JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD. Address: No. 5, West Huimin Road, Economic Development Zone, Rugao, Jiangsu Province, P.R.China. Zip code: 226572 Tel: 0086-513-87303629 Fax: 0086-513-87530056 Email: [email protected] Http://www.sieyuan.net !"#$%&'()* JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO.,LTD. Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan ® ! Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan ®

Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Embed Size (px)

Citation preview

Page 1: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

Address: No. 5, West Huimin Road, Economic Development Zone, Rugao, Jiangsu Province, P.R.China.

Zip code: 226572

Tel: 0086-513-87303629

Fax: 0086-513-87530056

Email: [email protected]

Http://www.sieyuan.net �� !"#$%&'()*JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO.,LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®�� !

SieyuanSieyuanSieyuanSieyuanSieyuan®

Page 2: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Jiangsu Sieyuan Hertz Instrument Transformer Co., Ltd. conducts research and development on

technically advanced and safe quality products on its own, including:

35-500 kV Oil Impregnated Inverted Current Transformers,

35-500 kV Sulfur Hexafluoride Gas Insulated Inverted Current Transformers,

35-500 kV Capacitor Voltage Transformers,

35-500 kV Sulfur Hexafluoride Gas Insulated Voltage Transformers for mounting in GIS,

35-220 kV Inductive Voltage Transformers,

10-220 kV Oil Impregnated Tank type Current Transformers,

35-110 kV Dry type Current Transformers and Dry Graded Wall Bushing, etc.

The products have obtained KEMA test certification in Holland, as well as inspection and examination

by national authorities.

Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained speed, with ardent

enthusiasm, prudent attitude

and customer orientation.

Jiangsu Sieyuan Hertz Instrument Transformer Co., Ltd. ( www.sieyuan.net ) covers the land

area of more than 100,000 square meters and the construction area of over 60,000 square

meters, which is within the factory area of more than 50,000 square meters. With a sealing &

purifying workshop up to 100,000 grade, it is regarded as a world-class instrument transformer

production base in China.

Sieyuan Hertz has a R&D and management team with the most competitive power, it now has

more than 400 employees, among the employees, the percent of engineering and technology

talents who got Ph. D or master degree or graduated from universities is 45%, and the

Company also invites foreign professionals to take charge of the technology and quality

management.

Sieyuan Hertz leads the instrument transformer trade to ahigher level at a sustained speed, with ardent enthusiasm,prudent attitude and customer orientation.

Company Brief

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

Comp any Brief

1 2

SieyuanSieyuanSieyuanSieyuanSieyuan®

Page 3: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Advanced Facilities

In order to realize the product design con-

cept and reduce the uncertainty brought by

manual operation, during the production

process, Siyuan Hertz adopts automatic pro-

duction equipments.

World Class Testing Condition

Secondary Coil Winding Machine Capacitance Graded Bushings Wind-

ing Machines

German Welding Robots

Sieyuan Hertz has the world-classy testing conditions and perfect testing equipments, including three

six-facet shielding high voltage testing laboratory with the rated voltage 1000 kilovolt, 600 kilovolt, 300

kilovolt and also an impulse voltage generator up to 3000 kilovolt with automatic measuring system.

In the profession field, the company introduces firstly the partial discharge test in power frequency

withstand voltage, which is more stringent than national and IEC standards, and ensures much more

reliance and safety for product running.

Transient Characteristics Tester for

Current Transformer

600kV Power Frequency Testing Trans-

former

300kV Power Frequency Testing Trans-

former

1000kV Power Frequency Testing

Transformer

3000kV Lightning Impulse Generator

High Frequency Capacitance and Stray

Capacitance Meter

Ferro-resonance Testing Analysis Sys-

tem for Capacitor Voltage Transformer

(CVT)

3 4

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

G e r m a n L e y b o l d

Vacuum Treatment

System

Capacitance Graded Bushings Winding

Machine for SF6 Gas Insulated Products

Assembly Shop for SF6 Gas Insulated

Current TransformerGerman B&R Aptitude Coil Machine

Page 4: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Sieyuan Hertz promotes total quality management and strictly abiding by

ISO9000 quality management system, the regulation of technical re-

quirement is quite clear and uniform from parts inspection to routine test,

so as to ensure the whole production under control and the products can

be traced back. To ensure the product quality meeting international

standards, all major raw materials are imported from foreign countries,

such as: cable paper, semiconducting paper, aluminum foil, transformer

oil, insulating material for sulfur hexafluoride gas insulated products,

enameled wire and compacting material for product etc.

Sieyuan Hertz consistently follows the mission of "service creates value" by professional, speedy,

sincere and quality service. We endeavor to help lower our customer' operation costs while improving

their business efficiency and competitiveness.

Sieyuan Hertz is committed to offer our customers with products featuring "high-safety", "high-

reliance", "high-accuracy" and "high-standardization". Since our foundation, the company has gained

earnest support from users in all lines. At present, our sales network covers all the cities in China and

overseas markets. In north, east, south, and mid China, northwest and northeast China, sales offices

and after-sale service stations have been established. In addition, the company has established

perfect partnership with State Grid Corporation of China, and China Southern Power Grid Co., Ltd.,

Sieyuan Hertz has continuously won bids in major power station projects in Vietnam, Burma and

Nigeria, which marks that our products have known worldwide.

Reliable Products & Quality

ISO9000 Quality System Certificate (SGS)

General Customer Service

Hebei Electric Power

Corporation, China

Jiangsu Electric Power Corporation, China

500kV SF6 Gas Insulated Inverted Cur-

rent Transformers

Zhejiang Electric Power Corporation,

China 500kV Oil Impregnated Inverted

Current Transformers

Shanxi Electric Powr

Corporation, China

Jiangsu Electric Power

Corporation, China

Jilin Electric Power

Corporation, China

Ningxia Electric Power

Corporation, China

Nanjing Electric

Power

Corporation,

China

Shanxi Electric Power

Corporation, China

Guangdong Electric

Power Corporation,

China

5 6

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Page 5: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Symbol Explanation

LVB Series Oil Immersed Inverted Current Transformers

L V B (T) �==�

Antipollution Class (W2, W3)

Voltage Grade (kV)

With Transient Protection

With Protection

Inverted

Current Transformer

� LVB (T) series current transformer has an inverted structure with oil-immersed paper insulation (Please see the left figure).

It is connected in series with electric energy measurement, measuring, relay protection and transient protection functions.

� Primary coil has a through-type conducting rod structure with good dynamic and thermal stability; its maximum thermal

current can be up to 63kA/3s (when primary coil is connected in series).

� Primary coil passes through the center of secondary coil without flux leakage. Measurement precision can be up to 0.1and

0.2S grades.

� Secondary coil is fixed in an aluminum shielded-case by casting organic materials; secondary measurement and

protection circuits cannot be damaged by insulation breakdown.

� Optimal capacitor screen bushing is made of a complete piece of imported broadsheet cable paper; it is coiled by an

automatic wrapping machine which is controlled by a computer with high performance. It has a technological de-centrality

and an excellent insulation property. Partial discharge test is carried out under power frequency test voltage.

� Use the automatic vacuum drying treatment system produced by LEYBOLD in Germany, carry out pressure-changing

vacuum drying treatment and oiling after a product is assembled completely, and all insulation materials are imported from

foreign countries. All these ensure that the dielectric dissipation factor of complete product tan_ is less than 0.3%.

� External insulation uses a porcelain cover with high strength, optimal surface field intensity together with lower field

intensity of internal bushing make the porcelain cover avoid explosion.

