24
RAS GAS COMPANY RasGas PLANT HARMONICS STUDY ‐Harmonics Measurement‐ Prof. Lazhar Benbrahim 1 , Prof. Mohieddine Benammar 1 , Eng. Jesus Romero 2 1 : Qatar University Professors and RasGas Chairs in Industrial Electronics 2 : Electrical Engineer at RasGas 01/8/2010 [The increasing use of nonlinear loads, in modern industry is keeping harmonic distortion in distribution networks on the rise. Keeping the level harmonics under the standard limits is very crucial to the stability of the power networks. The objective of this harmonic study of RasGas LNG plant is the measurement of harmonics and investigation of compliance with IEEE 519 harmonics standards.]

RasGas Plant Harmonics Study-Final Report

Embed Size (px)

DESCRIPTION

RasGas Plant Harmonics Study-Final Report

Citation preview

  • RASGASCOMPANY

    RasGas PLANTHARMONICSSTUDY

    HarmonicsMeasurement

    Prof.LazharBenbrahim1,Prof.MohieddineBenammar1 ,Eng.JesusRomero2

    1: Qatar University Professors and RasGas Chairs in Industrial Electronics

    2: Electrical Engineer at RasGas

    01/8/2010[The increasing use of nonlinear loads, in modern industry is keeping harmonic

    distortion indistributionnetworkson the rise.Keeping the levelharmonicsunder the

    standard limits isverycrucial to the stabilityof thepowernetworks.Theobjectiveof

    this harmonic study of RasGas LNG plant is the measurement of harmonics and

    investigationofcompliancewithIEEE519harmonicsstandards.]

  • 2

    Acknowledgment

    We would like to acknowledge the help from RasGas Engineers and Technicians

    for their help in carrying out the measurements at RasGas plant.

    We would like also to thank all those who helped in this project.

    Prof.LazharBenBrahim

    Prof.MohieddineBenammar

    Eng.JesusRomero

  • 3

    Abstract

    The increasing use of power electronics equipment in modern industry is

    keeping harmonic distortion in distribution networks on the rise. The most nonlinear

    devices used in the gas processing industry are the VFDs. These and other devices

    generate harmonics in the network of the plant. Keeping the level of these disturbances

    under certain limits is very crucial to the stability of the power networks. The objective of

    this harmonic study of RasGas LNG plant is the measurement of harmonics and

    investigation of compliance with IEEE 519 harmonics standards.

    Measurements of harmonics at various points of the plant have been carried out

    using dedicated power quality analyzers. The results of these measurements have been

    thoroughly analyzed. The measurements and interpretation of the results indicate overall

    compliance with IEEE 519 standard. All voltage harmonics (Total Harmonics Distortion

    and individual harmonics) at the various PCC (33kV, 6.6kV and 415V) meet the

    standard. Almost the same goes for the Total Demand Distortion (TDD) for the current.

    However, in some cases, some concerns are noted for the 48th harmonic current around

    the VSCF. The UPS and battery chargers exhibit high THDI but given their low power, in

    many cases this translates to acceptable TDDI and in all cases the chargers have little

    impact on the power network. It is noted also that some 415 buses are not balanced from

    the point of view linear versus non-linear loads. It is recommended that this is taken into

    consideration in future expansion, as significant unbalance may result in violations of

    harmonics standards.

  • 4

    TABLE OF CONTENTS

    1. INTRODUCTION..................................................................................................5

    1.1. Motivation ........................................................................................................... 51.2. Measurement Preparation & Planning ................................................................ 62. BACKGROUND ....................................................................................................7

    2.1. Terminology ........................................................................................................ 72.2. Scope of Study and Standards ............................................................................. 92.3. Plant Network ................................................................................................... 122.4. Nonlinear Loads ................................................................................................ 133. MEASUREMENT................................................................................................13

    4. ANALYSIS ...........................................................................................................18

    4.1. Introduction ....................................................................................................... 184.2. Analysis............................................................................................................. 19

    4.2.1. Voltage Harmonics Study ........................................................................... 194.2.2. Current Harmonics Study ........................................................................... 20

