112
Lock-out and Tag Procedures •Presented By: •Paul Micheal Hall •District 3 – Morgantown •Robert Phillips •Headquarters - Arlington

Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Embed Size (px)

Citation preview

Page 1: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Lock-out and Tag Procedures

• Presented By:

• Paul Micheal Hall

• District 3 – Morgantown

• Robert Phillips

• Headquarters - Arlington

Page 2: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Purpose of Lock-Out and Tag

• Personal Safety

• Prevent Undue Exposure to Energized Circuits

• Reduce Electrical Fatalities and Accidents

Page 3: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Coal Fatals - Total & Electrical

– Year Total Electrical

– 1970 – 1999 2946 229

– 2000 38 2

– 2001 42 2

– 2002 27 4

– 2003 29 4

– 2004 8 1

– Total 3090 242

Page 4: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

ELECTRICAL FATALITIES 1970 - 2003

02468

10

1214161820

1970

1972

1974

1976

1978

1980

1982

1984

1986

1988

1990

1992

1994

1996

1998

2000

2002

Page 5: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Coal Fatals - Total & Electrical

– Average = 90.6 Electrical = 7.1 [7.8%]– (For 1970 to 2003 and Based on 3082

fatalities; 241 electrical)

Page 6: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Electricity

• Next to a nuclear reaction, an electrical arc is the hottest thing on earth, being seven times the temperature at the sun’s surface.

• Electricity can cause shock, burns, ignitions, explosions and even electrocution.

• Be Wise! Stay Alive! Always Deenergize!

Page 7: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Circuits that must be Locked-Out and Tagged

• Electrical

• Hydraulic

• Pneumatic

• Mechanical

• Thermal

Page 8: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Who must Lock-Out and TagWhen Performing Electrical

Work

• All person(s) doing electrical work on the circuit

Page 9: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Trouble Shooting Procedure For Equipment and Circuits

• Energized Circuit and EquipmentEnergized Circuit and Equipment– Low- and Medium-Voltage OnlyLow- and Medium-Voltage Only– Only to determine the problemOnly to determine the problem

• Lock- and Tag- out to perform electrical Lock- and Tag- out to perform electrical workwork

Page 10: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

EFFECTS OF CURRENT ON THE AVERAGE BODY

Page 11: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Current Effects

• How much current does it take to illuminate a 60 watt, 120 volt light bulb?

• The answer is 0.5 amperes or 500 milliamps.

• This is over five times the current that it takes to electrocute someone.

Page 12: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

CURRENTCURRENT EFFECT EFFECT 1 MILLIAMP1 MILLIAMP THRESHOLD OF THRESHOLD OF

PERCEPTION PERCEPTION

• 1 TO 8 MILLIAMPS1 TO 8 MILLIAMPS SENSATION OF SENSATION OF SHOCK SHOCK

• 8 TO 15 MILLIAMPS8 TO 15 MILLIAMPS PAINFUL SHOCK PAINFUL SHOCK

• 15 TO 20 MILLIAMPS15 TO 20 MILLIAMPS LOSS OF LOSS OF MUSCULAR MUSCULAR CONTROLCONTROL

Page 13: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

20 TO 50 MILLIAMPS20 TO 50 MILLIAMPS BREATHING IS BREATHING IS DIFFICULT DIFFICULT

• 100 TO 200 MILLIAMPS100 TO 200 MILLIAMPS VENTRICULAR VENTRICULAR FIBRILLATION (NO FIBRILLATION (NO KNOWN KNOWN

REMEDY)REMEDY)

• OVER 200 MILLIAMPSOVER 200 MILLIAMPS SEVERE BURNSSEVERE BURNS

Page 14: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Why People Do Not Lock- & Tag-Out

• Takes too long!

• Too far to travel to remove power!

• Will only take a minute!

• I’ll do it hot!

• I know what I’m doing!

• Have seen others do it or have done it themselves!

