67
PSN-PX 10.11.2010 RTU560/RTU211 © ABB Group February 18, 2012 | Slide 1 RTU560/RTU211 Modules 1KGT 150 648 V1.02

RTU560 ABB

Embed Size (px)

DESCRIPTION

document sur l'RTU 560 de ABBdescription des module

Citation preview

  • PSN-PX 10.11.2010

    RTU560/RTU211

    ABB Group February 18, 2012 | Slide 1

    RTU560/RTU211Modules

    1KGT 150 648 V1.02

  • ModulesContents

    RTU560 rack solutions

    Subracks

    CMUs CMUs

    I/Os

    Communication modules

    Auxiliary

    RTU560/RTU211 DIN rail solutions

    CMUs

    I/Os

    Communication modules

    ABB Group February 18, 2012 | Slide 2

    Communication modules

    Auxiliary

    RTU560E

  • Modules RTU560 rack solution

    560CSR01

    Available for wall mounting and

    Subracks

    CMUs

    I/Os

    Communication

    modules

    swing frame

    Supports redundant power supplies

    Up to 8 communication modules

    Expansion slot for 560BCU01

    Real time clocks 560RTC01/02/03

    Network modules 560NUS04/12

    Auxiliary

    ABB Group February 18, 2012 | Slide 3

    Network modules 560NUS04/12

    No I/O module

  • NCC(s)

    Modules RTU560 rack solution

    Subracks

    CMUs

    I/Os

    Communication

    modules

    560CSR01

    1...16 serial lines or

    Ethernet links

    560PSU02

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    560PSU02

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    560BCU01

    ALR

    WRN

    TSI

    TSO

    SEB

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560PSU02

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    560PSU02

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    560PSU02

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    560PSU02

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    560BCU01

    ALR

    WRN

    TSI

    TSO

    SEB

    560BCU01

    ALR

    WRN

    TSI

    TSO

    SEB

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    EE

    EE

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    EE

    EE

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    EE

    EE

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    560CMU05

    A

    B

    1

    2

    E1

    E2

    ERR

    EE

    EE

    560PSU02

    24 V

    560PSU02

    24 V

    560BCU01

    ALR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    560PSU02

    24 V

    560PSU02

    24 V

    560PSU02

    24 V

    560PSU02

    24 V

    560BCU01

    ALR

    560BCU01

    ALR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    560CMU05

    ERR

    System bus

    Distance < 2m

    560CSR01 (opt.)

    1... 32 subdevice lines

    560CSR01

    Auxiliary

    ABB Group February 18, 2012 | Slide 4

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    ALR

    WRN

    TSI

    TSO

    SEB

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    EA

    B

    1

    2

    E1

    E2

    ERR

    E

    EA

    B

    1

    2

    E1

    E2

    ERR

    E

    EA

    B

    1

    2

    E1

    E2

    ERR

    E

    E

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    24 V

    5 V

    ON

    OFF

    UE +

    UE -

    PE

    ALR

    WRN

    TSI

    TSO

    SEB

    ALR

    WRN

    TSI

    TSO

    SEB

    A

    B

    1

    2

    E1

    E2

    ERR

    E

    EA

    B

    1

    2

    E1

    E2

    ERR

    EE

    EEA

    B

    1

    2

    E1

    E2

    ERR

    E

    EA

    B

    1

    2

    E1

    E2

    ERR

    EE

    EEA

    B

    1

    2

    E1

    E2

    ERR

    E

    EA

    B

    1

    2

    E1

    E2

    ERR

    EE

    EEA

    B

    1

    2

    E1

    E2

    ERR

    E

    EA

    B

    1

    2

    E1

    E2

    ERR

    EE

    EE

    1... 32 subdevice lines

    (serial or Ethernet) with

    1> 32 IEDs per subdevice line

    IEDs

  • ModulesRTU560 rack solution

    560MPR03 & 560SFR02

    Available for wall mounting (560MPR03) and swing frame

    Subracks

    CMUs

    I/Os

    Communication

    modules(560MPR03) and swing frame (560SFR02)

    Supports 1 or 2 power supply units (560PSU01/02)

    Up to 8 units 560CMU05 (up to 5,000 data points) or 560CMU02R0002 are supported

    Solely CMU rack with 560CMU02 and 560CMU05

    Auxiliary

    ABB Group February 18, 2012 | Slide 5

    and 560CMU05

    Mixed configurations with CMU and I/O

    Mixed configurations with 560CMU05 and 560CMU02 (limited to 750 data points in the RTU)

