Copyright © 2002 Delmar Thomson Learning
Chapter 7
Input Modules
Copyright © 2002 Delmar Thomson Learning
ObjectivesExplain the differences between positive
and negative logic and sinking and sourcing.Describe the available types of input
modules.Explain the correlation between positive and
negative logic and sinking and sourcing.Explain how specialty I/O modules enhance
a PLC’s functionality.
Copyright © 2002 Delmar Thomson Learning
Objectives (cont’d.)
Define module and sensor specifications from data sheets.
List the advantages of three-wire solid-state sensors and the disadvantages of using two-wire sensors.
Explain the differences between analog and discrete inputs.
Copyright © 2002 Delmar Thomson Learning
PLC Connection to the Outside World
The input section of a PLC is the physical connection between the outside world and the CPU.
Modular PLCs use interchangeable I/O modules.
Modules are inserted into slots in the SLC 500 chassis.
Copyright © 2002 Delmar Thomson Learning
Types of I/O Modules
Discrete input and outputAnalog input and outputSpecialty I/O modulesCommunication modules
Copyright © 2002 Delmar Thomson Learning
Discrete versus Analog Inputs
Discrete or digital input signals are two-state signals:Input ON or OFF, 1 or 0
Analog input signals are values:0 to 10 volts DC-10 to +10 volts DC4 to 20 milliamps
Copyright © 2002 Delmar Thomson Learning
I/O Module Positioning in Chassis
Processor always goes in leftmost chassis slot.
SLC 500 slot numbering starts with the leftmost slot as slot 0.
I/O modules are inserted starting at slot 1.
Copyright © 2002 Delmar Thomson Learning
SLC 500 Four-Slot Chassis With I/O Module
Image courtesy of Allen-Bradley, a Rockwell Automation business
Copyright © 2002 Delmar Thomson Learning
Module Features
Identifier as to type of module:InputOutputCombination input or output
Status indicatorsScrew terminals for connecting
field devicesRemovable terminal blocks
Copyright © 2002 Delmar Thomson Learning
SLC 500 Combination I/O Module
Image courtesy of Allen-Bradley, a Rockwell Automation business
Copyright © 2002 Delmar Thomson Learning
SLC 500 Combination I/O Module (cont’d.)
Each screw terminal will have a unique identifier called an address.
Each field device input screw terminal will correlate to a status indicator.
Status indicator will be on when the input point sees an input signal.
Status indicator will have same address identifier as input screw terminal.
Copyright © 2002 Delmar Thomson Learning
Typical Wiring of Input Signals
Copyright © 2002 Delmar Thomson Learning
Block Diagram of a Typical AC Input Circuit
Copyright © 2002 Delmar Thomson Learning
Input Pulse with Valid Signal Areas Defined
Copyright © 2002 Delmar Thomson Learning
Optical Isolator
Copyright © 2002 Delmar Thomson Learning
16-Point Input Module with 8 Points Per Common
Copyright © 2002 Delmar Thomson Learning
Solving Leakage Current Problems
Carefully match input device to input module.Check manufacturer’s specifications.
When using a two-wire device, install bleeder resistor when necessary.
Use a three-wire input device.
Copyright © 2002 Delmar Thomson Learning
Sinking and Sourcing
Sinking and sourcing are terms used to describe current flow through a field device in relation to the power supply and the associated I/O point.
Copyright © 2002 Delmar Thomson Learning
In Which Direction Does Current Flow?
Copyright © 2002 Delmar Thomson Learning
PLC Current Flow
Many PLC manufacturers follow the theory that current flows from positive to negative.
Copyright © 2002 Delmar Thomson Learning
Switch Is Source of Current: the Light Sinks to Ground
Copyright © 2002 Delmar Thomson Learning
Light Is Source of Current: the Switch Sinks to Ground
Copyright © 2002 Delmar Thomson Learning
Sourcing DC Input Module with a Sinking Switch
Copyright © 2002 Delmar Thomson Learning
Sinking DC Input Module with a Sourcing Switch
Copyright © 2002 Delmar Thomson Learning
Sourcing Two-Wire Inductive Proximity Sensor
Copyright © 2002 Delmar Thomson Learning
Sinking Two-Wire Inductive Proximity Sensor
Copyright © 2002 Delmar Thomson Learning
Basic Principles
NPN transistors are open-collector, current sinking devices, which interface to a sourcing input module.
PNP transistors are open-collector, current sourcing devices, which interface to a sinking input module.
Copyright © 2002 Delmar Thomson Learning
Simplified Circuitry for a DC Input Module
Copyright © 2002 Delmar Thomson Learning
DC Input Modules
Except for the bridge rectifier circuit, the DC input module is very similar to the AC input module.
Copyright © 2002 Delmar Thomson Learning
Simplified DC Input Module Circuitry
Copyright © 2002 Delmar Thomson Learning
Leakage Current in DC Modules
Maximum off-state current:The maximum amount of leakage
current allowed in an input circuit that will keep the input circuit in an off state.
