H I G H T E C H , E N E R G Y S AV I N G A I R C O N D I T I O N E R S , E N S U R I N G C O M F O R T
I N L I G H T C O M M E R C I A L A P P L I C AT I O N S
EPC08-201.indb 1 18-03-2008 09:47:20
2
Air Conditioning and the EnvironmentAir conditioning systems provide a significant level of indoor comfort,making possible optimum working and living conditions in the mostextreme climates.In recent years, motivated by a global awareness of the need toreduce the burdens on the environment, some manufacturersincluding Daikin have invested enormous efforts in limiting thenegative effects associated with the production and the operation ofair conditioners.Hence, models with energy saving features and improved eco-production techniques have seen the light of day, making a significantcontribution to limiting the impact on the environment.
Daikin has a worldwide reputation based on over 80 years’ experiencein the successful manufacture of high quality air conditioningequipment for industrial, commercial and residential use.
Daikin Europe N.V.
EPC08-201.indb 2 18-03-2008 09:47:30
3
INTRODUCTION 2
FEATURES 4
1. Wide Application Range 42. Environmental Awareness 103. Installation & Maintenance Friendly Design 11
OUTDOOR UNITS 13
1. VRV®III-S Technology 132. Specifications 153. Accessories 15
INDOOR UNITS 16
1. Features 162. Specifications & Accessories 23
VENTILATION 36
1. VAM-FA 362. VKM-GAM / VKM-GA 37
POWERFUL SELECTION PROGRAMMES 38
1. VRV® XPRESS 382. VRV® PRO 39
USER FRIENDLY CONTROL SYSTEMS 40
1. Individual Control Systems 402. Centralised Control Systems 423. Network Solutions 434. Accessories 48
EPC08-201.indb 3 18-03-2008 09:47:37
4
VRV› ®III-S OUTDOOR UNIT RANGE
INDOOR UNIT CAPACITY INDEX›
eg. Selected indoor units:FXCQ25 + FXFQ50 + FXDQ25 + FXDQ50
Connection ratio: 25 + 50 + 25 + 50 = 150
Possible outdoor unit:RXYSQ5PAV1
RXYSQ4PAV1/RXYSQ4PAY1RXYSQ5PAV1/RXYSQ5PAY1RXYSQ6PAV1/RXYSQ6PAY1
®
9 Space saving
9 Small capacity
9 Slim design
9 Silent operation
9 Super wide range of indoor units
EPC08-201_1-22.indd 4 14-04-2008 10:32:18
5
FLEXIBLE PIPING DESIGN›
The VRV®III-S provides the long piping lengthpossibility of 150m1 (175m equivalent piping length),with a total piping length of 300m. If the outdoorunit is installed above the indoor units, the heightdifference can be up to a maximum of 50m2.These generous allowances facilitate an extensivevariety of system designs.
Notes:1. 40 m when the outdoor unit is installed below indoor units.2. Maximum piping length between the indoor unit and the first
branch is 40 m.
WIDE OPERATION RANGE›
The VRVIII®-S system can be installed practicallyanywhere. The incorporation of a high pressure“dome” type compressor results in a remarkableoutdoor operating temperature range from as low as-20°C in heating mode to as high as 46°C in coolingmode.
SPACE SAVING DESIGN›
The VRVIII®-S is slimmer and more compact, resultingin significant savings in installation space.
Outdoor temperature operating range
Cooling46°CDB
Heating15.5°CWB
-5°CDB
-20°CWB
50
40
30
20
10
0
-10
-20
-30
FOOTPRINTApprox. 40%reduction
(4,5,6HP)
900mm
796mm
765m
m
320mm
VOLUMEApprox. 50%reduction
(5HP)
EPC08-201.indb 5 18-03-2008 09:47:49
6
SUPER WIDE RANGE OF INDOOR UNITS›
Whatever the air conditioning requirement, a Daikin indoor unit can provide the solution. The VRV®III-S can be
combined with in a total of .
CASSETTE TYPE UNIT
CONCEALED CEILING UNIT
FLOOR STANDING UNIT
EPC08-201_1-22.indd 6 04-04-2008 16:27:28
7
CONCEALED FLOOR STANDING UNIT
CEILING SUSPENDED UNIT
WALL MOUNTED UNIT
EPC08-201_1-22.indd 7 04-04-2008 16:27:40
8
Step 1 max. - 3dB(4HP/11.2Kw)
Step 2 max. - 6dB(4HP/11.2Kw)
Step 3 max. - 9dB(4HP/11.2Kw)
Peak in the outdoor temperature
Night mode starts Night mode ends
Step 1: 47dB
Step 2: 44dB
Step 3: 41dB
Night Mode
8 hrs(initial setting)
10 hrs(initial setting)
— Operation Sound dBA
— Load %
— Capacity* %
Notes:This function is available for on site setting.›The relationship between outdoor temperature (load) and time shown›in the graph is merely an example.
SUPER SILENT OPERATION›
Quietness is another important feature. To reduce noise and ensure comfortable operation, the latest technologiesand features have been applied to the outdoor units.
During the night the sound level of the outdoor unit can be reduced for a certain period: starting time and endingtime can be input
2 modes*1 with low sound level at night:
Mode 1 Automatic mode›Set on the outdoor PCB. Time of maximum temperature is memorised. The low operating mode will become active8 hours*2 after the peak temperature in the daytime and operation will return to normal after 9 hours*3.
Mode 2 Customized mode›Starting and ending times can be input. (External control adapter for outdoor unit, DTA104A61 or DTA104A62and a separately ordered timer are necessary.)
Notes:*1. Determine which mode to select depending on the climatic characteristics of each country.*2. Initial setting. Can be selected from 6, 8 and 10 hours.*3. Initial setting. Can be selected from 8, 9 and 10 hours.
Night quiet function (max. -9dBA)
Daikin indoor units operate atsound levels as low as 25 dBA
(dB(A Perceived loudness Sound
0 Treshold of hearing -20 Extremely soft Rustling leaves40 Very soft Quiet room60 Moderately loud Normal conversation80 Very loud City traffic noise
100 Extremely loud Symphonic orchestra120 Threshold of feeling Jet taking off
Daikin indoor units
EPC08-201.indb 8 18-03-2008 09:48:08
9
40 30 20 10 6 5 4 3 2 1
10
9
8
7
6
5
4
3
2
1
0
8
6
4
2
05 4 3 2 1
ANTI CORROSION TREATMENT›
Special anti corrosion treatment of the heat exchanger provides5 to 6 times greater resistance ag nst acid rainand salt corrosion. The use of rust proof steel sheet on the underside of the unit gives additional protection.
Improvement in corrosion resistance
Corrosion resistance rating
Non-treated Anti-corrosion treatedSalt corrosion 1 5 to 6
Acid rain 1 5 to 6
An anti-corrosion heat exchanger cutaway view
Aluminium
Hydrophilic film
Corrosion-resistantacrylic resin
Performed tests:
VDA Wechseltest›Contents of single cycle (7 days):- 24 hours salt spray test SS DIN 50021- 96 hours humidity cycle test KFW DIN 50017- 48 hours room temperature & room humidityTesting period: 5 cycles
Kesternich test (SO2)›- Contents of single cycle (48 hours) according
to DIN50018 (0.21)- Testing period: 40 cycles
Cycle
Deg
ree
of
Co
rro
sio
n
Cycle
Deg
ree
of
Co
rro
sio
n
.DAIKIN P.E
Barealuminium
Heat exchanger
EPC08-201.indb 9 18-03-2008 09:48:18
10
HIGH COP VALUES›A major feature of VRV®III-S is its exceptional energy efficiency,the system achieving high COPs during both cooling and heatingoperation by the use of refined components and functions.
0 1 2 3 4 5
Heating
Nominal value
Cooling
1*3.99
2*4.56
Temperature remains stable
Slow start
Air conditioningwithout Inverter
Air conditioningwith Inverter
*1 Nominal cooling capacities are based on: indoor temperature: 27°CDB,19°CWB, inlet water temperature: 30°C, equivalent refrigerant piping: 7.5m,level difference: 0m.Unit: RXYSQ4PA7V1B
*2 Nominal heating capacities are based on: indoor temperature: 20°CDB,outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 7.5m,level difference: 0m.Unit: RXYSQ4PA7V1B
INVERTER CONTROL›
The application of inverter control saves energy for two basicreasons:
1. It enables compressor speed to vary according to the cooling/heating load and therefore consume only the power necessaryto match that load. The 50 Hz frequency of the power supply isinverted to a higher or lower frequency according to the requiredcapacity to heat or cool the room. If a lower capacity is needed,the frequency is decreased and less energy is used.