    Redundant power supply, 17 slots

    Single power supply, 18 slots

  • ModulesRTU560 rack solution

    23ET24 and 23TP22

    23TP22 version for mounting plate mounting

    Subracks

    CMUs

    I/Os

    Communication

    modulesmounting

    23ET24 version for swing frame mounting

    1 slot for power supply (560PSU01/02)

    19 general purpose slots

    All rack mounted I/O modules

    Real time clocks 560RTC01/02/03

    Auxiliary

    23ET24

    ABB Group February 18, 2012 | Slide 6

    Up to 2 communication modules

    Communication media interfaces

    Used as

    Basic rack

    I/O extension rack

    23TP22

  • 560MPR01

    1 or 2 Slots for 560CMU02 or 560CMU05

    ModulesRTU560 rack solution

    Subracks

    CMUs

    I/Os

    Communication

    modules 560CMU05

    Up to 8 slots for I/O modules

    24 V DC external power supply

    Extension connector for I/O bus (extension rack, I/O modules 110/220 V DC)

    Alarm and warning contact output

    Separate input for process voltage(48>60 V DC)

    Auxiliary

    ABB Group February 18, 2012 | Slide 7

    (48>60 V DC)

    Power distribution for monitoring and command voltage

    23BA22 configurable for 1,5 pole command outputs

    Screw connectors, access from front

  • ModulesRTU560 rack solution

    560BCU01 R0001

    Bus Connection Unit for 560 CSR 01

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Connecting extension

    communication rack

    Alarm and warning contacts

    Minute pulse in- and output

    560BCU02 R0001

    Bus Connection Unit for 23 TP 22

    Alarm and warning contacts

    Auxiliary

    ABB Group February 18, 2012 | Slide 8

    Minute pulse in- and output

    560BCU03 R0002

    Bus Connection Unit for 23 ET 24

    Alarm and warning contacts

    Minute pulse in- and output

  • ModulesRTU560 rack solution

    560BCU04 R0001

    Bus Connection Unit for

    560MPR03/23TP22

    Subracks

    CMUs

    I/Os

    Communication

    modules

    560MPR03/23TP22

    Basic board for extension of 2 units

    560CMU0x

    Alarm and warning contacts

    Minute pulse in- and output

    560BCU04 R0002

    Bus Connection Unit for 560MPR03

    Auxiliary

    ABB Group February 18, 2012 | Slide 9

    Bus Connection Unit for 560MPR03

    Extension kit for 10 additional

    560CMU0x

    Alarm and warning contacts

    Minute pulse in- and output

  • ModulesRTU560 rack solution

    560BCU05 R0001

    Bus Connection Unit for

    560SFR02/23ET24

    Subracks

    CMUs

    I/Os

    Communication

    modules

    560SFR02/23ET24

    Basic board for extension of 2 units

    560CMU0x

    Alarm and warning contacts

    Minute pulse in- and output

    560BCU05 R0002

    Bus Connection Unit for 560SFR02

    Auxiliary

    ABB Group February 18, 2012 | Slide 10

    Bus Connection Unit for 560SFR02

    Extension kit for 10 additional

    560CMU0x

    Alarm and warning contacts

    Minute pulse in- and output

  • ModulesRTU560 rack solution

    560CMU05

    R0001

    560CMU05

    R0002

    560CMU02

    R0001

    560CMU02

    R0002

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Serial

    interfaces

    4x RS232 or RS485 4x RS232 or RS485 2x RS232, 1x RS485 2x RS232 or RS485

    Ethernet

    interfaces

    2x 10/100 Base T 2x 10/100 Base T 1x 10/100 Base T 2x 10/100 Base T

    Number of

    data points

    Up to 10,000 data

    points (depending on

    Up to 10,000 data

    points (depending on

    Up to 750 data points Up to 750 data points

    Auxiliary

    ABB Group February 18, 2012 | Slide 11

    data points points (depending on

    configuration)

    points (depending on

    configuration)

    Support of Multi-

    CMU

    Yes Yes No Yes

  • ModulesRTU560 rack solution

    560CMU05 R0001 and R0002 Interfaces

    4 serial interfaces (RS232C or

    Subracks

    CMUs

    I/Os

    Communication

    modules 4 serial interfaces (RS232C or RS485)