    5. CONCLUSIONS & RECOMMENDATIONS ..................................................23

    6. REFERENCES .....................................................................................................24

    APPENDIX.Appendix1

  • 5

    1. INTRODUCTION

    1.1. Motivation

    Power quality is a big concern to facility designers and operators. When the quality of

    electrical power supplied to equipment is deficient, performance degradation results. A

    good power quality necessitates a thorough study of several issues (Fig. 1) [1]. In its

    quest to make sure that the power quality of its network is up to the international

    standards, RasGas has launched several studies. Among these studies is the harmonics

    study of their LNG plant. LNG plants are relying more and more on modern electronic equipments which are

    nonlinear loads that may cause harmonic distortion in distribution networks. The most

    used nonlinear device in modern industry is perhaps the static power electronics

    converter (e.g., UPS, battery chargers and drives), [1]. A situation that has raised

    waveform distortion levels in distribution networks. Keeping the level of these

    disturbances (also called harmonics) under certain limits is very crucial to the stability of

    the power networks. Harmonic studies are effective way to keep networks and equipment

    under acceptable operating conditions and to foresee potential problems with the

    installation.

    Fig. 1: Power quality issues

    PowerQuality

    POWER FREQUENCY

    DISTURBANCES

    ELECTRO MAGNETIC

    INTERFERENCE

    POWER SYSTEM

    TRANSIENTS

    ELECTRO STATIC

    DISCHARGE

    POWER SYSTEM

    HARMONICS

    POWER FACTOR

    GROUNDING AND

    BONDING

  • 6

    1.2. Measurement Preparation & Planning

    The RasGas chairs together with Engineer Romero have carried out a thorough search of

    suitable equipment to be used in the harmonics study. The main features of the

    recommended equipment, the manufacturer and regional supplier, datasheets and sample

    quotation from a vendor were included in the proposal. It was decided to acquire two sets

    of power quality analyzers (PQA) type HIOKI-3196 from Japan. This equipment is a

    highly advanced measuring instrument with excellent features that enable monitoring and

    recording of normal and abnormal phenomena related to power supply quality. The

    process of acquiring the equipment was lengthy, and as a result it was received on 6th of

    January 2009.

    The RasGas industrial electronics chairs received one of these two sets for testing and

    calibration in the Power Electronics Lab at Qatar University. Extensive tests have been

    carried out using a test bench made of power electronics equipment that can generate

    specific and controlled harmonics spectrum. It was concluded from these tests that the

    Hioki-3196 provides highly accurate harmonics measurements and is well suited to the

    harmonics study at RasGas plant.

    Following successful testing of the equipment in the lab, it was decided to proceed with

    training of RasGas engineers/technicians and with subsequent data collection from the

    plant as follows:

    1. Training was offered on February 3rd 2009 at the Power Electronics Lab of Qatar

    University (Fig. 2). Five persons from RasGas: 3 engineers and 2 technicians have

    attended this training on proper use and handling of the power quality analyzer

    (HIOKI-3196). After an appropriate introduction about power harmonics (see

    training slides in Appendix), various aspects have been detailed including

    techniques of connections and setting of the system for the measurement, what to

    measure, where to measure, for how long, how to record and collect the data, etc.

    RasGas engineers were then able to use the PQA in a real power system with

    proper power electronics equipment.

  • 7

    2. The measurements and data collection in the plant was planned. All critical points

    where potential generation of harmonics was suspected have been considered

    (VFDs, UPSs, Battery Chargers etc.).

    2. BACKGROUND

    2.1. Terminology

    9 Point of Common Connection (PCC): A point of metering between the utility and consumer. Within an industrial plant, the PCC is the point between the

    nonlinear load and other loads. This implies that harmonic limits must be met

    internally, in the consumers system. Many consultants, for example, use this

    Fig. 2: Harmonics Measurement Training: RasGas engineers and technicians in the training about the PQA at the Power Electronics Laboratory of Qatar University on February 3rd 2009

  • 8

    statement to try to force manufacturers of nonlinear loads (drives, UPS, battery

    chargers, rectifiers, etc.) to adhere to the IEEE 519 limits for a single load [2].

