8/13/2019 VIPAM 3000
1/24
Features
Rating & Performance
Operational Characteristic
Characteristic Curve
Operational Characteristic & Terminal Marks
Connecting Method
External Structure & Each Part Name
External Dimensions & Diagram
Control Circuit Diagram & Development
Test Report
D3-2
D3-4
D3-6
D3-10
D3-14
D3-16
D3-18
D3-20
D3-22
Digital Multifunction Integrated Protection RelayD3C O N T E N T S
VIPAM 3000
8/13/2019 VIPAM 3000
2/24
D3-2 VITZROTECH
Digital Multifunction Integrated Protection Relay _ Feature
VITZRO TECH VIPAM 3000-FI is a Compact Size Digital Integrated Protection Relay that provides a high-precision measurement and
protective relay on electric power receiving/distributing equipments. It is installed with a 32bit high-speed DSP that allows it to
perform the protective relay and measurement at the same time. VIPAM 3000-FI supports essential protective relay elements that
are used at extra HV panels and HV panels of general extra HV consumers. Its operation and setting are simplified compared to the
existing relay and the cost is reduced. VIPAM 3000-FI uses the RS-232 port in front to set equipments, measure and monitor power
and perform various additional services including saving, modifying and recovering the setting value[relay element]. It can also
download the fault waveform from PC to analyze. The RS-422/485 Port in rear part is connected to communicate with the upper
software and provides various application services such as measuring and monitoring power, controlling CB and so on.
VIPAM 3000
8/13/2019 VIPAM 3000
3/24
D3-3VIPAM 3000
Features
MainFunction
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
Protection Relay\Function
Over-Current Relay Time Delay & InstantaneousElement, OCR(51P, 50P)
Ground Over-Current Relay Delay & InstantaneousElement, OCGR(51G, 50G)
Directional Ground Over-Current Relay Delay
& Instantaneous Element, DOCGR(67N)
Selective Ground Relay Definite Time Element, SGR(67G)
Over Voltage Relay Definite Time Element, OVR(59P)
Low Voltage Relay Definite Time Element, UVR(27P)Ground Over Voltage Relay Definite Time Element,
OVGR(64G)
Open-Phase Relay Definite Time Element, POR(47P)
Negative-Phase Over Voltage Relay Definite Time
Element, NSOVR(47)
Unlike the existing method that requires peripheral analogue or digital relay equipments, the body of
VIPAM 3000 is equipped with all the digital relay elements to minimize the time and spatial loss.
All the measurements and relay values are digitized to ensure the reliability and precision.
VIPAM3000 uses DSP to perform a highly reliable and precise measurement function and relay function.
Various relay elements are repeatedly computed in real-time to enable the precise measurement
and the reliable and high-speed relay operations.
Provide 9 types of various relay elements that are vital for electric power system (9 types)
OCR(51P/50P), OCGR(51G/50G), DOCGR(67N), SGR(67G), OVR(59P), UVR(27P), OVGR(64G), POR(47P),
NSOVR(47)
Power quality function, including harmonic (Voltage/Current of each phase), K-Factor and so on
Function to save fault waveform using ferroelectric RAM.
