Site Preparation and Specifications: IBM PureData System for AnalyticsModel N200X

Revised: March 7, 2014

D27700-2 Rev. 7.0

Page 2: Netezza Site Prep Specs n200x

Note: Before using this information and the product that it supports, read the information in “Notices and Trademarks” on page B-1.

© Copyright IBM Corporation 2001-2014.US Government Users Restricted Rights – Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.

Page 3: Netezza Site Prep Specs n200x

Contents

Preface

1 IBM PureData System for Analytics N200X ModelsModel N2002-002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

Model N2002-005 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

Model N2002-010 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3

Model N2002-020 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4

Model N2002-040 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5

2 Model N2002-002 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2

Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3

Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3

Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4

3 Model N2002-005 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1

Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2

Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3

Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3

Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

4 Model N2002-010 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1

Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2

Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3

Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3

Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4

5 Model N2002-020 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1

Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2

Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3

Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3

Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4

iii

Page 4: Netezza Site Prep Specs n200x

6 Model N2002-040 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1

Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2

Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3

Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3

Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4

Appendix A: Model Comparison

Appendix B: Notices and TrademarksNotices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

Trademarks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3

Electronic Emission Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4

Regulatory and Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7

iv

Page 5: Netezza Site Prep Specs n200x

Tables

Table 2-1: Model N2002-002 Electrical Requirements . . . . . . . . . . . . . . . . . . . 2-1

Table 2-2: Model N2002-002 Space Requirements . . . . . . . . . . . . . . . . . . . . . 2-2

Table 2-3: Model N2002-002 Operating Environment. . . . . . . . . . . . . . . . . . . . 2-3

Table 2-4: Model N2002-002 Floor Loading Requirements . . . . . . . . . . . . . . . . 2-3

Table 2-5: IBM x3650 M4 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 2-4

Table 3-1: Model N2002-005 Electrical Requirements . . . . . . . . . . . . . . . . . . . 3-1

Table 3-2: Model N2002-005 Space Requirements . . . . . . . . . . . . . . . . . . . . . 3-2

Table 3-3: Model N2002-005 Operating Environment. . . . . . . . . . . . . . . . . . . . 3-3

Table 3-4: Model N2002-005 Floor Loading Requirements . . . . . . . . . . . . . . . . 3-3

Table 3-5: IBM x3650 M4 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 3-4

Table 4-1: Model N2002-010 Electrical Requirements . . . . . . . . . . . . . . . . . . . 4-1

Table 4-2: Model N2002-010 Space Requirements . . . . . . . . . . . . . . . . . . . . . 4-2

Table 4-3: Model N2002-010 Operating Environment. . . . . . . . . . . . . . . . . . . . 4-3

Table 4-4: Model N2002-010 Floor Loading Requirements . . . . . . . . . . . . . . . . 4-3

Table 4-5: IBM x3750 M4 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 4-4

Table 5-1: Model N2002-020 Electrical Requirements . . . . . . . . . . . . . . . . . . . 5-1

Table 5-2: Model N2002-020 Space Requirements . . . . . . . . . . . . . . . . . . . . . 5-2

Table 5-3: Model N2002-020 Operating Environment. . . . . . . . . . . . . . . . . . . . 5-3

Table 5-4: Model N2002-020 Floor Loading Requirements . . . . . . . . . . . . . . . . 5-3

Table 5-5: IBM x3750 M4 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 5-4

Table 6-1: Model N2002-040 Electrical Requirements . . . . . . . . . . . . . . . . . . . 6-1

Table 6-2: Model N2002-040 Space Requirements . . . . . . . . . . . . . . . . . . . . . 6-2

Table 6-3: Model N2002-040 Operating Environment. . . . . . . . . . . . . . . . . . . . 6-3

Table 6-4: Model N2002-040 Floor Loading Requirements . . . . . . . . . . . . . . . . 6-3

Table 6-5: IBM x3750 M4 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 6-4

Table A-1: Model Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1

v

Page 6: Netezza Site Prep Specs n200x

vi

Page 7: Netezza Site Prep Specs n200x

Figures

Figure 1-1: Model N2002-002 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

Figure 1-2: Model N2002-005 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

Figure 1-3: Model N2002-010 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3

Figure 1-4: Model N2002-020 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4

Figure 1-5: Model N2002-040 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5

Figure 2-1: Space Requirements for a Model N2002-002 . . . . . . . . . . . . . . . . . 2-2

Figure 3-1: Space Requirements for a Model N2002-005 . . . . . . . . . . . . . . . . . 3-2

Figure 4-1: Space Requirements for a Model N2002-010 . . . . . . . . . . . . . . . . . 4-2

Figure 5-1: Space Requirements for a Model N2002-020 . . . . . . . . . . . . . . . . . 5-2

Figure 6-1: Space Requirements for a Model N2002-040 . . . . . . . . . . . . . . . . . 6-2

vii

Page 8: Netezza Site Prep Specs n200x

viii

Page 9: Netezza Site Prep Specs n200x

PrefaceThe IBM PureData System for Analytics Model N200X is a high-performance, integrated data warehouse appliance that provides unparalleled performance, extensive scaling, high reliability, and ease of use. The system uses a unique architecture that combines current trends in processor, network, and software technologies to deliver a very high-performance system for large enterprise customers.

About This Guide

Site Preparation and Specifications: IBM PureData System for Analytics Model N200X is written for those who need to understand the site requirements and specifications of each IBM PureData System for Analytics Model N200X. This guide assumes that you understand the capabilities and capacities of the physical space in which you are installing a IBM PureData System for Analytics Model N200X system.

The guide describes the hardware components that make up the system, and discusses the following:

Preparing a physical location.

Maintaining a location.

Various IBM PureData System for Analytics Model N200X variants.

Hardware specifications.

Included in This Guide

This guide is designed to be used before and during installation of the IBM PureData Sys-tem for Analytics Model N200X system. It contains important information on preparing and maintaining your site. It specifically covers the following topics:

Chapter 1, “IBM PureData System for Analytics N200X Models” — Lists the different system models and describes the location of the major components within the system.