    Furthermore, in LNG plant, power is generated in house and several PCC exist as

    a result harmonics limit should be met at all voltage level and all bus bars.

    9 Short Circuit Ratio (ISC/IL): The ratio of the short circuit current (ISC) available at the point of common coupling (PCC) to the maximum fundamental load current

    (IL).

    9 Voltage THD (THDV): Total Harmonic Distortion of the voltage waveform. The ratio of the rms (root-mean-square) value of the harmonic content of the voltage

    to the rms value of the fundamental voltage:

    %100....

    1

    25

    24

    23

    22

    1

    2

    2

    ++++===

    VVVVV

    V

    VTHD h

    h

    V (1)

    where Vh is the rms of the hth harmonic voltage, in volt. V1 refers to the

    fundamental frequency (50Hz) voltage. V2 refers to the second harmonic, or the

    voltage at twice the fundamental frequency (100 Hz, if the fundamental is 50 Hz)

    and so on.

    9 Current THD (THDI): Total Harmonic Distortion of the current waveform. The ratio of the rms value of the harmonic content of the current to the rms value of

    the fundamental current:

    %100....

    1

    25

    24

    23

    22

    1

    2

    2

    ++++===

    IIIII

    I

    ITHD h

    h

    I (2)

    Where Ih is the rms of the hth harmonic current, in Amperes. I1 refers to the

    fundamental frequency (50Hz) current. I2 refers to the second harmonic, or the

    current at twice the fundamental frequency (100 Hz) and so on.

    9 Current TDD (TDDI): Total Demand Distortion of the current waveform. The

    ratio of the rms value of the harmonic content of the current to the maximum

    demand load current:

  • 9

    %100....25

    24

    23

    222

    2

    ++++===

    LL

    hh

    I IIIII

    I

    ITDD (3)

    Where IL is the maximum demand load current, in Amperes.

    The term total demand distortion or TDD is very much like the total harmonic distortion,

    or THD. The two definitions are very much alike. The only difference is the denominator.

    The THD calculation compares the measured harmonics with the measured fundamental

    current. The TDD calculation compares the measured harmonics with the maximum

    demand current. Similarly, the individual harmonic current limits are not given in terms

    of percent of fundamental (as is typical of most harmonic measurements) at a given point

    of time. The current limits in the standards are given in terms of Maximum Harmonic

    Current Distortion in Percent of IL. Note that commercially available instruments

    measure THD and individual harmonics in percent of I1. So a post-processing of

    measured data may be necessary to verify whether the measurement are complying with

    the standards or not.

    2.2. Scope of Study and Standards

    The scope of the present study is the measurement of harmonics for RasGas plant and the

    verification of the compliance of the plant power network with the standards. The IEEE

    519, Recommended Practice and Requirements for Harmonic Control in Electrical

    Power Systems (1992) has been used in this study [2].

    If harmonics increase above certain limits, some harmful effects on electrical equipment

    may occur. Some of these effects are listed below:

    9 Capacitor bank failure

    9 Excessive losses, heating, and harmonic torques in AC motors

    9 Over-voltages and excessive currents in the power system, resulting from resonance.

  • 10

    9 Derating of cables due to additional eddy current heating and skin effect losses.

    9 Inductive interference with telecommunication circuits.

    9 Signal interference and relay malfunctions, particularly in solid-state and digitally controlled systems.

    9 Unstable operation of firing circuits relying on zero voltage crossing detection and latching.

    9 Interference with large motor controllers

    Standards were developed to keep harmonics under some acceptable limits. These

    limits are described by IEEE 519 harmonics standard which indicates the Recommended

    Practice and Requirements for Harmonic Control in Electrical Power Systems (see Table

    1&2). Note that voltage harmonics and current harmonics are assessed through the THD

    and TDD respectively. The TDD is the total demand distortion and is identical to the

    THD except that the maximum load current (IL) is used instead of the fundamental

    current component (I1). The measured harmonics distortion of voltage and current levels

    are therefore compared to the allowable limits recommended by IEEE-519 standards [2].