Page 15: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

3

2

3

1

1

18

5

4 922

76 281

56

ELECTRICAL FATALITIES BY STATE

1970 - 2003

3

6

3

Page 16: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Percentage of Electrical Fatalities by Location

Page 17: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

12%

1%15%12%

60%

PREPARATION PLANT

SURFACE - CENTRAL SHOP

SURFACE AREA OF UNDERGROUND MINE

SURFACE MINE

UNDERGROUND MINE

Page 18: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

167 1

16

71

205

104

020406080

100120

VOLTAGE CONTACTED

Page 19: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

TYPE OF CONTACT

15047

40 1 3

DIRECT CONTACT WITH CURRENT-CARRYING CONDUCTOR OR PART

DIRECT CONTACT WITH ENERGIZED EQUIPMENT FRAME

INDIRECT CONTACT WITH CURRENT-CARRYING CONDUCTOR OR PART

LIGHTNING STRIKE

NO CONTACT WITH ENERGIZED PARTS

Page 20: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

QUALIFICATION OF VICTIMS

NOT QUALIFIED 67%

QUALIFIED33%

Page 21: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

ELECTRICAL WORK

52%NO

YES 48%

Page 22: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

AGE OF VICTIMS (1983 TO 2003 DATA)

20-2916%

30-3937%

40-4931%

50-6014%

UNDER 202%

Page 23: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

American Eagle Mine     460543702/18/2000           AGE 44

EMPLOYEE ENTERED SUBSTATION TO DETERMINE WHAT WORK WILL

BE REQUIRED TO REMOVE THE TRANSFORMER. HE CLIMBED THE TRANSFORMER TO LOOK AT TOP

WHEN HE CAME IN CONTACT WITH LINE.

Page 24: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

PE 2 Underground          1518008            04/30/2000       AGE 26  

A CERTIFIED ELECTRICIAN WAS GOING TO MAKE REPAIRS ON THE

RIGHT SIDE POWER CENTER IN THE NO. 5 ENTRY, AND WAS FOUND

LYING BESIDE THE POWER CENTER. IT APPEARS HE RECEIVED A FATAL

ELECTRICAL SHOCK

Page 25: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Still Run No. 4   460872603/13/2001    AGE 44

AFTER INSTALLATION OF A BANK OF CAPACITORS ON THE HIGH VOLTAGE LINES

FEEDING THE MINE SUBSTATION, EE (ACCORDING TO WITNESSES) UNPLUGGED THE 110 V CONTROL CIRCUIT FROM THE

RECEPTACLE, THREW IT TO THE GROUND, PICKED IT BACK UP TO INSPECT & AT THIS

TIME CAME IN CONTACT WITH ELECTRICAL CURRENT.

Page 26: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

#77       1509636   07/20/2001 AGE 26  EE WAS FATALLY

ELECTROCUTED AS HE DISASSEMBLED A CONVEYOR

BELT STARTING BOX SOURCE OF POWER CAUSING DEATH IN UNKNOWN AT THAT TIME.

Page 27: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Mine No. 5        440605101/24/2002   AGE 42

SECTION POWER MOVE HAD BEEN MADE. WORK BEING DONE TO CONNECT THE

PHASING. EMPLOYEE APPROXIMATELY 2 CROSSCUTS FROM POWER CENTER

STATED HE HEARD A STRANGE SOUND FROM THE AREA OF THE POWER

CENTER AND WENT TO THE POWER CENTER AND FOUND THE DECEASED

SLUMPED OVER THE POWER CENTER.

Page 28: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Mine 84 360095805/11/2002   AGE 46

EE WAS OPERATING A STAMLER COAL HAULER AND HAD ATTEMPTED TO TRAM

AROUND AN UN CUT CORNER. IN DOING SO HIS HAULER APPARENTLY PINCHED THE

ENEGIZED LOADER CABLE BETWEEN THE HAULER AND THE COAL RI B. EE EXITED THE MACHINE TO LOOK AT THE DAMAGE TO THE

CABLE AND WAS APPARENTLY ELECTROCUTED WHEN HE CONTACTED THE

FRAME OF THE COAL HAULER.

