Upload
others
View
6
Download
0
Embed Size (px)
Citation preview
06 / 07
CR-LVLS 전선 Busduct System Catalogue
06 of 08
ContentsII. General Data 20
III. Component
- Feeder 22
- Flanged End 23
- Fittings 24
- Hanger 26
- Etc 27
IV. Technical Data
- Impedence 28
- Voltage Drop 28
- Temperature Rise 29
V. Install Information 30
Ⅱ. General Data
Congration
Indoor Type
[3 conductor] [4 conductor] [5 conductor]
Outdoor Type (sun exposure)[
Basic StructureThe CR-LV consists of conductors and epoxy resin. Since the resin performs as insulation and housing which provides protec-
tion to the interior structure, additional bus ducts or housing are not necessary.
For outdoor installation (sun exposure), a sun shade is used to prevent the epoxy resin from being exposed to direct sunlight.
• Sunshade(steel)
While other bus ducts with metal housing require grounding, the CR-LV does not require additional grounding because the epoxy resin insulation
itself performs as housing. (Additional grounding is available on request. Please contact our design team for further information.)
R R RS S ST T TN/E N/E N/E
]
20 CR-LV/MV LS C&S-Busway System
06 / 07
Double-headed bolts are used to ensure a proper torque level when installing
the joint kit. If a torque wrench applies a pressure of 800 to 1000kgf·cm to the
outer bolt head, the head of the outer bolt and the tag attached to it will break
off on its own. Thus, it allows easy inspection for the proper application of the
bolts at the connection.
Double Head Bolts
Both joint plates of the joint kit and the conductors are tin plated. (A silver
plated option is available.) It prevents discoloration and corrosion of the joint
plates. In order to ensure easy maintenance and reliability, double -headed
bolts and visible labels are used to check the application, and a disc spring
allows an even connection of the contact surface.
Feature
The CR-Way uses a joint kit method.
!
sure a proper torque level when installing
ies a pressure of 800 to 1000kgf·cm to the
er bolt and the tag attached to it will break
spection for the proper application of the
pp pr g
ontact surface.
Joint Kit
Precaution
Be sure to clean the interior of the connections prior to installation. Use caution not to twist the joint kit while inserting it, and after it is inserted.
An excessive pressure during installation may break the kit. Make sure that the double-headed bolts and the red tags are intact.
If a proper torque is not applied at the connection, it may cause heat during operation.
The number of double-headed
Number of DH bolts 1 2 3 4 6
630, 800, 1000,
1250, 1600, 2000CU
Ampere
(A)AL
2500, 3200,
3600, 40005000 6300 7500
630, 800,
1000, 1250
1600,
2000, 2500-
3200,
3600, 40005000, 6300
Ge
me
ral D
ata
CR-LV/MV LS C&S-Busway System 21
Ⅲ Component
FeederAlthough the standard length of the LS C&S CR-LV Bus Duct feeder is 3 meters, it can be adjusted to the installation
environment, or on request.
[Fig. CL1-3]
B
t
W A
B B
W A
140
2B+140
[Fig. CL1-2] [Fig. CL1-2]
B
3B+280
B
W A
140B 140
Ampere(A)Dimension(mm) Weight(kg/m)
Fig.t W A 3W 4W 4W+50%E 4W+100%E
AL
630
6.35
41 78 21.3 23.7 23.2 23.3
CL1-1
800 65 102 26.7 30.4 29.5 29.6
1000 86 123 32.4 37.8 36.3 36.4
1250 108 145 38.5 42.7 42.7 42.6
1600 164 201 53.5 59.4 59.3 59.4
2000 210 247 65.7 72.9 72.8 71.9
2500 126 163 85.2 99.4 95.1 97.4
3200 164 201 106.3 118 118 118.4
CL1-23600 184 221 116.4 129.7 129.6 130.1
4000 210 247 124.7 138.6 139 139.3
5000 184 221 182.8 193.2 193.4 189.1
6300 210 247 192.6 214.8 215.3 214.4CL1-3
CU
630
6.35
41 78 26.5 30.1 30.9 31.8
800 41 78 26.5 30.1 30.9 31.8
CL1-1
1000 57 94 32.2 37.3 38.9 39.6
1250 73 110 38.3 44.6 46.4 47.7
1600 108 145 51.7 60.4 62.5 64.8
2000 145 182 66.3 77.5 80.2 83.4
2500 195 232 85.7 100.3 104.2 108.4
3200 108 145 104.6 122.9 127.8 131.8
CL1-23600 126 163 118.6 139.5 145 151.4
4000 145 182 134.8 158.3 164.6 170.4
5000 195 232 173.5 203.9 214 220.5
6300 164 201 204.3 241.5 252.3 260CL1-3
7500 195 232 261.2 309 324.1 334.5
* B : 3WGE=90mm, 4WGE/4WHE/4WFE=100mm
22 CR-LV/MV LS C&S-Busway System
06 / 07
Flanged EndThe !anged end is connected to either a transformer or a
panel. Dimension details are shown below.