    Table 1: IEEE 519-1992 Standard: Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems (Voltage Distortion Limits)

    Maximum harmonic voltage distortion in percentage of the fundamental

    Bus Voltage Voltage Harmonic limit as (%) of fundamental THD_V %

    = 161 KV 1.0 1.5

  • 11

    Table 2: IEEE standard 519-1992 maximum current distortion

    Maximum harmonic current distortion in percentage of the fundamental

    V 69 kV

    ISC

    / IL h

  • 12

    2.3. Plant Network

    The electrical network of the RasGas LNG plant is fed from Kahrama and local in house

    generators. All sources are working in parallel. The electrical network configuration used

    for the harmonic analysis is the complete system in normal operation with all the loads of

    Train 1 to 5 connected and Train 6&7 under commissioning.

    9 Utility KAHRAMAA (QGEWC) and 91-GT 052, 91-GT 053, 91-GT 054, 91-GT 055 generators feed the SS A HV 132kV substation.

    9 The LNG Trains 3 & 4 are fed by 91-GT 051 generator and by the SS A HV 132kV substation through three step down transformers 132/34.5 kV, 60/75 MVA

    (ONAN/ONAF) with automatic OLTC.

    9 The LNG Train 5 is fed by the SS A HV 132kV substation through two step down transformers 132/34.5 kV, 85/100MVA (ONAN/ONAF) with automatic OLTC

    9 The LNG Trains 1&2 are fed by four generators and export to SS A HV 132kV substation through one step down transformer 138/33 kV, 60/75 MVA

    (ONAN/ONAF) with automatic OLTC

    9 The substation SS 102 is fed by the SS A HV 132 kV substation through three step down transformers 132/34.5 kV, 75/90 MVA (ONAN/ONAF) with

    automatic OLTC.

    9 The LNG Train 6 & 7 are fed by two generators per train, EVFDs and backed up by the SS A HV 132 kV transformer 132/34.5 kV, 75/90 MVA (ONAN/ONAF)

    with automatic OLTC.

    9 The substation SS 103 is fed by the SS A HV 132 kV substation through two step down transformers 132/34.5 kV, 75/90 MVA (ONAN/ONAF) with automatic

    OLTC.

  • 13

    2.4. Nonlinear Loads

    Nonlinear loads are loads in which the current waveform does not resemble the applied

    voltage waveform due to a number of reasons [3]. Among the most common nonlinear

    loads in power systems are:

    9 Power converters 9 Variable Frequency Drives (VFDs) 9 DC Drives 9 Cycloconverters 9 Cranes 9 Elevators 9 Power supplies 9 Uninterruptible Power Supplies (UPSs) 9 Battery chargers (BCs) 9 Inverters 9 Fluorescent lighting 9 ARC furnaces 9 Welding machines

    In an LNG plant many nonlinear loads exist especially the VFDs, UPSs and BCs which

    are the main sources for voltage and current harmonics in the power plant networks.

    3. MEASUREMENT

    Following the acquisition of the two sets of PQA and the adequate training carried out

    for RasGas engineers, the first measurement was conducted on March 2nd 2009, we have

    recorded some data around a well know harmonics-generating equipment (SS-

    53:TR5342,TR5343, TR5344 which includes VFDs installations and we also verified the

    UPS units UPS5731A and UPS5731B) and the data confirmed the existence of harmonics

    as expected. This initial test gave us trust on the technician measurement capability and a

    confidence in the reliability of the PQA, and decided to proceed with a wide range of

    measurements at various locations in the plant. Instructions were given by the chairs to

  • 14

    the measurement team composed of RasGas engineers and technicians (to check the

    direction of connections of the current sensors and to increase the sampling frequency of

    measurement as the data taken is two little).

