General Description The Model B-1 Upright and Pendent Foam-Water Sprinklers are air-aspi- rating foam discharge outlets de- signed for use in foam-water deluge systems. They are designed for flam- mable liquid risks where it is desired to apply foam from overhead sprinklers (either upright or pendent) and where fol low-up wit h plain wat er in a standard spray sprinkler pattern is necessary as in the case of NFPA 16, “Standard for the Installation of Foam-Water Sprin- kler and Foam-Water Spray Systems”. It is recommended that theend userbe consult ed with respect to the suitabi lity of the materials of construction for any given corrosive environment . The ef- fects of ambient temperature, concen- tration of chemicals, and gas/chemical velocity, should be considered, at a minimum, along with the corrosive na- ture to which the sprinklers may be exposed. The Model B-1 Foam-Water Sprinkler is a redesignation for the Gem Issue B-1 and Star Model B-1. WARNINGS The Model B-1 Foam-Water Spri nklers described herein must be instal led and mai ntained in compliance with this  document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction.  Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper oper ating condi tion. The instal ling contractor or sprinkl er manufacturer should be contacted with any questions. Technical Data Approvals The Model B-1 Upright and Pendent Foam-Water Sprinklers are UL and ULC Listed. (Discharge outlets and foam concentrat es are Listed for use together. Refer to the individual foam concentrate Listing for operating limi- tations and compatibil ity with the B-1 Foam-Water Sprinklers as provided in the UL Fire Protection Equipment Di- rectory.) The Model B-1 Upright and Pendent Foam-Water Sprinklers meet the re- quirements of MIL-S-901C for light- weight Grade A shock proof equip- ment. The Model B-1 Pendent Foam-Water Sprinklers meet the requir ements of MIL-H-24146. Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 3.0 GPM/psi 1/2 (43,2 LPG/bar 1/2 ) Thread Connection 1/2 inch NPT Finishes Natural Bronze Physical Characteristics Body . . . . . . . . . . . . . . Bronze Defl ector . . . . . . . . . . . . Brass A gi ta to r . . . . . . . . . . . . Br as s Operation The Model B-1 Foam-Water Spri nklers are designed with a unique venturi style body. As foam solution (water and foam concentrate mixture) flows through the inlet of the body, air is drawn into the body through the open- ings adjacent to the wrenching area. The foam solution and air mix is then agitated to create an air-aspirated foam. The B-1 Foam-Water Sprinklers are designed to dischar ge foam in a pre- determined discharge pattern, as well as to discharge water similar to stand- ard spray sprinklers. To meet the in- tent of NFPA 16, foam-water sprin- klers must be able to sufficiently distribute water after depletion of the foam concentrate. Page 1 of 4 TFP840 MARCH, 2006 Model B-1 — 3.0 K-factor Upright and Pendent Foam-Water Sprinklers Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 IMPORTANT Always refer to Technical Data  Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a spri nkl er syst em or its compo-  nents and cause the sprinkler to fail to operate in a fire situat ion or cause it to operate prematurely.

Sprinkler Spuma K 40

Embed Size (px)

Citation preview

Page 1: Sprinkler Spuma K 40

8/9/2019 Sprinkler Spuma K 40

http://slidepdf.com/reader/full/sprinkler-spuma-k-40 1/4

General Description The Model B-1 Upright and PendentFoam-Water Sprinklers are air-aspi-

rating foam discharge outlets de-signed for use in foam-water delugesystems. They are designed for flam-mable liquid risks where it is desired toapply foam from overhead sprinklers(either upright or pendent) and wherefollow-up with plain water in a standardspray sprinkler pattern is necessary asin the case of NFPA 16, “Standard forthe Installation of Foam-Water Sprin-kler and Foam-Water Spray Systems”.

It is recommended that the end user beconsulted with respect to the suitabilityof the materials of construction for anygiven corrosive environment. The ef-fects of ambient temperature, concen-tration of chemicals, and gas/chemicalvelocity, should be considered, at aminimum, along with the corrosive na-ture to which the sprinklers may beexposed.

The Model B-1 Foam-Water Sprinkleris a redesignation for the Gem IssueB-1 and Star Model B-1.

WARNINGS The Model B-1 Foam-Water Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- 

tection Association, in addition to the standards of any other authorities hav- ing jurisdiction.  Failure to do so may impair the performance of these de- vices.

The owner is responsible for maintain- 

ing their fire protection system and de- vices in proper operating condition.The installing contractor or sprinkler manufacturer should be contacted with any questions.

Technical Data ApprovalsThe Model B-1 Upright and PendentFoam-Water Sprinklers are UL andULC Listed. (Discharge outlets and

foam concentrates are Listed for usetogether. Refer to the individual foamconcentrate Listing for operating limi-tations and compatibility with the B-1Foam-Water Sprinklers as provided inthe UL Fire Protection Equipment Di-rectory.)