Ampere(A)Dimension (mm)
Fig.t W A B
AL
630
6.35
41 ~
100
CL2-2800 62 ~
1,000 86 40CL2-3
1,250 108 50
1,600 164 60CL2-5
2,000 210 70
2,500 (2)126 40
130
CL2-4
3,200 (2)164 60
CL2-5
3,600 (2)184 60
4,000 (2)210 70
5,000 (3)184 60
6,300 (3)210 70
CU
630
6.35
41 ~
100
CL2-2800 41 ~
1,000 57 ~
1,250 73 40CL2-3
1,600 108 50
2,000 145 50 CL2-4
2,500 195 70 CL2-5
3,200 (2)108 50
130
CL2-3
3,600 (2)126 40CL2-4
4,000 (2)145 50
5,000 (2)195 70 CL2-5
6,300 (3)164 60 CL2-5
7,500 (3)195 70 CL2-5
[Fig. CL2-1]
[Fig. CL2-2] [Fig. CL2-3] [Fig. CL2-4] [Fig. CL2-5]
Co
mp
on
en
t
CR-LV/MV LS C&S-Busway System 23
Elbow[Vertical] [Horizontal]
O"set[Vertical] [Horizontal]
Ⅲ Component
XY
X
Y
Y
XZ
X
Z
Y
Ampere(A)Dimension(mm)
X Y
1 단 500 500
2 단 500 500
3 단 500 500
Ampere(A)Dimension(mm)
X Y Y
1 단 500 150 500
2 단 500 150 500
3 단 500 150 500
Ampere(A)Dimension(mm)
X Y Z
1 단 500 300 500
2 단 500 300 500
3 단 500 300 500
Ampere(A)Dimension(mm)
X Y
1 단 500 500
2 단 600 600
3 단 700 700
FittingsFittings including the elbow and tee are designed to adapt to any change made to the direction of the bus duct installation.
The same features have been applied to the fittings of the CR-Way, and the size specifications are shown below.
(The standard dimension of each fitting is the same as the dimension shown in the table below. Please contact our design
team for information about the minimum dimension.)
24 CR-LV/MV LS C&S-Busway System
06 / 07
Expansion(optional)
Tee
Combination
[Vertical] [Horizontal]
X
Y
Z
X
Y
Z
Y
Z
X
Ampere(A)Dimension(mm)
X Y Z
1 단 500 300 500
2 단 600 400 600
3 단 700 500 700
Ampere(A)Dimension(mm)
X Y Z
1 단 500 500 500
2 단 500 500 500
3 단 500 500 500
Ampere(A)Dimension(mm)
X Y Z
1 단 500 500 500
Co
mp
on
en
t
CR-LV/MV LS C&S-Busway System 25
Ⅲ Component
Horizontal
Vertical Hangers
Hangers Both horizontal and vertical hangers are available for the CR-LV depending on the installation environment.
The standard horizontal installation method of the CR-LV requires two supports for each product. The standard 3 meter bus ducts are designed to be
installed at 1.5 meters intervals, and the space between the hangers should not surpass 2 meters at the most. (Please contact the design team for further
information.)
For vertical installation of The CR-LV, install the vertical hangers first, and fix the bus ducts on the hangers for better support.
