25
JKR20601-0181-09 JABATAN KERJA RAYA MALAYSIA CAWANGAN KEJURUTERAAN AWAM, STRUKTUR & JAMBATAN 2009 SPECIFICATION FOR PLASTERBOARD CEILING SYSTEM Specification For Plasterboard Ceiling System

Specification Platerboard Ceiling System

Embed Size (px)

DESCRIPTION

Platerboard Ceiling System standard

Citation preview

  • JKR20601-0181-09

    JABATAN KERJA RAYA MALAYSIA

    CAWANGAN KEJURUTERAAN AWAM, STRUKTUR & JAMBATAN

    2009

    SPECIFICATION

    FOR

    PLASTERBOARD CEILING SYSTEM

    Specification For Plasterboard Ceiling System

  • JKR20601-0181-09

    COMMITTEE

    1. Prof Ir. Dr. Ismail Bin Mohamed Taib - Pengarah, CKASJ (Chairman)

    2. Ir. Abdul Hadi bin Jusuh - Cawangan Penyelidikan Dan Pembangunan

    3. Ir.Zurkarnine Bin Mohd Yaacob - Cawangan Penyelidikan Dan Pembangunan

    4. Cik Maslina Binti Abu Bakar - Cawangan Penyelidikan Dan Pembangunan

    5. Ir.Razdwan Bin Kasim - Cawangan Kejuruteraan Mekanikal

    6. Pn.Sabariah Bt. Hussin - Cawangan Kejuruteraan Elektrik

    7. En. Mohamad Fauzi Bin Abas - Cawangan Arkitek

    8. Ir. Muhammad Azman Bin Jamrus - Cawangan Kejuruteraan Awam, Struktur Dan Jambatan

    9. Ir. Sukhaimi Bin Marob - Cawangan Kejuruteraan Awam, Struktur Dan Jambatan

    10. En. Jamaluddin Md Yusof - Cawangan Kejuruteraan Awam, Struktur Dan Jambatan

    11. Ir. Che Mimi Suriyani Bt. Ismail - Cawangan Kejuruteraan Awam, Struktur Dan Jambatan

    12. Pn.Nurrul Hudha Haryati Amzah - Cawangan Kejuruteraan Awam, Struktur Dan Jambatan

    13. En. Norfaizal Bin Mohamed Salleh - Cawangan Kejuruteraan Awam, Struktur Dan Jambatan

    14. Cik Nur Aisyah Boon Siew Ping - Cawangan Kejuruteraan Awam, Struktur Dan Jambatan

    15. En. Leow Yuen Fooi - Boral Plasterboard(Malaysia) Sdn Bhd

    16. En. Sik Eng Hou - Boral Plasterboard(Malaysia) Sdn Bhd

    17. Pn. Mazni Bt Jaafar - Boral Plasterboard(Malaysia) Sdn Bhd

    18. Pn. Haliza Bt. Mohd Yusof - Boral Plasterboard (Malaysia) Sdn Bhd

    Specification For Plasterboard Ceiling System - 1

  • JKR20601-0181-09 -_......._-----.....--------_.........----------_..._--_.._----------..------------------_..------------------------

    SECTION 1

    1.1 1.2

    SEC"nON 2

    2.1 2.2 2.3 2.4 2.5

    SECTION 3

    3.1' 3.2 3.3 3.4

    SECTION 4

    4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.12

    REFERENCES

    CONTENTS

    SCOPE AND GENERAL Scope ........................................................................ .

    Definitions .................................................................. ..

    MATERIALS General .................................................................... ..

    Zinc-Coated Aluminium/Zinc-Coated Steel ........................ .

    Steel Sections ............................................................ .

    Concealed Ceiling System ............................................. .

    Exposed Grid Ceiling System ......................................... .

    PERFORMANCE SPECIFICATIONS - DESIGN REQUIREMENTS Design ....................................................................... .

    Loads ........................................................................ .

    Fire Reaction And Resistance ..........................................

    Acoustic Requirements .................................................. .

    INSTALLATION GUIDELINES Design ........................................................................

    Site Conditions And Installation ....................................... .

    Setting Out ................................................................. .

    Top Fixings ..................................................................

    Hangers ..................................................................... .

    Ceiling Systems......... ................................................. .

    Bulkhead .....................................................................

    Partitions .................................................................. '"

    Services ..................................................................... .

    Protection Of Installed Ceiling ................................................. ..

    Inspection Of Installed Ceiling ................................................. .

    Testing ................................................................................. .

    Maintenance ....................................................................... ..

    Cutting & Changes Of Installed Plasterboard Ceiling ........... .