2. Under partial load conditions, the energy efficiency is higher.If the compressor rotates more slowly because less capacityis needed, the coil becomes virtually oversized. Improvedefficiencies can therefore be achieved than are possible withnon inverter compressors, which always run at the same speed.
EPC08-201_1-22.indd 10 04-04-2008 16:27:51
11
32°C
20°C
0°C 43°C
AUTOMATIC CHARGE FUNCTION›
Conventional Way:›1. calculation of additional refrigerant charging volume2. charging the unit with additional refrigerant3. measuring the weight of the cylinder4. judgment based on pressure (test operation)
VRV› ®III-S:With VRV®III however, these 4 steps are omitted since VRVIII®-S canbe charged with the necessary amount of refrigerant automaticallyvia a push button on the PCB. Automatic charging will cease oncethe appropriate amount of refrigerant has been transferred.
If temperature drops below 20°C manual charging is necessary (toavoid overcharging the system). After having switched to heatingand once the indoor temperature rises above 20°C, push theauto charge button to initialise auto charge function. Refrigerantcontainment is only available after performing the automaticcharge function.
AUTOMATIC TEST›
When refrigerant charging has ceased, pushing the test operationbutton on the PCB will initiate a check on the wiring, shut off valves,sensors and refrigerant volume. This test ceases automatically whencompleted.
Indoor temperature
Outdoor temperature
*To avoid overcharging the system
Automaticcharge
function
Manualcharge*
EPC08-201_1-22.indd 11 04-04-2008 16:28:00
12
SIMPLE WIRING AND PIPING CONNECTION›
– simple wiringSuper Wiring allows the shared use of wiring between indoor units,›outdoor units and the centralised remote controls.This system makes it easy for the user to retrofit the existing system›with a centralised remote control, simply by connecting it to theoutdoor units.The use of non polarity wiring, makes incorrect connection impossible›and reduces installation time.
– piping connectionThe unified Daikin REFNET piping system is specially designed for›simple installation.REFNET joints and headers (both accessories) can cut down on›installation work and increase system reliability.
EPC08-201.indb 12 18-03-2008 09:48:46
N
S
N
NN
N
S SS
S
13
1 Smooth air inlet bell mouth and aero spiral fanThese features assist in significantly reducingnoise. Guides are added to the bell mouth intaketo reduce turbulence in the air flow generated byfan suction.The aero spiral fan features fan blades with bentblade edges, further reducing turbulence.
2 DC fan motorThe use of a DC fan motor offers substantialimprovements in operating efficiency comparedto conventional AC motors, especially during lowspeed rotation.
4 Reluctance brushless DC compressorThe reluctance brushless DC motor providessignificant increases in efficiency compared toconventional AC inverter motors, simultaneouslyusing two different forms of torque (normal andreluctance torque) to produce extra power fromsmall electric currents.
Powerful magnets›The motor comprises powerful neodymium magnetsthat create the reluctance torque. These magnets areapproximately 12 times stronger than ferrite typesand make a major contribution to its energy savingcharacteristics.
3 Super aero grilleThe spiral shaped ribs are aligned with the directionof discharge flow in order to minimise turbulenceand reduce noise.
Neodymiummagnet
Ferritemagnet
Low pressure side
High pressure side
Suction
Scroll
Dis-charge
Reluctance DCMotor
Neodymiummagnet Normal” torque”
Reluctance torque
Rotatingstator field
Iron
200 300 400 500 600 700 800 900 1000
100
80
60
40
20
0
Note:Data are based on studies conducted under controlled conditionsat a Daikin laboratory
DC fanmotor structure
magnet
DC motor efficiency(comparison with a conventional AC motor)
(%)
Effi
cien
cy
DC motor
Approx. 20%increase
AC motor
Approx. 40%increase
Motor speed (rpm)
Conventional New
Escaping edges are sucked in by the bent blade edges, reducingoverall turbulence.
Aero spiral fan blade tips
2
1
34
5
EPC08-201.indb 13 18-03-2008 09:48:51
2
1
34
5
14
Smooth sine wave DC inverter›Optimizing the sine wave curve results in smoothermotor rotation and improved motor efficiency.
Optimal refrigerant configuration›Changes to the shape of the spiral and volume ratioresult in optimal refrigerant layout.
Stronger materials›The strength of the casing has been increased byboosting the internal dome pressure.
5 e-Bridge circuitPrevents accumulation of liquid refrigerant inthe condenser. This results in more efficient useof the condenser surface under all conditionsand leads in turn to better energy efficiency.Increased evaporative capacity stems from thenewly developed refrigeration circuit, the SCe-bridge circuit, which adds super cooling priorto the expansion cycle. By adopting this circuit,the COPs in both cooling and heating have beendrastically improved.
6 e-Pass heat exchangerOptimization of the layout path of the heatexchanger prevents heat transferring from theoverheated gas section towards the sub cooledliquid section, a more efficient use of the heatexchanger.
7 i-Demand functionThe newly introduced current sensor minimizesthe difference between actual power consumptionand predefined power consumption.
27°C
27°C
27°C
55°C 37°C 43°C
55°C 60°C
50°C 55°C
27°C
27°C
27°C
55°C
In cooling mode, the heat exchanger of the condensor is improved.This means an improvement of COP by 3%.
Current Model HD Type
OUT 45°C
OUT 45°C
IN 85°C OUT 45°CIN 85°C
Pow
erco
nsu
mp
tio
n(K
VV
)
8:00 12:00 16:00 20:00Time
Evaporative capacitycan be raised bytaking super coolingjust before theelectronicexpansion valve
By the SCe- bridgecircuit, cooling andheating attain theimprovement in COP
CurrentEvaporative-
capacity
Evaporative-capacity has been improved byadopting the SCe-Bridge Circuit circuit.
SCe-Bridge Circuit
EPC08-201_1-22.indd 14 21-04-2008 10:32:52
15
RXYSQ4PA7V1B /RXYSQ4PA7Y1B RXYSQ5PA7V1B /RXYSQ5PA7Y1B RXYSQ6PA7V1B /RXYSQ6PA7Y1B
Nominal capacity cooling kWheating kW
COP coolingheating
Capacity range HPMax n° of indoor units to be connectedIndoor index connection minimum
maximumCasing colour
materialPower supply V3Dimensions unit height mm
width mmdepth mm
Weight unit kgFan type
air Flow Rate cooling m/min(nominal at 230V) heating m/min
Compressor typestarting method
Operation range cooling minimum °CDBmaximum °CDB
heating minimum °CWBmaximum °CWB
Sound level (nominal) cooling sound power dBAsound pressure dBA
heating sound pressure dBARefrigerant type
charge kgcontrol
Refrigerant Oil typecharged Volume l
Piping Connections liquid diameter (OD) mmgas diameter (OD) mmheat Insulationmax. total length m
Safety devices
11.2 14.0 15.512.5 16.0 18.0
3.99 / 3.88 3.99 / 3.88 3.42/ 3.334.56 / 4.43 4.15 / 4.03 3.94 / 3.83
4 5 66 8 9
50 62.5 70130 162.5 182
daikin whitepainted galvanised steel
1~, 50Hz, 220-240V / 3~, 50Hz, 380-415V1,345 1,345 1,345900 900 900320 320 320
125/120 125/120 125/120Propeller
106 106 106102 105 105
hermetically sealed scroll compressordirect on line
-5.0 -5.0 -5.046 46 46-20 -20 -2015.5 15.5 15.566 67 6950 51 5352 53 55
R-410A4.0 4.0 4.0
expansion valve (electronic type)daphne FVC68D
1.5 1.5 1.59.52 (Flare) 9.52 (Flare) 9.52 (Flare)15.9 (Flare) 15.9 (Flare) 19.1 (Braze)
both liquid and gas pipes300 300 300
HPS, fan motor thermal protection, inverter overload protector, PC board fuse
RXYSQ4PA7V1B /RXYSQ4PA7Y1B RXYSQ5PA7V1B /RXYSQ5PA7Y1B RXYSQ6PA7V1B /RXYSQ6PA7Y1B
KRC19-26A6KJB111A
KHRQ22M29HKHRQ22M20T
KKPJ5F180
Cool/heat selectorFixing boxRefnet headerrRefnet jointCentral drain plug
Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, inlet water temperature: 30°C, equivalent refrigerant piping:7.5m, level difference: 0m.Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 7.5m,level difference: 0m.Sound power level is an absolute value that a sound source generates.Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound leveldrawings.Sound values are measured in a semi-anechoic room.
