    A. GENERAL CHARACTERISTICS

    B. TECHNICAL SPECIFICATION

    Design standars

    Transformer type

    Service Condition

    Type of oil

    Cooling

    Number of phase

    Frequency

    : IEC 76

    : Hermetically Sealed Totally Oil Filled

    : Indoor

    Primary Voltage

    Capacity

    No load losses at nominal voltageOn load losses at principal tapping

    Impedance voltage

    Noise

    C. INSULATION CLASS OF THE WINDINGS

    : Mineral Oil Class 1 acc. to IEC 296

    : ONAN

    : 3

    : 50

    :

    :

    : 1225:

    : 4

    : 56

    TECHNICAL SPECIFICATIONS

    Original

    Date

    Est.

    Chk

    App.

    Client / Project:No

    Page

    :

    :

    Primary Secondary

    Applied test voltage (kV)

    Impulse test voltage (kV)

    STANDARD PRIVATE 630 KVA (INDOOR)

    Phase

    Hz

    630

    Watts8800 Watts

    %

    125

    50

    0

    3

    1 / 2

    Secondary Voltage

    20

    : 0.4

    Vector Group : Dyn5

    Temperature Rise : 60

    Temperature Insulation Class :

    Off load current at nominal voltage : 1.8 %

    A

    Efficiency ( % ) Voltage Regulation

    3/4 load4/4 load 1/4 load2/4 load in %in Volt

    Pf 0.8 98.05

    98.43

    98.39

    98.71

    98.66

    98.92

    98.61

    98.89

    386

    394

    3.39

    1.47Pf 1.0

    Highest system voltage (kV) 24 1.1

    : 65

    - Oil

    - Winding

    kVA

    kV

    kV

    oC

    oC

    E. APPROXIMATE WEIGHTS AND DIMENSION

    Total length 1,750:

    Total width 1,060:

    Total height 1,570:Weight of oil 560:

    Weight of core and winding 825:

    Total weight 1,920:

    mm

    mm

    mmkg

    kg

    kg

    Approximate Drawing No. :

    D. EFFICIENCY AND VOLTAGE REGULATION

    Light Grey RAL 7032:Painting Colour

    The above dimensions and masses are approximate and provided to give a general description of our proposed

    :

    :

    :

    Revision

    Off Circuit Tapping value : +/-2.5%;+/-5%

    dB

    transformer.

    Jakarta - Indonesia

    Joint venture between AREVA TD - P

    28-Oct-04

    DEL

    D 0698

  • 7/29/2019 Std 630kva Indoor

    2/2

    TECHNICAL SPECIFICATIONS

    Original

    Date

    Est.

    Chk

    App.

    Client / Project:No

    Page

    :

    :STANDARD PRIVATE 630 KVA (INDOOR)

    2 / 2

    Revision

    I. LIST OF TEST

    Routine Test :

    - Measurement of the resistance value and checking of polarities

    - Measurement of the ratio on all taps

    - No load test for measurement of the no load loss and no load current

    - Short circuit test for determination of the on load loss and impedance- Applied voltage test

    - Induced voltage test

    :

    :

    :

    ::

    :

    Type test :

    - Temperature rise test

    - Full wave impuls test ( 1.2 / 50 us )

    :

    :

    F. ACCESSORIES

    - Name Plate and Rating Plate

    - HV Plug in Bushings and LV Porcelain Bushings

    - Off Circuit Tap Changer

    - Oil Filling Plug

    - Oil Draining Valve

    - Lifting Lugs

    - Grounding Terminal

    - Bidirectional Rollers

    - Pressure Relief Device Without Contact

    - Protection Relay RIS

    Tests other than the above mentioned list needs further confirmation

    G. DEVIATIONS / EXCEPTIONS

    - None

    Yes No

    - None

    H. NOTES