    Page

    4

    4

    8

    8

    8

    9

    10

    12

    13

    14

    14

    16

    16

    16

    17

    18

    19

    27

    28

    28

    28

    28

    28

    29

    29

    30

    Specification For PlastertJoard Ceiling System -2

  • JKR20601-0181-09

    SECTION 1: SCOPE AND GENERAL

    1.1 SCOPE

    This document sets out the standard specifications for plasterboard ceiling systems and an installation details as guidelines in the appendix. The ceiling systems covered in this specification shall include concealed and exposed grid which is suspended from the main building structure. These systems are commonly used in commercial, industrial, residential and institutional buildings. The performance specification shall include design criteria and safety factor to comply service and accidental loading conditions. The material specification for board and metals is to conform to the relevant standards.

    Installation details appear in the appendix is to provide contractor and supervising officer guidelines in all building works.

    1.2 DEFINITIONS

    1.2.1 Access hatch - a hinged or removable cover to allow access, from below the ceiling soffit, to services within the ceiling plenum. It is not intended for human access on to the grid.

    NOTE: Access hatch should be taken into consideration in the design requirement.

    1.2.2 Approved - approved by the S.O.

    1.2.3 S.O. - means the Superintending Officer who shall be responsible for the overall supervision and direction of the Works.

    1.2.4 Building board - a dry ceiling lining product supplied in rigid or semi-rigid sheet or panel form in a variety of materials for the lining of ceiling grid systems.

    1.2.5 Ceiling hanger - a ceiling suspension component that is used to connect a main runner or primary channel to the supporting structure above.

    1.2.6 Ceiling suspension system - an assembly of ceiling components for suspending ceiling systems.

    1.2.7 Ceiling system - the components that together form a basis of a ceiling, including the grid members and suspension system. A ceiling system may be direct fixed or suspended.

    1.2.7.1 Concealed ceiling system A ceiling lined with building board where the joints between the boards is flush finished such that the supporting suspension system is not visible.

    1.2.7.2 Exposed grid ceiling system A ceiling with the soffit supporting grid members system is visible in two directions. Any purpose of access by personnel to the ceiling system is strictly prohibited.

    1.2.8 Ceiling tile - an infill unit that is fitted within or to the ceiling grid system to form a soffit in exposed grid ceiling system.

    1.2.9 Cross runner - a secondary member that is connected to the main runner to form a two-way exposed grid ceiling (see Figure 2).

    SpeCification For Plasterboard Ceiling System -3

  • JKR20601-0181-09

    1.2.10 Fire resistance level (FRL) - a measure of the ability of a construction or component to resist, for a stated test time, the spread and effects of a fire as required by BOMBA.

    1.2.11 Furring channel - ceiling suspension members in a concealed ceiling system to which the building board is mechanically fixed.

    1.2.12 Main runner - a primary member in an exposed grid ceiling system, Le. the suspension is fixed directly to the member.

    1.2.13 Perimeter trim - any component fitted around the outer edges of the ceiling to provide an aesthetic finish, particularly at the ceiling-to-wall join. It may also provide structural support to the outer edges of ceiling.

    1.2.14 Soffit

    1.2.14.1 Ceiling The surface of a ceiling system exposed to general view.

    1.2.14.2 Structural soffit (roof or floor) The underside of the structure from which the ceiling system is suspended.

    1.2.15 Suspended ceiling - a ceiling system hung at a distance from the structural floor soffit or roof above.

    1.2.16 Top fixing - a means structure above.

    or device by which suspension hangers are secured to the building

    1.2.17 Wall angle - the edge angle or channel of a ceiling system that is attached to a wall (see Figure 1). The wall angle may also provide support for the infi!! unit or ceiling components that are located at the periphery of the ceiling.

    1.2.18 Approved manufacturer - Plasterboard producer with approved manufacturing license by Ministry of Trade and Industry (MITI) including all necessary product tests and certification by SIRIM or other accredited testing authorities and in compliance with ISO certification.

    1.2.19 PE - Professional Engineer registered with the Board of Engineers, Malaysia.

    Specification For Plasterboard Ceiling System -4

  • JKR20601~0181~09

    InterallanQe Clip bet.e.n furrtno ohannels and prlmar,

    HeIght adjuatment clip .here required

    Perimeter trim

    Primary r.l/atroneMOk Buiding board

    Figura 1

    HeIght .d.....tme..t where requited

    We....gIe

    Ceiling tt. may be fitted within to the ceiling orld

    ollp

    or

    Ma.n runner vlble

    L

    ;-Oroaa-runner vlalble Two...wa,. expod grid

    Figura 2

    Specification For Plasterboard Ceiling System ~5~

  • JKR20601-0181-09

    SECTION 2: MATERIALS

    2.1 GENERAL

    The requirements specified in this Section is based on reliable industry practices over several years in Malaysia and is deemed to have considered materials with adequate mechanical properties, resistance to atmospheric attack, surface-finishing characteristics and properties of compound for joint-forming method in the construction of a safe and serviceable ceiling system.. The material speCification will cover components or parts used in Suspended Concealed and Exposed Grid Ceiling Systems.