Too much current leaking from input device will be seen as a valid on signal by input module all the time.
Most common with 2-wire solid state input devices.
Copyright © 2002 Delmar Thomson Learning
Bleeder Resistor and Leakage Current
Bleeder resistor creates a parallel circuit so excess current can be shunted away from input point.
Refer to manufacturers’ specifications for calculations.
Copyright © 2002 Delmar Thomson Learning
Bleeder Resistor Installation in an Input
Circuit
Copyright © 2002 Delmar Thomson Learning
Calculation ExampleIf:
Maximum off-state current equal to 1 milliamp
Input point impedance of 1 K ohmSensor leakage current equals 1.7 milliamps
A 1-K ohm resistor in parallel with the input will split current going into module input point in half to .85 milliamps.
Other .85 milliamps go through resistor to ground.
Copyright © 2002 Delmar Thomson Learning
Solving Leakage Current Problems
Check manufacturer’s specifications and carefully match input device to input module.
When using a two-wire device, install bleeder resistor when necessary.
Use a three-wire input device.
Copyright © 2002 Delmar Thomson Learning
Diagram of Connection for Three-Wire Sensor
Copyright © 2002 Delmar Thomson Learning
Discrete Input Status Table Word
16-point discrete input modules are assigned one word in the input status table.
A 16-point discrete input module residing in slot 3 would be addresses as I:3.0, bits 0 through 15.
Copyright © 2002 Delmar Thomson Learning
Input Status Table
Copyright © 2002 Delmar Thomson Learning
Discrete I/O Module With 32 Points
Because input status word is 16 bits wide, there are 16 bits available for up to 16 I/O screw terminals.
A 32-point I/O module will require two 16-bit words to accommodate all I/O points.
For a 32-point input module in slot 3, two words, I:3.0 and I:3.1 will be created as part of the I/O configuration.
Copyright © 2002 Delmar Thomson Learning
32-Point Input Module
Copyright © 2002 Delmar Thomson Learning
Input Addressing for Upper 16 Bits
Screw terminal 16 address would be I:3.1/0. Screw terminal 17 address would be I:3.1/1.Screw terminal 18 address would be I:3.1/2.Screw terminal 31 address would be I:3.1/15.
Can be entered on ladder as I:3/31, will display as set up in properties.
Copyright © 2002 Delmar Thomson Learning
Analog Inputs
Typical analog signals come from temperature, pressure, position, motor speed.
Analog input modules convert analog signals to digital words.
Analog input signals are current or voltage.
Copyright © 2002 Delmar Thomson Learning
Typical Analog Inputs
Analog input signals0 to 10 volts DC-10 to +10 volts DC0 to 5 or 1 to 5 volts DC4 to 20 milliamps0 to 20 milliamps-20 to +20 milliamps
Copyright © 2002 Delmar Thomson Learning
Analog Module Configurations
Analog input information comes in as an input channel.
Analog modules areAll inputsAll outputsCombination of input and output
channels
Copyright © 2002 Delmar Thomson Learning
Analog Input Signals Represent Values
A potentiometer supplying a 0 to 10 V DC input signal to an analog input module could send a converted signal of 0 to 32767 into PLC memory.
Analog data format determined by module and module configuration.
Copyright © 2002 Delmar Thomson Learning
Local Versus Remote I/O
Local analog modules in a SLC 500 system automatically send the converted signal into the input status table.
Remote I/O analog signals require block transfers.
Copyright © 2002 Delmar Thomson Learning
Selected Allen-Bradley SLC 500 Analog Modules
Image courtesy of Allen-Bradley, a Rockwell Automation business
Copyright © 2002 Delmar Thomson Learning
Analog Input Modules and the Input Status Table
Each analog channel will be represented by a entire word in the input status table.
A two-channel analog input module will have two words in the input status table to represent the binary representation of the analog voltage or current.
Copyright © 2002 Delmar Thomson Learning
Analog Data Is Represented as Whole Word Data
Analog signals are not digital signals represented as 1s and 0s.
Analog information is represented as a 16-bit signed integer in the data table.
Each channel will require one word.Data table will reserve one word for each
channel. This part of the I/O configuration process.
Copyright © 2002 Delmar Thomson Learning
Input Word Assignment
1746-NI8 is an 8-channel analog input module.
Eight words will be assigned to the input status table as part of the I/O configuration.
Module in slot 4 will have words I:4.0 through I:4.7, one for each channel.
Copyright © 2002 Delmar Thomson Learning
1746-NI8 Input Status Table Words
Copyright © 2002 Delmar Thomson Learning
SLC 500 Analog Voltage Input Specifications
Copyright © 2002 Delmar Thomson Learning
Percentage of Analog Potentiometer
Copyright © 2002 Delmar Thomson Learning
Single-Ended Analog Input Connections from Field
Devices
Image courtesy of Allen-Bradley, a Rockwell Automation business
Copyright © 2002 Delmar Thomson Learning
Differential Analog Input Connections
Image courtesy of Allen-Bradley, a Rockwell Automation business