Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 1 of XX

Protection Course

High Impedance

Circulating Current Protection

Presenter: Gustav Steynberg

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 2/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 2 of XX

3 Pole high impedance differential relay 7VH83

Integral CT shorting relay.

Robust solid state design.

Inrush stabilisation through filtering.

Fast operating time.

LED indicator.

Simple voltage setting.

Integral buswire supervision

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 3/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 3 of XX

3 Pole high impedance differential relay 7VH83

 Applications

Transformers

Busbars Reactor windings

Machine stator windings

Stub Protection

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 4/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 4 of XX

High impedance differential relay 7VH80

Robust solid state design.

Inrush stabilisation through filtering.

Fast operating time.

LED indicator.

Simple voltage setting.

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 5/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 5 of XX

High impedance differential relay 7VH80

 Applications

Transformers

Busbars

Reactor windings

Machine stator windings

Stub Protection

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 6/12

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 7/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 7 of XX

Restricted Earth Fault Protection

The Phase CT's are connected in parallel:

Ires = I1 + I2 + I3

During external earth faults:

Ires = Iearth (No trip)

During internal earth faults:

Ires has reversed polarity  (Trip)

7VH80

Protected Zone

Ires

Iearth

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 8/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 8 of XX

External Fault

The voltage measured by the relayduring external faults isapproximately zero

Vrelay = 07VH80

VCT1

VCT2

VCT1

VCT2

Vrelay

RCab RCab

RCab RCab

VCT

Imag

VKP

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 9/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 9 of XX

Internal Fault

The voltage measured by the relayduring internal faults issubstantially greater than zero

Vrelay > VSetting (Trip)

For secure operation theCT must have:

VKP > 2 x VSetting

7VH80VCT1VCT2

VCT1

VCT2

Vrelay

RCab RCab

RCab RCab

VSetting

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 10/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 10 of XX

Stability during external FaultWith CT Saturation

The voltage measured by therelay during external faults andCT saturation is determined bythe fault current andRCab as well as Rint 

Vrelay = IF Rint  + 2 IF RCab

= IF (Rint  + 2 RCab )

For stability:

VSetting > IF (Rint  + 2 RCab )

7VH80VCT1 Rint

VCT1

IF RintVrelay

RCab RCab

RCab RCab

VSetting

Saturated

IFIF

Saturated CT is replaced by R int 

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 11/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 11 of XX

Relay SensitivityDuring Internal Fault - Single end infeed

As Imin is small typ 20 mAVCT1 is approx. = VSetting 

IF = n x Imag + Imin 7VH80VCT1

Rint RCab

RCab

IF

Imag

CT1

Imag

CT2

ImagCTn

Imin

VSetting

Imag

VSetting

7/27/2019 Vh8fol_e

http://slidepdf.com/reader/full/vh8fole 12/12

Differential protection  EV SSubstation Control and Protection Systems

DateName.ppt -page 12 of XX

Relay SensitivityShunt resistor for reduced sensitivity

The max. sensitivity should approximatelybe 10% of full load to avoid the risk of operationdue to unsymmetry and measurement inaccuraciesVCT1 is approx. = VSetting 

IF = 0.1 x Ifull load = n x Imag + Imin + Ish 

The Value of Rsh must be selected to give the required Ish

7VH80VCT1

Rint RCab

RCab

IF

Imag

CT1

Imin

VSetting

Imag

CT Model

Rsh

Ish VSetting