TX242-Ch03

Embed Size (px)

Citation preview

  • 7/29/2019 TX242-Ch03

    1/3

    CHAPTER 3

    Basic Design Overview (Part 2)

    THIS chapter begins with the assumption that you are by

    now somewhat familiar with the building plans for theproject example, and that the initial drafting (blocking out)

    of the building layout is complete. Your sheet now looks

    something like the example on page 140 labeledFigure A-1.

    As is the typical procedure, what you have traced for areas of

    exposed construction is the architects floor plan, and what

    youhave traced for areas with finished construction is a close

    copy of the architects reflected ceiling plan.

    Once the building is blocked out in scale, it is time to draw

    the sprinklers and system piping on the plan. This is the most

    critical engineering portion of your work. It requires a com-

    plete knowledge of theapplicable codes, mental visualization

    of theproposed building, anda recall of your own knowledge

    and instincts that you attained from all your past experiencein this area.

    As was touched on in the last chapter, the architectural

    plans mayincludea preliminarysprinkler plan,complete with

    many legal disclaimers. It may be wise or unwise to use any

    part of this plan as your own. The preliminary plan may be

    an exact depiction of what the architect and building owner

    desire, or it may simply be a quick drawing made to satisfy

    some municipal requirement. Often, it has been prepared by

    anengineer (hiredby thearchitect)whosereal area of special-

    ization is his accompanying drawings (i.e., the mechanical,

    electrical, civil, and/or plumbing plans). If the quality of the

    preliminary sprinkler plan does not make this possibility ev-

    ident, a phone call to this engineer is always worthwhile: for

    only then will you find out if his design is diagrammatic in

    nature, or if you are expected to comply with his plan with

    limitedlatitudefor deviation. In many of thesecases however,

    thefiner pointsin theengineers plan maybe wayoff themark

    of conforming to the fire sprinkler engineering code. If so, a

    good question to ask during this phone call would be about

    what, if any, requirements in excess of the NFPA Pamphlet

    No. 13 requirements are being asked for.

    Thereareprojectsin which systemdesign hasalready been

    thoroughly researched, prepared, andeven reviewed. When acommercial insurance company is very involved, as with one

    of their H.P.R. clients, a pre-construction meeting is held

    during the planning stages of a fire sprinkler system project

    to allow for recognition of the hazard, understanding of the

    project requirements, and providing bid specifications [1].

    This will take care of allthe majorengineeringissues after the

    local fire prevention bureau has their say, although the level

    of preconstruction document review may vary substantially

    depending on location [2]. Most fire prevention bureaus are

    only interested in reviewing the final shop drawings which

    you will prepare.

    * * *For our purpose in this chapter, we are assuming that none

    of the above preplanning activities have taken place. We will

    now move on to the task of laying out the system after first

    determining the occupancy and hazard level of the building

    tenant, and whether or not any chance of pipe freezing will

    exist.The answer weget isthatthis tenantis in the businessof

    manufacturing thermopane glass and aluminum patio doors,

    and that the facility will be heated year-round.

    Since we have established that there is no reasonable

    chance of future pipe rupture caused by freezing tempera-

    tures, we will immediately decide to install the most reliable

    system available, which is the wet-pipe automatic sprinkler

    system. Speed of operation, low installation cost, and ease

    of maintenance account for the fact that 75% of all sprin-

    kler systems in use are of the wet-pipe type. There is no

    size limitation on wet pipe systems, except that the max-

    imum area protected by any one system on any one floor

    of a single fire section cannot exceed 52,000 square feet

    [3]. Our example building in Figure A-1 is well below this

    maximum limit in size, and can be protected by a single

    system.

    1E\&5&3UHVV//&

    http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/
  • 7/29/2019 TX242-Ch03

    2/3

    We are not concerned in this chapter with gridded or looped

    systems, and so will utilize the only alternative left, which is

    called a tree system. In this layout configuration, the water

    flows from the system riser in a direction down feed-main and

    cross-main piping, and finally down smaller sized branch-line

    piping to the operating sprinkler. Water discharged from that

    sprinkler always comes from a single direction.