EPC08-201.indb 15 18-03-2008 09:48:54
16
850 mm
500mm
20-25-32-40-50
20-25-32-40-50-63-80-100-125
ROUND FLOW CEILING MOUNTED CASSETTE
ComfortModern style decoration panel in white (RAL9010)›360° air discharge ensures uniform air flow and temperature›distributionAir discharge from the corners avoids dead zones that may be›subject to temperature differencesComfortable horizontal air discharge ensures draughtfree operation›and prevents ceiling soiling23 different air flow patterns possible›Fresh air intake: up to 20%›
Flexible installation and easy maintenanceReduced installation height: 214mm for class 20-63›Easy visible drain check thanks to clear drain socket›Drain-up pump with 850 mm lift fitted as standard›
0°
60°
Ceiling voidis 295 mm
360° Round Flow 4-Way Flow 3-Way Flow 2-Way Flow
EXAMPLES OF AIRFLOW PATTERNS
4-WAY BLOW CEILING MOUNTED CASSETTE (600MMX600MM)
ComfortModern style decoration panel in white (RAL9010)›Extremely quiet in operation›Excellent low draught characteristics. Since the flaps can move to›a 0° position, virtually no draught can be experiencedAny one of 5 different air flow patterns can be freely selected›between 0° and 60° and will then be maintained during theoperational cycle of the air conditioner
Flexible Installation and Easy MaintenanceThanks to the compact casing, it matches standard architectural›modules of 600x600mm, therefore ceiling tile cutting is no longernecessaryAir can be discharged in any of 4 directions›Possibility to shut 1 or 2 flaps for easy installation in corners›Since the switch box is located within the unit, it is easy to access›from below for maintenance without removing ceiling tilesDrain-up pump with 500mm lift fitted as standard›
EPC08-201.indb 16 18-03-2008 09:49:02
17
20-32-40-63
20-25-32-40-50-63-80-125
2-WAY BLOW CEILING MOUNTED CASSETTE
ComfortQuiet in operation›Leaves maximum floor and wall space for furniture, decorations›and fittingsAutomatic air flow director ensures uniform air flow and›temperature distributionAnti-ceiling soiling technology›
FilterStandard long life filter›
Flexible Installation and Easy MaintenanceEasy installation in false ceilings of only 355mm›Drain-up pump with 600mm lift fitted as standard›Maintenance can be performed by simply removing›the front panelEasy to clean flat suction grille›Detachable swing flaps›
CEILING MOUNTED CORNER CASSETTEComfort
Equipped with special draught prevention and anti-ceiling soiling›technology
Automatic air flow director ensures uniform air flow and›temperature distributionAir flow by either downward air discharge, frontal discharge or a›combination of both
Flexible InstallationCompact dimensions, can easily be mounted in a narrow ceiling›void (only 220mm ceiling space required, 195 with panel spacer,available as accessory)
Drain-up pump with 500mm lift fitted as standard›
1Standard
Note: Standard setting when shipped.
2Draughtprevention
3Anti-ceilingsoiling technology
minimum ceilingheight is 355mm
600mm
CombinationFrontal discharge
Closed by the decoration panel
Downward discharge
Min. 195 mm
Panel spacer
20 mm 500 mm
EPC08-201_1-22.indd 17 21-04-2008 10:33:04
18
20-25-32-40-50-63
20-25
SMALL CONCEALED CEILING UNIT
ComfortDesigned for hotel bedrooms›Blends unobtrusively with any interior décor: only the suction and›discharge grilles are visibleExtremely quiet in operation›
FilterAir suction filter fitted as standard›
Flexible InstallationCompact dimensions (230mm high & 652mm deep), can easily be›mounted in a ceiling voidThe air suction direction can be altered from rear to bottom›suctionFor easy mounting, the drain pan can be located to the left or the›right of the unit
SLIM CONCEALED CEILING UNIT
ComfortQuiet in operation›Blends unobtrusively with any interior décor›Leaves maximum floor and wall space for furniture, decorations›and fittings
200mm
Ceiling
Suction Chamber[Duct connection]
Air filter
Can be installed in both new and existing buildings›Medium external static pressure facilitates unit use with flexible›ducts of varying lengthsDrain-up pump with 750mm lift fitted as standard›
Flexible InstallationSlim design, can easily be mounted in a ceiling void of only›240mm
EPC08-201.indb 18 18-03-2008 09:49:18
19
20-25-32-40-50-63-80-100-125
40-50-63-80-100-125
CONCEALED CEILING UNIT
ComfortHigh flexibility for a wide variety of applications›Quiet in operation›Blends unobtrusively with any interior décor›
FilterLong life filter fitted as standard›High efficiency filters (65% and 95%) available as accessory›
Flexible Installation and Easy MaintenanceHigh external static pressure facilitates unit use with flexible ducts›of varying lengthsWhen using suction panel, unit requires›only 350mm of ceiling spaceDrain-up pump with 625mm lift fitted as›standardThe air suction direction can be altered›from rear to bottom suctionThe switch box can be reached from the›side or from the bottom side of the unit foreasy servicing
CONCEALED CEILING UNIT
ComfortLeaves maximum floor and wall space for furniture, decorations›and fittings
Flexible InstallationCompact unit (a height of 300 mm), allows installation in narrow›ceiling voidsComplete range of models (FXMQ-PVE: 4.5 - 14 kW)›Built-in drain pump (standard for sizes 40 to 125) increases›reliability of the drain systemReduction of power consumption of 20%›(compared to FXMQ-MAVE series) through use of new DC FanPossibility to change ESP through wired remote control allows›optimisation of the supply air volume
625mm625mm
Min.350mm
EPC08-201_1-22.indd 19 04-04-2008 16:28:10
20
1025
4055 70
100°
10° Cooling
70° Heating
32-63-100
20-25-32-40-50-63
WALL MOUNTED UNIT
ComfortCompact and stylish design blends unobtrusively in any interior›décorAutomatic air flow director ensures efficient air distribution via›louvers that close automatically when the unit is switched off5 different discharge angles can be programmed via the remote›controlDischarge angle automatically returns to its previous position on›restart (initial setting 10 degrees for cooling and 70 degrees forheating)
FilterMildew proof polystyrene filter and drain pan›
Flexible Installation and Easy MaintanceBoth horizontal flaps and front panel can easily be removed and›washedAll maintenance operations can be carried out from the front of›the unitDrain-up pump with 1,000mm lift available as accessory›Drain pipe can be fitted either to the left or right side of the unit›
SLIM CONCEALED CEILING UNIT
ComfortQuiet in operation›Leaves maximum floor and wall space for furniture, decorations›and fittingsEnhanced horizontal and vertical air circulation in all directions›thanks to an air flow pattern of 100°
FilterLong life filter fitted as standard›
Flexible Installation and Easy MaintanceCan be installed in both new and existing buildings›The ideal solution for installation without false ceilings›Drain-up pump with 600mm lift available as accessory›
Maintenance can be performed easily from below the unit›Bristle free flap makes cleaning easier›
1025
4055 70
Drain-up kit(built inside mainunit)
Drain-up kit(built inside mainunit)
10° Cooling
70° Heating
1,000mm
Height of drain-up
Drain-upkitIndoor unit
Drain-up kit
32-63-100
20-25-32-40-50-63
EPC08-201.indb 20 18-03-2008 09:49:33
21
71-100-125
4-WAY BLOW CEILING SUSPENDED UNIT
ComfortGroup control with other VRV indoor units possible›Cool heat selection›Prevention of cold draught at hot start, defrost and oil return in›heatingAir can be discharged in any of 4 directions›Air can be discharged at 5 different angles between 0 and›60 degrees
Automatic air flow director ensures efficient air and temperature›distribution.Air flow distribution for ceiling heights up to 3.5m without loss of›capacity.