Chapter 2, “Model N2002-002 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM PureData System for Analytics Model N2002-002 system.

Chapter 3, “Model N2002-005 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM PureData System for Analytics Model N2002-005 system.

Chapter 4, “Model N2002-010 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM PureData System for Analytics Model N2002-010 system.

Chapter 5, “Model N2002-020 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM PureData System for Analytics Model N2002-020 system.

ix

Page 10: Netezza Site Prep Specs n200x

Chapter 6, “Model N2002-040 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM PureData System for Analytics Model N2002-040 system.

Appendix A, “Model Comparison” — Provides a model comparison of the systems in the current IBM PureData System for Analytics Model N2002 product line.

Symbols and Conventions

This guide uses the following typographical conventions:

Numbered steps for procedures

Single-step procedures are preceded by the q symbol

Bulleted lists for topics

Italics for terms, and user-defined variables such as filenames

Abbreviations

This guide uses the following abbreviations throughout:

Abbreviation Description

A ampere

ACID Atomicity, Consistency, Isolation, and Durability

GB Gigabyte

HTTP HyperText Transport Protocol

Hz Hertz

in. Inch

kg Kilogram

KVA Kilo Volt-Amps

KVM Keyboard-Video-Mouse

lb Pound

m meter

Mb Megabit

MB Megabyte

ms Milliseconds

MSFI Mustang Snippet Fabric Interface

x

Page 11: Netezza Site Prep Specs n200x

If You Need Help

If you are having trouble using the IBM PureData for Analytics appliance, you should:

1. Retry the action, carefully following the instructions given for that task in the documentation.

2. Go to the IBM Support Portal at: http://www.ibm.com/support. Log in using your IBM ID and password. You can search the Support Portal for solutions. To submit a support request, click the Service Requests & PMRs tab.

3. If you have an active service contract maintenance agreement with IBM, you can con-tact customer support teams via telephone. For individual countries, visit the Technical Support section of the IBM Directory of worldwide contacts (http://www14.soft-ware.ibm.com/webapp/set2/sas/f/handbook/contacts.html#phone).

MSPU Mustang Snippet Processing Unit

NIC Network Interface Card

NPS system Netezza Performance Server system

PCI Peripheral Component Interconnect

PCIe PCI Express

PCIx PCI eXtended

PDU Power Distribution Unit

RAID Redundant Array of Independent Disks

RPC Remote Power Controller

SAS Serial Attached SCSI

SATA Serial Advanced Technology Attachment

SCSI Small Computer System Interface

SFI Snippet Fabric Interface

SNMP Simple Network Management Protocol

SPA Snippet Processing Array

SPU Snippet Processing Unit

TB Terabyte

VAC Volts Alternating Current

Abbreviation Description

xi

Page 12: Netezza Site Prep Specs n200x

Comments on the Documentation

We welcome any questions, comments, or suggestions that you have for the IBM Netezza documentation. Please send us an e-mail message at [email protected] and include the following information:

The name and version of the manual that you are using

Any comments that you have about the manual

Your name, address, and phone number

We appreciate your comments on the documentation.

xii

Page 13: Netezza Site Prep Specs n200x

C H A P T E R 1

IBM PureData System for Analytics N200X Models

This chapter contains the following information:

A description of each system, including the number of racks, S-Blades, and SPAs in the system

An illustration of each system showing the placement of components within each rack.

Model N2002-002

The Model N2002-002 is a single-rack system containing 2 S-Blades housed in 1 SPA.

Note: The racks are bolted together into a single unit and cannot be separated.

Figure 1-1 shows a Model N2002-002 system.

Note: The switches are only visible from the rear of the rack.

Figure 1-1: Model N2002-002 (front view)

1-1

Page 14: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Model N2002-005

The Model N2002-005 is a single-rack system containing 4 S-Blades housed in 1 SPA.

Note: The racks are bolted together into a single unit and cannot be separated.

Figure 1-2 shows a Model N2002-005 system.

Note: The switches are only visible from the rear of the rack.

Figure 1-2: Model N2002-005 (front view)

1-2 D27700-2 Rev.7.0

Page 15: Netezza Site Prep Specs n200x

Model N2002-010

Model N2002-010

The Model N2002-010 is a single-rack system containing 7 S-Blades housed in 1 SPA.

Note: The racks are bolted together into a single unit and cannot be separated.

Figure 1-3 shows a Model N2002-010 system.

Note: The switches are only visible from the rear of the rack.

Figure 1-3: Model N2002-010 (front view)

D27700-2 Rev.7.0 1-3

Page 16: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Model N2002-020

The Model N2002-020 is a two-rack system containing 14 S-Blades housed in 2 SPAs.

Note: The racks are bolted together into a single unit and cannot be separated.

Figure 1-4 shows a Model N2002-020 system.

Note: The switches are only visible from the rear of the rack.

Figure 1-4: Model N2002-020 (front view)

1-4 D27700-2 Rev.7.0

Page 17: Netezza Site Prep Specs n200x

Model N2002-040

Model N2002-040

The Model N2002-040 is a four-rack system containing 28 S-Blades housed in 4 SPAs.

Note: The racks are bolted together into a single unit and cannot be separated.

Figure 1-5 shows a Model N2002-040 system.

Note: The switches are only visible from the rear of the rack.

Figure 1-5: Model N2002-040 (front view)

D27700-2 Rev.7.0 1-5

Page 18: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

1-6 D27700-2 Rev.7.0

Page 19: Netezza Site Prep Specs n200x

C H A P T E R 2

Model N2002-002 Specifications

This chapter explains the following requirements for the Model N2002-002 system:

Electrical power requirements

Space requirements

Environmental requirements

Floor loading requirements

Electrical Power Requirements

Each Model N2002-002 system requires two separately protected power circuits. The power requirements for each circuit are listed in Table 2-1.

Note: IBM recommends that the power supplied to the rack be uninterruptible.