- Save 1sec data when a failure is generated (10 cycles before failure/50 cycles after failure)
- Maintain the recent failure data
Provide a function to analyze the fault waveform using PC monitoring program
Event, Fault Recording Function
KEMC1120 Certified
Measurement Function
32 Sampling/Cycle Measurement
Current(Phase, Ground, Zero-Phase)
Voltage(Phase, Line, Ground)
Current(Active, Reactive, Apparent)
Electric Energy(Active, Reactive, Apparent)
Reverse Electric Energy(Active, Reactive)Power-Factor(PF)/Frequency)
User-Convenient Function
Event Record
Fault Record
Fault Wave Record
Alarm DO Count RecordCB Count Record
Display Function
204 Mono Character LCD Applied
Display Various Operating Statesusing 24 LEDs
Confirm Menu to prevent error
operation of CB ON/OFF
Power Quality Function
Harmonic
(Voltage & Current of each phase)
K-Factor
Communication Function
Front RS-232 Port, 1EA (For PC HMI)
Rear RS-422/485 Port, 1EA
(For Modbus RTU)
8/13/2019 VIPAM 3000
4/24
Rating & Performance
D3-4 VITZROTECH
Item Specification
Connecting Method
Control Power
Power Consumption
Frequency
Rating
Burden
Rating
Burden
Type
Rating
Type
Rating
Operating Temperature Range
Storage Temperature Range
Operating Humidity Range
Altitude
Others
Applied Standard
1P2W, 1P3W, 3P3W, 3P4W
AC85V220V, DC100V300V
Normal: 30W or below, During Operation : 50W or below
60Hz(50HzOption)
PT: 110V or 110/3V
GPT: 190V or 190/3V
PT: 0.5VA or below
GPT: 0.5VA or below
PT: 2V350V[L-N]
GPT : 2V200V[L-N]
CT:5A
ZCT : 1.5mA
CT: 1.0VA or below
ZCT: 1.0VA or below
CT(Phase): 0.05A150A
CT(Ground): 0.02A60A
ZCT : 0.5mA9mA
CB ON/OFF State Input: 2EA
Digital Input : 14EA
Wet Contacts Input
AC/DC80125V(Ripple factor 30% or below)
For Interruption : 2EA
For Alarm:8-Channel, For L/R: 2-Channel, For Buzzer: 1-Channel
System For Fail : 1-Channel
Dry Contact Output
For Interruption : AC250V 16A/DC30V 16A Resister Load
Others : AC250V 5A /DC30V 5A Resister Load
-10 55
-25 70
Daily Average 90% or less (No dewdrops form)
Altitude of 1,000m or below
Place without abnormal vibrations & impulses
Place with less contaminated air
KEMC1120, IEC60255, IEC61000-4
Voltage
Current
Input Contact
Output Contact
Rating
Measurement Range(Multiplying Factornot applied)
Measurement Range(Multiplying Factor
not applied)
Number of Contacts: 16EA
Number of Contacts: 14EA
8/13/2019 VIPAM 3000
5/24
D3
D3-5VIPAM 3000
VIPAM 3000
ProtectionElement
Operation Type Operating Value SettingOperating Time Characteristic
Setting Range CharacteristicRemarks
Time Delay Element
Time Delay Element
Time Delay Element
Time Delay Element
Time Delay Element
disable, 1.0In~24.0In / 0.1In
disable, 0.2In~10.0In / 0.01In
disable, 1.0In~10.0In / 0.1In
disable, 0.02In~2.0In / 0.01In
disable, 1.0In~10.0In / 0.1Io
0.07Vo~1.0Vo / 0.01Vo
0 359 / 1 , 90
disable, 0.02In~2.0In / 0.01Io
0.07Vo~1.0Vo / 0.01Vo
0 359 / 1 , 90
disable, 0.6Iz~4.0Iz / 0.01Iz
0.07Vo~1.0Vo / 0.01Vo
0 359 / 1 , 90
disable, 0.8Vn~1.6Vn / 0.01Vn
disable, 0.2Vn~1.0Vn / 0.01Vn
disable, 0.05Vo~0.8Vo / 0.01Vo
disable, 5~100% / 1%
disable, 5~100% / 1%
In=5A
In=5A
Vo=110,190VIn=5A
Vo=110,190V
Vo=110,190V
Iz=1.5mA
Vn=110,63.5V
0.05~100s/0.01s50ms or below
0.05~10/0.01
0.1~100s/0.01s
0.05~100s/0.01s50ms or below
0.05~10/0.010.1~100s/0.01s
0.05~100s/0.01s50ms or below
0.05~10/0.010.1~100s/0.01s
0.1~100s/0.01s
0.1~100s/0.01s
0.1~100s/0.01s
0.1~100s/0.01s
0.1~100s/0.01s
0.1~100s/0.01s
OCR(50/51)
OCGR(50/51G)
DOCGR(67N)
Instan-taneousElement
TimeDelayElement
TimeDelayElement
SGR(67G)
OVR(59)
UVR(27)
OVGR(64G)
POR(47P)
NSOVR(47)
Type Display Range Precision
Phase Voltage
Phase-phase voltage
Current
Active
Reactive
Apparent
ActiveReactive
Apparent
Active
Reactive