    2 Ethernet ports (10/100BaseT) forcommunication to

    Host systems and/or Subordinated devices and/or RTU I/O

    CPU AMD ELAN520 CPU @133MHz 128 MB flash memory 64 MB RAM

    Auxiliary

    ABB Group February 18, 2012 | Slide 12

    64 MB RAM

    Web server for diagnosis and maintenance via Ethernet ports

    PLC capable Bit protocols (Hitachi, Conitel) are

    supported only by 560CMU05 R0002

  • ModulesRTU560 rack solution

    560CMU02 R0001

    Interfaces

    Subracks

    CMUs

    I/Os

    Communication

    modules

    3 serial interfaces (2x RS232, 1x

    RS485)

    1x Ethernet 10/100 BaseT

    1x IO Bus (RS485, on backside)

    CPU

    AMD ELAN520 CPU @133MHz

    128 MB flash memory

    Auxiliary

    ABB Group February 18, 2012 | Slide 13

    128 MB flash memory

    64 MB RAM

    Only one slot width

    Usable in single CMU configurations

    Maximum of 750 data points

  • ModulesRTU560 rack solution

    560CMU02 R0002

    Interfaces

    Subracks

    CMUs

    I/Os

    Communication

    modules

    2 serial interfaces (RS232 or RS485)

    2x Ethernet 10/100 BaseT

    1x IO Bus (RS485, on backside)

    CPU

    AMD ELAN520 CPU @133MHz

    128 MB flash memory

    64 MB RAM

    Auxiliary

    ABB Group February 18, 2012 | Slide 14

    64 MB RAM

    Only one slot width

    Usable in multiple CMU

    configurations

    Maximum of 750 data points

  • ModulesRack I/O modules - Overview

    Binary input Binary output Analog input Analog output

    23BE23

    16 inputs 24>60

    23BA20/22

    24>60 VDC / 2A

    23AE23

    0...20 VDC / 2 / 5 /

    23AA21

    2.5 / 5 / 10 /

    Subracks

    CMUs

    I/Os

    Communication

    modules

    VDC / 2mA 10 / 20 / 40mA 20mA or 4...20mAAuxiliary

    ABB Group February 18, 2012 | Slide 15

  • Modules RTU560 rack solution

    Binary input board 23BE23

    16 binary input channels

    Subracks

    CMUs

    I/Os

    Communication

    modules

    One module for all types of binary

    input signals ( single indications,

    double point indications, digital

    measured values, counters)

    Galvanic insulation by optocouplers

    Input voltage 24...60 VDC,

    LED's for signalization of input

    Auxiliary

    ABB Group February 18, 2012 | Slide 16

    LED's for signalization of input

    channels

  • Modules RTU560 rack solution

    Binary output board 23BA20

    16 binary relay output channels

    Subracks

    CMUs

    I/Os

    Communication

    modules

    One module for all types of binary

    output signals (single commands,

    double point commands, setpoint

    commands)

    Galvanic insulation by relays

    Output voltage 24...60 VDC

    Switching capacity:

    Auxiliary

    ABB Group February 18, 2012 | Slide 17

    Switching capacity:

    40 VA (L/R=30ms) @ 60 VDC

    Continuous current: 2A

  • ModulesRTU560 rack solution

    Command Output monitoring board

    23BA22

    Usage in combination with 23BA20

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Usage in combination with 23BA20