Page 29: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Huff Creek No 1 151723405/21/2002   AGE 50

EMPLOYEE WAS WORKING ON A POWER DISTRIBUTION BOX TO

DETERMINE WHY A CIRCUIT BREAKER WOULD NOT OPERATE.

HE APPARENTLY CAME IN CONTACT WITH AN ENERGIZED CIRCUIT DURING THE TROUBLE

SHOOTING PROCESS.

Page 30: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Calvary No. 80   151634905/23/2002   AGE 58

THE ELECTRICIAN WAS WORKING ON A GROUNDED SHUTTLE CAR CABLE

AND RECEIVED FLASH BURNS WHEN A SHORT CIRCUIT OCCURED AT THE

FEMALE RECEPTACLE ON THE ELECTRICAL POWER CENTER.

Page 31: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Mine No. 4        440705201/21/2003   AGE 33

THE VICTIM WAS ELECTROCUTED NEAR THE FACE OF NO. 8 ENTRY OF THE 001-0 MMU WHILE INSTALLING SUPPLEMENTAL ROOF SUPPORTS. WHEN ANOTHER WORKER FINISHED CUTTING A STEEL BEAM WITH A TORCH, AN ENERGIZ ED TRAILING CABLE WAS DAMAGED CAUSING THE

BEAM & TRAILER ON WHICH IT RESTED TO BECOME ENERGIZED. THE VICTIM THEN CAME

IN CONTACT WITH THE TRAILER, RESULTING IN ELECTROCUTION.

Page 32: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

No. 50 Mine       460877603/23/2003    AGE 49

BREAKER BLEW UP AND BURNED EMPLOYEE.

Page 33: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Beaver Valley    360872506/13/2003    AGE 41

WHILE TROUBLE SHOOTING MAIN OUTSIDE SUBSTATION,

EMPLOYEE CAME IN CONTACT WITH HIGH VOLTAGE RESULTING IN DEATH.

Page 34: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Upper Big Branch Mine-South     460843607/19/2003       AGE  27

EMPLOYEE WAS IN THE PROCESS OF REPAIRING #3 SHUTTLE CAR CABLE. POWER

TO CABLE HAD BEEN TAGGED & LOCKED OUT. HE WAS DISCOVERED LYING ON HIS BACK & NOT BREATHING. CPR WAS ADMINISTERED

AND HE WAS TRANSPORTED TO THE HOSPITAL WHERE HE WAS PRONOUNCED DEAD AT

APPROX. 8:20 P.M. MSHA/STATE INVESTIGATIONS ARE INCONCLUSIVE AT THIS

TIME.

Page 35: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Ruby Energy     460880802/05/2004  AGE 33

ELECTRICIAN WAS FATALLY ELECTROCUTED WHILE

REPAIRING A MINER CABLE. THE CABLE WAS NOT LOCKED AND

TAGGED OUT BY THE ELECTRICIAN.

Page 36: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Regulations requiring Disconnecting Devices?

• 30 CFR 75.509

• "All power circuits and electric equipment shall be de-energized before work is done on such circuits and equipment, except when trouble shooting or testing".

Page 37: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.509 Policy states,

• PPM states in part, …"a violation of this Section shall be cited only when electrical work is being performed on an energized machine.... Troubleshooting or testing does not include the repair of electrical, hydraulic, or mechanical problems".

Page 38: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.511

• No electrical work shall be performed on low-, medium-, or high-voltage distribution circuits or equipment, except by a qualified person or a person trained to perform electrical work and to maintain electrical equipment under the direct supervision of a qualified person....

Page 39: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.511 cont.

• Disconnecting devices shall be locked out and suitably tagged by such persons. Locks or tags shall be removed only by the persons who installed them or, if such persons are unavailable, by persons authorized by the operator or his agent.