FilterAir filter, drain pan and heat exchanger fin are mildew proof and›anti-bacterial treated
Flexible InstallationIdeal for installation in new and existing buildings›5m maximum distance between FXUQ unit and junction box›Possibility to shut 1 or 2 flaps for easy installation in corners›Drain-up pump with 500mm lift fitted as standard›
EPC08-201.indb 21 18-03-2008 09:49:42
22
Wall mounted Floor standing
20-25-32-40-50-63
20-25-32-40-50-63
FLOOR STANDING UNIT
ComfortIdeal for installation beneath a window›Compact dimensions (only 222mm deep and 600mm high)›All models are available with remote control›
FilterLong life filter fitted as standard›
Flexible Installation and Easy MaintanceRunning the pipes from connections at the back, enables the unit›to be wall mounted
CONCEALED FLOOR STANDING UNIT
ComfortIdeal for perimeter air conditioning›Ideal for installation below a window›All models are available with remote control›
FilterLong life filter fitted as standard›
Flexible Installation and Easy MaintanceOn site connection during installation is easier›The connecting port faces downward, eliminating the need to›attach auxiliary piping
Connectingport
Refrigerantpiping
On site connection during installation is easier›The fibreless discharge grille prevents condensation and staining›
EPC08-201.indb 22 18-03-2008 09:49:47
23
R o u n d f l o w c e i l i n g m o u n t e d c a s s e t t e
20 25 32 40 50 63 80 100 125FXFQ-P
Capacity cooling kWheating kW
Power inputcooling kWheating kW
Dimensions (H x W x D) mmWeight unit kgCasing
Air Flow Ratecooling high / low m3 /minheating high / low m3 /min
Sound power (nominal) cooling dB(A)
Sound pressurecooling high / low dB(A)heating high / low dB(A)
Refrigerant namePower SupplyPiping Connections L / G / D diameter mmAir FilterDrain-up Height mm
Decoration Panel
modelcolour(H x W x D) mmweight kg
2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.02.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0
0.053 0.063 0.083 0.095 0.120 0.173 0.2580.045 0.055 0.067 0.114 0.108 0.176 0.246
204 x 840 x 840 246 x 840 x 840 288 x 840 x84020.0 21.0 24.0 26.0
Galvanised steel12.5 / 9.0 13.5 / 9.0 15.5 / 10.0 16.5 / 11.0 23.5 / 14.5 26.5 / 17.0 33.0 / 20.012.5 / 9.0 13.5 / 9.0 15.0 / 9.5 17.5 / 12.0 23.5 / 14.5 28.0 / 17.5 33.0 / 20.0
49 50 51 52 55 58 6131 / 28 32 / 28 33 / 28 34 / 29 38 / 32 41 / 33 44 / 3431 / 28 32 / 28 33 / 28 36 / 30 38 / 32 42 / 34 44 / 34
R-410A1~ / 220-240V / 50Hz
6.35 / 12.7 / 32 6.4 / 12.7 / 32 9.5 / 15.9 / 32Resin net with mold resistance
750BYCQ140CW1
RAL901050x950x950
5.5
Notes:The sound pressure values are mentioned for a unit installed with rear suctionThe sound power level is an absolute value indicating the power wich a sound source generates.Nominal cooling capacities are based on: indoor temperature: 270CDB, 190CWB, outdoor temperature: 350CDB, equivalent refrigerant piping: 5m, level difference: 0m.Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
ACCESSORIES
SPECIFICATIONS
Wired remote controlInfrared remote control cooling only
heat pumpDecoration panelReplacement long life filter (non-woven type)Fresh air intake kit (20 % fresh air intake) (chamber type)Air discharge outlet sealing member
BRC1D52BRC7F533FBRC7F532F
BYCQ140CW1KAFP551K160KDDQ5C140
KDBHQ55C140
FXFQ-P 20 25 32 40 50 63 80 125
EPC08-201.indb 23 18-03-2008 09:49:55
24
4 - w a y b l o w c e i l i n g m o u n t e d c a s s e t t e ( 6 0 0 m m x 6 0 0 m m )
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
2.2 2.8 3.6 4.5 5.62.5 3.2 4.0 5.0 6.373 73 76 89 11564 64 68 80 107
286 x 575 x 57518
galvanised steel plate9.0 / 7.0 9.0 / 7.0 9.5 / 7.5 11.0 / 8.0 14.0 / 10.030 / 25 30 / 25 32 / 26 36 / 28 41 / 33
47 47 49 53 58R-410A
ø6.4 / ø12.7resin net with mold resistant
5001~, 50Hz, 220-240V
55 x 700 x 7002.7
white (RAL 9010)
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply V1Decoration panel dimensions (H x W x D) mm
weight kgColour
20 25 32 40 50FXZQ-M8
20 25 32 40 50FXZQ-M8
BRC1D52BRC7E531BRC7E530BYFQ60B
KDBH44B60KDBQ44B60KAFQ441B60KDDQ44X60
Wired remote controlInfrared remote control cooling only
heat pumpDecoration panelSealing member of air discharge outletPanel spacerReplacement long life filterFresh air intake kit direct installation type
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 24 18-03-2008 09:50:07
25
2 - w a y b l o w c e i l i n g m o u n t e d c a s s e t t e
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply V3Decoration panel dimensions (H x W x D) mm
weight kgcolour
FXCQ-M8 20 25 32 40 50 63 80 125
2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.02.5 3.2 4.0 5.0 6.3 8.0 10.0 16.077 92 92 130 130 161 209 25644 59 59 97 97 126 176 223
305 x 780 x 600 305 x 995 x 600 305 x 1,180 x 600 305 x 1,670 x 60026 31 32 35 47 48
galvanised steel plate7 / 5 9 / 6.5 9 / 6.5 12 / 9 12 / 9 16.5 / 13 26 / 21 33 / 25
33 / 28 35 / 29 35 / 29 35.5 / 30.5 35.5 / 30.5 38 / 33 40 / 35 45 / 3945 50 50 50 50 52 54 60
R-410Aø6.4 / ø12.7 ø9.5 / ø15.9
resin net with mold resistant600
1~, 50Hz, 230V53 x 1,030 x 680 53 x 1,245 x 680 53 x 1,430 x 680 53 x 1,920 x 680
8 8.5 9.5 12ivory white
Wired remote controlInfrared remote control cooling only
heat pumpDecoration panelHigh efficiency filter 65% *1High efficiency filter 90% *1Filter chamber for bottom suctionReplacement long life filter
BRC1D52BRC7C67BRC7C62
BYBC32G BYBC50G BYBC63G BYBC125GKAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
20 25 32 40 50 63 80 125FXCQ-M8
Note:*1. Filter chamber is required when installing a high efficiency filter.
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 25 18-03-2008 09:50:14
26
C e i l i n g m o u n t e d c o r n e r c a s s e t t e
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*Data were not available at time of publication.
2.8 3.6 4.5 7.13.2 4.0 5.0 8.066 66 76 10546 46 56 85
215 x 1,110 x 710 215 x 1,310 x 71031 34
galvanised steel plate11 / 9 11 / 9 13 / 10 18 / 1538 / 33 38 / 33 40 / 34 42 / 37
* * * *R-410A
ø6.4 / ø12.7 ø9.5 / ø15.9resin net with mold resistant
5001~, 50Hz, 220-240V
70 x 1,240 x 800 70 x 1,440 x 8008.5 9.5
ivory white
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply VEDecoration panel dimensions (H x W x D) mm
weight kgcolour
FXKQ-MA 25 32 40 63
BRC1D52BRC4C63BRC4C61
BYK45F BYK71FKPBJ52F56 KPBJ52F80KAFJ521F56 KAFJ521F80K-HV7AW K-HV9AW
KDBJ52F56W KDBJ52F80WKFDJ52F56 KFDJ52F80
FXKQ-MA
Wired remote controlInfrared remote control cooling only
heat pumpDecoration panelPanel spacerReplacement long life filterAir discharge grilleAir discharge blind panelFlexible duct (with shutter)
25 32 40 63
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 26 18-03-2008 09:50:21
27
S m a l l c o n c e a l e d c e i l i n g u n i t
Notes :
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
20 25
2.2 2.82.5 3.2
5050
230x502x65217
galvanised steel plate6.7/5.2 7.4/5.8
37/3250
R-410Aø6.4/ø12.7
resin net with mold resistant50Hz, 230V ,~1
FXDQ-M8
Cooling capacity kWHeating capacity kWNominal input cooling W
heating W(Dimensions (HxWxD mmWeight kgCasing(Air flow rate (H/L m3/min(Sound pressure level (H/L (dB(ASound power level (dB(ARefrigerant typePiping connections liquid/gas mmAir filterPower supply V3
20 25FXDQ-M8
Wired remote controlInfrared remote control cooling
heating
BRC1D52, BRC2C51, BRC3A61BRC4C64BRC4C62
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 27 18-03-2008 09:50:28
28
S l i m c o n c e a l e d c e i l i n g u n i t
2.2 2.8 3.6 4.5 5.6 7.12.5 3.2 4.0 5.0 6.3 8.086 86 89 160 165 18167 67 70 70 152 168
200 x 700 x 620 200 x 900 x 620 200 x 1,100 x 62023 23 23 27 28 31
galvanised steel plate8.0 / 6.4 8.0 / 6.4 8.0 / 6.4 10.5 / 8.5 12.5 / 10.0 16.5 / 13.033 / 29 33 / 29 33 / 29 34 / 30 35 / 31 36 / 32
* * * * * *R-410A
750ø6.4 / ø12.7 ø9.5 / ø15.9
removable, washable, mildew proof1~, 50Hz, 220-240V
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) dB(A)Sound power level dB(A)Refrigerant typeDrain-up height mmPiping connections liquid / gas mmAir filterPower supply VE
FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NAFXDQ-P/NA
FXDQ-P/NA
BRC1D52BRC4C64BRC4C62
Wired remote controlInfrared remote control cooling only
heat pump
FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.The sound pressure values are mentioned for a unit installed with rear suction.* Data were not available at time of publication.