Table 2-1: Model N2002-002 Electrical Requirements

Specification

Single Phase

EU NA

Circuits 2 2

Total Plugs (Drops) 2 2

Voltage 200-240 VAC, 50Hz/60 Hz 200-240 VAC, 50Hz/60 Hz

Circuit Breaker Rating 30 - 32A

Connector IEC 309 32A P+N+GHubbell 332C6 or similar

NEMA L6-30C 2P+G

Maximum Power 3,200 W 3,200 W

Power/Area 420 W/ft2

(4,522 W/m2)420 W/ft2

(4,522 W/m2)

2-1

Page 20: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Space requirements

Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.

IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to allow unrestricted access for service.

Note: The Model N2002-002 system is housed in a rack that is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.

A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.

Figure 2-1 shows the space requirements for each rack.

Figure 2-1: Space Requirements for a Model N2002-002

The total space requirements for the Model N2002-002 system are listed in Table 2-2.

Table 2-2: Model N2002-002 Space Requirements

Physical Including Clearance

Footprint (WxD) 25.5 in. by 43 in.(64.8 cm x 109.2 cm)

25.5 in. by 130 in.(64.8 cm x 330.2 cm)

25.5 in(64.8 cm)

30 in(76 cm)

40 in(101.6 cm)

60 in(152 cm)

between rowsrecommended

36 in91.5 cm)

2-2 D27700-2 Rev.7.0

Page 21: Netezza Site Prep Specs n200x

Environmental Requirements

Environmental Requirements

The Model N2002-002 system is designed to operate within the following temperature, humidity, and altitude ranges:

Floor Loading Requirements

The floor that supports the Model N2002-002 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).

Table 2-3: Model N2002-002 Operating Environment

Operating Non-operating

Temperature 10°C to 35°C (50°F to 95°F)

-15°C to 45°C (5°F to 113°F)

Altitude 0 to 3,048 m (0 to 10,000 ft)

0 to 9,144 m (0 to 30,000 ft)

Humidity 20% to 80% non-condensing 10% to 90% non-condensing

Cooling 10,850 BTU/hr —

Air Changes The IBM PureData System for Analytics N200X appliance requires adequate ventilation during the first 120 days of continuous opera-tion. Adequate ventilation of an appliance is met with an average roomsize of 65 cubic meters and an average room intake make-up air rate of 0.4 air changes per hour. The room size can be met by allowing a 3.5 meter clearance on each side of the system for a solid floor installation or a 3.1 meter clearance on each side of the system for a raised floor installation.

Table 2-4: Model N2002-002 Floor Loading Requirements

Specification Value

Maximum Weight 1,400 lb (636.4 kg)

Maximum Weight/Area 183.9 lb/ft2 (899.4 kg/m2)

D27700-2 Rev.7.0 2-3

Page 22: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Host Server Specifications

Table 2-5: IBM x3650 M4 Host Specifications

Feature Number Description

Processors two Six-core Intel Xeon 2.5 GHz, 15MB L2 1333MHz 95w

Memory — 64 GB, PC3L-10600 (DDR3) SDRAM

Power supplies two 750W, Redundant, hot-pluggable

Fans four N+1 Redundant, hot-pluggable

Ethernet ports(1 Gigabit)

four ports (one available)

Four - 1 Gigabit ethernet ports (embedded)

Ethernet ports(10 Gigabit)

six ports(two available)

Two - embedded 10 Gigabit portsTwo - Dual Port PCIe 10 Gigabit Adapters

IMM port two Integrated Management Module one - dedicated NIC (10/100 Mbone - shared on port LOM 1

FibreChannel ports two(two available)

One - Dual Port FibreChannel Adapter

300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration

PCI slots six(three available)

Six - PCI-Express x8 (one full length, one half length, one low profile are available)

USB 2.0 ports six(five available)

Two front, four rear

Serial port one

DVD-ROM/CD-RW one 8X / 24X max

Form Factor 2U (3.5”) rack-mountable

Management IMM2

2-4 D27700-2 Rev.7.0

Page 23: Netezza Site Prep Specs n200x

C H A P T E R 3

Model N2002-005 Specifications

This chapter explains the following requirements for the Model N2002-005 system:

Electrical power requirements

Space requirements

Environmental requirements

Floor loading requirements

Electrical Power Requirements

Each Model N2002-005 system requires two separately protected power circuits. The power requirements for each circuit are listed in Table 3-1.

Note: IBM recommends that the power supplied to the rack be uninterruptible.

Table 3-1: Model N2002-005 Electrical Requirements

Specification

Single Phase

EU NA

Circuits 2 2

Total Plugs (Drops) 2 2

Voltage 200-240 VAC, 50Hz/60 Hz 200-240 VAC, 50Hz/60 Hz

Circuit Breaker Rating 30 to 32A 30A

Connector IEC 309 32A P+N+GHubbell 332C6 or similar

NEMA L6-30C 2P+G

Maximum Power 4,200 W 4,200 W

Power/Area 552 W/ft2

(5,935 W/m2)552 W/ft2

(5,935 W/m2)

3-1

Page 24: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Space requirements

Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.

IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to allow unrestricted access for service.

Note: The Model N2002-005 system is housed in a rack that is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.

A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.

Figure 3-1 shows the space requirements for each rack.

Figure 3-1: Space Requirements for a Model N2002-005

The total space requirements for the Model N2002-005 system are listed in Table 3-2.

Table 3-2: Model N2002-005 Space Requirements

Physical Including Clearance

Footprint (WxD) 25.5 in. by 43 in.(64.8 cm x 109.2 cm)

25.5 in. by 130 in.(64.8 cm x 330.2 cm)

25.5 in(64.8 cm)

30 in(76 cm)

40 in(101.6 cm)

60 in(152 cm)

between rowsrecommended

36 in91.5 cm)

3-2 D27700-2 Rev.7.0

Page 25: Netezza Site Prep Specs n200x

Environmental Requirements

Environmental Requirements

The Model N2002-005 system is designed to operate within the following temperature, humidity, and altitude ranges:

Floor Loading Requirements

The floor that supports the Model N2002-005 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).

