Type:MCS4Article No.:019711Sales textMCS, 1POLE
Variable switching differential
Ordering information
Contacts Number 1 changeover contact
Description Variable switching differential
Max. operating pressure bar 7
Cutin pressure and cutout pressure: separate stepless adjustment. All the intersectionpoints within the diagram area can be set.
1
8/12/2019 Moeller Datasheet MCS4 019711
2/5
Cutin pressure and cutout pressure: separate stepless adjustment. All the intersectionpoints within the diagram area can be set.
Min. switching differential: 0.15 bar
Example:
Cutout pressure 3.3 bar
Cutin pressure 2.2 bar
Notes concerning the product group
Features:
Pressure pipe flange R 1/4If required: pressure pipe flange R 1/2IP65 in conjunction with VM20 cable gland1 insulated earth terminal2 cable entry knockouts for M20Neoprene diaphragm
2
8/12/2019 Moeller Datasheet MCS4 019711
3/5
Cutin and cutout pressures are factorypreset as specified with type suffix: 203948
R 1/4 corresponds to G 1/4
R 1/2 corresponds to G 1/2 according to ISO 2281
Auxilliary contacts to IEC/EN 609471
MCS...G:
Goldplated contacts, particularly suitable for switching low voltages and currents from 5 V AC/DC 1mA.
General
Standards IEC/EN 6094751
Test pressure bar 32
Rupturing pressure bar 90
Operating frequency Operations/h 3000
Climatic proofing
Damp heat, constant, toIEC 60068278Damp heat, cyclic, to IEC60068230
Ambient temperature C ... 25...+70
Protection type IP 65
Mounting position As required
Mechanical shock resistance to IEC60068227
Halfsinusoidalshock 20 ms
g > 10
Vibration resistance acc. to IEC/EN6006826
Amplitude 1mm
Hz 36
Lifespan at 50 12% pressuredifferential
Operations 106 1 2
Terminal capacities
Solid mm2 1 (0.75 2.5)
Flexible with ferrules to DIN 46228 mm2 1 (0.5 1.5)
Terminations Tunnel terminal
Terminal screw M3
Tightening torque of terminal screw Nm 0.5
Contacts/switching capacity
Rated impulse withstand voltage Uimp V AC 4000
Rated insulation voltage Ui V 400
Overvoltage category/pollutiondegree
III/3
Max. shortcircuit protective device
Fuseless Type PKZ2/ZM6
3
http://gotobest%28%27203948%27%29/8/12/2019 Moeller Datasheet MCS4 019711
4/5
Fuse gG/gL A 10
AC15
Rated operational current
230 V A 2
DC13
Rated operational current
24 V A 2
110 V A 0,5
Rated frequency f Hz 50
Notes
Notes
The following applies to the rated operational current for DC13:
with 24 V: ...SOND910G: 0.25 Awith 110 V: ...SOND910G: 0.8 A
Dimensions
Moeller GmbH, HeinMoellerStr. 711, D53115 BonnEMail: [email protected], Internet: www.moeller.net, http://catalog.moeller.net
4
8/12/2019 Moeller Datasheet MCS4 019711
5/5
HPLC2007G V2.1 2007 by Moeller GmbH
5