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 28 18-03-2008 09:50:37
29
C o n c e a l e d c e i l i n g u n i t
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply V3Decoration panel dimensions (H x W x D)
weight kgcolour
2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.02.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0110 110 114 127 143 189 234 242 32190 90 94 107 123 169 214 222 301
300 x 550 x 800 300 x 700 x 800 300 x 1,000 x 800 300 x 1,400 x 80030 30 30 30 31 41 51 51 52
galvanised steel plate9 / 6.5 9 / 6.5 9.5 / 7 11.5 / 9 15 / 11 21 / 15.5 27 / 20 28 / 20.5 38 / 2832 / 28 32 / 28 33 / 28 33 / 29 35 / 31 35 / 30 37 / 31 38 / 33 40 / 35
50 50 51 56 58 56 55 56 65R-410A
ø6.4 / ø12.7 ø9.5 / ø15.9resin net with mold resistant
6251~, 50Hz, 230V
55 x 650 x 500 55 x 800 x 500 55 x 1,100 x 500 55 x 1,500 x 5003 3.5 4.5 6.5
ivory white
20 25 32 40 50 63 80 100 125FXSQ-M8
Wired remote controlInfrared remote control cooling only
heat pumpDecoration panelService access panelHigh efficiency filter 65% *1High efficiency filter 90% *1Filter chamber for bottom suctionFilter chamber rear suctionAir suction canvasScreening door / blind boardAir discharge adapter for round duct
BRC1D52, BRC2C51, BRC3A61BRC4C64BRC4C62
BYBS32D BYBS45D BYB571D BYBS125DKTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160WKAFJ252L36 KAFJ252L56 KAFJ252L80 KAFJ252L160KAFJ253L36 KAFJ253L56 KAFJ253L80 KAFJ253L160KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160DKAJ25L36B KAJ25L56B KAJ25L80B KAJ25L160BKSA-25K36 KSA-25K56 KSA-25K80 KSA-25K160KBBJ25K36 KBBJ25K56 KBBJ25K80 KBBJ25K160KDAJ25K36 KDAJ25K56 KDAJ25K71 KDAJ25K140
20 25 32 40 50 63 80 100 125FXSQ-M8
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.The sound pressure values are mentioned for a unit installed with rear suction.
Notes:*1. If installing a high efficiency filter in the unit, an assembly chamber for either bottom or rear suction is required.
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 29 18-03-2008 09:50:46
30
C o n c e a l e d c e i l i n g u n i t
4.5 5.6 7.1 9.0 11.2 14.05.0 6.3 8.0 10.0 12.5 16.0
0.194(1) / 0.193(2) 0.215(1) / 0.214(2) 0.230(1) / 0.229(2) 0.298(1) / 0.297(2) 0.376(1) / 0.375(2) 0.461(1) / 0.460(2)0.182 0.203 0.218 0.286 0.364 0.449
300 x 700 x 700 300 x 1,000 x 700 300 x 1,400 x 70028 36 36 36 46 46
galvanised steel plate16/13/11 18/16.5/15 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28note 3 note 3 note 3 note 3 note 3 note 3note 3 note 3 note 3 note 3 note 3 note 3
R-410Aø6.4 / ø12.7 ø9.5 / ø15.9
note 41~, 50Hz, 220-240V / 1~, 60Hz, 220V
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (HH / H / L) m3 /minSound pressure level dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterPower supply VE
FXMQ-P 40 50 63 80 100 125
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.(1) 50Hz, 220-240V(2) 60Hz, 220V(3) Data were not available at time of publication.(4) The air filter is not standard accessory, but please mount it in the duct system at the suction side. Select its colorimetric method (gravity method) 50% or more.
40 50 63 80 100 125
BRC1D52BRC4C66BRC4C65
KAF372AA56 KAF372AA80 KAF372AA160KAF373AA56 KAF373AA80 KAF373AA160KDDF37AA56 KDDF37AA80 KDDF37AA160KAF371AA56 KAF371AA80 KAF371AA160
Wired remote controlInfrared remote control cooling only
heat pumpHigh efficiency filter 65%High efficiency filter 90%Filter chamberLonglife replacement filter
FXMQ-P
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 30 18-03-2008 09:50:54
31
W a l l m o u n t e d u n i t
20 25 32 40 50 63FXAQ-MA
Cooling capacity kWcapacity kWNominal input cooling W
heating WDimensions (HxWxD) mmWeight kgColourAir flow rate (H / L) m3 /minSound pressure level (H / L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterPower supply VE
2.2 2.8 3.6 4.5 5.6 7.12.5 3.2 4.0 5.0 6.3 8.016 22 27 20 27 5024 27 32 20 32 60
290 x 795 x 230 290 x 1,050 x 23011 14
white7.5 / 4.5 8 / 5 9 / 5.5 12 / 9 15 / 12 19 / 1435 / 29 36 / 29 37 / 29 39 / 34 42 / 36 46 / 39
* * * * * *R-410A
ø6.4 / ø12.7 ø9.5 / ø15.9resin net washable
1~, 50Hz, 220-240V
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*Data were not available at time of publication.
20 25 32 40 50 63FXAQ-MA
Wired remote controlInfrared remote control cooling only
heat pumpDrain pump kit
BRC1D52BRC7E619BRC7E618
K-KDU572DVE
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 31 18-03-2008 09:51:03
32
C e i l i n g s u s p e n d e d u n i t
32 63 100FXHQ-MA
Notes:
32 63 100FXHQ-MA
ACCESSORIES
SPECIFICATIONS
EPC08-201_23-52.indd 32 04-04-2008 16:20:39
33
4 - w a y b l o w c e i l i n g s u s p e n d e d u n i t
71 100 125FXUQ-MA
8.0 11.2 14.09.0 12.5 14.0180 289 289160 269 269
165 x 895 x 895 230 x 895 x 895 230 x 895 x 89525 31 31
white19 / 14 29 / 21 32 / 2340 / 35 43 / 38 44 / 39
56 59 60R-410A
ø9.5 / ø15.9 ø9.5 / ø15.9 ø9.5 / ø15.9resin net with mold resistant
1~, 50Hz, 230VBEVQ71MA BEVQ100MA BEVQ125MA
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (HxWxD) mmWeight kgColourAir flow rate (H / L)Sound pressure level (H / L) (220V) dB(A)Sound power level (H) dB(A)Refrigerant typePiping connections liquid / gas mmAir filterPower supply V1Combination with junction box
Notes:
Capacities are net including a deduction for cooling (an addition for heating) for indoor fan motor heat.