� Secondary outlet box is a complete structure by casting the aluminum alloy; its sealing structure meets the requirement

of IP55, which is dust proof, water proof and air permeable; secondary terminal for wiring uses Phoenix special terminal; it

is more convenient for operations such as plug-in, pull-out and wiring etc.

� Connection between components uses argon-arc welding, fill in high pressure nitrogen to detect leakage after assembly

is complete, so oil penetration and oil leakage caused by oil-immersed products are resolved at root.

Use an aluminum alloy cast case, all components including the base, connection box, stainless steel expander, and

nameplate etc do not rust forever.

� It is light and handy with a small volume and light weight.

� This product is free-maintenance.

Introduction to Structure

Stainless Steel Expander

Primary Terminal Plate on P1 Side

Bushing

Core and winding assembly

Porcelain Cover

Oil Drain ValueNameplate

Secondary Terminal Box

Oil Level Observation Window

Primary Terminal Plate on P2 Side

7 8

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Page 6: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Technical Parameters of LVB (T) - 35

LVB-35W2/1X LVB-35W3/1X LVB(T)-35W2/2X LVB(T)-35W3/2X

Technical Parameters of LVB 66

LVB-66W2/1X LVB-66W3/1X LVB-66W2/2X LVB-66W3/2X

TypeLVB-66W2/1X LVB-66W3/2X

LVB-66W3/1X LVB-66W3/2XHighest voltage for equipment kV 72.5

Rated frequency Hz 50/60

Rated power-frquency withstand voltage (rms) kV 160

Rated lightning impulse withstand voltage (full wave)(peak) kV 350

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 403

Flashover distance mm 700

Creepage distance mm 1812/2250

Rated primary current (Maximum) A 4000

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S;0.5S;5P;10P;TPU;TPS��

Rated output VA 10-50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (Maximum) kA 63kA/3s (In series)

Dynamic current (Maximum) kA 160

Allowable mechanical load of transformer: Static N 3000

Allowable mechanical load of transformer: Dynamic N 5000

Net weight kg 200 450

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

TypeLVB-35W2/1X LVB(T)-35W2/2X

LVB-35W3/1X LVB(T)-35W3/2XHighest voltage for equipment kV 40.5

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 95

Rated lightning impulse withstand voltage(full wave)(peak)kV 200

Rated lightning impulse withstand voltage (Chopped wave) (Peak) kV 230

Flashover distance mm 500

Creepage distance mm 1015/1260

Rated primary current (Maximum) A 4000(8000)

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.1;0.2;0.5;0.2S;0.5S;5P;10P;TPY;TPS��

Rated output VA 10-50

Safety factor FS 5;10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (Maximum) kA 63kA/3s (In series)

Dynamic current (Maximum) kA 160

Allowable mechanical load of transformer (Static) N 3000

Allowable mechanical load of transformer (Dynamic) N 5000

Net weight kg 170 420

Outline and Dimensional Drawing Outline and Dimensional Drawing

9 10

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Page 7: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

LVB-110(132)W2/1X

LVB-110(132)W3/1X

LVB-110(132)W2/2X

LVB-110(132)W3/2X

LVB-110(132)W2/3X

LVB-110(132)W3/3X

11 12

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Outline and Dimensional Drawing

Note: 1 The Company reserves the right to change the parameters in the table.2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.3 There are several current ratios for one-time switch of the transformer.4 We also can provide with products which meet the requirement of IEC and ANSI.

Technical Parameters of LVB-110

TypeLVB-110W2/1X LVB-110W2/2X LVB-110W2/3X

LVB-110W3/1X LVB-110W3/2X LVB-110W3/3XHighest voltage for equipment kV 126

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 230

Rated lightning impulse withstand voltage (full wave)(peak) kV 550

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

Flashover distance mm 1200

Creepage distance mm 3150/3910

Rated primary current (Maximum) A 4000

Rated secondary current A 1;5

Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS��

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (Maximum) kA 50kA/3s (In series)

Dynamic current (Maximum) kA 125

Allowable mechanical load of transformer (Static) N 3000

Allowable mechanical load of transformer (Dynamic) N 5000

Net weight kg 230 475 525

Note: 1 The Company reserves the right to change the parameters in the table.2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.3 There are several current ratios for one-time switch of the transformer.4 We also can provide with products which meet the requirement of IEC and ANSI.

Technical Parameters of LVB-132

TypeLVB-132W2/1X LVB-132W2/2X LVB-132W2/3X

LVB-132W3/1X LVB-132W3/2X LVB-132W3/3XHighest voltage for equipment kV 145

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 275

Rated lightning impulse withstand voltage (full wave)(peak) kV 650

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 748

Flashover distance mm 1200

Creepage distance mm 3625/4495

Rated primary current (Maximum) A 4000

Rated secondary current A 1;5

Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS��

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (Maximum) kA 50kA/3s (In series)

Dynamic current (Maximum) kA 125

Allowable mechanical load of transformer (Static) N 3000

Allowable mechanical load of transformer (Dynamic) N 5000

Net weight kg 230 475 525

Page 8: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Technical Parameters of LVB (T)-330�500

Outline and dimensional drawings for

LVB(T)-330W2 Current Transformer

Outline and dimensional drawings for

LVB(T)-500W2 Current Transformer

Outline and Dimensional Drawing

Type LVB (T) -330W2 LVB (T) -500W2

Highest voltage for equipment kV 363 550

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 510 740

Rated lightning impulse withstand voltage (full wave)(peak) kV 1175 1675

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1352 1930

Impulse withstand voltage (Wet Test) kV 950 1175

Flashover distance mm � 2650 � 4000

Creepage distance mm � 9100 � 13750

Rated primary current (Maximum) A 5000 5000

Rated secondary current A 5; 1 5; 1

Accuracy classes (they can be combined if necessary) 0.2S; 0.5S; 0.1; 0.2S; 0.5S; 0.1;

0.2; 0.5; 5P; 10P; TPY 0.2; 0.5; 5P; 10P; TPY

Rated output VA 10~50 10~50

Safety factor FS 5; 10 5; 10

Accuracy limit factor ALF 10; 15; 20; 30; 40 10; 15; 20; 30; 40

Times of symmetry short-circuit current Kssc 10, 15, 20, 25, 30

TPY Parameter Operating cycle C-O-C-O

Output capacity VA 10, 15

Thermal current (Maximum) kA 63 kA / 3s ( in series )

Dynamic current (Maximum) kA 160 ( in series )

Weight of oil 280 432

Net weight 1000 2250

Gross weight 1300 3000

13 14

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

LVB-220W2/1X LVB-220W3/1X LVB-220W2/2X LVB-220W3/2X

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Technical Parameters of LVB (T)-220

TypeLVB-220W2/2X LVB (T)-220W2/3X

LVB-220W3/2X LVB (T)-220W3/3XHighest voltage for equipment kV 252

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 460

Rated lightning impulse withstand voltage (full wave)(peak) kV 1050

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208

Flashover distance mm 2200

Creepage distance mm 6300/7900

Rated primary current (Maximum) A 4000

Rated secondary current A 1�5

Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS��

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (Maximum) kA 63kA/3s (In series)

Dynamic current (Maximum) kA 160

Allowable mechanical load of transformer: Static N 4000

Allowable mechanical load of transformer: Dynamic N 6000

Net weight kg 550 800

Outline and Dimensional Drawing

Page 9: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

� LVQB series current transformer has an inverted structure with SF6 gas insulation (Please see the figure). It is connected

in series with electric energy measurement, measuring, and relay protection functions.

