNOWLEDGMENT
Described problems are the parts of the project number N
R01 0015 06/2009 “Complex solution for low speed small
wind turbine with energy storage module for distributed
generation systems” and sponsored by The National Centre
for Research and Development.
REFERENCES
[1] IEC 61400-02 Design requirements for small wind turbines, IEC, (2007)
[2] M. Malinowski, “Sensorless Control Strategies for Three – Phase PWM Rectifiers”, Ph.D. Thesis, Warsaw University of Technology, (2001)
[3] A. Milczarek, “Control of Three-phase PWM Converter for Small Wind Turbine in Stand-Alone and Grid-Connected Mode”, M.Sc. Thesis (in Polish), Warsaw University of Technology, (2010)
[4] M. Fatu., L. Tuteaea, R. Teodorescu, F. Blaabjerg, I. Boldea, ”Motion Sensorless Bidirectional PWM Converter Control with Seamless Switching from Power Grid to Stan Alone and Back”, Power Electronics Specialists Conference, pp. 1239-1244,(2007)
[5] R. Teodorescu, F. Blaabjerg, “Fexible Control of Small Wind Turbines Turbines With Grid Failure Detection Operating in Stand-Alone and Grid-Connected Mode”, IEEE transaction on power electronics, vol. 19, pp. 1323-1332, (2004)
[6] PN-EN 50160:2008, Polish Grid Codes, (2008) [7] M. Malinowski, M. Jasinski, M. P. Kazmierkowski, “Simple Direct
Power Control of Three-Phase PWM Rectifier Using Space Vector Modulation”, EPE-PEMC`02, vol.4, pp. 1114 – 1118, (2002)
[8] Z. Goryca, M. Ziolek, M. Malinowski, „Cogging Torque of the Multipolar Generator with Permanent Magnets”, (in Polish) "Maszyny Elektryczne Zeszyty Problemowe nr 88", pp. 53-56, (2010)
[9] Kot R., “Design, Investigation and Development of the Rectifier and DC/DC Converter with Maximum Power Point Tracking Algorithm for Optimum Operation of PMSG”, M.Sc. Thesis (in Polish), Warsaw University of Technology, (2010)
[10] Spagnuolo G., Petrone G. Araujo S.V. Cecati, C., Friis-Madsen, E., Gubia E., Hissel, D., Jasinski, M., Knapp, W., Liserre, M., Rodriguez, P., Teodorescu, R., Zacharias, P., , "Renewable Energy Operation and Conversion Schemes: A Summary of Discussions During the Seminar on Renewable Energy Systems," Industrial Electronics Magazine, IEEE , vol.4, no.1, pp.38-51, (2010)
1010