71 100 125FXUQ-MA
BRC1D52BRC7C529BRC7C528
KDBHJ49F80 KDBHJ49F140KDBTJ49F80 KDBTJ49F140KDGJ49F80 KDGJ49F140
KAFJ495F140KHFP49M63 KHFP49M140
Wired remote controlInfrared remote control cooling only
heat pumpSealing member of air discharge outletAir discharge decoration panelVertical flap kitReplacement long life filterL-type connection piping kit
JUNCTION BOX FOR CONNECTION TO VRV
71 100 125BEVQ-MA
100x350x225x 3.0 3.5
galvanised steel plate1~, 50Hz, 220-240V
Dimensions H x W x D mmWeight kgCasingPower supply VE
BEVQ-MA
ACCESSORIES
SPECIFICATIONS
EPC08-201.indb 33 18-03-2008 09:51:22
34
F l o o r s t a n d i n g u n i t
Notes:
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*Data were not available at time of publication.
2.2 2.8 3.6 4.5 5.6 7.12.5 3.2 4.0 5.0 6.3 8.049 49 90 90 110 11049 49 90 90 110 110
600 x 1,000 x 222 600 x 1,140 x 222 600 x 1,420 x 22225 30 36
ivory white7/6 7/6 8/6 11/8.5 14/11 16/12
35/32 35/32 35/32 38/33 39/34 40/35* * * * * *
R-410Aø6.4/ø12.7 ø9.5/ø15.9
resin net with mold resistant1~, 50Hz, 220-240V
Cooling capacity kWHeating capacity kWNominal input cooling W
heating WDimensions (H x W x D) mmWeight kgColourAir flow rate (H/L) m3 /minSound pressure level (H/L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid/gas mmAir filterPower supply VE
ACCESSORIES
SPECIFICATIONS
20 25 32 40 50 63FXLQ-MA
FXLQ-MA
BRC1D52, BRC2C51, BRC3A61BRC4C64BRC4C62
KAFJ361K28 KAFJ361K45 KAFJ361K71
Wired remote controlInfrared remote control cooling only
heat pumpLong life replacement filter
20 25 32 40 50 63
EPC08-201.indb 34 18-03-2008 09:51:28
35
C o n c e a l e d f l o o r s t a n d i n g u n i t
Notes:
20 25 32 40 50 63FXNQ-MA
20 25 32 40 50 63FXNQ-MA
ACCESSORIES
SPECIFICATIONS
EPC08-201_23-52.indd 35 16-04-2008 09:35:42
36
The Daikin heat recovery ventilation system modulates thetemperature and humidity of incoming fresh air to matchindoor conditions. A balance is thus achieved betweenindoor and outdoor ambients, enabling the cooling orheating load placed on the air conditioning system tobe reduced significantlyHRV units can be controlledindividually or integral with the air conditioning systemDaikin VRV® or Sky Air series)
9 models to choose from›Compact, energy saving ventilation›Specially developed heat exchange element with›HEP (High Efficiency Paper)Easy integration into the VRV› ® systemConnectable to current Daikin control systems:›
Total heatexchangedfoul air
Clean outdoor air
Total heatexchangedclean airFoul indoor air
(1) Sound pressure level is measured in heat exchange mode.
VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM1000FA VAM1500FA VAM2000FA150 250 350 500 650 800 1,000 1,500 2,000
27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.569 64 98 98 93 137 157 137 13774 72 75 74 74 74 75 75 7558 58 61 58 58 60 61 61 6164 64 65 62 63 65 66 66 66269 269 285 285 348 348 348 710 710760 760 812 812 988 988 988 1,498 1,498509 509 800 800 852 852 1,140 852 1,14024 24 33 33 48 48 61 132 158
Ø 100 Ø 150 Ø 150 Ø 200 Ø 200 Ø 250 Ø 250 Ø 350 Ø 3501~, 50Hz, 220-240V
VAM-FA
VENTILATIONAir flow rate m3/hSound pressure level (max.) (1) dBAExternal static pressure (max.) PaTemperature exchange efficiency %Enthalpy exchange efficiency heating %
cooling %Dimensions H mm
W mmD mm
Weight kgDuct diameter mmPower supply VE
EPC08-201.indb 36 18-03-2008 09:51:54
37
VKM50GAM VKM80GAM VKM100GAM4.71 7.46 9.125.58 8.79 10.69
500 - 500 - 440 750 - 750 - 640 950 - 950 - 82037 - 35.5 - 32 38.5 - 36 - 33 39 - 37 - 3438 - 36 - 34 40 - 37.5 - 35.5 40 - 38 - 35.5
160 - 120 - 100 140 - 90 - 70 110 - 70 - 6076 - 76 - 77.5 78 - 78 - 79 74 - 74 - 76.564 - 64 - 67 66 - 66 - 68 62 - 62 - 6667 - 67- 69 71 - 71 - 73 65 - 65 -69
natural evaporating humdifier2.70 4.00 5.40387 387 387
1,764 1,764 1,764832 1,214 1,214102 120 125
1~, 220-240V, 50Hz
VENTILATION, DX COIL & HUMIDIFIERFresh air conditioning load cooling kW
heating kWAir flow rate ultra high - high - low m3/hSound pressure level - 220V ultra high - high - low dBASound pressure level - 240V ultra high - high - low dBAStatic pressure ultra high - high - low PaTemperature exchange efficiency ultra high - high - low %Enthalpy exchange efficiency - cooling ultra high - high - low %Enthalpy exchange efficiency - heating ultra high - high - low %Humidifier typeHumidification capacity kg/hDimensions height mm
width mmdepth mm
Weight kgPower supply V1
VKM-GAM
VKM-GA
VKM50GA VKM80GA VKM100GA4.71 7.46 9.125.58 8.79 10.69
500 - 500 - 440 750 - 750 - 640 950 - 950 - 82038 - 36 - 33.5 40 - 37.5 - 34.5 40 - 38 - 3539 - 37 - 35.5 41.5 - 39 - 37 41 - 39 - 36.5
180 - 150 - 110 170 - 120 - 80 150 - 100 - 7076 - 76 - 77.5 78 - 78 - 79 74 - 74 - 76.564 - 64 - 67 66 - 66 - 68 62 - 62 - 6667 - 67- 69 71 - 71 - 73 65 - 65 -69
387 387 3871,764 1,764 1,764832 1,214 1,21496 109 114
1~, 220-240V, 50Hz
VENTILATION & DX COILFresh air conditioning load cooling kW
heating kWAir flow rate ultra high - high - low m3/hSound pressure level - 220V ultra high - high - low dBASound pressure level - 240V ultra high - high - low dBAStatic pressure ultra high - high - low PaTemperature exchange efficiency ultra high - high - low %Enthalpy exchange efficiency - cooling ultra high - high - low %Enthalpy exchange efficiency - heating ultra high - high - low %Dimensions height mm
width mmdepth mm
Weight kgPower supply V1
Heat purge (economiser): heat accumulated indoors›is discharged at nightIntegration of humidification and air conditioning›into HRV unitIncreased static pressure thanks to improved fan›performanceIndividual control via HRV remote control›Connectable to current Daikin control systems:›
EPC08-201.indb 37 18-03-2008 09:51:58
38
Daikin has developed a new user friendly, software tool that allowsrapid VRV® selection and provides a professional result in the7 following steps:
Select indoor units1.Connect outdoor units to indoor units2.Automatic receipt of piping diagram with joints3.Automatic receipt of wiring diagram4.Connect appropriate centralised control systems5.Visualise result in Microsoft Word, Microsoft Excel and AutoCAD6. ®
Save project7.
Using VRV® Xpress enables VRV® selection to be achieved in a simple,complete and professional manner.
Windows95®, Windows98®, WindowsNT®, Windows2000®, WindowsXP® and WindowsVista®
are registered trademarks of Microsoft corporation.
EPC08-201_23-52.indd 38 21-04-2008 10:34:27
39
FEATURES:›
®
Expert mode:1.
Quick mode:2.
Drawing mode:3.