Page 40: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.511 Policy states,

• "For the purpose of this Section, electrical work is considered to be work required to install or maintain electric equipment or conductors..... The phrase "under the direct supervision of a qualified person" must, as a minimum, include the following:

Page 41: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.511 PPM cont.• 1. The qualified person shall examine

and/or test an electric circuit or machine and determine the need for repair or maintenance;

• 2. The qualified person must give specific instructions to the employee assigned to perform this work with respect to the nature and extent of the repairs to be performed and, where necessary, prescribe the manner in which the work is to be performed;

Page 42: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.511 PPM cont.• 3. The qualified person is, at all times,

under continuing duty to instruct, advise, or consult with the employee in the event the work which he has assigned cannot be performed by the employee in the manner prescribed; and

• 4. The qualified person must examine and test, if necessary, the completed work before the circuit is energized or the machine is returned to service.

Page 43: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.511 PPM cont.• Disconnecting devices shall be locked out,

where possible, and suitably tagged by persons who perform the work. In all instances, trailing cables equipped with cable couplers or fuse nips shall be opened, tagged and locked out.

• The person doing the work shall keep the key to the padlock in his/her possession to insure that the circuit or cable will not be inadvertently energized while he or she is in contact with the conductors.

Page 44: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.511 PPM cont.• In every instance, the padlock shall be

removed by the person who installed it if the person is present in the mine. If the person who installed the padlock is not present, the operator or the operator's agent (a responsible official) must designate a person to remove the padlock.

• "Suitably tagged" means that a sign with the wording such as "Danger, Repairs in Progress," shall be attached to the locked disconnecting device.

Page 45: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Disconnecting Devices Installed On-Board Mine Equipment

• When disconnecting devices are installed on-board mine equipment, they may be used to meet the requirements of 30 CFR 75.509, 75.511 and 75.1725 (c)....

Page 46: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Disconnect PPM cont.• To meet the requirements of 30 CFR

75.509, 75.511 and 75.1725 (c), disconnecting devices must function so as to provide positive visual conformation that the equipment or circuit is deenergized. The worker must be able to easily see the power disconnect blades or contacts to determine, without any doubt, that the equipment or circuit is deenergized and...

Page 47: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Disconnect PPM cont.

• To meet the requirements of 30 CFR 75.520, disconnecting device enclosures must be explosion-proof..... In addition, the enclosure housing the disconnecting device must be the first enclosure on-board the machine that the trailing cable enters....

Page 48: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Disconnect PPM cont.• Permitting a disconnecting device installed on-

board a machine to be used as the visual disconnect for the equipment creates a change in established electrical work procedures. As a result, all miners who perform maintenance on this equipment must receive task training as required by 30 CFR 48.7 (a) (3). This training must include clear instructions that the disconnecting device will only deenergize the machine, and that the trailing cable will remain energized.

Page 49: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.519

• In all main power circuits, disconnecting switches shall be installed within 500 feet of the bottoms of shafts and boreholes through which main power circuits enter the underground area of the mine and within 500 feet of all other places where main power circuits enter the underground area of the mine.

Page 50: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.519-1 Policy, Main Power Circuit; Disconnecting Switches; Locations

• This Section applies to low- and medium-voltage power circuits entering a mine and to low-, medium-, and high-voltage power circuits at the bottom of shafts and boreholes. The requirements for disconnecting switches for high-voltage power circuits entering a mine are contained in Section 75.802 (c).

Page 51: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.519-1 PPM cont.

• A high-voltage cable coupler, switch, or other device not designed for load-breaking duty that is located at the bottom of a shaft or borehole may be used in conjunction with a high-voltage circuit breaker located on the surface provided:

• (1) A remote control switch that, when activated, will open the circuit breaker is provided at the shaft or borehole; and

Page 52: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.519-1 PPM cont.

• (2) A visual or audible means to indicate that the circuit breaker has opened when the remote control switch is activated is provided at the bottom of the shaft or borehole. Signal lights will be acceptable if the lights receive power through the auxiliary contacts on the circuit breaker.

Page 53: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.519-1 PPM cont.