Table 3-3: Model N2002-005 Operating Environment

Operating Non-operating

Temperature 10°C to 35°C (50°F to 95°F)

-15°C to 45°C (5°F to 113°F)

Altitude 0 to 3,048 m (0 to 10,000 ft)

0 to 9,144 m (0 to 30,000 ft)

Humidity 20% to 80% non-condensing 10% to 90% non-condensing

Cooling 15,500 BTU/hr —

Air Changes The IBM PureData System for Analytics N2001 appliance requires adequate ventilation during the first 120 days of continuous opera-tion. Adequate ventilation of an appliance is met with an average roomsize of 65 cubic meters and an average room intake make-up air rate of 0.4 air changes per hour. The room size can be met by allowing a 3.5 meter clearance on each side of the system for a solid floor installation or a 3.1 meter clearance on each side of the system for a raised floor installation.

Table 3-4: Model N2002-005 Floor Loading Requirements

Specification Value

Maximum Weight 1,700 lb (771.1 kg)

Maximum Weight/Area 223.3 lb/ft2 (1,089.7 kg/m2)

D27700-2 Rev.7.0 3-3

Page 26: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Host Server Specifications

Table 3-5: IBM x3650 M4 Host Specifications

Feature Number Description

Processors two Six-core Intel Xeon 2.5 GHz, 15MB L2 1333MHz 95w

Memory — 64 GB, PC3L-10600 (DDR3) SDRAM

Power supplies two 750W, Redundant, hot-pluggable

Fans four N+1 Redundant, hot-pluggable

Ethernet ports(1 Gigabit)

four ports (one available)

Four - 1 Gigabit ethernet ports (embedded)

Ethernet ports(10 Gigabit)

six ports(two available)

Two - embedded 10 Gigabit portsTwo - Dual Port PCIe 10 Gigabit Adapters

IMM port two Integrated Management Module one - dedicated NIC (10/100 Mbone - shared on port LOM 1

FibreChannel ports two(two available)

One - Dual Port FibreChannel Adapter

300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration

PCI slots six(three available)

Six - PCI-Express x8 (one full length, one half length, one low profile are available)

USB 2.0 ports six(five available)

Two front, four rear

Serial port one

DVD-ROM/CD-RW one 8X / 24X max

Form Factor 2U (3.5”) rack-mountable

Management IMM2

3-4 D27700-2 Rev.7.0

Page 27: Netezza Site Prep Specs n200x

C H A P T E R 4

Model N2002-010 Specifications

This chapter explains the following requirements for the Model N2002-010 system:

Electrical power requirements

Space requirements

Environmental requirements

Floor loading requirements

Electrical Power Requirements

Each Model N2002-010 system requires two separately protected power circuits. The power requirements for each circuit are listed in Table 4-1.

Note: IBM recommends that the power supplied to the rack be uninterruptible.

Table 4-1: Model N2002-010 Electrical Requirements

Specification

3-Phase Wye 3-Phase Delta Single Phase

EU NA NA EU NA

Circuits 2

Total Plugs (Drops) 2

Voltage 200-240/380-415 VAC, 50 Hz/60 Hz

200-208 VAC, 50 Hz/60 Hz

200-240 VAC, 50 Hz/60 Hz

Circuit Breaker Rating

16 to 32A 20 to 32A 30A 60 to 63A 60A

Connector IEC 309 32A3P+N+G

Hubbell C532C6W

IEC 309 60A 3P4WMennekes 460C9W

(3P+Earth)

IEC 309 63A P+N+G

Hubbell 363C6W

IEC 309 63A2P+G

Hubbell 360C6W

Maximum Power 7,500 W

Power/Area 985 W/ft2

(10,600 W/m2)

4-1

Page 28: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Space requirements

Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.

IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to allow unrestricted access for service.

Note: The Model N2002-010 system is housed in a rack that is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.

A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.

Figure 4-1 shows the space requirements for each rack.

Figure 4-1: Space Requirements for a Model N2002-010

The total space requirements for the Model N2002-010 system are listed in Table 4-2.

Table 4-2: Model N2002-010 Space Requirements

Physical Including Clearance

Footprint (WxD) 25.5 in. by 43 in.(64.8 cm x 109.2 cm)

25.5 in. by 130 in.(64.8 cm x 330.2 cm)

25.5 in(64.8 cm)

30 in(76 cm)

40 in(101.6 cm)

60 in(152 cm)

between rowsrecommended

36 in91.5 cm)

4-2 D27700-2 Rev.7.0

Page 29: Netezza Site Prep Specs n200x

Environmental Requirements

Environmental Requirements

The Model N2002-010 system is designed to operate within the following temperature, humidity, and altitude ranges:

Floor Loading Requirements

The floor that supports the Model N2002-010 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).

Table 4-3: Model N2002-010 Operating Environment

Operating Non-operating

Temperature 10°C to 35°C (50°F to 95°F)

-15°C to 45°C (5°F to 113°F)

Altitude 0 to 3,048 m (0 to 10,000 ft)

0 to 9,144 m (0 to 30,000 ft)

Humidity 20% to 80% non-condensing 10% to 90% non-condensing

Cooling 27,000 BTU/hr —

Air Changes The IBM PureData System for Analytics N200X appliance requires adequate ventilation during the first 120 days of continuous opera-tion. Adequate ventilation of an appliance is met with an average roomsize of 65 cubic meters and an average room intake make-up air rate of 0.4 air changes per hour. The room size can be met by allowing a 3.5 meter clearance on each side of the system for a solid floor installation or a 3.1 meter clearance on each side of the system for a raised floor installation.