    1 out of n check

    Supervision of up to 32 different

    relay types

    Galvanic isolation of the check

    circuit

    Suppression of line frequency during

    measuring

    Auxiliary

    ABB Group February 18, 2012 | Slide 18

    measuring

    Monitoring of output duration and

    reset in case of fault

    Monitoring of switching voltage

    before and during the command

    output

  • ModulesRTU560 rack solution

    Analog input board 23AE23

    8 differential inputs

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Input current 2 mA, 5 mA,

    10 mA, 20 mA, 40mA

    Input voltage 2 VDC,

    0...20 VDC

    12 bit + sign = 4096 steps

    Occupies one slots in RTU560

    subrack

    Auxiliary

    ABB Group February 18, 2012 | Slide 19

    subrack

    Low-pass filter

    Over voltage protection

  • ModulesRTU560 rack solution

    Analog output board 23AA21

    2 channels

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Output current 2.5 mA,

    5 mA, +-10 mA, 20 mA or

    4...20mA

    11 bit + sign

    Occupies one slots in RTU560

    subrack

    Auxiliary

    ABB Group February 18, 2012 | Slide 20

  • ModulesRTU560 rack solution

    Analog line modems Serial optical interfaces Ethernet and optical switches

    23WT23/24/25

    5/24 VDC

    23OK24 560NUS04/12

    unmanaged

    560NMS24/34

    managed/DSL

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 21

  • ModulesRTU560 rack solution

    Modem 23WT23

    FSK modem for voice band range

    (300-2400 Hz) according to CCITT

    Subracks

    CMUs

    I/Os

    Communication

    modules

    (300-2400 Hz) according to CCITT

    V.23

    2- or 4-wire lines, duplex or half

    duplex

    Baudrate 1200 bit/s

    Adjustable by jumpers

    Point to point or multidrop

    configurations, in multidrop

    configurations up to 10 remote

    Auxiliary

    ABB Group February 18, 2012 | Slide 22

    configurations up to 10 remote

    station in one line

    Disconnect test sockets on front

    side

    Only one slot necessary

    R0001: 5 VDC, R0002: 24 VDC

  • ModulesRTU560 rack solution

    Modem 23WT24

    FSK modem for wide band range

    Subracks

    CMUs

    I/Os

    Communication

    modules

    (300-18000 Hz)

    2- or 4-wire lines, duplex or half

    duplex

    Baudrate: 9600 Baud

    Distances up to 20 km, Point to

    point

    Distances up to 10 km, multi-drop

    Auxiliary

    ABB Group February 18, 2012 | Slide 23

    Distances up to 10 km, multi-drop

    configuration

    Disconnect test sockets on front

    side

    Only one slot necessary

  • ModulesRTU560 rack solution

    Modem 23WT25

    FSK modem in voice band range (300-

    2400Hz) according to CCITT

    Subracks

    CMUs

    I/Os

    Communication

    modules 2400Hz) according to CCITT

    Variants:

    R0001: supply voltage 5 VDC

    R0002: supply voltage 24 VDC

    2- or 4-wire lines, duplex or half duplex

    Baudrate 50 bit/s if 24-channel-CCITT-

    raster is used, up to 2400 bit/s if one

    channel is used

    Digital signal processor (DSP) for

    conversion of binary information to voice

    Auxiliary

    ABB Group February 18, 2012 | Slide 24

    conversion of binary information to voice

    band and vice versa

    Point to point or multi-drop

    configurations, in multi-drop

    configurations carrier can be switched

    off

    Disconnect test sockets on front side

  • ModulesRTU560 rack solution

    Optical coupler 23OK24

    Optic connection of extension

    Subracks

    CMUs

    I/Os

    Communication

    modules

    racks in star or line configuration

    Optic connection of SPA bus

    devices point to point or loop

    Optic connection of protection

    devices according IEC 60870-5-103

    Glass fiber optic wave length 820

    nm

    Auxiliary

    ABB Group February 18, 2012 | Slide 25

    nm

    ST connector (BFOC 2,5)

    Cable length up to 2600 m

  • ModulesRTU560 rack solution

    4 port unmanaged local switch

    560NUS04

    4 fast Ethernet 10/100 BaseT ports

    Subracks

    CMUs

    I/Os

    Communication

    modules

    4 fast Ethernet 10/100 BaseT ports

    for LAN port multiplication

    Additional interfaces for diagnosis

    and LAN/WAN communication

    Unmanaged

    Auto negotiation 10/100Mbps

    Automatic Cross over detection

    Only for linear networks (no ring

    Auxiliary

    ABB Group February 18, 2012 | Slide 26

    Only for linear networks (no ring

    configuration)

    No STP/ RSTP supported

    No additional power supply required

    Plug and play no configuration

    required

  • ModulesRTU560 rack solution

    4 port switch with 2 x FX 560NUS12 2 fast Ethernet 10/100 BaseT ports 2 SFP cages for fiber optical

    Subracks

    CMUs

    I/Os

    Communication

    modules 2 SFP cages for fiber optical interfaces

    Unmanaged Auto negotiation 10/100Mbps Automatic cross over detection Different SFPs

    560NFO13: mono-mode fiber, up to 15 km

    560NFO15: mono-mode fiber, up to 40 km

    560NFO85: multi-mode fiber, up to 2

    Auxiliary

    ABB Group February 18, 2012 | Slide 27

    560NFO85: multi-mode fiber, up to 2 km

    Only for linear networks No STP/RSTP supported Media converter to optical Ethernet Plug and play no configuration

    required

  • ModulesRTU560 rack solution

    4 port switch with 2 x DSL 560NMS24

    SDSL interface (Symmetric Digital

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Subscriber Line)