    Extensive measurement has started on April 7th 2009, and due to periodic maintenance

    at the RasGas plant several delays in the measurement occur. It is worth noting that we

    were suspecting harmonics from nonlinear loads such as VFDs, UPSs, BCs and in a

    lesser gravity from transformers that may operate in saturation or resonant conditions. As

    data was received, the chairs and engineer Romero were checking for data that may

    represent a threat to the grid. Depending on measurement results, in some cases further

    measurements were carried out to verify the causes for some of the measured harmonics,

    this is the case of the Variable Speed Constant Frequency (VSCF) generators. Therefore,

    harmonics spectrum especially at the 6.6kV may change depending on the operating

    conditions of the plant where VSCF is in service. This has caused some delays in order to

    investigate more the causes of these harmonics. The last data collected were carried out

    by mid-December 2009. The period of measurement lasted 8 months which were enough

    to carry out measurement at various operating conditions.

    Sample of measurement data are shown in the Appendix. For each measurement point the

    followings are given:

    1. A general information about the measurement point (Hioki DMM tables)

    2. Voltages and currents waveforms as well as harmonics spectrum

    3. Lists of harmonics and THDs for the voltages and currents

    Note that all measured data are stored into a CD included with this report.

    The plant is composed of several trains and several substations which are more or less

    similar. Measurements shown in this report were selected and represent all types of

    loads within the plant. Focus is on the SubStation SS02 which contains the most critical

    nonlinear loads of the plant. Measurements at other substations (SS01 & SS03) were

    carried out for the validation of the results obtained in SS02.

  • 15

    A summary of the results obtained from measurements carried out in SS01, SS03 and

    mainly in SS02 is given in Table 3 below. A detailed analysis of these results is given in

    the section below.

    Table 3 : Summary of voltage/current harmonics measurement (the noted problems are highlighted).

    LoadTypes POWER(MW)

    (measured)Short Circuit

    Current Isc (kA)

    VOLTAGE(kV)(atMeasurement

    point)TotalHarmonicDistortionTHDV

    CURRENT(A)(atMeasurementpoint)

    TotalHarmonicDistortionTHDITotalDemandDistortionTDDI

    TR 0221 (GT 051)

    12.00 33 222.7 THDV=3.15% THDI=3.28%

    TR 5143 11.96 33 228 THDV=2.67% THDI=1.8%

    TR 5142 12.38 33 239 THDV=2.74% THDI=0.43%

    TR 5154-2 1950 KVA

    1.13 6.6 99.7

    Isc= 0.2 THDV=3.03% THDI=4.46% I48/I1=3.7%

    Isc /IL=1.2 TDDI=2.61% (0.3%)

    TR 5141B 4/5 MVA

    0.67 6.6 69.7

    Isc= 5.6 THDV=2.72% THDI=6.8% I48/I1 =4.3%

    Isc /IL=16 TDDI=1.35% (0.3%)

    TR 5155-2 1550 KVA

    0.884 6.6 77.88

    Isc= 0.2 THDV=2.65% THDI=6.65% I48/I1=3.9%

    Isc /IL=1.5 TDDI=3.82% (0.3%)

    TR 5151A 1600 KVA

    0.330 0.415 540.8

    Isc= 26 THDV=2.26% THDI=1.52% I48=0.9%

    Isc /IL=11 TDDI=0.36% (

  • 16

    TR 5152E 400 KVA

    0.047 0.415 90.23

    Isc= 24.6 THDV=1.53% THDI=30.73% I5/I1=28.52%

    Isc /IL=44 TDDI=5.0% (

  • 17

    1950 KVA Isc= 0.2 THDV=2.94%

    THDI=4.26% I48/I1=3.64%

    Isc /IL=1.2 TDDI=1.84% (0.30%)

    TR 5355-2 1550 KVA

    0.733 6.6 76.38

    Isc= 0.2 THDV=2.79% THDI=4.24% I48/IL=3.56%

    Isc /IL=1.5 TDDI=2.38% (0.30%)

    TR 5351A 1600 KVA

    0.366 0.415 563

    Isc= 26 THDV=2.02%

    THDI=2.17% I48/I1=1.19%

    Isc /IL=11 TDDI=0.55% (0.30%)