The Model B-1 Upright and PendentFoam-Water Sprinklers meet the re-quirements of MIL-S-901C for light-weight Grade A shock proof equip-ment.

The Model B-1 Pendent Foam-WaterSprinklers meet the requirements ofMIL-H-24146.

Maximum Working Pressure175 psi (12,1 bar)

Discharge CoefficientK = 3.0 GPM/psi1/2 (43,2 LPG/bar1/2)

Thread Connection1/2 inch NPT

FinishesNatural Bronze

Physical CharacteristicsBody . . . . . . . . . . . . . . BronzeDeflector . . . . . . . . . . . . BrassAgitator . . . . . . . . . . . . Brass

Operation The Model B-1 Foam-Water Sprinklersare designed with a unique venturistyle body. As foam solution (waterand foam concentrate mixture) flowsthrough the inlet of the body, air isdrawn into the body through the open-ings adjacent to the wrenching area.The foam solution and air mix is thenagitated to create an air-aspiratedfoam.

The B-1 Foam-Water Sprinklers aredesigned to discharge foam in a pre-determined discharge pattern, as wellas to discharge water similar to stand-ard spray sprinklers. To meet the in-tent of NFPA 16, foam-water sprin-klers must be able to sufficientlydistribute water after depletion of thefoam concentrate.

Page 1 of 4 TFP840MARCH, 2006

Model B-1 — 3.0 K-factor Upright and Pendent Foam-Water Sprinklers 

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

IMPORTANT Always refer t o Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Page 2: Sprinkler Spuma K 40

8/9/2019 Sprinkler Spuma K 40

http://slidepdf.com/reader/full/sprinkler-spuma-k-40 2/4

Design Criteria The Model B-1 Upright and PendentFoam-Water Sprinklers are intendedfor fire protection systems designed inaccordance with the standard installa-tion rules for foam-water sprinklerssystems recognized by the applicableListing agency (e.g., UL Listing isbasedon the requirements of NFPA 13and 16).

Figure 2 provides the nominal dis-charge patterns for reference use.

NOTE The discharge patterns shown in Fig- ure 2 are not to be used for design purposes or to disregard standard in- stallation rules.

Not less than two foam-water sprin-klers are to be installed in any area,regardless of size, in order to obtainpattern overlap.

The applied density (flow per unit ofarea) of foam solution must meet therequirements of the Authority HavingJurisdiction for the type flammable liq-uid and occupancy. Per NFPA 16, cov-erage density must not be less than0.16 GPM/ft2 (6,52 mm/min) of floor

area with a resulting minimum dis-charge pressure of not less than 30 psi(2,1 bar).

Foam-water sprinkler spacing mustnot exceed the requirements of NFPA13 for extra hazard occupancies andthe system must be hydraulically cal-culated to obtain the required densityand discharge pressure.

NOTE Discharge outlets and foam concen- trates are Listed for use together. Re- fer to the individual foam concentrate Listing for operating limitations and compatibility with the B-1 Foam-Water Sprinklers as provided in the UL Fire Protection Equipment Directory.

Installation The Model B-1 Foam-Water Sprinklers

must be installed in accordance withthe following instructions:

NOTE A leak tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- mum of 21 ft. lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT connections. Higher levels of torque may distort the sprinkler inlet and cause impairment of the sprinkler.

Step 1. Pendent sprinklers are to beinstalled in the pendent position, andupright sprinklers are to be installed inthe upright position.

Step 2.  With pipe thread sealant ap-plied to the pipe threads, hand tightenthe sprinkler into the sprinkler fitting.

Step 3. Tighten the sprinkler into thesprinkler fitting using an 8 or 10 inchadjustable Crescent wrench. With ref-erence to Figures 1 and 3, the adjust-able Crescent wrench is only to beapplied to the wrench flats of thewrenching area.

Page 2 of 4   TFP840

FIGURE 1MODEL B-1 UPRIGHT AND PENDENT FOAM-WATER SPRINKLERS 

NOMINAL DIMENSIONS 

UPRIGHT

2-1/8" DIA.(54,0 mm)

(11,1 mm)7/16"

MAKE-INNOMINAL

1/2"

NPTAREA

WRENCHING

5-13/16"(147,6 mm)

NPT1/2"

PENDENT

5-15/16"(150,8 mm)

(54,0 mm)2-1/8" DIA.

AREAWRENCHING

7/16"

MAKE-INNOMINAL(11,1 mm)

AGITATOR

WRENCHFLATS

1" (25,4 mm)

ACROSS

1" (25,4 mm)ACROSS

FLATSWRENCH

DEFLECTOR

DEFLECTOR

BODY

(9,5 mm)3/8" DIA.

AGITATOR

BODY

3/8" DIA.(9,5 mm)

Page 3: Sprinkler Spuma K 40

8/9/2019 Sprinkler Spuma K 40

http://slidepdf.com/reader/full/sprinkler-spuma-k-40 3/4

Care and Maintenance The Model B-1 Foam-Water Sprinklersmust be maintained and serviced inaccordance with the following instruc-tions:

NOTE Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shutdown the affected fire protection system must be 

obtained from the proper authorities and all personnel who may be affected by this action must be notified.