    2.2 ZINC-COATED AND ALUMINIUM/ZINC-COATED STEEL

    Zinc-coated and aluminum/zinc-coated steel used for the construction of suspended ceiling components shall comply with BS 1230-1 or other equivalent Standards, as appropriate. The Contractor shall provide proof of compliance to the approval of the S.O.

    NOTE: Where sections have been cut from zinc-coated or aluminium/zinc-coated sheets, the cut edges may be left untreated.

    2.3 STEEL SECTIONS

    All steel sections used for the construction of suspended ceiling components shall comply with the suspension system, and to the approval of the S.O. Cold drawn wire shall not be allowed.

    2.4 CONCEALED CEILING SYSTEM

    2.4.1 Suspension system

    2.4.1.1 Hangers - shall not be taken as less than 5mm diameter galvanized mild steel suspension rods.

    2.4.1.2 Suspension clips - adjustable galvanized suspension clip, and shall not be less than 0.5mm thick.

    2.4.1.3 Primary member - top cross rail 38mm deep x 0.55mm thick with minimum linear density of 0.66kg/m, and having a characteristic strength of at least 250N/mm2.

    2.4.1.4 Secondary member - furring channel 28mm deep x 0.5mm thick with minimum linear density of 0.468kg/m, and having a characteristic strength of at least 250 N/mm2.

    2.4.1.5 Locking clip - shall not be less than 0.8mm thick, galvanized.

    2.4.1.6 Anchors - A minimum of 3.8mm diameter with steel disc and 32mm penetration into a minimum of Grade 20 concrete base, and a minimum of 3.8mm diameter x 18mm length Steel Pin into a minimum of 5mm thick steel plate.

    Specification For Plasterboard Ceiling System -6

  • JKR20601-0181-09

    2.4.2 Building board

    2.4.2.1 Plasterboard / gypsum board

    The types of board and test requirements shall be in accordance with Table 1 and Clause 5.0 of BS 1230 Part 1: 1985, respectively, and to the approval of the S.O. The board shall carry class '0' approval from BOMBA.

    2.4.2.2 Wet area plasterboard / Moisture resistance gypsum board

    The types of moisture resistance board to receive paint finish shall be in accordance with Table 1 and Clause 5.0 of BS 1230 Part 1: 1985, respectively, and to the approval of the S.O. The board shall carry class '0' approval from BOMBA.

    2.4.2.3 Fire stop plasterboard / Fire resistance gypsum board

    The type of board and test requirements shall be in accordance with Type 5 of Table 1 and Clause 5.0 of BS 1230 Part 1: 1985, respectively, and to the approval of the S.O. The board shall carry class '0' approval from BOMBA.

    2.4.3 Finishing

    2.4.3.1 Reinforcing tape - shall not be less than 50mm wide perforated paper tape from an approved manufacturer, and to the approval of the S.O.

    2.4.3.2 jointing compound - shall be pre-mixed multi-purpose gypsum based air drying type compound, in accordance with BS 8212: 1995 and to the approval of the S.O.

    2.4.4 Accessories

    2.4.4.1 Fasteners - all mechanical fixing devices, including, but not limited to, plasterboard nails, drywall screws, and framing screws shall be in accordance with Clause 2.2.3 - Mechanical fixing devices of BS 8212: 1995, and to the approval of the S.O.

    2.4.4.2 Sealants - fire sealant for fire rated plasterboard and wet area sealant for wet area plasterboard/moisture resistance gypsum board shall be in accordance with Clause 2.2.6, BS 8212: 1995, and to the approval of the S.O.

    2.4.4.3 Insulation (thermal/acoustical) - semi rigid insulation/acoustic slab, with minimum thickness of 50mm, with density as indicated as supplied by approved manufacturer.

    2.4.4.4 Control joint - required in a long continuous runs of ceiling, spaced at not more than 9mm in continuous plasterboard ceiling.