� Primary coil has a through-type conducting rod structure with good dynamic and thermal stability; its maximum thermal

current can be up to 63kA/3s (when primary coil is connected in series).

� Primary coil passes through the center of secondary coil without flux leakage. Measurement precision can be up to 0.1

and 0.2S grades.

� Secondary coil is fixed in an aluminum shielded-case by casting organic materials; measurement and protection circuits

cannot be damaged by insulation breakdown.

� Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an excellent

insulation property. Partial discharge test is carried out under power frequency test voltage.

� There are two types of external insulation bushing for customers: they have excellent explosion-resistant and shock-

resistant behaviors.

� External bushing uses silicon rubber umbrella type apron reinforced by glass fiber. Optimal external surface field makes

silicon rubber avoid electrical erosion.

� Porcelain bushing shell with high-strength.

� Secondary outlet box is a complete structure by casting the aluminum alloy; its sealing structure meets the requirement

of IP55, which is dust proof, water proof and air permeable; secondary terminal for wiring uses Phoenix special terminal; it

is more convenient for operations such as plug-in, pull-out and wiring etc.

� Seal ring is made of imported fluorocarbon silicone rubber, it is suitable for using in the area where there is great

temperature change or the environmental temperature is extreme. The leakage rate per year is less than 0.5%.

� Product performance keeps changeless after severe transporting test.

� Use an aluminum alloy cast case, all components including the base, connection box, stainless steel expander, and

nameplate etc do not rust forever.

� A density meter is installed on the base, this meter can show the gas pressure and density in the transformer (The show

value is turned to be the internal gas pressure at 20� automatically). A signal for refilling gas is sent out when the pressure

in the transformer drops down to the alarm pressure.

Introduction to Structure

Shell

Silicon Rubber Bushing

Secondary Lead Pipe

Outlet BoxBase

Nameplate

Electrode

Conducting Block

Main Body

Rupture Disc

15 16

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

LVQB Series SF6 Gas-insulated Inverted Current Transformer

Antipollution Class (W2, W3)

Voltage Grade (kV)

With Transient protection

With Protection

SF6 Gas-insulation

Inverted

Current Transformer

L V Q B (T) � �

Symbol Explanation

Page 10: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

17 18

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Fig. 2

Technical Parameters of LVQB-110

LVQB-110W2/1X LVQB-110W3/1X LVQB-110W2/2X LVQB-110W3/2X

Outline and Dimensional Drawing

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

TypeLVQB-110W2/1X LVQB-110W2/2X

LVQB-110W3/1X LVQB-110W3/2XHighest Voltage for Equipment kV 126

Rated Frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 230

Rated lightning impulse withstand voltage (full wave)(peak) kV 550

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

Flashover Distance mm 1100

Creepage Distance mm 3150, 3950

Rated Primary Current In (Maximum) A 2400 (1:2; 1:2:4 available)

Rated Secondary Current A 1; 5

Accuracy Classes (They can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated Output VA 10~50

Safety Factor FS 5; 10

Accuracy limit Factor ALF 10; 15; 20; 30

Thermal Current (Maximum) kA 50kA/3s

Dynamic Current (Maximum) kA 125

Air Pressure (Absolute value) MPa 0.5

Outline and Installation Dimensions Fig.2

Net Weight kg 490 565

Gross Weight kg 590 670

Technical Parameters of LVQB-66

Fig.1 LVQB-66W2

Type LVQB-66W2 LVQB-66W3

Highest voltage for Equipment kV 72.5

Rated Frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 160

Rated lightning impulse withstand voltage (full wave)(peak) kV 350

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 403

Flashover Distance mm 650

Creepage Distance mm 1812, 2250

Rated Primary Current In (Maximum) A 4000

Rated Secondary Current A 1; 5

Accuracy Classes (They can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated Output VA 10~50

Safety Factor FS 5; 10

Accuracy Limit Factor ALF 10; 15; 20; 30

Thermal Current (Maximum) kA 50kA/3s (In series)

Dynamic Current (Maximum) kA 125

Air Pressure (Absolute Value) MPa 0.5

Outline and Installation Dimensions Fig.1

Net Weight kg 400

Gross Weight kg 490

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Outline and Dimensional Drawing

Page 11: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

19 20

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Outline and dimensional drawings for

LVQB(T)-330W3 Current Transformer

Outline and dimensional drawings for

LVQB(T)-500W3 Current Transformer

Technical Parameters of LVB (T)-330�500

Outline and Dimensional Drawing

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Type LVQB(T)-330W3 LVQB(T) -500W3

Highest voltage for equipment kV 363 550

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 510/567 740

Rated lightning impulse withstand voltage (full wave)(peak) kV 1175/1305 1675

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1352/1501 1930

Impulse withstand voltage (Wet Test) kV 950/1156 1175

Flashover distance mm � 2850 � 4220

Creepage distance mm � 9080 � 17050

Rated primary current (Maximum) A 5000(2 � 2500) 5000(2 � 2500)

Rated secondary current A 5; 1 5; 1

Accuracy classes (they can be combined if necessary)0.2S;0.5S;0.1;0.2; 0.2S;0.5S;0.1;0.2;

0.5;5P;10P;TPY 0.5;5P;10P;TPY

Rated output VA 10~50 10~50

Safety factor FS 5; 10 5; 10

Accuracy limit factor ALF 10; 15; 20; 30; 40 10; 15; 20; 30; 40

Times of symmetry short-circuit current Kssc 10, 15, 20, 25, 30

TPY Parameter Operating cycle C - O - C - O

Output capacity VA 10, 15

Thermal current (Maximum) kA 63 kA / 3s ( in series )

Dynamic current (Maximum) kA 160 ( in series )

Weight of oil 280 432

Net weight 1800 3000

Gross weight 2600 4000

Fig. 3LVQB-220W2/1X LVQB-220W3/1X

Technical Parameters of LVQB-220

Outline and Dimensional Drawing

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

LVQB(T)-220W2/2X LVQB(T)-220W3/2X

TypeLVQB-220W2/1X LVQB(T)-220W2/2X

LVQB-220W3/1X LVQB(T)-220W3/2XHighest voltage for equipment kV 252

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 460

Rated lightning impulse withstand voltage (full wave)(peak) kV 1050

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208

Flashover distance mm 2250

Creepage distance mm 6300, 7900

Rated primary current In (Maximum) A 4000

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.1;0.2;0.5;0.2S;0.5S;5P;10P 0.1;0.2;0.5;0.2S;0.5S5P;10PTPY;TPS

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Thermal current (Maximum) kA 63kA/3s

Dynamic current (Maximum) kA 160

Rated gas pressure (Absolute value) MPa 0.5

Outline and installation dimensions Fig.3

Net weight kg 1050 1200

Gross weight kg 1350 1500

Page 12: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

21 22

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

JDQXF Series SF6 Gas-insulated Voltage Transformer

� Transformer cabinet is at the bottom of product, main body is in

it, there is a silicon rubber composite insulation bushing or high

strength porcelain bushing at the middle and primary terminals are

at top both sides of product.

� A SF6 gas density controller is equipped on the transformer

cabinet; it can monitor the SF6 gas pressure in-line. There is a

pressure-relief device on the top; the rupture (relief) pressure is 0.

7 MPa without oil or explosion risk, and it is free-maintenance.

� Main body is inside the cabinet, use the composite insulation of

polyester film and SF6 as interlayer insulation, so it has high

strength insulation. Coil uses single-staged tower structure, so it

has a good shock resistant performance.

� Product shell is carried out hot galvanizing or uses cast aluminum

alloy, all components including stainless steel fasteners and name-

plate etc work in outdoor for long time without rust.