    TR 5351B 1600 KVA

    0.065 0.415 140

    Isc= 24.4 THDV=3.0% THDI=4.32% I48/I1=0.45%

    Isc /IL=11 TDDI=0.27% (

  • 18

    11.5/2-5.75 MVA Isc= 31.4 THDV=2.66%

    THDI=8.87% I11/I1=7.03%

    Isc /IL=156 TDDI=2.75% (

  • 19

    a. 33kV bus level

    b. 6.6kV bus level

    c. 415V bus level

    2. Current harmonics measurement data measured at nonlinear and linear loads which are connected to PCCs with various voltage levels.

    4.2. Analysis

    4.2.1. Voltage Harmonics Study

    This is the most critical information in the analysis of harmonics. The acceptance criteria

    for the harmonic study according with the IEEE 519 standard (Table 1) are:

    1. Maximum total voltage distortion THDV : 5%;

    2. Maximum voltage distortion for each harmonic Vh : 3%;

    Summary of all harmonics measurement data are given in Table 3. The study showed that

    all the measured voltage harmonics at the plant comply with the IEEE 519 standard; the

    highest THDV was only 3.03% and it is well below the 5% limit of the standard; this

    maximum THD was recorded at the PCC SB5141A (TR5154-2, in train#4 Substation

    SS51 at the 6.6kV level). It is worth to note that this distortion is at the point of coupling

    with the Variable Speed Constant Frequency (VSCF) and was recorded on November

    25th 2009. This VSCF indicated some concerns in the current harmonics compliance, and

    is further discussed below.

  • 20

    Figure 3: Voltage & current waveforms at 6.6kV PCC : TR5154-2 with THDV= 3.03%

    (while the VSCF is connected to the PCC and generating power to the network).

    4.2.2. Current Harmonics Study

    Methodology:

    Unlike the voltage harmonic limits of the IEEE 519 standard, the current harmonic limits

    depend on the short circuit level of the system they are being injected into. The limit for

    the current harmonics according with the IEEE 519 (Table2) depends on (Isc/IL): ratio of

    the short circuit current (Isc) available at the PCC to the maximum load current (IL).

    In the current harmonics study, we should be selective as it is impractical to measure at

    all loads. Sometimes current harmonic distortion can be assessed through simple

    inspection of the types of loads. All this requires is familiarity with the characteristic

    harmonic spectrum of each type of common nonlinear load. However, harmonics

    measurement is essential to verify their compliance with the IEEE519 standards. These

    current harmonic measurement data are useful for some of these nonlinear loads that may

    need designing suitable harmonic filters. This involves direct measurements at selected

    locations for example, the point of common coupling (PCC) and the node where

    nonlinear loads are connected.

  • 21

    We started the measurements by emphasis on the nonlinear high power loads which

    consist of the Mega- drives called VDFs, AFDs or simply drives. Given that the power

    quality analyzer (PQA) instruments provide measurement of the THD for both current

    and voltage quantities, and in order to compare results against the IEEE standard, it was

    necessary to compute the TDDI from the THDI, IL, I1, and Isc. Since the TDDI is always

    less or equal than THDI, the followings procedure for current harmonics analysis is

    adopted and applied in Table 3:

    Case 1. THDI and all individual harmonics are less than the minimum of the

    standard limits (for the strictest limit applicable to ISC/IL1000), then there is violation of the IEEE 519 standards and no

    further calculation is needed.

    Case 3. Above cases are not applicable. In this case, we proceed as follows:

    i. The ratio ISC/IL is determined to identify the appropriate row in

    Table 2.

    ii. TDDI is determined: TDDI= THDI(I1/IL).

    iii. Determine harmonic current distortion in percent of IL from (Ih/I1)

    which is PQA-measured value: Ih/IL= (Ih/I1)(I1/IL).

    iv. Use the computed values in (ii) and (iii) to compare distortion to

    the IEEE limits (Table 2). The example shown below illustrates the

    applied method.