• Unless fuse-type and knife-blade cutout switches are designed for load-breaking duty on high-voltage circuits, such switches shall be used for a disconnecting means only when some other means is first used to deenergize the circuit.

Page 54: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.601 states in part,…

• “Disconnecting devices used to disconnect power from trailing cables shall be plainly marked and identified and such devices shall be equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.”

Page 55: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.601 Policy states,

• Enclosed circuit breakers are not acceptable as visual evidence that the power is disconnected. Plugs and receptacles located at the circuit breaker and trolley nips are acceptable as visual means of disconnecting the power.

Page 56: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.705 states in part,...

• “High-voltage lines, both on the surface and underground, shall be deenergized and grounded before work is performed on them,…”

Page 57: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.705-1 (b) states in part,...

• “No high-voltage line, either on the surface or underground, shall be regarded as deenergized for the purpose of performing work on it, until it has been determined by a qualified person (as provided in 75.153) that such high-voltage line has been deenergized and grounded. Such qualified person shall by visual observation

Page 58: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.705-1 (b) cont.

• (1) determine that the disconnecting devices on the high-voltage circuit are in open position and (2) ensure that each ungrounded conductor of the high-voltage circuit upon which work is to be done is properly connected to the system-grounding medium…”.

Page 59: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.705-1 (c) states,

• “No work shall be performed on any high-voltage line on the surface which is supported by any pole or structure which also supports other high-voltage lines until:

• (1) All lines supported on the pole or structure are deenergized and grounded in accordance with all the provisions of this section which apply to the repair of energized surface high-voltage lines; or

Page 60: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.705-1 (c) cont.

• (2) the provisions of 75.705-2 through 75.705-10 have been complied with, with respect to all lines, which are supported on the pole or structure.”

Page 61: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.802 (c) states in part,...

• “Within 100 feet of the point on the surface where high-voltage circuits enter the underground portion of the mine, disconnecting devices shall be installed and so equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected,… .”

Page 62: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.808 states,

• “Disconnecting devices shall be installed at the beginning of branch lines in high-voltage circuits and equipped or designed in such a manner that it can be determined by visual observation that the circuit is deenergized when the switches are open.”

Page 63: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.808 Policy states in part,...

• Cable couplers are acceptable as a disconnecting device only when used with an acceptable device such as a circuit breaker or oil-filled fused cutouts that are used to deenergize the circuit before the cable coupler is uncoupled.

Page 64: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.808 PPM cont.

• If a remote switch in the ground check circuit is used to trip a circuit breaker prior to uncoupling the coupler, visible or audible evidence must be provided to indicate that the circuit breaker has opened before the coupler is uncoupled.

Page 65: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.815(a) states

The section power center must be equipped with a main disconnecting device installed to deenergize all cables extending to longwall equipment when the device is in the ``open'' position.    

Page 66: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.815(b) states    Disconnecting devices for motor-starter

enclosures must be maintained in accordance with the approval requirements of paragraph (f) of Sec. 18.53 of part 18 of this chapter. The compartment for the disconnect device must be provided with a caution label to warn miners against entering the compartment before deenergizing the incoming high- voltage circuits to the compartment.     

Page 67: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Each motor-starter enclosure, with the exception of a controller on a high-voltage shearer, must be equipped with a disconnect device installed to deenergize all high-voltage power conductors extending from the enclosure when the device is in the ``open'' position.      (1) When multiple disconnect devices located in the same enclosure are used to satisfy the above requirement they must be mechanically connected to provide simultaneous operation by one handle.      (2) The disconnect device must be rated for the maximum phase-to- phase voltage and the full-load current of the circuit in which it is located, and installed so that--      (i) Visual observation determines that the contacts are open without removing any cover;

     (ii) The load-side power conductors are grounded when the device is in the ``open'' position;      (iii) The device can be locked in the ``open'' position;      (iv) When located in an explosion-proof enclosure, the device must be designed and installed to cause the current to be interrupted automatically prior to the opening of the contacts; and      (v) When located in a non-explosion-proof enclosure, the device must be designed and installed to cause the current to be interrupted automatically prior to the opening of the contacts, or the device must be capable of interrupting the full-load current of the circuit.