� Primary terminal block uses cast aluminum part, the static test

load it can bear is no less than 3000N.

� Secondary outlet box is a complete structure by casting the

aluminum alloy; its sealing structure meets the requirement of IP55,

which is dust proof, water proof and air permeable; secondary

terminal for wiring uses Phoenix special terminal; it is more conve-

Introduction to Structure

Symbol Explanation

Antipollution Class W2 or W3

Rated Voltage Grade

Measurement Coil and Pro-

tection Coil Being Separate

With Residual Voltage Coil

Gas-insulation

Single Phase

Voltage Transformer

nient for operations such as plug-in, pull-out and wiring etc.

� Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an excellent

insulation property. Partial discharge test is carried out under power frequency test voltage.

� Seal ring is made of imported fluorocarbon silicone rubber, it is suitable for using in the area where there is great

temperature change or the environmental temperature is extreme. The leakage rate per year is less than 0.5%.

� High voltage coil is made of imported polyester film and conducting wires with high insulation strength and stable

performance; use imported automatic winding equipment to complete the wire winding and the wrapping of interlayer

insulation automatically according to entered instructions.

J D Q X F � �

Secondary Outlet Box

Cabinet

Main Body

Primary Conducting Pipe

Bushing Electrode

Silicon Rubber Insulated Bushing

Primary Terminal Block

Explosion Resistant Device

Technical Parameters

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 We also can provide with products which meet the requirement of IEC and ANSI.

Type JDQXF-110W2 / JDQXF-110W3

Highest voltage for equipment kV 126

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 230

Rated lightning impulse withstand voltage (full wave)(peak) kV 550

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

Flashover distance mm 1160

Creepage distance mm 3150 / 3950

Rated gas pressure (Absolute value) MPa 0.5

Rated voltage factor/time1.2/continual 1.5/30s

Accuracy class and rated output

Secondary coil 1 Secondary coil 2 Residual voltage coil

Accuracy class 0.2 0.5or3P 3P

Rated output VA150 �� 300

100 150 300

Thermal limit output VA 2000

Outline and installation dimensions See the figure

Net weight kg 450

Gross weight kg 550

JDQXF-110W2

� It can be designed and made with three coils (one primary coil, one secondary coil and one residual voltage coil) or four

coils (one primary coil, two secondary coils and one residual voltage coil) according to the requirement of customer.

� Integrated design is reasonable; it shows capacitive character under certain voltage.

Outline and Dimensional Drawing

Page 13: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Technical Parameters

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 We also can provide with products which meet the requirement of IEC and ANSI.

� Leading wire of secondary coil and leading wire of ground terminal of primary coil are connected with Phoenix special

terminal in the secondary terminal box via the terminal block cast as a whole with epoxy on the shell. It is more convenient

for operations such as plug-in, pull-out and wiring etc. The sealing performance meets the requirement of IP55.

� The transformer can be installed horizontally or vertically.

Type JDQXF-110ZH

Highest voltage for equipment kV 126/145

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 230/275

Rated lightning impulse withstand voltage (full wave)(peak) kV 550/650

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633/748

Rated gas pressure (Absol ute value) MPa 0.5/0.6

Rated voltage factor/time 1.2/continual 1.5/30s

Accuracy class and rated output

Secondary coil 1 Secondary coil 2 Residual voltage coil

Accuracy class 0.2 0.5or3P 3P

Rated output VA150 �� 300

75 120 300

Thermal limit output VA 2000 �� ��

Outline and installation dimensions See the figure

Net weight kg 400

Gross weight kg 500

Outline and Dimensional Drawing

23 24

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

GIS Gas-insulated Voltage Transformer

Voltage transformer matched with GIS is used for SF6

close combined apparatus; it is connected between the

phase and ground. It uses SF6 gas as main insulation, and

uses polyester film, which is used for interlayer insulation,

as additional insulation.

Main components of transformer

� There are lifting blocks, a ground terminal, a nameplate,

an instruction plate and a secondary terminal box on the

metal shell. The shell body is formed by welding steel

plates and hot galvanizing, all connecting bolts uses stain-

less standard parts, they can work in outdoor place for long

time, and do not rust forever. A metal rupture disc is

installed on the base. If a high energy discharge occurs in

it, the rupture disc will break to relief pressure, so the safety

of product is improved.

� Main body is installed in the shell, high voltage electrode

Introduction to Structure

J D Q X F �

Supporting rack

Shell

Charging

Connection

Lifting Block

Grounding Base

Insulator

Conduit

Core andWindingAssembly

and low voltage shielded plate use aluminum plates, which are rotated and pressed to form and carried out polishing

treatment. Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an

excellent insulation property. Partial discharge test is carried out under power frequency test voltage.

� High voltage coil uses single-staged tower structure, so it has a good shock resistant performance. Use imported polyester

films and high strength enameled wires, so it has high insulation strength. Use imported automatic winding equipment to

complete the wire winding and the wrapping of interlayer insulation automatically according to entered instructions.

� It can be designed and made with three coils (one primary coil, one secondary coil and one residual voltage coil) or four

coils (one primary coil, two secondary coils and one residual voltage coil) according to the requirement of customer.

� Disc insulator is used as the partition between the gas chamber of transformer and that of composite apparatus.

Transformer and composite apparatus can have SF6 gas with different pressure. The connection between high voltage

conductor and high voltage electrode on main body uses elastic structure.

Rated Voltage

Measurement Coil and Protection Coil Being Separate

With Residual Voltage Coil

Gas-insulation

�D�for Single Phase; �S�for Three Phases

Voltage Transformer

Symbol Explanation

Secondary

Outlet Box

Explosion Re-

sistant Device

Page 14: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Fig.1 Outline and Installation Dimensions of LB6-110 type Current Transformer (Primary Coil is in series)

Outline and Dimensional Drawing

Main technical Parameters

Type LB6-110(W2) LB6-110(W3) GY

Rated primary voltage kV 110

Highest Voltage for Equipment kV 126

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 230

Rated lightning impulse withstand voltage (full wave)(peak) kV 550

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

Flashover distance mm 1000

Creepage distance mm 3150, 3906

Rated primary current In (Maximum) A 2 � 50~2� 1000

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated output (Maximum) VA 50 (Pigtail 30)

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (depend on the number of31.5~45kA / 1s

turns of primary and secondary coils) kA

Dynamic current (Maximum) kA 80~115

Allowable mechanical load of transformer: Static 2000N

Outline and installation dimensions Fig.1

Net weight kg 690 730

Gross weight kg 750 780

25 26

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

LB6-110 type Current Transformer

Symbol Explanation

L B 6 � 110�

Voltage Grade, kV

Design No.

With Protection

Current Transformer

Except for the above basic symbol, suffix �W2� means that it is

suitable for using in Grade � area, suffix �W3� means that it is

suitable for using in Grade � area, and suffix �GY�means that it

is suitable for using in plateau area.

Introduction to Structure

� LB6-110 type current transformer has an oil-immersed fully-

sealed structure. The primary coil is U-shape, the main body is fixed

on the bracket, the main insulation uses capacitor type oilpaper, use

the high voltage cable paper to wrap the core of primary coil, and set

up several capacitor shields among it, the internal shield is con-

nected to high potential, and the external shield is connected to

ground reliably.

� There is a porcelain bushing at the upper part of oil tank, and an

oil conservator is set up on top of porcelain bushing, primary outlet

terminal is on the oil conservator, series-parallel connection uses an

external switch device, i.e., the switching operation is carried out

outside the oil conservator.