    4 x fast Ethernet RJ45 ports

    2 DSL WAN ports for copper

    Bandwidth from 192kbit/s up to

    6Mbit/s

    Automatic through-connection in

    case of power cut

    Auxiliary

    ABB Group February 18, 2012 | Slide 28

    case of power cut

    Managed switch

    Ring configuration possible

    NMS34 with 1 DSL port

  • ModulesRTU560 rack solution

    Power supply units Real time clocks

    560PSU01/02 560RTC01/02/03

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 29

  • ModulesRTU560 rack solution

    Power supply unit 560PSU01

    Input: 24...60 VDC (R0001) or

    Subracks

    CMUs

    I/Os

    Communication

    modules

    110...220 VDC (R0002)

    Output total 44 W,

    5 VDC: 0.2 A ...5.5 A and

    24 VDC: 0...0.7 A

    1 LED for 5V, 1 LED for 24 V

    signalization

    Electronic power limitation, short

    Auxiliary

    ABB Group February 18, 2012 | Slide 30

    Electronic power limitation, short

    circuit proof, controlled load

    balancing

    Alarm indication relay in case of

    failure

  • ModulesRTU560 rack solution

    Power supply unit 560PSU02

    Input: 48...220 VDC

    Subracks

    CMUs

    I/Os

    Communication

    modules

    Output total 80 W,

    5 VDC: 0>15 A and

    24 VDC: 0...0.7 A

    1 LED for 5V, 1 LED for 24 V

    signalization

    Electronic power limitation, short

    circuit proof, controlled load

    Auxiliary

    ABB Group February 18, 2012 | Slide 31

    circuit proof, controlled load

    balancing

    Alarm indication relay in case of

    failure

    Stipulated for redundant operation

  • ModulesRTU560 rack solution

    Real time clock 560RTC01/02/03

    560RTC01: designed for GPS

    Subracks

    CMUs

    I/Os

    Communication

    modules

    receiving

    560RTC02: designed for long-wave

    DCF 77 transmitter receiving

    560RTC03: IRIG-B time codes

    IRIG-B123

    IRIG-B122

    AFNOR NFS 87-500

    Auxiliary

    ABB Group February 18, 2012 | Slide 32

    AFNOR NFS 87-500

    IRIG-B003

    IRIG-B002

    AFNOR NFS 87-500 (DC)

  • ModulesRTU560/RTU211 DIN rail solution

    560CMG10 560CIG10Technical data RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Serial interfaces 3

    Ethernet 10/100 BaseT 1

    Integrated I/Os 16 binary inputs8 binary outputs

    8 analog inputs (mA)

    Extension

    I/O modules

    Binary inputs/outputsAnalogue inputs/outputs

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 33

    I/O modulesAnalogue inputs/outputs

    Direct analog inputs Optional: fault current detection

    Dimensions

    W x H x D204 x 105 x 55 mm 230 x 150 x 84 mm

  • ModulesRTU560/RTU211 DIN rail solution

    DIN rail RTU211

    23CM61 560CMU01

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Serial interfaces 1/4 3

    Ethernet 10/100

    BaseT

    0 1

    Integrated I/Os 16 binary inputs

    8 binary outputs

    Up to 4 of the following modules:

    16 binary inputs

    8 binary outputs

    6 analog inputs (mA)

    2 analog outputs

    6 temperature sensors

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 34

    Extension

    I/O modules

    Binary inputs/outputs

    Analog inputs/outputs

    Binary inputs/outputs

    Analog inputs/outputs

    Direct analog inputs

    Optional: Fault current detection

    Dimensions

    W x H x D

    (290 400) x 116 x 81 mm (181 741) x 116 x 81 mm

    Depending on integrated I/Os

  • 23CM61

    512 kByte flash memory

    256 kByte RAM

    ModulesRTU560/RTU211 DIN rail solution

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    256 kByte RAM

    4 x RS232 ports

    RP570 communication protocols

    IEC 60870-5-101 or DNP3

    communication protocols

    Built-in Local Automation Function

    (LAF)

    Monitoring of system power

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 35

    Monitoring of system power

    Integrated alarm relay

    16 binary inputs

    8 binary outputs

    6 analog inputs

    1 out of n check

  • ModulesRTU560/RTU211 DIN rail solution

    RTU211 based on 560CMU01

    560CMU01

    3 serial interfaces

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    3 serial interfaces

    1 ethernet interface

    Up to 4 of the following I/O modules:

    16 binary inputs

    8 binary outputs

    6 analog inputs (mA)

    2 analog outputs

    6 temperature sensors

    560PSU10

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 36

    560PSU10

    Total output of approx. 38 W, split to:

    + 5 V DC and 1 A = 5 Watt

    + 15 V DC and 0.5 A = 7.5 Watt

    15 V DC and 0.5 A = 7.5 Watt

    + 18 V DC and 1A = 18 W

  • ModulesRTU560/RTU211 DIN rail solution

    Binary input Binary output Analog input Analog output

    23BI61

    16 inputs 24/ 48/ 60 VDC

    23BO62/63

    3A @ 110 VDC / 3A

    23AI60

    Analog inputs mA DC

    23AO60

    Analog output mA DC

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs 16 inputs 24/ 48/ 60 VDC 3A @ 110 VDC / 3A Analog inputs mA DC Analog output mA DC

    23BE40

    16 inputs 110/ 220/250 VDC

    23BA40

    50 VA (L/R=40ms) @ 220 VDC / 8A

    560CVT02

    Analog inputs A/V AC

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 37

    23BE50

    64 inputs 24/ 48/ 60 VDC

    560CVT10

    Analog inputs

  • ModulesRTU560/RTU211 DIN rail solution

    Binary input 23BI61

    16 binary inputs for single or double

    indication, digital measurands,

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    indication, digital measurands,

    pulse counter

    R0001: 24>48 VDC

    R0002: 60>110 VDC

    Grouped with common return per 8

    inputs

    One LED per input

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 38

    One LED per input

    1 ms time resolution

    Length 105 mm

    Housing should be ordered

    separately

  • ModulesRTU560/RTU211 DIN rail solution

    Direct process-interface 23BE40

    16 binary input channels

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Input Voltage

    110 VDC: 23BE40 R0011

    220 VDC: 23BE40 R0012

    Inputs without common

    return

    Galvanic insulation by optocouplers

    Input current 1,5 mA (chopped)

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 39

    Oxide film break function for 8

    inputs

    LEDs for signalization of input

    channels

    Power supply: 24 Vdc

  • ModulesRTU560/RTU211 DIN rail solution

    64 binary input module 23BE50

    64 binary inputs

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Input range: 24>60 VDC

    Input functions as 23BE23

    Groups with common return per 16

    inputs

    Galvanic insulation by optical

    couplers

    LEDs for signalization of each input

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 40

    LEDs for signalization of each input

    channel

    Power supply: 24 VDC

    Usable without additional terminals

  • ModulesRTU560/RTU211 DIN rail solution

    Binary output 23BO62

    8 binary relay outputs for 1, 1,5 or 2

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    pole commands

    Isolated outputs

    One LED per output

    High switching capacity:

    3A @ 110 VDC

    Continuous current: 3A

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 41

    Length 140 mm

    Housing should be ordered

    separately

  • ModulesRTU560/RTU211 DIN rail solution

    1 out of n check 23BO63

    1 out of n supervision in

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    combination with 23BO62

    High switching capacity up to 110

    VDC, 3 A

    Length 70 mm

    Housing should be ordered

    separately

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 42

  • ModulesRTU560/RTU211 DIN rail solution

    Direct process-interface 23BA40

    16 binary relay output channels

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Outputs without common return

    (23BA40 R0011)

    Galvanic insulation by relays

    Switching voltage

    max. 250 VDC/AC

    Switching capacity:

    50 VA (L/R=40ms) @ 220 VDC

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 43

    50 VA (L/R=40ms) @ 220 VDC

    Continuous current: 8A

  • ModulesRTU560/RTU211 DIN rail solution

    Analog input 23AI60

    6 analog inputs

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Resolution: 11 bit +sign

    Accuracy class: 0,25

    Ranges: 5mA, 10 mA,

    +20 mA, 4>20 mA, VDC,

    10VDC

    Length: 70 mm

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 44

    Housing should be ordered

    separately

  • ModulesRTU560/RTU211 DIN rail solution

    Direct transducer interface 560CVT02 3 voltage inputs 110 VAC

    110 VAC: 560CVT02 R000x

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs 110 VAC: 560CVT02 R000x(for measurement with voltage transformers)

    230 VAC: 560CVT02 R001x (for direct voltage measurement at the low voltage side)

    3 Current Inputs 1A: 560CVT02 R00x1 5A: 560CVT02 R00x5

    Accuracy: 0,2% Calculated values:

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 45

    Calculated values: Active, reactive, apparent power Active, reactive energy Power factor Frequency Harmonic distortion (THD)

    Integrated in RTU560 engineering

  • ModulesRTU560/RTU211 DIN rail solution

    Direct transducer interface 560CVT10 3 current inputs

    R0011: 1A

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs R0011: 1A R0015: 5A

    3 voltage inputs max. 300V Accuracy up to 0.2% Low input burden

    Voltage 0.15VA at 300 V Current 0.2 VA of rating

    Additional fault current measurement up to 20 x line

    Over current detection

    Over Current Detection

    Saturation

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 46

    Over current detection Total harmonic distortion (THD) PLC applications for voltage dip

    detection available Power supply: 24V DC ( 20%) MODBUS interface Integrated in RTU560 engineeringOCx_FV