18.53(f) states

Page 68: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.815(c) states

    Disconnecting devices must be rated for the maximum phase-to- phase voltage of the circuit in which they are installed, and for the full-load current of the circuit that is supplied power through the device.

Page 69: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.815(d) states• Each disconnecting device must be designed and

installed so that --

• (1) Visual observation determines that the contacts are open without removing any cover;

• (2) All load power conductors can be grounded when the device is in the ``open'' position; and

• (3) The device can be locked in the ``open'' position.      

Page 70: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.815(d) states

Disconnecting devices, except those installed in explosion- proof enclosures, must be capable of interrupting the full-load current of the circuit or designed and installed to cause the current to be interrupted automatically prior to the opening of the contacts of the device. Disconnecting devices installed in explosion-proof enclosures must be maintained in accordance with the approval requirements of paragraph (f)(2)(iv) of Sec. 18.53 of part 18 of this chapter.

Page 71: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.903 states,

• “Disconnecting devices shall be installed in conjunction with the circuit breaker to provide visual evidence that the power is disconnected.”

Page 72: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.903 Policy, Disconnecting Devices

• “A connecting plug on the outby end of the trailing cable connected to the power center or distribution box will be accepted as a disconnecting device. Other means, such as switches with visible contacts, may also be acceptable for this purpose. Molded-case circuit breakers are not acceptable as visible disconnecting devices.”

Page 73: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.1725 (c) states,

• “Repairs or maintenance shall not be performed on machinery until the power is off and the machinery is blocked against motion, except where machinery motion is necessary to make adjustments.”

Page 74: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

75.1725 (c) Policy states in part,..• “The trailing cable shall be disconnected from the

source of power before repairs are made on portable or mobile equipment , except when the equipment must be operated for making adjustments.”

• “Opening a circuit breaker which is installed on the machine, and which opens all power conductors entering the machine, shall be acceptable as compliance with this Section for lubrication or changing bits.”

Page 75: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.500 states,

• “Power circuits and equipment shall be deenergized before work is done on such circuits and equipment, except necessary for trouble-shooting or testing.”

Page 76: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.500 Policy states in part,...

• “When electrical work is being performed on equipment, it is not necessary to completely deenergize the power system if means are provided on the equipment to deenergize the particular part or circuit on which repair work is to be done.”

Page 77: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.500 PPM cont.

• “When work is performed in close physical proximity to exposed electrical circuits or parts, they shall be deenergized. High-voltage circuits that are not equipped with metallic shielding are considered to be exposed. Sections 110-16 and 710-34 of the 1968 National Electrical Code pertaining to working clearances can be used as a guide in determining “close physical proximity”.”

Page 78: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.500 PPM cont.

• “All circuits within an electrical enclosure shall be deenergized before work is performed within the enclosure unless such energized circuits are guarded by suitable physical guards or adequate physical separation.”

Page 79: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.500 PPM cont.

• “As the accident and injury data associated with working on energized circuits and equipment clearly indicates, this type of work presents a significant risk of hand injury. Therefore, gloves worn in accordance with 75.1720 (c) and 77.1710 (c) will be required whenever miners trouble-shoot or test energized electrical power circuits or electric equipment.”

Page 80: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 states,

• “No electrical work shall be performed on electric distribution circuits or equipment, except by a qualified person or by a person trained to perform electrical work and to maintain electrical equipment under the direct supervision of a qualified person.”

Page 81: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 cont.

• “Disconnecting devices shall be locked out and suitably tagged by the persons who perform such work, except that in cases where locking out is not possible, such devices shall be opened and suitably tagged by such persons. Locks or tags shall be removed only by the persons who installed them or, if such persons are unavailable, by persons authorized by the operator or his agent.”