    In the layout phase, we first establish where we would liketo run our cross-main piping. In all phases of sprinkler design,

    bear in mind this golden rule:

    DO NOT MAKE A MISTAKE ON THE CROSS-MAIN!

    Why? Because if branch-line (normally 12) piping can-

    not be routed where you show it, an installer can correct that

    without much fanfare. But rerouting the big cross-main pipe

    is a different matter altogether. Not only is it expensive and

    time-consuming, and not only does it affect all other down-

    stream piping, but it can halt the installation completely while

    the installers scratch their heads and attempt to achieve an en-

    gineering solution on the job. This wastes time and time ismoney.

    Again, the cross-main location and elevation is the first

    thing that you lay out. The elevation must be low enough to

    cross below structural beams, which usually means: lower

    than the branch-lines. Naturally, the cross-main should be

    hung high enough so as not to interfere with future building

    operations. The system pipe elevations should be designed so

    that all or most of the system can be drained when necessary

    at the base of the system riser.

    When steel bar-joists support the roof of the structure,

    the direction of the branch-line runs are always perpendic-

    ular to the joists, for ease of pipe hanging. Hence, to feed

    the branch-lines, the cross-main must run parallel to the

    joists.1

    ALWAYS KNOW WHAT YOURE HANGING

    THE PIPE TO!

    Specifically, for optimum cost efficiency, the main should

    be routed beneath a single joist, hung from one side of that

    joist or the other.2 Look at the HVAC (Mechanical) drawings

    to make absolutely certain that the joist location that you

    select has the least chance of obstructional interference. And

    dont select a joist (obviously) that rests directly above a

    column, or the pipe will be run smack into a structural columnor I-beam. In order to avoid ductwork, it may be necessary

    to offset the main once, or several times, or even change

    elevation. Offsets, though, shall be minimized to reduce labor

    andmaterialinstallation cost. Varying depths of I-beamsmust

    be checked (on the steel drawings),3 but the highest priority

    consideration must be that there is reasonable space available

    for the piping to fit where it is shown. This space includes

    space above the pipe as well: for example, there may be space

    available to run pipe below some ductwork, but then it is

    economically impractical to hang the pipe.

    * * *

    On concealedjobs (where all piping is concealed above

    a drywall or drop-ceiling), the main piping must be hung at a

    low elevation, beneath all other mechanical tradework. Many

    designers routinely set cross-main elevations at 7

    to 9

    (pipecenterline) above the highest drop-ceiling height in these

    instances. This is done because it is generally observed that

    the sprinkler trade, being the last of the mechanical trades to

    man a job, hang their pipe on concealed jobs below all

    the ductwork, storm piping, electrical cable trays, and the

    like; but also that the main must lay high enough to avoid

    hindrances such as ceiling speakers and recessed lighting

    fixtures. On tightjobs, where space available above ceiling

    is at the bare minimum, it may be necessary to run the main

    at an even lower elevation, being careful to route this pipe to

    avoid hitting all the recessed lights.

    * * *Before you lay out your branch-lines and fix their ele-

    vation, you need to spot all the sprinkler-head locations.

    The information youll need for this task is detailed more

    thoroughly in Chapter 10, and requires knowledge of spac-

    ing limitations. As previously mentioned, our example job

    is of a glass-door manufacturer, an ordinary hazard occu-

    pancy. The maximum head spacing for this tenant would be

    130 sq. ft. The sprinklers must be positioned high enough

    to fuse from a collection of heat, so factory and warehouse

    sprinkler branch-line piping always run high, through the bar

    joists. The pipe will run through either an A or V space

    in these joists (Note Figure B-2 on page 151). To avoid run-

    ning into joist bracing material, your safe bet is to space the

    sprinkler lines an even number apart from one another (i.e.,

    10, 12, or 14). The spacing between sprinklers in light and

    ordinary hazard occupancies is only allowable up to a 15

    maximum.6

    Onceyouhave determined thedistancefrombranch-line to

    branch-line, you can set the number of sprinklers on a line. In

    the Figure A-2 example, the branch-lines are spaced 12apart,

    andthesprinkler-headsare107 apart on-center, givingyoua

    coverage per sprinkler of (12 107) 127 square feet. Your

    distance from the sprinkler-head to a wall is not to exceed

    one-half the distance between sprinklers in any direction (as

    noted in NFPA #131999 ed.-5-5.3.2).