� Use a stainless steel expander as the oil compensation device to

ensure oil quality. Oil level is indicated by the pointer at the upper

window of expander.

� A nameplate is set up on the oil tank to show the technical data. There are four lifting blocks for hoisting, an oil-discharge

valve and earthing bolts at the bottom of oil tank.

� The product can have four to six secondary coils, the secondary measurement coil is made by microcrystalline alloy with

high magnetic conductivity, thus can ensure that the measurement precision reaches up to 0.2 grade or 0.2S grade. 2�600A

or above current transformer has a pigtail at measurement secondary coil, in order to get two current ratios.

� Use new technology and new materials such as hot galvanizing or stainless steel standard parts etc for outside of the

product to make complete equipment rustless.

� Reasonable and originative structure as well as advanced technology ensures that the product runs reliably, safely and

durably.

Page 15: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Outline and Dimensional Drawings for LB7-220 type Current Transformer

Outline and Dimensional Drawing

Technical Parameters of LB7-220

Type LB7-220

Highest Voltage for Equipment kV 252

Rated frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 460

Rated lightning impulse withstand voltage (full wave)(peak) kV 1050

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208

Flashover distance mm 2200

Creepage distance mm 6300�W2)�7900�W3�

Rated primary current (Maximum) A 2 � 600�2� 800

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (Maximum) kA 50kA/3s (In series)

Dynamic current (Maximum) kA 125

Allowable mechanical load of transformer (Static) N 3000

Net weight kg 1180

27 28

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Introduction to Product

� This product has an oil-immersed fully-sealed structure. It con-

sists of metal expander, oil conservator, main body and other

accessories. The primary coil is U-shape, the main insulation uses

capacitor type oilpaper, use the high voltage cable paper to wrap

the core of primary coil, and set up several main shields among it.

� The secondary coil is set up at the lower part of primary coil; the

whole main body is fixed in the oil tank. There is a bushing at upper

part of oil tank, and an oil conservator is set up on top of bushing, the

primary wire is lead out via the hole of oil conservator, the series-

parallel switching operation is carried out outside the oil conservator.

� Use a stainless steel expander as the oil compensation device to

ensure oil quality. Oil level is indicated by the pointer at the upper window of expander.

� A nameplate showing the technical data and a description plate showing the coils arrangement schematic diagram are set

up on the oil tank. There are four holes or lifting blocks on the under-frame for hoisting the product, and an oil-discharge valve

and earthing bolts at bottom of oil tank.

� The product can have five or six secondary coils, the secondary measurement coil is made by microcrystalline alloy with

high magnetic conductivity, thus can ensure that the measurement precision reaches up to 0.2 grade or 0.2S grade.

� The secondary terminal has limit and double sealing functions. The outlet box is made by stretching wholly; it is elaborate

and practical. The oil tank is carried out surface treatment; it is bright and durable.

� Complete transformer is fully sealed. New technology and new materials such as hot galvanizing or stainless steel

standard parts etc are used for outside of the product to prevent from rustless and get long working life.

� Reasonable and originative structure as well as advanced technology ensures that the product runs reliably, safely and

durably.

LB7-220 type Current Transformer

Symbol Explanation

L B 7 � 220�

Voltage Grade, kV

Design No.

With Protection

Current Transformer

Except for the above basic symbol, suffix�W2�means that it is

suitable for using in Grade � area, suffix�W3�means that it is

suitable for using in Grade � area, and suffix �GY�means that it

is suitable for using in plateau area.

Page 16: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

29 30

Rated primary voltage kV 35

Highest voltage for the equipment kV 40.5

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 95

Rated lightning impulse withstand voltage (full wave)(peak) 185

Flashover distance mm 450

Creepage distance mm 1050�1256

Rated primary current A 5�2000

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 40. 2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated output VA 10~40

Safety factor FS � 10

Accuracy limit factor ALF 10; 15; 20; 30

Thermal current (Maximum) kA 40 kA/ 1s

Dynamic current (Maximum) kA 100

Type LAB6-35

Main Technical Parameters

Outline and Dimensional Drawing

Outline and Dimensional Drawing for LAB6-35 type Current Transformer with Expander

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

LAB6-35 type Current Transformer

Symbol explanation

L A B 6 � 35�

Voltage Grade, kV

Design No.

With Protection

Chain type

Current Transformer

Except for the above basic symbol, suffix �W2�means that it is suitable for using in Grade � polluted area, suffix �W3�

means that it is suitable for using in Grade � polluted area.

Introduction to product

�LAB6-35 type current transformer uses oilpaper insulation for outdoor use, it is a fully sealed product. It is used as a current,

electric energy measurement and relay protective device for AC power system with highest voltage for the equipment of the

equipment 40.5 kV and rated frequency 50Hz.

� The product can have three or four secondary coils, the magnetic core uses microcrystalline alloy with high magnetic

conductivity, the measurement precision of secondary coil can be up to 0.2 grade or 0.2S grade.

�The oil conservator of this product is made of aluminum alloy. The oil tank is made by high-quality steel plate stretching

to form as a whole, in order to reduce welding seam leakage points; it has not exposed sealing structure, so it can lengthen

the aging period of seal ring, ensure that the sealing performance is reliable, improve the run quality of insulation oil, and

ensure that the run is safe and reliable.

Page 17: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Outline and Dimensional Drawing for LGBJ-35 type Current Transformer

Technical Parameters of LGBJ-35 Current Transformer

Outline and Dimensional Drawing

Highest voltage for the equipment kV 40.5

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 95

Rated lightning impulse withstand voltage (full wave)(peak)kV 200

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230

Flashover distance mm 380

Creepage distance mm 1020/1260

Rated primary current (Maximum) A 2000

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (depend on the number of turns of 50kA/3s (In series)

primary and secondary coils) �Maximum� kA

Dynamic Current (Maximum) kA 125

Allowable mechanical load of transformer: Static 2000N

Outline and installation dimensions Fig.1

Net weight kg 100

Gross weight kg 120

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Type LGBJ-35W2 LGBJ-35W3

31 32

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

LGBJ type Current Transformer

Introduction to Product

� This product uses the capacitor equalizing theory; it uses optimal

structural design by special electric field analysis and calculation; it

is light and handy, and it is convenient for installation.

� The product is made of fire resistant and corrosion resistant

material without oil or porcelain. It not only can be used in the city

with high sanitary requirement, but also can be used in the area with

severe pollution.

� This series product consists of primary coil, secondary coil, shell

and base plate etc components.

� The secondary coil is set up at the bottom; it is covered by shell

completely to prevent from dust and outer matters entering, and

prevent from being corroded by sand blown by wind.

� The end shield or ground shield is led out separately to be convenient for test, and it also has good humidity resistance.

The insulation resistance is stable and reliable.

� The secondary terminal block uses cast as a whole.

� This is a patented product of our company, and the patent No. is ZL 02 2 88478.5.

� This product uses organic composite material as its main insulation, so it has a long working life, and can be up to 30 years.

� No oil: there is not explosion risk, it is safe and does not leak forever.

� No porcelain: small and light.

� No gas: there is not possibility to pollute environment.

� Non-epoxy cast: it is used in the open air, it is stable and reliable.

� Advanced technology: use the optimal design concept with uniform voltage distribution; partial discharge is small and

dielectric loss factor is low.

� Use special technology, carry out 1% NaCl water cooking test for 42 hours, the data do not change obviously before and

after the test.

� The primary terminal uses copper or aluminium; it is led out horizontally, so it is convenient for wiring.