    2.5 EXPOSED GRID CEILING SYSTEM

    2.5.1 Suspension system

    2.5.1.1 Hangers - shall not be less than 3mm diameter galvanized mild steel suspension rods.

    2.5.1.2 SuspenSion clips - adjustable butterfly galvanized suspension clip shall not be less than 0.5mm thick.

    Specification For Plasterboard Ceiling System - 7

  • JKR20601-018109

    2.5.1.3 Main runners - shall have a minimum of 24 gauge galvanized steel, not exceeding 3600 mm long, and not less than 25mm width.

    2.5.1.4 Cross runners - shall be having a minimum of 24 gauge galvanized steel and not exceeding 1200 mm long.

    2.5.1.5 Wall angle - shall be either L-Angle or W-Angle with a minimum of 24 gauge galvanized steel, not exceeding 3000mm long and finished on exposed surfaces with off-white enamel to the approval ofthe S.O.

    2.5.2 Ceiling tile

    2.5.2.1 Plasterboard ceiling tile

    Non-directional pattern square edge, 600mm x 600mm x 9.5mm thick or 600mm x 1200mm x 9.5mm thick shall be approved by the S.O. The ceiling tiles shall comply in accordance with the following:

    Non-combustibility to BS 476 Part 4: 1970 (1984) Fire propagation to BS 476 Part 6: 1989 Surface spread of flame to BS 476 Part 7: 1997 Sag performance to ASTM C367 -95 Whiteness index to ASTM E313-73 Noise reduction co-efficient to ASTM E1414-91a Anti fungus to ASTM 03273 OO/ASTM 03274 - 95 Moisture absorption to BS 1230; Part 1: Clause 5.1.4 (Type 3 only)

    2.5.2.2 Vinyl laminated ceiling tile

    Vinyl ceiling tiles is made from standard plasterboard finish with a high quality PVC lining that provides a durable and easy to clean face. However, prior approval by the S.O has to be obtained.

    Specification For Plasterboard Ceiling System -8

  • .IKR20601-0181-09

    SEC T ION 3: PER FOR MAN C ESP Eel Fie A T ION T 0 ME E T DES I G N R E QUI REM E N T S

    3.1 DESIGN

    3.1.1 Aim

    The aim of design is to provide a safe ceiling system that has adequate strength and serviceability, is stable and durable, and satisfies other objectives such as economy and ease of construction.

    3.1.2 Requirements

    The ceiling suspension system and its connections to the structure shall satisfy the design requirements for strength, serviceability, stability and durability in accordance with the procedures specified in this SpeCification, where appropriate. In the absence of such procedures, the Contractor's responsibilities in satisfying the design requirements of the ceiling suspension system are not relinquished, in any manner.

    Ceiling systems shall be designed and installed in such a manner that the suspension and frame will remain structurally sound, without the need for any maintenance.

    Ceiling systems that provide structural stability to the building shall have a design life not less than that of the building.

    3.1.3 Submission

    The Contractor shall submit shop drawings and design calculations of the ceiling suspension system showing compliance to all design requirements and duly certified by a P.E. No work shall commence until approval is given in writing by the S.O. Manufactures of suspended ceiling systems must submit calculation showing compliance to all design requirements and certified by PE and the SO for approval prior to acceptance.

    3.2 LOADS

    3.2.1 General

    The design of a ceiling for ultimate and serviceability limit states shall take into account the action effects ariSing from the following and the load requirements specified in Clause 3.2.2 herein after.

    (a) Air pressure fluctuation. (b) Other loads that may occur (for example, any speCific requirement such as large and heavy

    lighting, mechanical facilities, earthquake etc.).

    3.2.2 Requirements

    The following deSign parameters shall apply:

    (a) Dead, live, wind and earthquake.

    Specification For Plasterboard Ceiling System - 9

  • JKR20601-0181-09

    (b) Allowance should be made for a distributed service load (U) of not less than 0.03 kN/m2. The mass of insulation or other materials supported directly by the plasterboard ceiling must not exceed 0.02 kN/m2. Unless fastened directly to the ceiling frame, designers must provide for extra framework above the ceiling to support heavy items such as large light fittings, hanging TV monitors etc. No M&E fittings and facilities shall be allowed to be supported by the ceiling frame system.

    (c) All ceiling hangers shall be designed for a minimum design action effect (Su) of 0.5 kN (50 kg) for non-trafficable ceiling systems.

    (d) At access hatches, a service point load (U) equals 0.3 kN (30 kg) shall be applied in addition to the other loads. Access hatches shall not be used for personnel to enter the ceiling plenum space. Maintenance and other personnel shall be supported independently of the ceiling system.

    Plasterboards are not designed for and shall not be regarded as structural elements. Therefore, surface mounted fixtures such as light fittings, air-condition diffusers, sprinkler pOints, etc. shall need independent support framing hidden above or exposed below the ceiling line to provide adequate and appropriate support.