    * * *

    Noticethat we aresupplying seven sprinklers from a single

    riser nipple, as opposed to six, or eight. The east half of

    the building, framed by the I-beam, creates an area4 of

    (23 74) 1702 sq. ft. Since our sprinkler spacing cannot

    exceed130 sq. ft., and 1702 130 = 13.1, we know that we

    will needat leastfourteenautomaticsprinklers to protect that

    1E\&5&3UHVV//&

    http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/
  • 7/29/2019 TX242-Ch03

    3/3

    23 74area. Twelve sprinklers would not be enough (for

    any ordinary hazard occupancy). If sixteen sprinklers were to

    be designed, the heads would be spaced 93apart, center-to-

    center, giving you a coverage per sprinkler of (120 93)

    111sq. ft.Butundernormalcircumstancesa contractor would

    much prefer to install fourteen sprinklers in this area rather

    than sixteen, for the same reason that one would only install

    one unit heater (and not two or three) in a room if just onecould adequately do the job.

    * * *

    To set the elevation of the piping, we need to collect the

    following facts: the building inFigure A-2 has a flat roof,5

    the underside of which is 15

    high. Its bar joists are all 62

    apart and 20deep. The supporting I-beams all have a depth

    of 24.

    We have an obligation to keep our cross-main as high as

    it can reasonably be situated, to maintain clearance for the

    building owner. Our main piping would be safely installed at a

    centerline elevation 6below the bottom of the solid I-beam.

    This would translate to an elevation of (150 24 6)126. Hanging the branch-lines to run through the center of

    the bar joists is also a safe bet, so we would be inclined to

    have these installed at an elevation of (15 0 10) 142.

    Attention must always be given to the HVAC contractor, the

    no. 1 suspect in all sprinkler installation cases of conflict.

    If his large airhandling equipment is to be installed on the

    roof, we must be careful to avoid running sprinkler piping

    below that area or areas. A basic goal of the sprinkler de-

    signer is to avoid situations where field labor must cut pre-

    fabricated piping because it will not fit where it is intended

    to go.

    Referring again to the example sketched in Figure A-2, the

    fire sprinkler branch-linescould be placed116apart inorder

    to reduce the overall sprinkler head spacing to (116107)

    121.7 sq. ft. It may even be that this arrangement will work

    well for installation, and the piping may be hung in that

    fashion without field adjustment. In fact, the only field ad-

    justment necessary for a branch-line obstruction, consisting

    of steel bar-joist bracing in this case, would be to lengthen or

    shorten the riser nipple (fed by the cross-main) to an eleva-

    tion without obstruction for the line path.But our job is not to

    take chances. Running the lines 116 apart would increase

    thepossibility of positioning the sprinkler within 3 of a joist

    web, which is a code violation as well as a sprinkler spraydischarge interference. Making use again of the information

    derived from Figure B-2, I would recommend the 120spac-

    ing to reduce your odds of running into structural members.

    CITATIONS

    1. Bruce A. Edwards, Fire Sprinkler Plan Review Process, FireProtection Contractor, Feb. 1995, p. 13.

    2. Michael A. Crowley, Meeting Hospital Fire Codes: MissionImpossible? Consulting-Specifying Engineer, Feb. 1995, p. 57.

    3. Sprinkler System Guide, Viking Fire Protection Associates In-corporated, Hastings, Michigan, 1981, p. 10.

    ENDNOTES

    1 As a general rule, 1 1/2 to 3 from the centerline of the joist is theusual spot for the pipe to hang. See Piping Methods and Details,Chapter 13.2 An installer will appreciate a note stating from which side of the

    joist you intend to hang the cross-main.3 The optimum location for the main piping is to cross under theshallowest I-beam.4 Such an area created by ceiling-level beams is sometimes called atrave, or a bay.5

    You will never encounter a single-story building with a perfectlyflat roof without pitch. This is strictly a hypothetical example.6 Sprinklersmay be positionedfurther apart only if specialextended-coverage sprinklers are used, in accordance with the manufacturersspecifications for installation.

    1E\&5&3UHVV//&

    http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/http://tx242-app-d.pdf/