Rigid hanger
Hanger rod
Hanger clamp
Hanger bar
Base
26 CR-LV/MV LS C&S-Busway System
06 / 07
Etc.Wall Flange Floor Opening
• W : The width of the product
• H : The height of the product
• W : The width of the product
• H : The height of the product
The required minimum distances from a wall for heat dissipation and maintenance
W+160
W+60
W+10
W
H+160
H+60
H+10
H
Wall opening sizeCut out
W+60
H+60
W
H
Floor opening sizeCut out
250mm
50mm
50mm
50mm
500mm
BEAM
벽, 천정 벽, 천정 벽
벽벽
접속부
A wall flange is used to seal the gaps produced during
bus duct installation on the walls, ceilings and floors.
The company does not provide glass wool or fire forms.
Co
mp
on
en
t
CR-LV/MV LS C&S-Busway System 27
Ⅳ. Technical Data
The short circuit strength of the CL-LV has been tested as specified in IEC 61439-2, 6 [(previous standard) IEC 60439-1, 2], and certified by KEMA.
Short Circuit Strength
Ampere(A) 630 800 1000 1250 1600 2000 2500 3200 3600 4000 5000 6300 7500
AL1sec 40 40 50 50 50 80 80 80 100 100 100 130 130
3sec 23 23 29 29 29 46 46 46 58 58 58 75 75
CU1sec 40 40 50 50 50 80 80 80 100 100 100 130 -3sec 23 23 29 29 29 46 46 46 58 58 58 75 -
Ampere(A) Impedancex10-3Ω(uΩ/100m,60Hz) Voltage Drop (V/100m)
R X Z 0.7 0.8 0.9 1
AL
630 14.72 7.11 16.34 16.78 17.50 17.83 16.06800 9.78 5.44 11.19 14.87 15.37 15.49 13.55
1000 7.14 4.30 8.34 13.98 14.37 14.38 12.371250 5.76 3.61 6.80 14.32 14.67 14.64 12.471600 3.92 2.57 4.69 12.70 12.98 12.89 10.872000 3.14 2.09 3.77 12.78 13.04 12.95 10.892500 2.68 1.78 3.21 13.60 13.88 13.78 11.583200 2.13 1.40 2.55 13.81 14.10 14.00 11.793600 1.58 1.26 2.03 12.54 12.63 12.32 9.884000 1.39 1.12 1.78 12.26 12.34 12.03 9.625000 1.06 0.87 1.36 11.75 11.81 11.49 9.146300 0.92 0.76 1.20 13.00 13.06 12.70 10.08
CU
630 8.57 7.11 11.14 12.09 12.14 11.80 9.35800 8.57 7.11 11.14 15.35 15.41 14.98 11.87
1000 6.42 5.77 8.63 14.91 14.88 14.36 11.111250 5.09 4.85 7.03 15.21 15.12 14.50 11.021600 3.56 3.61 5.07 14.06 13.90 13.25 9.872000 2.74 2.85 3.96 13.71 13.53 12.86 9.502500 2.12 2.22 3.07 13.30 13.12 12.46 9.183200 1.94 2.03 2.81 15.59 15.38 14.60 10.763600 1.70 1.78 2.46 15.34 15.14 14.38 10.614000 1.51 1.57 2.18 15.08 14.89 14.15 10.465000 0.88 1.20 1.48 12.72 12.30 11.35 7.606300 0.79 1.08 1.34 14.44 13.95 12.87 8.587500 0.58 0.82 1.01 12.91 12.45 11.47 7.59
F F F P P P P Pα(부하 상수)
VdVV = I x 3(R cosθ + X sinθ)
실제 전압 강하 = α x VdVV x x Rated load current
Actual load current
100m
Actual length of the line (m)
α = 1== , concentrated load
(a place such as an electrical room)
α = 0.5== , Distributed load
(a place such as a vertical section)
F : Flanged End (panel connections) P : Plug-in Unit
VdVV = voltage drop[V] I = rated road amperes[A] R = R resistance[Ω] X = X reactance[Ω] / cos = power factor / sim = reactive factor
Technical DataImpedance and Voltage DropThe formula to measure the voltage drop of a busduct is shown below. The impedance and voltage drop values for aluminum and
copper conductors are shown in the table below.