Symbol explanation

L G B J � 110 GY W2

Antipollution Class

Tableland type

Voltage Class, kV

With High Insulation

With Protection

Dry type

Current Transformer

Page 18: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Technical Parameters of LGBJ-110 type Current Transformer

Outline and Dimensional Drawing for LGBJ-110 type Current Transformer

Outline and Dimensional Drawing

Type LGBJ -110W2 LGBJ -110W3

Highest voltage for the equipment kV 126

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 230

Rated lightning impulse withstand voltage (full wave)(peak) kV 550

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

Flashover distance mm 1000

Creepage distance mm 3150/3910

Rated primary current (Maximum) A 2000

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (depend on the number of turns of primary and 50kA/3s (In series)

secondary coils) (Maximum) kA

Dynamic current (Maximum) kA 125

Allowable mechanical load of transformer: Static N 2000N

Outline and installation dimensions Fig.3

Net weight kg 300

Gross weight kg 350

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

33 34

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Outline and Dimensional Drawing for LGBJ-66 type Current Transformer

Technical Parameters of LGBJ-66 type Current Transformer

Outline and Dimensional Drawing

Type LGBJ-66W2 LGBJ-66W3

Highest voltage for the equipment kV 72.5

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 140

Rated lightning impulse withstand voltage (full wave)(peak) kV 325

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 374

Flashover distance mm 700

Creepage distance mm 1820/2250

Rated primary current (Maximum) A 1250

Rated secondary current A 1; 5

Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

Rated output VA 10~50

Safety factor FS 5; 10

Accuracy limit factor ALF 10; 15; 20; 30

Short-time thermal current (depend on the number of turns of primary 50kA/3s (In series)

and secondary coils) (Maximum) kA

Dynamic current (Maximum) kA 125

Allowable mechanical load of transformer: Static N 2000N

Net weight kg 220

Gross weight kg 230

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

Page 19: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

Note: 1 We can supply the plateau type product which is suitable for altitude 3000m or above according to the requirement of customer,

its technical parameters are the same as that of the product with 31mm/kV ratio of creepage distance and the highest voltage for

equipment of the system;

2 We also can provide with products which meet the requirement of IEC and ANSI.

Type JDC6-110 JDCF-110

Highest voltage for equipment kV 126

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 200

Rated lightning impulse withstand voltage (full wave)(peak) kV 480

Flashover distance mm 552

Creepage distance mm 3150/3910

Rated voltage factor 1.2/ continual 1.5/ 30s 1.2/ continual 1.5/ 30s

Rated voltage ratio 110/ /0.1/ /0.1 110/ /0.1/ /0.1/ /0.1

Accuracy class 0.2(0.5, 3P)/3P 0.2/0.5/3P

Rated output VA 150(300,500)/300 100/250/300

Limit output VA 2000 2000

Oil weight kg 130/165 130/165

Total weight kg 675/695 675/695

Main Technical Parameters

33 333

Outline and Dimensional Drawing

35 36

JDCF-110 type Inductive Voltage Transformer

(Creepage Distance�25mm/kV�

JDCF-110 type Inductive Voltage Transformer

�Creepage Distance�31mm/kV�

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

JDC6-110 and JDCF-110 type Inductive Voltage Transformers

Introduction to Product

� JDC6 -110 and JDCF-110 type voltage transformers use electromagnetic oilpaper insulation for outdoor use; it is a fully

sealed product. It is used as a current, electric energy measurement and relay protective device for the system with effectively

earthed neutral with the highest voltage for equipment 126 kV and rated frequency 50Hz.

� This product has a reliable design and low magnetic density, it can avoid ferroresonance over-voltage, the secondary coil

can separate measurement from protection; the measuring precision can be up to grade 0.2 to meet the different requirement

of customers and the high precision measuring requirement required by power departments.

� This product uses a stainless steel expander; it is carried out advanced vacuum drying and vacuum oiling treatment

technology, so it has small dielectric loss and low partial discharge, and can ensure that the operation of product is safe and

reliable.

Symbol explanation

J D� C 6 � 110�W

Anti Fouling

Rated Voltage, kV

Design Number

With Residual Voltage

Winding in Cascade Stage

Single Phase

Voltage Transformer

J D� C F � 110�W

Anti Fouling

Rated Voltage, kV

With Secondary Winding for

Measurement and Protection

respectively

With Residual Voltage

Winding in Cascade Stage

Single Phase

Voltage Transformer

Page 20: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

37 38

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Outline and Dimensional Drawing of

JDX6-35W3 Inductive Voltage Transformer(Accuracy Class 0.5/3P)

Outline and Dimensional Drawing of

JD6-35W3 Inductive Voltage Transformer

Main Technical Parameters

Outline and Dimensional Drawing

Type JD6-35 JDX6-35

Highest voltage for equipment kV 40.5

Rated frequency Hz 50

Rated power-frequency withstand voltage (rms) kV 95

Rated lightning impulse withstand voltage (full wave)(peak) kV 200

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230

Creepage distance 31

Rated voltage factor 1.2 continual 1.2 continual/ 1.98h

Rated voltage ratio 35/0.135/ /0.1/ /0.1/3

35/ /0.1/ /0.1/ /0.1/3

Accuracy class 0.2(0.5)0.2(0.5)/3P

0.2/1.5/3P

Rated output VA 80(150)80(150)/10

30/80/1000

Limit output VA 1000 1000

Oil weight kg 29 24

Total weight kg 135 127

3 3

3 3 3

Outline and Dimensional Drawing of

JDX6-35W3 Inductive Voltage Transformer(Accuracy Class 0.2/0.5/3P)

JD6-35 and JDX6-35 type Inductive Voltage Transformers

Symbol explanation

J D (X) 6 �� 35 W

Anti Fouling

Rated Voltage, kV

Design Number

With Residual Voltage Winding

Single Phase

Voltage Transformer

Introduction to Product

� JD6-35 and JDX6-35 type voltage transformers use oilpaper insulation for outdoor use; it is a fully sealed product. It is used

as a current, electric energy measurement and relay protective device for the system with the highest voltage for equipment

40.5 kV and rated frequency 50Hz.

� JD6-35 type voltage transformer has a structure with single phase and double coils, it is suitable for connecting at the place

between the phase and phase in a system with ineffectively earthed neutral.

� JDX6-35 type voltage transformer has a structure with single phase and triple coils; it is suitable for connecting at the place

between the phase and ground in a system with ineffectively earthed neutral.

� The core of product uses high quality silicon steel sheets, the measuring precision can be up to grade 0.2; the oil tank has

a form structure, it is formed by stretching high quality steel plate wholly to reduce the number of welding seam leakage points.

The rubber ring uses double sealing to ensure that the operation of product is reliable.

JDX6-35JD6-35

Page 21: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

39 40

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

TYD110/220 type Capacitor Voltage Transformer

Symbol explanation

T YD 110/220 � 0.01 HAnti Fouling

Rated Capacitance, μF

Rated Phase Voltage

Capacitor Voltage Transformer

Integrated Equipment

Introduction to Product� Capacitor voltage transformer series products are suitable for current, electric energy measurement and relay protection

in a system with effectively earthed neutral with rated voltage 35kV, 66kV, 110kV or 220kV and rated frequency 50Hz. It can

also be used for carrier wave communication concurrently.

� This product consists of capacitor voltage divider and electromagnetic unit the medium voltage terminal and low voltage

terminal of capacitor voltage divider are lead out into an oil tank equipped with electromagnetic unit. The electromagnetic unit

consists of middle transformer, a compensation reactor and a damper

� The capacitor voltage divider consists of a bushing, a core and a metal expander. The core of capacitor is combined by

several film-paper composite media and serial parts which are made by coiling aluminum foils, it is carried out vacuum dipping

treatment, the porcelain bushing is filled with transformer oil, and it is equipped with the metal expander to compensate the

change of oil volume at different temperatures.