Page 82: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 Policy states in part,...• “Electrical work”, as referred to in this Section,

includes the design, installation, maintenance or repair of electric equipment and circuits.”

• “The term “direct supervision” shall not be interrupted to mean that the qualified person be physically present at all times during the performance of such repairs, but the qualified person has the following responsibilities:

Page 83: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 PPM cont.• 1. The qualified person shall examine and/or test

an electric circuit or machine and determine the need for repair or maintenance;

• 2. The qualified person must give specific instructions to the employee assigned to perform this work with respect to the nature and extent of the repairs to be performed and, where necessary, prescribe the manner in which the work is to be performed;

Page 84: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 PPM cont.• 3. The qualified person is, at all times, under

continuing duty to instruct, advise, or consult with the employee in the event the work which he has assigned cannot be performed by the employee in the manner prescribed; and

• 4. The qualified person must examine and test, if necessary, the completed work before the circuit is energized or the machine is returned to service.

Page 85: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 PPM cont.• It is MSHA’s policy that a person trained to

perform electrical work and to maintain electric equipment under the direct supervision of a qualified person shall not be assigned the duty of testing or trouble-shooting energized circuits. Persons trained to perform electrical work and to maintain electric equipment may only do testing and trouble-shooting on energized circuits as part of their training program.

Page 86: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 PPM cont.

• During this testing and trouble-shooting operation, a qualified person, as defined in Section 77.103, must be present at all times to observe, instruct, and aid the trainee.

Page 87: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.501 PPM cont.

• “Suitably tagged” means that a sign with the wording such as “Danger - Hands Off - Do Not Close - Miners Working on Line,” shall be attached to the opened disconnecting device. The tag should bear the name of the workman who installed it.”

• “Keys to locks used to lock out switches should be kept by the person working on the circuit or equipment.”

Page 88: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.600 states in part,...

• “Disconnecting devices used to disconnect power from trailing cables shall be plainly marked and identified and such devices shall be equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.”

Page 89: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.600 Policy states in part,...• “A visual means of disconnecting the power

from the trailing cable must be provided so that it can readily be determined whether or not the cable is deenergized. Enclosed circuit breakers are not acceptable as visual evidence that power is disconnected. Plugs and receptacles located at the circuit breaker would be acceptable as the visible means of disconnecting the power.”

Page 90: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.704 states in part,...

• “High-voltage lines shall be deenergized and grounded before work is performed on them, except that repairs may be permitted on energized high-voltage lines if…”

Page 91: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.704 Policy states,

• “High-voltage lines shall be deenergized with a disconnecting device so that it can be determined by visual observation that the circuit is deenergized before the lines are grounded (refer to Section 77.704-9 when operating disconnecting devices), except that repairs may be permitted on energized high-voltage lines as specified in the regulations.”

Page 92: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.704-1 states,

• (a) “No high-voltage line, either on the surface or underground, shall be regarded as deenergized for the purpose of performing work on it, until it has been determined by a qualified person (as provided in 77.103) that such high-voltage line has been deenergized and grounded. Such qualified person shall by visual observation

Page 93: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.704-1 cont.

• (1) determine that the disconnecting devices on the high-voltage circuit are in open position and (2) ensure that each ungrounded conductor of the high-voltage circuit upon which work is to be done is properly connected to the system-grounding medium…”.

Page 94: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.704-1 (b) states,

• “No work shall be performed on any high-voltage line which is supported by any pole or structure which also supports other high-voltage lines until:

• (1) All lines supported on the pole or structure are deenergized and grounded in accordance with all the provisions of this 77.704-1 which apply to the repair of energized surface high-voltage lines; or

Page 95: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.704-1 (b) cont.

• (2) the provisions of 77.704-2 through 77.704-10 have been complied with, with respect to all energized lines, which are supported on the pole or structure.”

Page 96: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.704-1 Policy states,• There may be instances where one qualified

electrician will go back some distance from the work site and deenergize and ground the high-voltage system to be repaired. This qualified electrician must be in either direct telephone or radio communication with the qualified electrician performing the actual work, and when he/she has deenergized and grounded the system, can inform the qualified electrician to make the repairs.”