    Phase x Current

    Time

    Saturation

    Over Current detected

  • ModulesRTU560/RTU211 DIN rail solution

    Analog output 23AO60

    2 analog outputs for set points

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Resolution: 11 bit +sign

    Accuracy class: 0,25

    Ranges: 2,5 mA, 5mA, 10 m,

    20 mA, 4>20 mA, 1 VDC,

    10VDC

    Length: 105 mm

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 47

    Housing should be ordered

    separately

  • ModulesRTU560/RTU211 DIN rail solution

    Analog line modems Serial optical interfaces

    560FSM10/11

    18>72 VDC

    560FOC40

    18...30VDC

    23SC60

    R008 glass fiber

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs18>72 VDC 18...30VDC

    560FOC80

    5 VDC

    R008 glass fiber

    R009 plastic fiberI/Os

    Communication

    modules

    Auxiliary

    ABB 560FOC80

    ABB Group February 18, 2012 | Slide 48

  • Modules RTU560/RTU211 DIN rail solution

    Modem 560FSM10 and 560FSM11

    560FSM10

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    V.23 modem

    Functionality comparable to

    23WT23

    Power supply: 18>72 VDC

    560FSM11 R0001

    9600 baud modem

    Functionality comparable to

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 49

    Functionality comparable to

    23WT24

    Power supply: 18..72 VDC

  • Modules RTU560/RTU211 DIN rail solution

    Serial optical interface 560FOC40 and

    560FOC80

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Opto coupler unit

    Power supply:

    560FOC40: 24 VDC (18..30VDC)

    560FOC80: 5 VDC

    Support of glass fiber (62,5/125m)

    BFOC 2,5 connector

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 50

    RS485 electrical interface

    Compatible to 23OK22/24

    ABB 560FOC80

  • Modules RTU560/RTU211 DIN rail solution

    Star coupler 23SC60

    Used to connect decentralize I/O

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    racks up to 2 km

    Versions for different medias

    R008x: multi mode glass fiber

    R009x: plastic fiber

    2..5 optical interfaces per housing

    available

    To be used to connect 23BE40,

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 51

    To be used to connect 23BE40,

    23BA40 and 23BE50 to DIN rail

    RTUs

  • ModulesRTU560/RTU211 DIN rail solution

    Power supply units

    560PSU10 560PSU40

    Input 110>220

    VDC

    560PSU41

    Input 24>60 VDC

    Output 24 VDC/2,5A

    23PU63

    Input 24>110 VDC

    Output 5V/1A, 15V/0,

    23VG23/24

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    VDC

    Output 24

    VDC/2,5A

    Output 24 VDC/2,5A Output 5V/1A, 15V/0,

    18V/1A, 24V/0,5A

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 52

  • ModulesRTU560/RTU211 DIN rail solution

    Power supply 23PSU40/41

    Input voltage

    560PSU40: 110>220 VDC

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    560PSU40: 110>220 VDC

    560PSU41: 24>60 VDC

    Max. output power 60 W, 24 VDC:

    2,5 A

    1 LED for voltage supervision

    24VDC

    Overload and short-circuit

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 53

    protection

    Power good signal available (only

    560PSU40)

    Parallel peration possible (only

    560PSU40)

  • Modules RTU560/RTU211 DIN rail solution

    560PSU10

    560PSU10: Power supply unit for

    RTU560 DIN rail in cooperation with

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    RTU560 DIN rail in cooperation with

    560CMU01

    The 560PSU10 supplies a total

    output of approx. 38 W. This is split

    to:

    + 5 V DC and 1 A = 5 Watt

    + 15 V DC and 0.5 A = 7.5 Watt

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 54

    15 V DC and 0.5 A = 7.5 Watt

    + 18 V DC and 1A = 18 W

  • ModulesRTU560/RTU211 DIN rail solution

    Power supply 23PU63

    25W power supply

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Input voltage

    24 110 VDC (+/- 20%)

    Output voltage

    5V 1A (internal usage)

    +/-15V 0,2 A (RS232, AI/AO)

    18 V 1A (relays, AO)

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 55

    24V 0,5A (process voltage)

    Used in main module 23CM61 and

    together with 23AD64

  • Modules RTU560/RTU211 DIN rail solution

    Main adapter 23VG23

    Input Voltage 115 / 230 V AC

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    without switch over

    24 VDC output voltage

    Power output 48 W

    Output current min. 0.2 A and max.