� This series transformer has a quick saturation damping device with a quick transient response speed, and it also can damp

ferroresonance reliably.

� There is a carrier wave communication terminal in the secondary outlet box, and it also has an over-voltage protection clearance.

� There are an oil level gauge, an outlet box, a nameplate, an oil-discharge plug and an earthing base outside the oil tank.

� The sealing structure of product is optimized, so it has a good sealing performance.

3

Mai

n te

chni

cal p

aram

eter

s

Not

e:1

The

par

amet

ers

in th

e ta

ble

are

not c

hang

eles

s; th

e C

ompa

ny r

eser

ves

the

right

to c

hang

e th

em.

2 W

hen

the

para

met

ers

requ

ired

by th

e cu

stom

er a

re d

iffer

ent f

rom

that

in th

e ta

ble,

they

can

be

nego

tiate

d ac

cord

ing

to th

e re

quire

men

t of t

he c

usto

mer

.

3 W

e ca

n su

pply

the

prod

uct w

ith 3

1mm

/kV

rat

io o

f cre

epag

e di

stan

ce a

nd h

ighe

st v

olta

ge fo

r eq

uipm

ent o

f the

sys

tem

;

4 W

e al

so c

an p

rovi

de w

ith p

rodu

cts

whi

ch m

eet t

he r

equi

rem

ent o

f IE

C a

nd A

NS

I �

3 3 3 3 3 3

1T

YD

35/

-0

.02W

340

.535

/0.

1/0.

1/0.

1/3

50�

0.2�

50�

0.5�

100�

3P�

95/2

0031

500

2T

YD

66/

-0

.02W

372

.566

/0.

1/0.

1/0.

1/3

100�

0.2�

100�

0.5�

100�

3P�

140/

325

3150

0

3T

YD

110/

-

0.00

66H

126

110/

0.1/

�0.

110

0/0.

2

150/

0.5

100/

3P20

0/48

025

500

4T

YD

110/

-

0.00

7H12

611

0/0.

1/�

0.1

100/

0.2

150/

0.5

100/

3P20

0/48

025

500

5T

YD

110/

-

0.00

8H12

611

0/0.

1/�

0.1

100/

0.2

150/

0.5

100/

3P20

0/48

025

500

6T

YD

110/

-

0.01

H12

611

0/0.

1/�

0.1

100/

0.2

150/

0.5

100/

3P20

0/48

025

500

7T

YD

110/

-

0.01

H12

611

0/0.

1/0.

1/0.

110

0/0.

210

0/0.

5

100/

3P10

0/3P

200/

480

2557

0

8T

YD

110/

-

0.01

5H12

611

0/0.

1/0.

1/0.

110

0/0.

210

0/0.

5

100/

3P10

0/3P

200/

480

2557

0

9T

YD

110/

-

0.02

H12

611

0/0.

1/0.

1/0.

115

0/0.

215

0/0.

5

150/

3P10

0/3P

200/

480

2568

0

10T

YD

220/

-

0.00

33H

252

220/

0.1/

�0.

110

0/0.

2

150/

0.5

100/

3P39

5/95

025

750

11T

YD

220/

-

0.00

35H

252

220/

0.1/

�0.

110

0/0.

2

150/

0.5

100/

3P39

5/95

025

750

12T

YD

220/

-

0.00

4H25

222

0/0.

1/�

0.1

100/

0.2

150/

0.5

100/

3P39

5/95

025

750

13T

YD

220/

-

0.00

5H25

222

0/0.

1/�

0.1

100/

0.2

150/

0.5

100/

3P39

5/95

025

750

14T

YD

220/

-

0.00

5H25

222

0/0.

1/0.

1/0.

110

0/0.

210

0/0.

5

100/

3P10

0/3P

395/

950

2582

0

15T

YD

220/

-

0.00

75H

252

220/

0.1/

0.1/

0.1

100/

0.2

100/

0.5

100/

3P10

0/3P

395/

950

2582

0

16T

YD

220/

-

0.01

H25

222

0/0.

1/0.

1/0.

115

0/0.

215

0/0.

5

150/

3P10

0/3P

395/

950

2591

0

Hig

hest

Rat

ed P

rimar

yR

ated

Sec

onda

ryR

ated

Out

put (

VA

)In

sula

tion

Rat

io o

f cre

epag

e di

stan

ce

S/N

Typ

eV

olta

geV

olta

ge V

olta

ge(k

V)

/ Acc

urac

y C

lass

Leve

l(kV

)an

d H

ighe

st v

olta

ge fo

rW

eigh

t

(kV

)(k

V)

1a-1

n2a

-2n

da-d

n1a

-1n

2a-2

nda

-dn

Powe

r Fre

quen

cy/L

ight

nin

equi

pmen

t (m

m/k

V)

(kg)

33 3 3 3 3 3 3 3 3 3 3 3 3

33 3 3 3 3 3 3 3 3 3 3 3 3

33 3 3 3 3 3 3 3 3 3 3 3 3

3 3

3 3

3 3

3 3

Page 22: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

41 42

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

CWG type Dry Wall Bushing

Symbol explanation

Introduction to Structure and Features�This product uses the capacitor equalizing theory; it uses optimal structural design by special electric field analysis and

calculation; it is light and handy, and it is convenient for installation.

�The product is made of fire resistant and corrosion resistant material without oil or porcelain. It not only can be used in the

city with high sanitary requirement, but also can be used in the area with severe pollution.

� This series product consists of primary coil, bushing flanges, and terminal block etc components.

�The end shield or ground shield is lead out separately to be convenient for test, and it also has good humidity resistance.

The insulation resistance is stable and reliable.

�The secondary terminal block is formed by casting as a whole, it can prevent from turning, so the insulation resistance is

stable and reliable.

C W G � � � � / � � � � � � �

Whether used in plateau

Supplemental feature code

Installation mode

Rated current (A)

Rated voltage (kV)

With current transformer

Dry type

Outdoor bushing

Through the wall

Outline and Dimensional Drawing

Outline and dimensional drawing of

TYD-110 type voltage transformer

Outline and dimensional drawing of

TYD-220 type voltage transformer

TYD35/ -0.02W3 type Inductive Voltage Transformers TYD35/ -0.02W3 type Inductive Voltage Transformers3 3

Page 23: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

43 44

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Outline and Dimensional Drawings of CWG - L - 40.5 - CWG - L - 126

CWG-72.5/630 220 22040 4-φ14

60

CWG-72.5/800 220 220 1815�65

CWG-72.5/1000 2470 770 220 770 220 1040 550 275 300 2250

CWG-72.5/1250 220 220 50 4-φ18 70

CWG-72.5/1600 220 2206-φ18

75

CWG-126/6301040

2201040

2201390 40 4-φ14

80

CWG-126/800 220 220 90

CWG-126/10003160 1040

2201040

2201390 700 350 350

3150�95

CWG-126/1250 220 220 50 4-φ18 3906

CWG-126/16001040

2201040

2201390

110

CWG-126/2000 220 220 120

Table 2 unit: mmOutdoorside Indoor Side Earth Potential Installation Flange Terminal Block Cree- Wei-

Type Total Insulation Maximum Insulation Maximum Total Total Indoor Diameter of Installation Distance Between Install- page ght

Length Distance External Insulation External Length Length L5 Installation Hole Hole the Center of Two Holes ation dist- kg