Page 97: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.808 states,

• “Disconnecting devices shall be installed at the beginning of branch lines in high-voltage circuits and equipped or designed in such a manner that it can be determined by visual observation that the circuit is deenergized when the switches are open.”

Page 98: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.808 Policy states in part,...• “Visual observation,” as referred to in this

Section, means that a physical separation in the current-carrying parts of the disconnecting device can actually be seen.

• Enclosed circuit breakers, oil-filled cutout switches, and other devices which do not have a visual means of determining that the circuit is deenergized do not meet the requirements of this Section.

Page 99: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.808 PPM cont.

• A cable coupler or other device that is not designed for load-break purposes is not acceptable as a disconnecting device unless it is used in conjunction with a current-interrupting device such as a circuit breaker or oil-filled cutout which can be used to deenergize the circuit before the cable coupler of other device is opened.

Page 100: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.808 PPM cont.

• If a remote switch in the ground check circuit is used to trip a circuit breaker prior to uncoupling the coupler, visual or audible evidence must be provided to indicate that the circuit breaker has opened when the control switch is operated.

Page 101: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.903 states,

• “Disconnecting devices shall be installed in circuits supplying power to portable or mobile equipment and shall provide visual evidence that the power is disconnected.”

Page 102: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.903 Policy, Disconnecting Devices

• “Visual evidence,” as used in this Section, means that a physical separation of the current-carrying parts of the disconnecting device can actually be seen.

Page 103: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.903 PPM cont.

• Consequently, molded-case circuit breakers are not acceptable as disconnecting devices. A connecting plug on the outby end of a cable with which the cable is connected to the power source box shall be accepted as a disconnecting device. Other visible disconnecting means, such as switches with visibly open contacts, will also meet the requirements of this Section.

Page 104: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.404 (c) states,

• “Repairs or maintenance shall not be performed on machinery until the power is off and the machinery is blocked against motion, except where machinery motion is necessary to make adjustments.”

Page 105: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.404 (c) Policy states in part,...

• “MSHA’s policy on Paragraph (c) of this section is similar to the policy on Section 77.500, which states that it is not necessary to completely deenergize large surface mining equipment where means are provided in the equipment to deenergize any part where repair work is to be done.

Page 106: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.404 (c) PPM cont.

• Similarly, to comply with Paragraph (c) , it is not necessary to completely deenergize large surface mining equipment where the motion of the operating equipment does not pose a hazard, and means are provided in the equipment to deenergize that part where the repair or maintenance work is to be done.

Page 107: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.404 (c) PPM cont.

• Each repair or maintenance job must be examined separately for hazards related to that particular job or area. If the machine’s operation poses a hazard to the employee performing the work, the machine shall be shut down until the work is completed or the hazard no longer exists.

Page 108: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

77.404 (c) PPM cont.

• General maintenance and housekeeping can normally be performed while the machine is in motion except around unguarded energized electric or moving mechanical equipment.

Page 109: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

To Prevent Electrical Fatalities and Accidents

• Properly assess task to be performed and communicate!

• Team work. Never troubleshoot alone!

• Always lock out and tag the circuit or equipment before making any repairs!

• Always use equipment rated for circuit voltages!

• Always wear proper personal protection!

• Remember, it’s your life that is on the line!

Page 110: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Total Electrical Fatalities

• 1970-Present

• 242 total electrical fatalities

Page 111: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington

Five Steps To SafetyFive Steps To Safety

• Turn equipment off and disconnect the energy source

• Lock and tag energy source (electrical, mechanical, pneumatic, hydraulic, etc.)

• Release energy in charged conductors, pipes, and etc.

• Test the equipment to assure energy source is isolated

• Restore energy safelyRestore energy safely

Page 112: Lock-out and Tag Procedures Presented By: Paul Micheal Hall District 3 – Morgantown Robert Phillips Headquarters - Arlington