    3.2.3 Air pressure fluctuation

    Provision shall be made for the restraining of the suspension system and for the anchoring of the panels. tiles or other materials of the ceiling proper against the effects of any air pressure fluctuations that are likely to be encountered (for example wind pressure for external ceiling, airport areas etc.)

    3.2.4 Deflection limit

    The deflection of ceiling grid system under service condition shall be controlled by a limit for the calculated deflection of the element chosen to the structure and its intended use. The value shall not less than L/360.

    3.3 FIRE REACTION AND RESISTANCE

    3.3.1 General

    Suspended ceiling systems, roof-ceiling or floor-ceiling assemblies incorporating suspended ceiling systems are fequired to provide fire resistance between floors or between the compartment below the ceiling and the ceiling void. In addition. the surface finish of a ceiling system shall meet the performance requirements for reaction to fire.

    3.3.2 Method

    3.3.2.1 Reaction to fire (early fire hazard properties) Where a suspended ceiling system is required to have specific early fire hazard properties, such properties shall be tested in accordance with AS/NZS 1530.3,

    3.3.2.2 Resistance to fire

    Where a suspended ceiling forms part of a roof-ceiling or floor-ceiling system, which is required to have a fire resistance rating, such rating shall be tested in accordance with AS 1530.4.

    Specification For Plasterboard Ceiling System - 10

  • JKR2060 1-0181-09

    3.4 ACOUSTIC REQUIREMENTS

    3.4.1 General

    Roof-ceiling or floor-ceiling assemblies incorporating suspended ceiling systems are often required to provide acoustic performance or noise control between adjacent rooms and other areas.

    3.4.2 Method

    3.4.2.1 Sound absorption

    Ceilings specified to have a sound absorption performance shall be tested in accordance with AS 1045, ASTM C 423 or BS EN 20354. The commonly used rating term is Noise Reduction Coefficient (NRC).

    3.4.2.2 Airborne sound insulation

    Suspended ceilings specified to contribute to the airborne sound insulation between adjacent

    separated rooms with a common plenum, shall be tested in accordance with AS/NZS 2499,

    ASTM E 1414 or ISO 140-9 (two room methods)

    The commonly used rating term is Ceiling Attenuation Class (CAC).

    Ceiling specified to contribute to airborne sound insulation vertically between separated

    rooms shall be tested in accordance with ISO 140-3. The field performance may be verified

    using ISO 140-4.

    The commonly used rating terms for vertical spaces is Sound Transmission Class (STC).

    3.4.2.3 Impact sound insulation

    Ceilings specified to contribute to impact sound insulation vertically between separated

    spaced shall be tested in accordance with ISO 140-6. Site performance may be verified using

    the method described in ISO 140-7.

    The commonly used rating terms is Impact Insulation Class (IIC).

    3.4.2.4 Testing method statement

    A full test report shall be submitted to the 5.0 as proof of compliance. It shall relate to the entire specified system. Any variations shall be endorsed by formal opinion from the test laboratory or field testing. Test reports, opinions and the testing authority shall be stated in the supplier's trade literature or be made available on request, or both.

    NOTE:

    1. Attention is drawn to the fact that the acoustic performance and sound transmission is a property of the complete system, including penetrations.

    2. Alteration, addition or deletion of any component of the system may alter the sound transmission.

    Specification For Plasterboard Ceiling System - 11

  • JKR20601-018109

    SEC T ION 4: INS TAL LA T ION G U IDE LIN ES

    4.1 DESIGN

    The design process shall consider all aspects of the ceiling systems, including the capacity of the primary structure to provide the necessary support to the ceiling and the function of the building.

    4.2 SITE CONDn"IONS

    Internal ceiling installation shall not proceed until the building is effectively weather tight and the work area of wet trades has been completed and dried, unless specifically designed for this situation. External ceilings shall be installed when construction above the ceiling is completed.

    Prior to commencing work, the Contractor shall be provided with the approved shop drawings to allow the installation to proceed.

    4.3 SETTING OUT

    The shop drawings used for the ceiling installation shall contain sufficient information to allow the installer to set out the ceiling grid. The finished height of the ceiling shall be included on the drawings.

    Sufficient information should be clearly indicated on the hop drawings to enable the ceiling module and setting out points in each ceiling area applicable to all relevant trades to be established early. All trades shall work to the same setting out points and data.

    The ceiling height in each area shall be marked in relation to the elevation benchmarks and then transferred by means of a water level, or rotating laser or other devices.