L1 Diameter L3 Diameter L4 L2 D1 a1 Hole ance

CWG-L-40.5/630 180 18040 4-φ14

50

CWG-L-40.5/800 55

CWG-L-40.5/1000 1910 220 220 1015�60

CWG-L-40.5/1250 470 220 470 220 970 450 500 200 50 4-φ18 126065

CWG-L-40.5/1600 220 220

CWG-L-40.5/3150 2070 220 220 60 8-φ18 70

CWG-L-40.5/4000 2070 220 220 60 8-φ18 70

CWG-L-72.5/630 220 220 40 4-φ14 65

CWG-L-72.5/800 220 220 6-φ18 1815�70

CWG-L-72.5/1000 2820 730 220 730 220 1400 970 670 300 2250

CWG-L-72.5/1250 220 220 50 4-φ18 75

CWG-L-72.5/1600 220 220 80

CWG-L-126/6301100

2201100

2202070 40 4-φ14

80

CWG-L-126/800 220 220 90

CWG-L-126/1000 35601100

2201100

2202070 950 600 350

3150�95

CWG-L-126/1250 220 22050 4-φ18

3906

CWG-L-126/16001100

2201100

2202070

110

CWG-L-126/2000 220 220 120

Main Technical Parameters� Type test items

Complete all test items according to the requirement of GB/T4109-1991.

� Rated voltage is 12~126 kV, standard current values can be chosen from the following (Unit: A)

250, 400, 630, 800, 1000, 1250, 1600, 2000, 3150, 4000

� Precision of attached current transformer:

1. Measurement coil: 0.1, 0.2, 0.5, 0.2S, 0.5S (Grade)

2. Accuracy grade of protection coil: 5P, 10P; Accuracy limit factor:10, 15, 20, 30

3. Secondary output capacity (VA): 20, 25, 30, 40 50

� Antipollution grade and creepage distance

Outline and Dimensional Drawings of CWG-40.5-CWG-126

� Insulation Level and Discharge Level (Voltage Unit: kV)

Rated Voltage Nominal Voltage Power-frequency Withstand Lightning Impulse Partial Discharge Level

�Ur� of the System Voltage (Dry or Wet) Withstand Voltage Measurement Voltage pC40.5 35 95 200 35 � 10

72.5 66 147 325 63 � 10

126 110 230 550 109 � 10

� Light, Medium 20 � 3.5

� Severe 25 � 4.0

� Special severe 31 � 4.0

Nominal Value of Minimum Ratio of Creepage Distance and Highest Voltage

for Equipment Relative to Ground mm/kV ( Highest Voltage for Equipment )

Ratio of Creepage Distance and Highest

Voltage for Equipment/ Flashover Distance

Antipollution

Grade

Table 1 unit: mmOutdoorside Indoor Side Earth Potential Installation Flange Terminal Block Cree- Wei-

Type Total Insulation Maximum Insulation Maximum Total Total Indoor Diameter of Installation Distance Between Install- page ght

Length Distance External Insulation External Length Length L5 Installation Hole Hole the Center of Two Holes ation dist- kg

L1 Diameter L3 Diameter L4 L2 D1 a1 Hole ance

CWG-40.5/630180 180 40 4-φ14

45

CWG-40.5/800 50

CWG-40.5/1000 1560 220 220 1015�55

CWG-40.5/1250440

220440

220600 300 150 200 6-f18

50 4-φ18 1260 60

CWG-40.5/1600 220 220 60

CWG-40.5/31501720

220 22060 8-φ18

65

CWG-40.5/4000 220 220 65

Page 24: Sieyuan - Inno Consultinginnoconsulting.com.ar/innorep/html/pdf/catalogue--Jiangsu_Sieyuan... · Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained

45

�� !"#$%&'()*

JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

SieyuanSieyuanSieyuanSieyuanSieyuan®

Parameters of CWG-126 (CWG-L-126)

Type CWG-126/250~4000 CWG-L-126/250~4000Highest Voltage for Equipment kV 126

Rated Frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 230

Rated lightning impulse withstand voltage (full wave)(peak) kV 550

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

Flashout Distance mm 1200

Creepage Distance mm 3150 or 3906

Rated Primary Current (Maximum) A 2000

Rated Secondary Current of Built-in Current Transformer A 1�5

Accuracy Classes of Built-in Current Transformer0.1�0.2�0.5�0.2S; 0.5S; 5P; 10P

(They can be combined if necessary)

Rated Output of Built-in Current Transformer VA 10-50

Safety Factor of Built-in Current Transformer FS 5; 10

Accuracy Limit Factor of Built-in Current Transformer 10; 15; 20; 30

Short-time Thermal Current 25 times of rated current

Bending Load Withstand Test 2000N

Outline and Installation Dimensions See the corresponding drawings

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 We can supply the product with 31mm/kV ratio of creepage distance and highest voltage for equipment of the system;

4 We also can provide with products which meet the requirement of IEC and ANSI.

CWG-126/250�4000

CWG-L-126/250�4000126

50/60

230

550

633

1200

3150 or 3906

2000

1�5

0.1�0.2�0.5�0.2S; 0.5S; 5P; 10P

10-50

5; 10

10; 15; 20; 30

25 times of rated current

2000N

See the corresponding drawings

Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the requirement of the customer.

3 We can supply the product with 31mm/kV ratio of creepage distance and highest voltage for equipment of the system;

4 We also can provide with products which meet the requirement of IEC and ANSI.

TypeCWG-72.5/250�4000

CWG-L-72.5/250�4000Highest Voltage for Equipment kV 126

Rated Frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 230

Rated lightning impulse withstand voltage (full wave)(peak) kV 550

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

Flashout Distance mm 1200

Creepage Distance mm 1815 or 2250

Rated Primary Current (Maximum) A 2000

Rated Secondary Current of Built-in Current Transformer A 1�5

Accuracy Classes of Built-in Current Transformer0.1�0.2�0.5�0.2S;0.5S;5P;10P

(They can be combined if necessary)

Rated Output of Built-in Current Transformer VA 10-50

Safety Factor of Built-in Current Transformer FS 5;10

Accuracy Limit factor of Built-in Current Transformer 10; 15; 20; 30

Short-time Thermal Current 25 times of rated current

Bending Load Withstand Test 2000N

Outline and Installation Dimensions See the corresponding drawings

Parameters of CWG-72.5 (CWG-L-72.5)

Parameters of CWG-40.5 (CWG-L-40.5)

Type CWG-40.5/250~4000 CWG-L-40.5/250~4000

Highest Voltage for Equipment kV 40.5

Rated Frequency Hz 50/60

Rated power-frequency withstand voltage (rms) kV 95

Rated lightning impulse withstand voltage (full wave)(peak) kV 200

Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230

Creepage Distance mm 1015 or 1260

Rated Primary Current (Maximum) A 4000

Rated Secondary Current of Built-in Current Transformer A 1, 5

Accuracy Classes of Built-in Current Transformer0.2; 0.5; 0.2S; 0.5S; 5P; 10P

(They can be combined if necessary)

Rated Output VA 10-50

Safety Factor FS 5, 10

Accuracy limit Factor ALF 10; 15; 20; 30

Short-time Thermal Current 25 times of rated current

Bending Load Withstand Test 2000N

Outline and Installation Dimensions See the corresponding drawings

Note: 1 The Company reserves the right to change the parameters in the table.

2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

requirement of the customer.

3 There are several current ratios for one-time switch of the transformer.

4 We also can provide with products which meet the requirement of IEC and ANSI.

46