Table 4-4: Model N2002-010 Floor Loading Requirements

Specification Value

Maximum Weight 2,000 lb(907.2 kg)

Maximum Weight/Area 262.7 lb/ft2

(1,282.6 kg/m2)

D27700-2 Rev.7.0 4-3

Page 30: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Host Server Specifications

Table 4-5: IBM x3750 M4 Host Specifications

Feature Number Description

Processors four Six-core Intel Xeon 2.7 GHz, 20MB L2 1600MHz 130w

Memory — 128 GB, PC3L-10600 (DDR3) SDRAM

Power supplies two 1400W, Redundant, hot-pluggable

Fans three N+1 Redundant, hot-pluggable

NIC - 1Gb six ports(four available)

One - 4-port 1Gb NICTwo - onboard 1Gb ports

NIC - 10Gb eight ports(two available)

Three - 2-port 10Gb NICsOne - mezzanine 2-port NIC

Fibre Channel- 8Gb two ports(two available)

One - 2-port 8Gb Fibre Channel card

IMM port one Integrated Management Module dedicated NIC (10/100 Mb)

300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration

PCI slots eight(three available)

Eight - PCI-Express x8 (three full height/half length, five low pro-file/half length)

USB 2.0 ports six Two front, two rear, two internal

Serial port one

DVD-ROM/CD-RW one 8X / 24X max

Form Factor 2U (3.5”) rack-mountable

Management IMM

4-4 D27700-2 Rev.7.0

Page 31: Netezza Site Prep Specs n200x

C H A P T E R 5

Model N2002-020 Specifications

This chapter explains the following requirements for the Model N2002-020 system:

Electrical power requirements

Space requirements

Environmental requirements

Floor loading requirements

Electrical Power Requirements

Each system requires two separately protected power circuits, with two power drops for each rack. The power requirements for each circuit are listed in Table 5-1.

Note: IBM recommends that the power supplied to the rack be uninterruptible.

Table 5-1: Model N2002-020 Electrical Requirements

Specification

3-Phase Wye 3-Phase Delta Single Phase

EU NA NA EU NA

Circuits 2

Total Plugs (Drops) 4

Voltage 200-240/380-415 VAC, 50 Hz/60 Hz

200-208 VAC, 50 Hz/60 Hz

200-240 VAC, 50 Hz/60 Hz

Circuit Breaker Rating

16 to 32A 20 to 32A 30A 60 to 63A 60A

Connector IEC 309 32A3P+N+G

Hubbell C532C6W

IEC 309 60A 3P4WMennekes 460C9W

(3P+Earth)

IEC 309 63A P+N+G

Hubbell 363C6W

IEC 309 63A2P+G

Hubbell 360C6W

Maximum Power 15,000 W

Power/Area 985 W/ft2

(10,600 W/m2)

5-1

Page 32: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Space requirements

The Model N2002-020 consists of two racks. The racks are bolted together into a group of racks called a pod. In this system there is a single pod of two racks.

Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.

IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to allow unrestricted access for service.

Note: Each rack in the Model N2002-020 system is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.

A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.

Figure 5-1 shows the space requirements for the pod.

Figure 5-1: Space Requirements for a Model N2002-020

The space requirements for a Model N2002-020 are listed in Table 5-2.

Table 5-2: Model N2002-020 Space Requirements

Number of RacksFootprint

Physical Including Clearance

2 51 in. by 43 in.(128.6 cm x 109.2 cm)

51 in. by 130 in.(128.6 cm x 330.2 cm)

51.0 in(129.6 cm)

30 in(76 cm)

40 in(101.6 cm)

60 in(152 cm)

between rowsrecommended

36 in91.5 cm)

5-2 D27700-2 Rev.7.0

Page 33: Netezza Site Prep Specs n200x

Environmental Requirements

Environmental Requirements

The Model N2002-020 system is designed to operate within the following temperature, humidity, and altitude ranges:

Floor Loading Requirements

The floor that supports the Model N2002-020 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).

Table 5-3: Model N2002-020 Operating Environment

Operating Non-operating

Temperature 10°C to 35°C (50°F to 95°F)

-15°C to 45°C (5°F to 113°F)

Altitude 0 to 3,048 m (0 to 10,000 ft)

0 to 9,144 m (0 to 30,000 ft)

Humidity 20% to 80% non-condensing 10% to 90% non-condensing

Cooling 54,000 BTU/hr —

Air Changes The IBM PureData System for Analytics N200X appliance requires adequate ventilation during the first 120 days of continuous opera-tion. Adequate ventilation of an appliance is met with an average roomsize of 65 cubic meters and an average room intake make-up air rate of 0.4 air changes per hour. The room size can be met by allowing a 3.5 meter clearance on each side of the system for a solid floor installation or a 3.1 meter clearance on each side of the system for a raised floor installation.

Table 5-4: Model N2002-020 Floor Loading Requirements

Specification 2-Rack Pod

Maximum Weight 4,000 lb (1814.4 kg)

Maximum Weight/Area 262.7 lb/ft2 (1,282.6 kg/m2)

D27700-2 Rev.7.0 5-3

Page 34: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Host Server Specifications

Table 5-5: IBM x3750 M4 Host Specifications

Feature Number Description

Processors four Six-core Intel Xeon 2.7 GHz, 20MB L2 1600MHz 130w

Memory — 128 GB, PC3L-10600 (DDR3) SDRAM

Power supplies two 1400W, Redundant, hot-pluggable

Fans three N+1 Redundant, hot-pluggable

NIC - 1Gb six ports(four available)

One - 4-port 1Gb NICTwo - onboard 1Gb ports

NIC - 10Gb eight ports(two available)

Three - 2-port 10Gb NICsOne - mezzanine 2-port NIC

Fibre Channel- 8Gb two ports(two available)

One - 2-port 8Gb Fibre Channel card

IMM port one Integrated Management Module dedicated NIC (10/100 Mb)

300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration

PCI slots eight(three available)

Eight - PCI-Express x8 (three full height/half length, five low pro-file/half length)

USB 2.0 ports six Two front, two rear, two internal

Serial port one

DVD-ROM/CD-RW one 8X / 24X max

Form Factor 2U (3.5”) rack-mountable

Management IMM

5-4 D27700-2 Rev.7.0

Page 35: Netezza Site Prep Specs n200x

C H A P T E R 6

Model N2002-040 Specifications

This chapter explains the following requirements for the Model N2002-040 system:

Electrical power requirements

Space requirements

Environmental requirements

Floor loading requirements

Electrical Power Requirements

Each system requires two separately protected power circuits, with two power drops for each rack. The power requirements for each circuit are listed in Table 6-1.