    Setting out lines should be in both directions and squared accurately at the outset.

    NOTE: Building tolerances are such that it may be difficult in large ceiling areas to maintain a strict alignment with modular elements, such as structural columns or window mullions.

    4.4 TOP FIXINGS

    The top fixing to all ceiling hangers should be made to the primary structural framing element, unless

    specifically designed otherwise.

    Screw fasteners used for tension connections shall consider pullout, pull through and over torqueing.

    The Contractor shall ensure the fixings are of a corrosion-resistant material suitable for the intended

    application, and fixings are compatible with the material of the structure to which they are to be fitted.

    In the case of refurbishment, prior to commencing work, the primary structure form which the ceiling is to be suspended shall be verified as being structurally adequate, duly certified by a P.E.

    Specification For Plasterboard Ceiling System 12

  • JKR20601-0181-09

    4.4.1 Purlin fixings

    The top fixing to purlin shall be as follows:

    (a) Fixings shall be made of steel plate straps. No connections requiring drillings to the webllip of the purlins are allowed, unless specifically designed otherwise.

    (b) Where flange connections are necessary, they should be made as close as possible to the web of the purlin, and design calculations shall be provided to ensure the structural capacity of the purlin is not compromised.

    (c) Fixings should be selected and installed in accordance with the manufacturer's specification and approved by the 5.0.

    4.4.2 Concrete fixings

    The top fixing to concrete shall be as follows:

    (a) Shot-fired fasteners are to be approved by 5.0 for the individual site. The type of fasteners shall be referred to Section 2 - Materials - 2.4.4.1 Fasteners.

    (b) When using concrete anchors, they should be installed in accordance with the manufacturer's recommendations taking due care to maintain minimum edge distances, spacing and embedment depth.

    (c) No fasteners, either shot-fired or drilled into are allowed to be installed directly to the flat roof slab. Separate structural framing element shall be specifically designed, and approved by the 5.0.

    4.4.3 Aeratedlllghtweight concrete fixings

    Fixing to aerated/lightweight concrete requires special attention and shall only be made in accordance with the manufacturer's recommendations.

    4.4.4 Structural steel

    The top fixing to structural steel framing element, unless specifically designed otherwise, shall be as follows:

    (a) Self-drilling screws are not allowed for structural steel, unless specifically deSigned otherwise. These screws are not to be placed in tension unless specifically deSigned for that purpose.

    (b) All holes drill to the structural steel by drilling shall be duly approved by the 5.0. (c) Shot-fired anchors shall be approved by the 5.0. (d) Clips are available, but the specific application needs to be checked and installation should be

    strictly in accordance with the manufacturer's recommendations.

    SpeCification For Plasterboard Ceiling System - 13

  • JKR20601-0181-09

    4.4.5 Cold formed steel truss I timber truss

    The top fixing to trusses shall be as follows:

    (a) Fixings shall be made of steel plate straps. Self-drilling screws are not allowed unless specifically designed, otherwise. For the case of proprietary truss system, the Contractor shall obtain written approval from the vendor and the S.O.

    The top fixing to timber shall be as follows:

    (a) Fixing to timber jOist shall be made into the side of the timber, with five times the diameter of the fastener clear edge distances.

    4.5 HANGERS

    The materials used for hangers shall be in accordance with Clause 2.3, above and installed in accordance with the ceiling system manufacturer's specification. Bends as a means of levelling the ceiling or to avoid plenum services, shall not be made in the hangers.

    Where hangers cannot be fitted at the specified spacing, secondary members shall be installed. The secondary framing members shall satiSfy the design requirements specified in Clause 3.2.2. The ceiling system shall not be suspended from, and shall be kept clear of, any building services such as ducts. Ancillary services such as electrical cables and air-conditioning duct works shall not be suspended from the ceiling hangers.

    4.6 CEILING SYSTEMS

    4.6.1 Concealed ceiling system

    4.6.1.1 Set-out

    When setting out a concealed ceiling system, a number of procedures must be considered. If suspending from timber joists or metal purl ins, the primary member (top cross rail) must run at a right angle. Plasterboard is fixed at a right angle to the furring channel, i.e. plasterboard sheets run in the same direction as the top cross rail. When setting out a suspended concealed ceiling system, allow for the least amount of butt joints and recessed joints. The suspension pOints shall carry the suspended ceiling only. For additional ceiling fixtures, extra suspension points should be installed.

    4.6.1.2 Installation procedures

    (a) This suspended ceiling system is to be installed using wall angle. (b) Establish a finished ceiling height from a given mark or plan provided. (c) Measure the depth of the wall angle to be used and place this mark above the finished

    ceiling height.