    2 A

    Integrated components:

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 56

    Battery charging device

    Switch over device

    Exhaustive discharge protection

  • Modules RTU560/RTU211 DIN rail solution

    Main adapter 23VG24

    Input Voltage 115 / 230 V AC

    Technical data

    RTU560 for DIN rail

    Technical data

    RTU211 for DIN rail

    CMUs

    Power output approx. 240 W

    24 VDC output voltage

    Output current max. 10 A

    I/Os

    Communication

    modules

    Auxiliary

    ABB Group February 18, 2012 | Slide 57

  • ModulesRTU560E

    Applications:

    Small distribution substations

    Distributed architectures with

    decentralized I/O units

    Benefits:

    Cost optimized solution for medium

    and small data amounts

    Easy and fast assembling,

    mounting and commissioning

    ABB Group February 18, 2012 | Slide 58

    mounting and commissioning

    No additional housing needed

    Mounting space for additional

    devices

  • ModulesRTU560E

    General modules

    Housing 560HOS80 Multi I/O 560MIO80

    ABB Group February 18, 2012 | Slide 59

    Communication Unit 560CMU80 Modem Unit 560MOD8x

  • ModulesRTU560E

    Housing 560HOS80

    Size: 366mm x 258mm x 310mm

    (H x W x D)

    Hinged housing with terminals on

    the back-plane

    IP 30

    ABB Group February 18, 2012 | Slide 60

  • ModulesRTU560E

    Multi I/O board 560MIO80

    16 binary inputs

    R0001: 24...60 VDC

    R0002: 110...220 VDC

    8 binary outputs

    R0001: technical data according 23BA20

    R0002:

    Continuous current rating: max. 5 A

    Breaking current (L/R 40ms, 70C)

    4 analog inputs

    ABB Group February 18, 2012 | Slide 61

    4 analog inputs

    Input range

    Input current 2 mA, 5 mA, 10 mA, 20 mA,

    40mA

    Input voltage 2 VDC, 0...20 VDC

    Resolution: 12 bit + sign

  • ModulesRTU560E

    Modems

    560MOD80

    FSK modem V.23 halfduplex

    1200 bps

    560MOD81

    Analog modem, dial up

    Data transfer 300 - 33.600 bps

    560MOD82

    ABB Group February 18, 2012 | Slide 62

    GSM modem

    Dual band GSM Modul 900/1800 MHz

    Compliant with ETSI GSM phase 2 standard

    Class 4 (2W @ 900 MHz)

    Class 2 (1W @ 1800 MHz)

  • ModulesRTU560E

    Communication unit 560CMU80

    Communication interfacesAMD

    SC400

    AMD SCC

    85C30Com /

    2x5Pol

    ModemModem1 / RJ45

    Modem2 / RJ45

    CP1, CP2:

    2x RS232 interfaces with opt.

    modem socket, baudrate 50

    38400 Baud

    CPA:

    1x RS485 baudrate 19200 Baud

    Opt. Ethernet 10BaseT (RJ45)

    1 MMI (Front Access) RS232

    baudrate 38400 Baud

    MMI / DB9

    CPA / RJ45

    FPGA

    ASIC

    BIOS

    +

    DIP32

    SMSC

    37C93x

    ISA

    -B

    US

    80C251 +

    DualPort

    RAM

    Compact

    RS232

    RS485

    SMSC

    10BaseT /

    RJ45

    RS232

    RS232

    CP1 / RJ45

    CP2 / RJ45

    RS485E-Bus SPB /

    DIN41612

    ModemModem2 / RJ45

    ABB Group February 18, 2012 | Slide 63

    baudrate 38400 Baud

    CPU

    CPU ELAN 400 @ 66MHz

    16 MB DRAM

    32 MB compact flash card

    Compact

    Flash

    optional

    SMSC

    91C94

    RJ45

    AUI / DB15

    PC104-Bus

  • ModulesRTU560E

    Power supply

    AC/DC converter 560PSU81

    Input voltage: 115...230 VAC

    DC/DC converter 560PSU80

    Input voltage:

    R0001: 24...60 VDC

    R0002: 110...220 VDC

    ABB Group February 18, 2012 | Slide 64

  • ABB Group February 18, 2012 | Slide 65

  • Revisions

    Version Description Date

    V1.01 New document 30.09.2010

    V1.02 Correction of picture file sizes 10.11.2010V1.02 Correction of picture file sizes 10.11.2010