Note: IBM recommends that the power supplied to the rack be uninterruptible.

Table 6-1: Model N2002-040 Electrical Requirements

Specification

3-Phase Wye 3-Phase Delta Single Phase

EU NA NA EU NA

Circuits 2

Total Plugs (Drops) 8

Voltage 200-240/380-415 VAC, 50 Hz/60 Hz

200-208 VAC, 50 Hz/60 Hz

200-240 VAC, 50 Hz/60 Hz

Circuit Breaker Rating

16 to 32A 20 to 32A 30A 60 to 63A 60A

Connector IEC 309 32A3P+N+G

Hubbell C532C6W

IEC 309 60A 3P4WMennekes 460C9W

(3P+Earth)

IEC 309 63A P+N+G

Hubbell 363C6W

IEC 309 63A2P+G

Hubbell 360C6W

Maximum Power 30,000 W

Power/Area 985 W/ft2

(10,600 W/m2)

6-1

Page 36: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Space requirements

The Model N2002-040 consists of four racks. The racks are bolted together into a group of racks called a pod. In this system there is a single pod of four racks.

Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 36 in. (91.5 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.

IBM recommends an extended service clearance of 60 in. (152 cm) in front of the rack to allow unrestricted access for service.

Note: Each rack in the Model N2002-040 system is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.

A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.

Figure 6-1 shows the space requirements for the Pod.

Figure 6-1: Space Requirements for a Model N2002-040

The space requirements for a Model N2002-040 are listed in Table 6-2.

Table 6-2: Model N2002-040 Space Requirements

Number of RacksFootprint

Physical Including Clearance

4 102 in. by 43 in.(259.2 cm x 109.2 cm)

102 in. by 130 in.(259.2 cm x 330.2 cm)

102.0 in(259.2 cm)

30 in(76 cm)

40 in(101.6 cm)

60 in(152 cm)

between rowsrecommended

36 in91.5 cm)

6-2 D27700-2 Rev.7.0

Page 37: Netezza Site Prep Specs n200x

Environmental Requirements

Environmental Requirements

The Model N2002-040 system is designed to operate within the following temperature, humidity, and altitude ranges:

Floor Loading Requirements

The floor that supports the Model N2002-040 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).

Table 6-3: Model N2002-040 Operating Environment

Operating Non-operating

Temperature 10°C to 35°C (50°F to 95°F)

-15°C to 45°C (5°F to 113°F)

Altitude 0 to 3,048 m (0 to 10,000 ft)

0 to 9,144 m (0 to 30,000 ft)

Humidity 20% to 80% non-condensing 10% to 90% non-condensing

Cooling 108,000 BTU/hr —

Air Changes The IBM PureData System for Analytics N200X appliance requires adequate ventilation during the first 120 days of continuous opera-tion. Adequate ventilation of an appliance is met with an average roomsize of 65 cubic meters and an average room intake make-up air rate of 0.4 air changes per hour. The room size can be met by allowing a 3.5 meter clearance on each side of the system for a solid floor installation or a 3.1 meter clearance on each side of the system for a raised floor installation.

Table 6-4: Model N2002-040 Floor Loading Requirements

Specification 4-Rack Pod

Maximum Weight 8,000 lb (3628.8 kg)

Maximum Weight/Area 262.7 lb/ft2 (1,282.6 kg/m2)

D27700-2 Rev.7.0 6-3

Page 38: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Host Server Specifications

Table 6-5: IBM x3750 M4 Host Specifications

Feature Number Description

Processors four Six-core Intel Xeon 2.7 GHz, 20MB L2 1600MHz 130w

Memory — 128 GB, PC3L-10600 (DDR3) SDRAM

Power supplies two 1400W, Redundant, hot-pluggable

Fans three N+1 Redundant, hot-pluggable

NIC - 1Gb six ports(four available)

One - 4-port 1Gb NICTwo - onboard 1Gb ports

NIC - 10Gb eight ports(two available)

Three - 2-port 10Gb NICsOne - mezzanine 2-port NIC

Fibre Channel- 8Gb two ports(two available)

One - 2-port 8Gb Fibre Channel card

IMM port one Integrated Management Module dedicated NIC (10/100 Mb)

300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration

PCI slots eight(three available)

Eight - PCI-Express x8 (three full height/half length, five low pro-file/half length)

USB 2.0 ports six Two front, two rear, two internal

Serial port one

DVD-ROM/CD-RW one 8X / 24X max

Form Factor 2U (3.5”) rack-mountable

Management IMM

6-4 D27700-2 Rev.7.0

Page 39: Netezza Site Prep Specs n200x

A P P E N D I X A

Model Comparison

Table A-1 provides a comparison between the available models of the IBM PureData Sys-tem for Analytics Model N200X.

Table A-1: Model Comparison

SystemUser Data Host

ProcessorsS-Blades Racks

High Availability

no compression 4x compression

Model N2002-002 8 TB 32 TB 2 2 1 Yes

Model N2002-005 24 TB 96 TB 2 4 1 Yes

Model N2002-010 48 TB 192 TB 4 7 1 Yes

Model N2002-020 96 TB 384 TB 4 14 2 Yes

Model N2002-040 192 TB 768 TB 4 28 4 Yes

A-1

Page 40: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

A-2 D27700-2 Rev.7.0

Page 41: Netezza Site Prep Specs n200x

A P P E N D I X B

Notices and Trademarks

What’s in this appendix Notices

Trademarks

Electronic Emission Notices

Regulatory and Compliance

This section describes some important notices, trademarks, and compliance information.

Notices

This information was developed for products and services offered in the U.S.A.

IBM may not offer the products, services, or features discussed in this document in other countries. Consult your local IBM representative for information on the products and ser-vices currently available in your area. Any reference to an IBM product, program, or service is not intended to state or imply that only that IBM product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any IBM intellectual property right may be used instead. However, it is the user's responsibility to evaluate and verify the operation of any non-IBM product, program, or service.