    Specification For Plasterboard Ceiling System - 14

  • JKR20601-0181-09

    (d) Transfer the new mark around the room, using a water level, laser level, etc and a chalk line.

    (e) Fix the top of the wall angle to the chalk line mark. Wall angle is to be fixed at 600mm maximum centres. The first fixing should be 50mm from the edges.

    Specification For Plasterboard Ceiling System -15

  • JKR20601-0181-09

    (f) Suspension brackets are fixed into place. The first line of suspension brackets must be 200mm from the wall face.

    (g) The first suspension bracket on the first top cross rail must also be 200mm from the wall face, with intermediate suspension brackets spaced at 1200mm maximum centres along the top cross rail.

    (h) Top cross rails are spaced at 1200mm maximum centres (with a minimum of two suspension points per top cross rail). When joining top cross rail, joins must be staggered and a top cross rail joiner used to join the two together.

    (i) Furring channels are fixed at right angles to the top cross rail. A furring channel to top cross rail clip is used to join them together.

    Specification For Plasterboard Ceiling System - 16

  • JKR20601-0181-09

    (j) Furring channel spacing depends upon the type and thickness of plasterboard used.

    Plasterboard type Furring channel spacing 9.5mm Standard core 450mm ctrs max. 9.5mm Unispan 600mm ctrs max. 12.5mm Standard core 600mm ctrs max.

    (k) If furring channel must be joined, then furring channel joiners must be used. Furring channel joins must also be staggered.

    (I) Once the entire concealed ceiling system has been installed, level the ceiling grid using a spirit, laser or water level then install plasterboard sheets.

    SpeCification For Plasterboard Ceiling System - 17

  • JKR20601-0181-09

    Fixing procedures of plasterboard to a concealed ceiling system.

    The following procedures are important when fixing plasterboard to a concealed ceiling system:

    (a) Plasterboard must be fixed at right angle to the furring channell (b) Butt joints must be kept to a minimum. (c) Butt joints must be centred on furring channel. (d) Butt joints must be staggered. (e) Plasterboard is to be fixed using 25mm bugle head needle point type '5' screws (f) Screw spacing for butt joints are at 200mm max. Centres. (g) Screw spacing in the middle of the board are at 300mm max. Centres.

    Suspet Ilion Rods CD 1200 nm max. cenIres

    4.6.2 Exposed grid ceiling system

    4.6.2.1 Set-out

    Allowing for the largest possible margin tile An exposed grid ceiling system should be installed allowing for the largest cut margin tiles possible. By following this method, the system will be aesthetically pleasing and cost effective. An appropriate guide for working out the size of a margin tile is that the margin tile should be more than half of the tile's length or width.

    Specification For Plasterboard Ceiling System -18

  • JKR20601-0181-09

    Working out even margins

    400

    lIDO

    lIDO

    lIDO

    lIDO

    lIDO

    lIDO

    lIDO

    400

    8110 12111 1200 lIDO

    4.6.2.2 Installation procedures

    (d) From a given plan or datum line, establish a finished ceiling height. Measure the depth of the wall angle to be used, then place this distance above the finished ceiling line. This mark will represent where the top of the wall angle will sit.

    400 ~--------------~--~

    (e) Transfer this mark around the room using a water leveller, laser leveller etc.

    ---ond_rtalr_

    SpeCification For Plasterboard Ceiling System - 19

  • JKR20601-0181-09

    (f) Fix wall angle in place with fixing centres at 600mm max.

    wal angle aligned with chait line mark and fixed at specified centres.

    (g) Position two string lines to represent the margin tiles (install string lines using the builder square method)

    (h) Set out main runners, with the first main runner from the wall in line with the margin tile string line. The cross tee slot must line up with the second margin tile string line.

    NOTE: Main runners are to run in the direction shown on the plan. Under a concrete slab, main runners are to run to the room's width. If suspended from C-purlin, main runners are to run at right angle from them.

    Specification For Plasterboard Ceiling System - 20

  • JKR20601-0181-09 ------------------------------------------,------------------------------------------------------------------

    (i) The main runners are to be suspended at 1200mm maximum centres. with the first suspension point 200mm from the wall. Extra suspension pOints must be installed to carry any type of additional ceiling fixing.

    Light fittings roost alwayS be supported on main runner head

    U) The top of the suspension rod or hangers that connects with the suspension bracket should be folded to a 30 angle and 40mm in length.

    Specification For Plasterboard Ceiling System - 21

  • JKR20601-0181-09

    (k) Install cross tee, taking care to ensure that they are fixed and clipped together tightly.