A simple to use, Daikin computerised selection programme, designed®, Windows 98®, WindowsNT®, Windows
®, Windows XP® ® systems, enables consulting
® air conditioning systems to be
®, Windows98®, WindowsNT® ®, WindowsXP® and®
EPC08-201_23-52.indd 39 04-04-2008 16:20:47
40
INFRARED REMOTE CONTROL›
Operation buttons: ON/OFF, timer mode start / stop, timer modeon /off, programme time, temperature setting, air flow direction (FXHQ,FXFQ, FXCQ and FXAQ models only), operating mode, fan speed control,filter sign reset, inspection / test indication
Display: Operating mode, battery change, set temperature, air flowdirection (FXHQ, FXFQ, FXCQ and FXAQ models only), programmed time,inspection / test operation, fan speed
SIMPLIFIED REMOTE CONTROL›
Simple, compact and easy to operate unit, suitable for use in hotelbedrooms
Operation buttons: ON/OFF, operating mode selection, fan speedcontrol, temperature setting
Display: Cool /heat changeover control, Heat Recovery Ventilation (HRV) inoperation, set temperature, operating mode, centralised control indication,fan speed, defrost /hot start, malfunction adjustment, operating modeselection, fan speed control, filter sign reset, inspection test /operation
SIMPLIFIED BUILT-IN REMOTE CONTROL›FOR HOTEL APPLICATIONS
Compact, user friendly unit, ideal for use in hotel bedrooms
Operation buttons: ON/OFF, fan speed control, temperature setting
Display: Heat Recovery Ventilation (HRV) in operation, set temperature,operating mode, centralised control indication, fan speed, defrost /hotstart, malfunction
EPC08-201.indb 40 18-03-2008 09:52:12
41
WIRED REMOTE CONTROL›
Limit operation (min/max): room temperature is controlled within›adjustable upper and lower limits. Limit operation can be activatedmanually or by schedule timerReal time clock: indicates real time and day›Schedule timer:›- It is possible to programme a weekly schedule timer- It is possible to programme the remote control for each day of
the week.Five day actions can be set as follows:· Set point: unit is switched ON and normal operation is
maintained· OFF: unit is switched OFF· Limits: unit is switched ON and min /max control (cf. limit
operation for more details)Home leave (frost protection): during occupants’ absence, the›indoor temperature can be maintained at a certain level. Thisfunction can also switch the unit ON/OFFDifferent levels of disabled buttons can be selected as follows:›- Level 1: all buttons are accessible- Level 2: all buttons are disabled except for: ON / OFF, set
temperature up /down, fan speed, cooling /heating mode,enable /disable schedule timer, air flow direction adjustmentbutton
- Level 3: all buttons are disabled except for: ON/OFF, settemperature up /down, fan speed
User friendly HRV function, thanks to the introduction of a button›for ventilation mode and fan speedConstantly monitoring of the system for malfunctions in a total of›80 componentsImmediate display of fault location and condition›Reduction of maintenance time and costs›
Operation buttons: ON /OFF, timer mode start / stop, timer on /off,programmed time, temperature setting, air flow direction adjustment,operating mode selection, fan speed control, filter sign reset, inspectiontest /operation
Display: Operating mode, Heat Recovery Ventilation (HRV) in operation,cool / heat changeover control, centralised control indication, groupcontrol indication, set temperature, air flow direction, programmedtime, inspection / test operation, fan speed, clean air filter, defrost /hotstart, malfunction
EPC08-201.indb 41 18-03-2008 09:52:13
42
UNIFIED ON/OFF CONTROL›
units›
2 remote controls in separate locations can be used››
Centralised control indication››
CENTRALISED REMOTE CONTROL›
›can be controlled
›
locationsZone control›
›››››
SCHEDULE TIMER›
››››
EPC08-201_23-52.indd 42 04-04-2008 16:20:47
Modem
43
The ideal solution forcontrol and managementup to 2,000 indoor units
APPLICATION AREAA small commercial area of less than›40 indoor units.Critical applications for centralized monitoring.›
SYSTEM LAYOUTAllows monitoring and control of up to up to 50›stores or sites and 2,000 indoor units with justone modem and phone line.Automates daily air conditioningoperation inorder›to free users from the hassle of air conditioningoperation /management.The daily schedule setting allows automatic›operation afterward.Automates alarm (report messages) for any›malfunctions /errors. Immediate report of anyindoor unit breakdown to the servicing company.Automatic report of breakdown/ malfunction›information.Minimizes the inconvenience of not having air›conditioning via rapid messages
FUNCTIONSSchedule setup (Daily schedule)›- Start / stopA/C malfunction report›- Send message to monitoring systemManual operation›- Start / Stop, set temperature, operation mode,
fan speedStatus monitoring›- Start / Stop, set temperature,- Operation mode, room temperature, operation
time, error code
Modem
Public phoneline
PC for monitoring
Malfunction
DS-NETadapter
Max. of 10 DS-NETadapters
RS4
85R
S232
C
P1 - P2 F1 - F2
P1 - P2 F1 - F2
EPC08-201.indb 43 18-03-2008 09:52:25
44
DIII-NET
Allows detailed and easy monitoring and operation of VRV® systems (max. 2 x 64 control groups)
LANGUAGESEnglish, French, German, Italian, Spanish
SYSTEM LAYOUTUp to 2x64 indoor units can be controlled›Onboard Ethernet port (web browser & e-mail)›Digital i / o contacts (option)›Touch panel (full colour LCD via icon display)›
MANAGEMENTWeb application & internet compatibility›- Monitoring & control according to user- Remote monitoring & control of more than one
building- Remote monitoring & control of more than one
building via internetPower Proportional Distribution (option)›PPD data is available on the internet›Easy management of electricity consumption›Enhanced history function›
CONTROLIndividual control (set point, start / stop, fan speed)›(max. 2x64 indoor units /groups)Schedule control (8 schedules, 17 patterns)›Flexible grouping in zones›Yearly schedule›Fire emergency stop control›Interlocking control›Increased HRV monitoring and control function›Automatic cooling /heating changeover›Quick selection and full control›Simple navigation›Heating optimization›Temperature limit›Password security: 3 levels›(general, administration & service)
CSV output of PPD(option) result
Public line
Air ConditioningNetwork ServiceSystem
OnboardEthernet
port
PCMCIAflash
memory
Onboard
modem
third party controller(domotics, BMS, etc.)
Ethernet
Links to the wattmeter whenusing the PPD (option) function
Remote monitoring /controlvia internet, e-mailPPD data is available oninternet
Pi-port
Malfunction
EPC08-201.indb 44 18-03-2008 09:52:34
45
MONITORINGVisualisation via Graphical User Interface (GUI)
Icon colour display change function›Indoor units operation mode›Error messages via e-mail & mobile phone (option)›Indication filter replacement›Multi PC›
COST PERFORMANCELabour saving›Easy installation›Compact design: limited installation space›Overall energy saving›
OPEN INTERFACECommunication to any third party controller›(domotics, BMS, etc.) is possible via open interface.
CONNECTABLE TOVRV› ®
HRV›Sky Air (via interface adapter)›Split (via interface adapter)›
Fire alarm
Forced OFF contact input
DIII-NET
Indoor units
Controls drainpump, lighting etc.
Monitoring of roomenter/exit sign
HRV
DIO unit
RS-232C
DIII-NET PLUSadapter
DIII-NET Allows monitoring/controlof up to 64 units (groups)
HRVIndoor unit
DI unit
EPC08-201.indb 45 18-03-2008 09:52:49
~
~
46
The ideal solution for control and managementof maximum 1,024 VRV® indoor units
SYSTEM LAYOUTUp to 1,024 indoor units can be controlled›(by 4 iPUs)Ethernet TCPIP /10 base / T communication›Integrated digital contacts on the Intelligent›Processing Unit (iPU)- 19 general input ports- 2 digital outputsStand alone operation of the iPU for minimum›48 hoursCompatible with UPS shutdown software›
Web Access
Sub PC
ETH
ERN
ET
Intranet/Internet Web Access
Malfunction reportby E-Mail
Dio unitPower supply facility
Daikin CentralAir Conditioning System
VRV® SystemLocal
monitoring& control
DMS502A51BACnet Gateway(monitoring only)
Air ConditioningNetwork Service System(Optional Maintenance Service)
ElectricityMeasurement
(Via Internet)
Ai unit
HRV
DAM602B51/52
MANAGEMENTWeb access function (option)›Power Proportional Distribution (option)›Operational history management (start/stop,›malfunction, operation hours)Generation of reports (graphics & tables)›(daily, weekly, monthly)Peak load shedding›Advanced tenant management›Sliding temperature›Eco mode (option)›
CONTROLIndividual control (setpoint, start / stop, fan speed)›(max. 1,024 indoor units)Group control (100 groups)›Schedule control (128 programs)›Fire emergency stop control (32 programs)›Interlocking control›Setpoint limitation›Automatic cooling heating changeover›Power failure / release control›Temperature limit (automatic start)›Timer extension›
MONITORINGVisualisation via a Graphical User Interface (GUI)›featuring free layoutOperation mode of indoor & outdoor units›Fault indication›Indication filter replacement›Setpoint indication›Operation time monitoring›Multi PC›On-line help›
Fire alarm
DIII-NET
DIII-NET
DIII-NET
DIII-N
ET
EPC08-201_23-52.indd 46 21-04-2008 10:34:39
47
Lonworks Networks CompatibleGateway
Interface for connection to›LonWorks® networksCommunication via Lon protocol›(twisted pair wire)64 units connectable per DMS-IF›Unlimited site size›Quick and easy installation›
Integrated control system connecting VRV® system with BMS system.