IBM may have patents or pending patent applications covering subject matter described in this document. The furnishing of this document does not grant you any license to these patents. You can send license inquiries, in writing, to: This information was developed for products and services offered in the U.S.A.

IBM Director of LicensingIBM CorporationNorth Castle DriveArmonk, NY 10504-1785 U.S.A.

For license inquiries regarding double-byte (DBCS) information, contact the IBM Intellec-tual Property Department in your country or send inquiries, in writing, to:

IBM World Trade Asia CorporationLicensing 2-31 Roppongi 3-chome, Minato-kuTokyo 106-0032, Japan

The following paragraph does not apply to the United Kingdom or any other country where such provisions are inconsistent with local law: INTERNATIONAL BUSINESS MACHINES CORPORATION PROVIDES THIS PUBLICATION "AS IS" WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE

B-1

Page 42: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

IMPLIED WARRANTIES OF NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow disclaimer of express or implied war-ranties in certain transactions, therefore, this statement may not apply to you.

This information could include technical inaccuracies or typographical errors. Changes are periodically made to the information herein; these changes will be incorporated in new edi-tions of the publication. IBM may make improvements and/or changes in the product(s) and/or the program(s) described in this publication at any time without notice.

Any references in this information to non-IBM Web sites are provided for convenience only and do not in any manner serve as an endorsement of those Web sites. The materials at those Web sites are not part of the materials for this IBM product and use of those Web sites is at your own risk.

IBM may use or distribute any of the information you supply in any way it believes appropri-ate without incurring any obligation to you.

Licensees of this program who wish to have information about it for the purpose of enabling: (i) the exchange of information between independently created programs and other programs (including this one) and (ii) the mutual use of the information which has been exchanged, should contact:

IBM CorporationSoftware Interoperability Coordinator, Department 49XA3605 Highway 52 NRochester, MN 55901U.S.A.

Such information may be available, subject to appropriate terms and conditions, including in some cases, payment of a fee.

The licensed program described in this document and all licensed material available for it are provided by IBM under terms of the IBM Customer Agreement, IBM International Pro-gram License Agreement or any equivalent agreement between us.

Any performance data contained herein was determined in a controlled environment. Therefore, the results obtained in other operating environments may vary significantly. Some measurements may have been made on development-level systems and there is no guarantee that these measurements will be the same on generally available systems. Fur-thermore, some measurements may have been estimated through extrapolation. Actual results may vary. Users of this document should verify the applicable data for their specific environment.

Information concerning non-IBM products was obtained from the suppliers of those prod-ucts, their published announcements or other publicly available sources. IBM has not tested those products and cannot confirm the accuracy of performance, compatibility or any other claims related to non-IBM products. Questions on the capabilities of non-IBM products should be addressed to the suppliers of those products.

All statements regarding IBM's future direction or intent are subject to change or with-drawal without notice, and represent goals and objectives only.

All IBM prices shown are IBM's suggested retail prices, are current and are subject to change without notice. Dealer prices may vary.

This information contains examples of data and reports used in daily business operations. To illustrate them as completely as possible, the examples include the names of individu-als, companies, brands, and products. All of these names are fictitious and any similarity to the names and addresses used by an actual business enterprise is entirely coincidental.

B-2 D27700-2 Rev.7.0

Page 43: Netezza Site Prep Specs n200x

Trademarks

COPYRIGHT LICENSE:

This information contains sample application programs in source language, which illustrate programming techniques on various operating platforms. You may copy, modify, and distrib-ute these sample programs in any form without payment to IBM, for the purposes of developing, using, marketing or distributing application programs conforming to the appli-cation programming interface for the operating platform for which the sample programs are written. These examples have not been thoroughly tested under all conditions. IBM, there-fore, cannot guarantee or imply reliability, serviceability, or function of these programs.

Each copy or any portion of these sample programs or any derivative work, must include a copyright notice as follows:

© your company name) (year). Portions of this code are derived from IBM Corp. Sample Programs.

© Copyright IBM Corp. _enter the year or years_.

If you are viewing this information softcopy, the photographs and color illustrations may not appear.

Trademarks

IBM, the IBM logo, ibm.com and Netezza are trademarks or registered trademarks of Inter-national Business Machines Corporation in the United States, other countries, or both. If these and other IBM trademarked terms are marked on their first occurrence in this infor-mation with a trademark symbol (® or ™), these symbols indicate U.S. registered or common law trademarks owned by IBM at the time this information was published. Such trademarks may also be registered or common law trademarks in other countries. A current list of IBM trademarks is available on the Web at “Copyright and trademark information” at ibm.com/legal/copytrade.shtml.

Adobe is a registered trademark of Adobe Systems Incorporated in the United States, and/or other countries.

Linux is a registered trademark of Linus Torvalds in the United States, other countries, or both.

Microsoft, Windows, Windows NT, and the Windows logo are trademarks of Microsoft Corpo-ration in the United States, other countries, or both.

NEC is a registered trademark of NEC Corporation.

UNIX is a registered trademark of The Open Group in the United States and other countries.

Java and all Java-based trademarks are trademarks of Sun Microsystems, Inc. in the United States, other countries, or both.

Red Hat is a trademark or registered trademark of Red Hat, Inc. in the United States and/or other countries.

D-CC, D-C++, Diab+, FastJ, pSOS+, SingleStep, Tornado, VxWorks, Wind River, and the Wind River logo are trademarks, registered trademarks, or service marks of Wind River Sys-tems, Inc. Tornado patent pending.

APC and the APC logo are trademarks or registered trademarks of American Power Conver-sion Corporation.

Other company, product or service names may be trademarks or service marks of others.

D27700-2 Rev.7.0 B-3

Page 44: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Electronic Emission Notices

When you attach a monitor to the equipment, you must use the designated monitor cable and any interference suppression devices that are supplied with the monitor.

Federal Communications Commission (FCC) Statement

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to cor-rect the interference at his own expense.

Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. IBM is not responsible for any radio or television interference caused by using other than recommended cables and connectors or by unauthorized changes or mod-ifications to this equipment. Unauthorized changes or modifications could void the user's authority to operate the equipment.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that might cause undesired operation.

Industry Canada Class A Emission Compliance Statement

This Class A digital apparatus complies with Canadian ICES-003.

Avis de conformité à la réglementation d'Industrie Canada

Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.

Australia and New Zealand Class A Statement

Attention: This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

European Union EMC Directive Conformance Statement

This product is in conformity with the protection requirements of EU Council Directive 2004/108/EC on the approximation of the laws of the Member States relating to electro-magnetic compatibility. IBM cannot accept responsibility for any failure to satisfy the protection requirements resulting from a nonrecommended modification of the product, including the fitting of non-IBM option cards.

Attention: This is an EN 55022 Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

Responsible manufacturer:

International Business Machines Corp.New Orchard RoadArmonk, New York 10504914-499-1900

B-4 D27700-2 Rev.7.0

Page 45: Netezza Site Prep Specs n200x

Electronic Emission Notices

European Community contact:

IBM Technical Regulations, Department M456IBM-Allee 1, 71137 Ehningen, GermanyTelephone: +49 7032 15-2937Email: [email protected]

Germany Class A Statement

Deutschsprachiger EU Hinweis: Hinweis für Geräte der Klasse A EU-Richtlinie zur Elektro-magnetischen Verträglichkeit

Dieses Produkt entspricht den Schutzanforderungen der EU-Richtlinie 2004/108/EG zur Angleichung der Rechtsvorschriften über die elektromagnetische Verträglichkeit in den EU-Mitgliedsstaaten und hält die Grenzwerte der EN 55022 Klasse A ein.

Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu instal-lieren und zu betreiben. Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden. IBM übernimmt keine Verantwortung für die Einhaltung der Schut-zanforderungen, wenn das Produkt ohne Zustimmung der IBM verändert bzw. wenn Erweiterungskomponenten von Fremdherstellern ohne Empfehlung der IBM gesteckt/einge-baut werden.

EN 55022 Klasse A Geräte müssen mit folgendem Warnhinweis versehen werden: “Warnung: Dieses ist eine Einrichtung der Klasse A. Diese Einrichtung kann im Wohnbere-ich Funk-Störungen verursachen; in diesem Fall kann vom Betreiber verlangt werden, angemessene Maßnahmen zu ergreifen und dafür aufzukommen.”

Deutschland: Einhaltung des Gesetzes über die elektromagnetische Verträglichkeit von Geräten

Dieses Produkt entspricht dem “Gesetz über die elektromagnetische Verträglichkeit von Geräten (EMVG)”. Dies ist die Umsetzung der EU-Richtlinie 2004/108/EG in der Bundes-republik Deutschland.

Zulassungsbescheinigung laut dem Deutschen Gesetz über die elektromagnetische Verträglichkeit von Geräten (EMVG) (bzw. der EMC EG Richtlinie 2004/108/EG) für Geräte der Klasse A

Dieses Gerät ist berechtigt, in Übereinstimmung mit dem Deutschen EMVG das EG-Konfor-mitätszeichen - CE - zu führen.

Verantwortlich für die Einhaltung der EMV Vorschriften ist der Hersteller:

International Business Machines Corp.New Orchard RoadArmonk, New York 10504914-499-1900

Der verantwortliche Ansprechpartner des Herstellers in der EU ist:

IBM DeutschlandTechnical Regulations, Department M456IBM-Allee 1, 71137 Ehningen, GermanyTelephone: +49 7032 15-2937Email: [email protected]

Generelle Informationen:

Das Gerät erfüllt die Schutzanforderungen nach EN 55024 und EN 55022 Klasse A.

D27700-2 Rev.7.0 B-5

Page 46: Netezza Site Prep Specs n200x

Site Preparation and Specifications: IBM PureData System for Analytics Model N200x

Japan VCCI Class A Statement

This is a Class A product based on the standard of the Voluntary Control Council for Inter-ference (VCCI). If this equipment is used in a domestic environment, radio interference may occur, in which case the user may be required to take corrective actions.

Japan Electronics and Information Technology Industries Association (JEITA) Statement

Japan Electronics and Information Technology Industries Association (JEITA) Confirmed Harmonics Guidelines (products less than or equal to 20 A per phase)

Japan Electronics and Information Technology Industries Association (JEITA) Statement

Japan Electronics and Information Technology Industries Association (JEITA) Confirmed Harmonics Guidelines (products greater than 20 A per phase)

Korea Communications Commission (KCC) Statement

This is electromagnetic wave compatibility equipment for business (Type A). Sellers and users need to pay attention to it. This is for any areas other than home.

Russia Electromagnetic Interference (EMI) Class A Statement

People's Republic of China Class A Electronic Emission Statement

B-6 D27700-2 Rev.7.0

Page 47: Netezza Site Prep Specs n200x

Regulatory and Compliance

Taiwan Class A Compliance Statement

Regulatory and Compliance

Regulatory Notices

Install the NPS system in a restricted-access location. Ensure that only those trained to operate or service the equipment have physical access to it. Install each AC power outlet near the NPS rack that plugs into it, and keep it freely accessible.

Provide approved circuit breakers on all power sources.

Product may be powered by redundant power sources. Disconnect ALL power sources before servicing.

High leakage current. Earth connection essential before connecting supply. Courant de fuite élevé. Raccordement à la terre indispensable avant le raccordement au réseau.

Homologation Statement

This product may not be certified in your country for connection by any means whatsoever to interfaces of public telecommunications networks.

Further certification may be required by law prior to making any such connection. Contact an IBM representative or reseller for any questions.

WEEE

Netezza Corporation is committed to meeting the requirements of the European Union (EU) Waste Electrical and Electronic Equipment (WEEE) Directive. This Directive requires pro-ducers of electrical and electronic equipment to finance the takeback, for reuse or recycling, of their products placed on the EU market after August 13, 2005.

D27700-2 Rev.7.0 B-7