    ~ ~~~nerto cross nmer joini'lg method - note lodUng tab

    providing easy disoonnection

    (I) Once the entire grid has been installed, level the area. (m) Place full tiles into the grid. (n) Cut and install all margin tiles.

    NOTE: Take care not to leave any finger marks on the ceiling tile face - use gloves wherever possible.

    4.7 BULKHEADS

    All bulkheads shall be attached to the structural soffit, independent of the ceiling unless the ceiling system has been designed otherwise.

    4.8 PARTITIONS

    Partition shall be fixed to the primary framing members of the grid and not to the tiles or infill panels. Where the partition is face loaded, the top track of the partition shall be braced within the ceiling plenum or the partition shall be continuous through to the structural soffit.

    4.9 SERVICES

    The ceiling layout shall be planned prior to installation to determine the grid configuration, direction and the like, to ensure that all fixing pOints are compatible with the structural members or other services, or both.

    Mechanical and electrical services shall be completed before installation of the suspension systems. Down-lights or other services shall not rely on the ceiling panel for support. The load shall be transferred back to the ceiling structural components.

    NOTE: Suspension rods or hangers can be installed before or during installation of services.

    Specification For Plasterboard Ceiling System - 22

  • JKR20601-0181-09

    4.10 PRO'rECTION OF INSTALLED CEILING

    All practical steps shall be taken to protect the ceiling from damage.

    NOTE: It is generally impracticable for finished ceiling or partly finished ceilings to be fully protected from damage by other trades. To minimize damage to the finished ceilings, program the ceiling installation as late as possible within the time schedule and control access to the finished areas.

    4.11 INSPECTION OF INSTALLED CEILING

    The ceiling shall be inspected and approved in accordance with the contract documents.

    4.12 TESTING

    The Contractor shall carry out in-situ Pull-out Tests for the top fixings of ceiling hangers. A minimum of 10% of the total quantity of the top fixings shall be tested at random to twice the design load. However, the design load shall not be taken as less than 3kN.

    4.13 MAINTENANCE

    All maintenance of the ceiling system shall be carried out in accordance with the ceiling system

    manufacturer's specification.

    NOTE: The manufacturer should provide advice on the care and maintenance of the ceiling system.

    4.14 CUTTING AND CHANGES OF INSTALLED PLASTERBOARD CEILING

    To make openings for electrical wiring and plumbing etc. measure and mark the location of the penetration on the plasterboard sheet and cut a small hole using a keyhole saw.

    For any light fittings that is are heavier than the allowable load, the Contractor shall obtain written approval from plasterboard manufacturer and submitted to the S.O

    SpeCification For Plasterboard Ceiling System - 23

  • JKR20601-0181-09

    REFERENCES:

    AUSTRALIAN STANDARD

    AS 1045 Acoustics - Measurement of sound absorption in a reverberation room.

    AUSTRALIAN/NEW ZEALAND STANDARD

    AS/NZS 2499 Acoustics - Measurement of sound insulation in buildings and of Building elements Laboratory measurement of room-to-room airborne sound insulation of a suspended ceiling with a plenum above it.

    AMERICAN STANDARD OF TESTING MATERIALS

    ASTM C423 Test Method for Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method.

    ASTM E 1414 Standard Test Method for Airborne Sound Attenuation between Rooms sharing a Common Ceiling Plenum

    BRITISH STANDARD

    BS476 Fire tests on building materials and structures

    BS476 Part 4: Non-combustibility test for materials

    BS476 Part 6: Method of tests for fire propagation for products

    BS476 Part 7: Method for classification of the surface spread of flame of products.

    BS 1230 Part 1: Specification for plasterboard excluding materials submitted to secondary operations

    BS 1230 Part 1: Clause 5.1.4 - Water absorption (type 3 only)

    BS 8212 1985: Code of practice for Dry Wall Lining and Partition Using gypsum plasterboard.

    BRITISH/EUROPEAN STANDARD

    BS EN 20354 Acoustics - Measurement of sound absorption in a reverberation room.

    INTERNATIONAL STANDARD

    ISO 140-3 Part 3: Laboratory measurements or airborne sound insulation of building

    Elements.

    ISO 140-4 Part 4: Field measurements or airborne sound insulation between rooms.

    ISO 140-6' Part 6: Laboratory measurements of impact sound insulation of floors.

    ISO 140-7 Part 7: Field measurements of impact sound insulation of floors.

    ISO 140-9 Part 9: Laboratory measurement of room-to-room airborne sound insulation of a suspended ceiling with a plenum above it.

    Specification For Plasterboard Ceiling System - 24