PPD data is available on BMS-system›Interface for BMS system›Communication via BACnet protocol›(connection via Ethernet)
256 units connectable per BACnet gateway›Unlimited site size›Easy and fast installation›
BUILDINGCONTROLNETWORK
LON BMS
FirealarmSystem
Security
adapterLonTalk
LonTalk
LonPoint LonPoint
(ETH
ERN
ET(T
CP/
IP
adapter
DMS504B51
Local Control
DIII- NET
VRV®
Outdoor unit
HRV
Remote Control
DAIKIN A/C INFRASTRUCTURE
DAIKIN A/C INFRASTRUCTURE
BMS
BA
CN
ET/E
THER
NET
Fire alarm Security
DMS502A51
Local ControlDAM602B51 /52(Intelligent Manager)
Control and monitoring
DIII- NET
VRV®
Outdoor unit
HRV
Remote Control
Power supply facility
Pump Lighting Elevator
BUILDINGCONTROLNETWORK
EPC08-201.indb 47 18-03-2008 09:53:17
48
INDIVIDUAL CONTROL SYSTEMS
BRC1D52BRC7F533 BRC7E531 BRC7C67 BRC4C63 BRC4C64 BRC4C64 BRC4C64 BRC4C66 BRC7C529 BRC7E66 BRC7E619 BRC4C64 BRC4C64BRC7F532 BRC7E530 BRC7C62 BRC4C61 BRC4C62 BRC4C62 BRC4C62 BRC4C65 BRC7C528 BRC7E63 BRC7E618 BRC4C62 BRC4C62
- - - - BRC2C51 BRC2C51 BRC2C51 BRC2C51 - - - BRC2C51 BRC2C51- - - - BRC3A61 BRC3A61 BRC3A61 BRC3A61 - - - BRC3A61 BRC3A61
Wired remote controlInfrared remote control cooling only
heat pumpSimplified remote controlSimplified remote control for hotel use
CENTRALISED CONTROL SYSTEMS
DCS302C51DCS301B51DST301B51
Centralised remote controlUnified ON/OFF controlSchedule timer
DESCRIPTION
OTHERS
DESCRIPTION
Wiring adapterWiring adapter (hour meter)Wiring adapter for electrical appendices (1)Wiring adapter for electrical appendices (2)Remote sensorInstallation box for adapter PCBElectrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)Noise filter (for electromagnetic interface only)External control adapterInterface adapter for Sky Air seriesConnector for forced on/forced off
- KRP1B57*1 - KRP1B61 KRP1B61 KRP1B56 - KRP1B61 KRP4A53 KRP1B3 - KRP1B61 KRP1B61EKRP1C11*1 - EKRP1B2 - EKRP1B2*2 - EKRP1B2 - - - - -KRP2A526*1 KRP2A526*1 KRP2A516*1 KRP2A61 KRP2A516 KRP2A53 KRP2A516 KRP2A61 KRP2A62* KRP2A51 KRP2A51 KRP2A51KRP4AA53*1 KRP4A536*1 KRP4A516*1 KRP4A51 KRP4A516 KRP4A54 KRP4A516 KRP4A51 KRP4A52* KRP4A51 KRP4A51 KRP4A51KRCS01-4 KRCS01-1KRP1H98 KRP1BA101 KRP1B96*3/4 - - KRP1BA101 - KRP1B97 KRP1C93*3 KRP4A93*3/4 - -
- KJB311AKJB212AA KJB212A
- KEK26-1A- DTA104A52 DTA104A51*1 DTA104A61 DTA104A51 DTA104A53 DTA104A51 DTA104A61 DTA104A62 DTA104A51 DTA104A61 DTA104A61- - - - - - - - DTA102A52 - - - -- - - - - - - - EKRORO - - - -
Notes:*1: Installation box is required*2: Fixing box is KRP1A90*3: Up to 2 adapters can be fixed per installation box*4: Only 1 installation box can be installed per indoor unit
DS-net adapterSoftware
DTA113B51 4 units can be connected per adapter, 40 units when 10 adapters are connectedDPC001B1-B51 Monitoring panel software
DCS601C51 2x64 units can be connectedDCS002C51 Power Proportional Distribution (PPD) softwareDCS004A51 E-mail / Web softwareDCS601A52 DIII NET-Plus adapterKJB411A For wall mounted installation1264009 Spare part n° of Touch-Pen for Intelligent Touch Controller
KRP928A2S For connection to Split unitsDTA102A52 For connection to R-22 / R-407C Sky Air unitsDTA112B51 For connection to R-410A Sky Air unitsDEC101A51 Input contacts: 16 pointsDEC102A51 Input contacts: 8 points; output contacts: 4 points
Intelligent Touch ControllerSoftware
HardwareInstallation boxTouch-PenInterface adapters
Digital inputDigital input/output
DESCRIPTION
DESCRIPTION
REFERENCE COMMENTS
REFERENCE COMMENTS
DESCRIPTION FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
EPC08-201.indb 48 18-03-2008 09:53:19
49
DAM602B51 256 indoor units per IPUDAM602B52 128 indoor units per IPU
IM3.XX Up to 1,024 indoor unitsKRP928A2S For connection to Split unitsDTA102A52 For connection to R-407C/R-22 Sky Air unitsDTA112B51 For connection to R-410A Sky Air units
DAM101A51 Outdoor temperature sensorDEC10151* Input contacts: 16 pointsDEC10251* Input contacts: 8 points; output contacts: 4 points
DAM002A51DAM003A51DAM004A51
Intelligent Processing unit
SoftwareInterface adapters
DIII AiDigital inputDigital input / outputPower Proportional DistributionECO ModeWeb Acces Function
DESCRIPTION REFERENCE COMMENTS
DMS502B51 64 units per GatewayDAM411B51 Extension of 3 x DIII lines (3 x 64) indoor unitsDAM412B51 For forced shutdownKRP928A2S For connection to Split unitsDTA102A52 For connection to R-407C/R-22 Sky Air unitsDTA112B51 For connection to R-410A Sky Air units
BACnet GatewayDIII boardDigital input/outputInterface adapters
DESCRIPTION REFERENCE COMMENTS
BMS: BUILDING MANAGEMENT SYSTEM
Conta
ct/a
nalog
signa
l
Parallel interface - Basic unitTemperature measurement unitsTemperature setting unitsUnification adapter for computerised controlWiring adapter for electrical appendices (1)
Wiring adapter for electrical appendices (2)External control adapter for outdoor unit
DIII-net expander adapter
Mounting kit
DPF201A51 enables ON/OFF command, operation and display of malfunction can be used in combination with up to 4 units.DPF201A52 enables temperature measurement output for 4 groups; 0~5VDC.»DPF201A53 enables temperature setting input for 16 groups; 0~5VDC.»DCS302A52 used for combining of air conditioning control computer and central remote controller (ON/OFF, display)KRP2A51 simultaneously controls air conditioning control computer and up to 64 groups of indoor units.KRP2A52
KRP4A51-53 to control the group of indoor units collectively, which are connected by the transmission wiring of remote controller.DTA104A51
cooling/heating mode change over, demand control and low noise control are available between the plural outdoor units.DTA104A52DTA109A51 a maximum of 10 outdoors or 128 indoors can be connected to 1 DTA109A51
a maximum of 8 DTA109A51 can be connected to DIII-netKRP4A92 for easy installation of the DTA109A51
DESCRIPTION REFERENCE COMMENTS
DMS504B51 Up to 64 units can be connected per DMS-IFKRP928A2S For connection to Split unitsDTA102A52 For connection to R-407C/R-22 Sky Air unitsDTA112B51 For connection to R-410A Sky Air units
LONWORKS® networks compatible GatewayInterface adapters
DESCRIPTION REFERENCE COMMENTS
EPC08-201.indb 49 18-03-2008 09:53:20