The values listed are measured between the upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
28 CR-LV/MV LS C&S-Busway System
06 / 07
Classication 1 2 3 4 5 6 7 8 9
Censer Location Joint Conductor Exterior of EpoxyAmbient
Temperature
Temperature Rise
Value 69K 62K 65K 63K 52K 51K 44K 50K 21.4
80
70
60
50
40
30
20
10
0 1 2 3 4 5 6 7 8
5
6
7 8
1 2 3 4
Tem
pe
ratu
re(
)
Time(hr)
- Joint -
1
2 3
4
5
6
9
7 8
The temperature rise limit is an important property which determines the performance of bus ducts. The temperature rise limit of the
bus duct is designed so that when a bus duct is operated with a rated current , the temperature limit values of the housing are within
55K as specified in IEC61439-2 and 6 [(previous standard) IEC 60439-1 and 2].
Temperature Rise
Tech
nica
l Da
ta
CR-LV/MV LS C&S-Busway System 29
Ⅴ. Install Information
Before connecting the bus ducts, be sure to align them at the top and the bottom and the
left and the right as well as horizontally and vertically. (This applies for joint connection of
the horizontal and vertical ducts.) Make sure that the joint kit is not tilted. Be sure that the
surface is clear of particles before connecting them.
Check List
• The alignment of the bus ducts.
• The surface of the joint must be clear of dust or particles.
Using a torque wrench, slowly tighten the exposed bolt head of a double head bolt. Connect
the bus ducts temporally first, and check the function of the insulation (100MΩ or higher)
by checking the insulation resistance. Make sure the insulation is working normally before
breaking off the double-head bolt head. The double-head bolt head is designed to break off
at 800~1000Kgf•cm, therefore tighten the exposed head until it breaks off. Once the exposed
head and the red tag attached to it have been cut off, the state of the joint connection should
be visible, which means they are properly connected.
Check List
• Check the connection of the joint: The head of the double-head bolt and the red
tag should be cut off.
Assemble the ducts using a molding flask and rubber packing. Spray plenty of release
agent inside of the molding flask when the assembly is finished.
Check List
• Assembling the molding flask
• Spraying the release agent
• Assorting the vertical type and horizontal type
While assembling the molding flask, be sure to position the rubber packing of the mold-
ing flask at 40 mm from the block end. Make sure there are no gaps between the rubber
packing and the bus ducts.
Check List
• The location of the rubber packing: 40mm from the block end
1
2
3
4
CR – LV (Joint Kit)
30 CR-LV/MV LS C&S-Busway System
06 / 07
Be sure to keep the ambient temperature at 25°C or higher before mixing the epoxy resin and
filler. When mixing the epoxy resin in a cool environment, be sure to cover the mixing container
to keep warm. It is to maintain the temperature of the container at 25°C or higher. In order of
filler, epoxy resin and hardener, add them into the mixing container, and mix it for 15 minutes
using a hand drill. (Please contact our design team for information about how to maintain the
temperature of the container when mixing the epoxy resin in a cool environment.)
Check List
• The ambient temperature: 25° C or higher
• Mix filler, epoxy resin and hardener for 15 minutes
Pour the mixture into the molding flask. Maintain the ambient temperature at 25° C. When
molding in a cool environment, cover the molding flask to keep warm to maintain the
temperature at the molding flask. Remove foams on the surface of the mixture for about
1 hour. Mold only three joints out of a total of four, and continue molding the entire line
following the same procedure. Wait for 8 hours, and check the function of the insulation
by checking the insulation resistance. When it is normal, finish molding the remaining
joint. (Please contact our design team for information about covering the container when
molding the epoxy resin in a cool environment.)
Check List
• Ambient temperature: 25°C or higher
• Removing foams on the surface of the mixture for 1 hour
Remove the mixture form the molding flask, and polish the rough surface with
sandpaper.
Check List
• When to remove the molding flask: 8 hours after the molding
• Polishing the surface with sandpaper
Perform the final inspection to check the performance of the joint.
Check List
• Final inspection of the joint
5
6
7
8
Inta
ll In
form
atio
n
CR-LV/MV LS C&S-Busway System 31