Model B-1 Foam-Water Sprinklersmust never be painted, plated, coatedor altered in any way after leaving thefactory; otherwise, the spray perform-ance may be impaired.

Care must be exercised to avoid dam-age to the sprinklers - before, during,and after installation. Sprinklers dam-aged by dropping, striking, wrenchtwist/slippage, or the like, must be re-placed.

Frequent visual inspections are rec-ommended to be initially performed forsprinklers installed in potentially corro-sive atmospheres to verify the integrityof the materials of construction as theymay be affected by the corrosive con-ditions present for a given installation.Thereafter, annual inspections perNFPA 25 are required.

The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association (e.g., NFPA 25), inaddition to the standards of any otherauthorities having jurisdiction. The in-stalling contractor or sprinkler manu-facturer should be contacted relativeto any questions.

It is recommended that foam-watersprinkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.

TFP840   Page 3 of 4

FIGURE 2 NOMINAL DISCHARGE PATTERNS 

(Shown for reference only — Not suitable for design purposes) 

FOAM DISCHARGEWATER DISCHARGE

DATAKEY

RADIUS, FEET

0 2 4

8

6 8

6

4

0

2

101,02,03,0

0,5

1,5

RADIUS, METRES

UPRIGHT

PENDENT

2,5

2

8

6

4

RADIUS, METRES

3,0 2,0

RADIUS, FEET

01,0 2 4 6 8 10

0

2,0

1,0

0

     C      E     I     L     I     N     G 

 ,       F

     E     E     T

     D     I     S      T     A     N     C      E     B     E     L     O      W

     C      E     I     L     I     N     G 

 ,       F     E     E     T

     D     I     S      T     A     N     C      E     B     E     L     O      W

     C      E     I     L     I     N     G 

 ,       M

     E     T     R     E     S 

     D     I     S      T     A     N     C      E     B     E     L     O      W

0

2,5

2,0

1,5

1,0

0,5

     D     I     S      T     A     N     C      E     B     E

     L     O      W

     C      E     I     L     I     N     G 

 ,       M

     E     T     R     E     S 

FIGURE 3 WRENCH FLATS 

ADJUSTABLE

WRENCH

8 OR 10 INCH

WRENCH

FLATS

APPLY TO

ONLY

Page 4: Sprinkler Spuma K 40

8/9/2019 Sprinkler Spuma K 40

http://slidepdf.com/reader/full/sprinkler-spuma-k-40 4/4

Limited Warranty Products manufactured by Tyco Fire &Building Products (TFBP) are war-ranted solely to the original Buyer for

ten (10) years against defects in mate-rial and workmanship when paid forand properly installed and maintainedunder normal use and service. Thiswarranty will expire ten (10) yearsfrom date of shipment by TFBP. Nowarranty is given for products or com-ponents manufactured by companiesnot affiliated by ownership with TFBPor for products and components whichhavebeen subject to misuse, improperinstallation, corrosion, or which havenot been installed, maintained, modi-fied or repaired in accordance with ap-plicable Standards of the National FireProtection Association, and/or the

standards of any other AuthoritiesHaving Jurisdiction. Materials foundby TFBP to be defective shall be eitherrepaired or replaced, at TFBP’s soleoption. TFBP neither assumes, norauthorizes any person to assume for it,any other obligation in connection withthe sale of products or parts of prod-ucts. TFBP shall not be responsible forsprinkler system design errors or inac-curate or incomplete information sup-pl ied by Buyer or Buyer’s repre-sentatives.

In no event shall TFBP be liable, incontract, tort, strict liability or underany other legal theory, for incidental,indirect, special or consequential dam-ages, including but not limited to laborcharges, regardless of whether TFBPwas informed about the possibility ofsuch damages, and in no event shallTFBP’s liability exceed an amountequal to the sales price.

The foregoing warranty is made in lieuof any and all other warranties, ex-press or implied, including warrantiesof merchantability and fitness fora par-ticular purpose.

This limited warranty sets forth the ex-clusive remedy for claims based onfailure of or defect in products, materi-als or components, whether the claimis made in contract, tort, strict liabilityor any other legal theory.

This warranty will apply to the full ex-tent permitted by law. The invalidity, inwhole or part, of any portion of thiswarranty will not affect the remainder.

Ordering Procedure When placing an order, indicate the fullproduct name. Refer to the Price Listfor complete listing of Part Numbers.

Contact your local distributor for avail-ability.

Upright Foam-Water Sprinklers:Specify: Model B-1 Upright Foam-Water Sprinkler, P/N 49-210-1-001.

Pendent Foam-Water Sprinklers:Specify: Model B-1 Pendent Foam-Water Sprinkler, P/N 49-211-1-001.

Page 4 of 4   TFP840