    Analysis:

    As illustrated in Table 3 the measurements show that the mega drives, whether VSI type

    (without filters) or LCI type (with filters) used for the helper motors of the compressors,

    are complying with the IEEE519 standards. This is a reassuring result as these drives are,

    currently, the largest non-linear loads. From the table, we note for example that the THDI

  • 22

    values for VFDs connected to TR5342, TR5343 and TR5344 are 3.07%, 1.75% and

    2.89% respectively. These values are complying even with the strictest limits of the TDDI

    (

  • 23

    carrying more measurements where VSCF are not connected to the bus. This has pointed

    out to the fact that the 48th harmonic was not load-injected distortion but rather VSCF-

    generated. This voltage harmonic component induced a current with the similar

    harmonics content where the dominant harmonic was the 48th (see Figure 3). The IEEE

    standard stipulates that the first row of Table 2 must be applied for all generators

    regardless of the actual value of Isc/IL. As shown in Table 3 and after processing all the

    data, the results indicate no violation at the TDDI level. However, the 48th harmonic

    component of the current is beyond the limits for TR5154-2 (I48/IL=2.16%>0.3%) and

    TR5155-2 (I48/IL=2.24%>0.3%), both of which are connected to the VSCF generators.

    This harmonic component is most likely caused by the VSCF; this may be substantiated

    by the following reasons: (a) the non-linear loads at the plant are not expected to inject

    this 2.4 kHz component (48th harmonic); (b) measurements at substations where no

    VSCF are connected show no presence of such harmonic (see data for TR5241A,

    TR5241B, TR5441A and TR5441B in Table 3). This could be further confirmed by

    measurement using the PQA, as this is capable distinguishing the outflow and inflow

    harmonics. Unfortunately, many of the measurements taken including these taken around

    the VSCF have been carried out by technicians without proper training. Thus the

    collected data is adequate for evaluating harmonics but could not be used to precisely

    determine source of injected harmonics.

    We note that, although not violating the TDDI limits of the IEEE standard in all cases

    except for one (UPS0171A in SS01), the UPS and battery chargers used in the plant are

    exhibiting very high THDI (in some cases around 50%). The reason the TDDI limits are

    not generally violated is because these units are operating well below their rated power.

    Care must be taken in future in case the load of these units is increased, as this would

    raise the TDDI to levels that may violate IEEE limits.

    5. CONCLUSIONS & RECOMMENDATIONS

    From the present harmonics study, the measurements and interpretation of the results

    indicate overall compliance with IEEE 519 standard. All voltage harmonics (Total

  • 24

    Harmonics Distortion and individual harmonics) at the various PCC (33kV, 6.6kV and

    415V) meet the standard. Almost the same goes for the Total Demand Distortion (TDD)

    for the current. However we note that, in some cases, the individual harmonic current

    violates the IEEE limit especially around the VSCF. From harmonics point of view, this

    VSCF generator is the weakest unit in the studied network; it is recommended that

    solutions to mitigate harmonics generated by these units be considered. Although so far

    this did not cause any problem to the LNG plant as the generated harmonics are

    intermittent and therefore the better way to deal with it is to report findings to the

    manufacturer in order to fix this within the equipment itself. The UPS and battery

    chargers exhibit high THDI (in some cases around 50%). The reason the TDDI limits are

    not generally violated is because these units are operating well below their rated power.

    Care must be taken in future in case the load of these units is increased, as this would

    raise the TDDI to levels that may violate IEEE limits.

    It is noted that some 415 buses are not balanced from the point of view linear versus non-

    linear loads. It is recommended that this is taken into consideration in future expansion,

    as significant unbalance may result in violations harmonics standards.

    6. REFERENCES

    [1] Francisco C. De La Rosa, Harmonics and Power Systems Taylor & Francis

    Group, LLC CRC Press, 2006.

    [2] IEEE 519 Standard : Reference Standard

    [3] Mohan, Undeland and Robbins Power Electronics: Converters, Application and

    Design,. Published by John Wiley & Sons, 1989, 667 pages.

    [4] RGX-S-91-2181-020Rev2- Electrical Network Studies-Short Circuit