Frequency
Power-Factor
Voltage
Current
Voltage
Current
Voltage
Current
0.0V~9999.99kV
0.0V~9999.99kV
0.0A~9999.99kA
0.0W~9999.99MW
0.0Var~9999.99MVar
0.0VA~9999.99MVA
0.0Wh~9999.99MWh0.0Varh~9999.99MVarh
0.0VAh~9999.99MVAh
0.0Wh~9999.99MWh
0.0Varh~9999.99MVarh
45Hz~65Hz
0.000~1.000Lead/Lag
Second Harmonic~15 Harmonic
Second Harmonic~15 Harmonic
0.0~100.0
0.0~100.0
0.0~100.0%
0.0~100.0%
0.5%
0.5%
0.5%
1.0%
1.0%
1.0%
1.0%1.0%
1.0%
1.0%
1.0%
0.03Hz
1.0%
0.5%
0.5%
-
-
1.0%
1.0%
Reverse ElectricEnergy
THD
K-Factor
Harmonic
ElectricEnergy
Power
PerformanceProtection Relay Element
Measurement Display Range
Dig
italMultifunction
Inte
gratedProtectionRelay
InstantaneousElement
InstantaneousElement
InstantaneousElement
Zero Phase Current
Zero Phase Voltage
Standard Phase Angle
Zero Phase Current
Zero Phase Voltage
Standard Phase Angle
Zero Phase Current
Zero Phase Voltage
Standard Phase Angle
Time DelayElement
DefiniteTime
Inverse TimeDefinite Time
Inverse TimeDefinite Time
Inverse TimeDefinite Time
DefiniteTime
DefiniteTime
DefiniteTime
Definite Time
Definite Time
Definite Time
Definite Time
Definite Time
8/13/2019 VIPAM 3000
6/24
Item Area
Current
Rated Current(In)
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Fundamental wave of phase current(Remove harmonic & DC offset)
5A
0.20 In~10.00In/0.01In unit adjustment
0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Definite(Definite Time)
Bigger value between 5% of setting value or 35ms
Item Area
Current
Rated Current(In)
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Time
Accuracy of Operating Time
Fundamental wave of phase current(Remove harmonic & DC offset)
5A
1.0In~24.0In/0.1In unit adjustment
0.05s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Operate within 0.05s when the operating time is set as 0.05sOperate within the set value when the operating time is set as that value
Bigger value between 5% of setting value or 35ms
Item Area
Current
Rated Current(In)
Operating Value Setting Range
Operating Time Setting(Lever)
Recovery Level
Accuracy
Operating Characteristic Curve
Accuracy of Operating Time
Fundamental wave of ground current(Remove harmonic & DC offset)
5A
0.02In~2.00Io/0.01In unit adjustment
0.05~10.0/0.01 unit adjustment
97% of operating value setting
5%
IEC(SI, VI, EI, LI), KEPCO(SI, VI)
Bigger value between 5% of setting value or 35ms
Operating Characteristic
D3-6 VITZROTECH
Over-CurrentRelay InverseTime Element
Over-CurrentRelay DefiniteTime Element
Over-CurrentRelayInstantaneousElement
GroundOver-CurrentRelay InverseTime Element
OCR(51P)
OCR(51P)
OCR(50P)
OCGR(51G)
Item Area
Current
Rated Current(In)
Operating Value Setting Range
Operating Time Setting(Lever)
Recovery Level
Accuracy
Operating Characteristic Curve
Accuracy of Operating Time
Fundamental wave of phase current(Remove harmonic & DC offset)
5A
0.20In~10.00In/0.01In unit adjustment
0.05~10.0/0.01 unit adjustment
97% of operating value setting
5%
IEC(SI, VI, EI, LI), KEPCO(SI, VI)
Bigger value between 5% of setting value or 35ms
8/13/2019 VIPAM 3000
7/24
D3
D3-7VIPAM 3000
VIPAM 3000
Current
Rated Current(Io)
Operating Value Setting Range
Standard Voltage
Rated Voltage(Vo)
Standard Voltage Setting Range
Operating Time Setting(Lever)
Recovery Level
Standard Sensitivity Phase Angle
Accuracy of Phase Angle
Operating Characteristic Curve
Accuracy of Operating Time
Fundamental wave of ground current(Remove harmonic & DC offset)
5A
0.02In~2.00In/0.01In unit adjustment
Fundamental wave of zero-phase voltage(Remove harmonic & DC offset)
110V, 190V
0.07Vo~1.00Vo/0.01Vo unit adjustment
0.05~10.0/0.01 unit adjustment
97% of operating value setting
0~359/1unit adjustment
3
IEC(SI, VI, EI, LI), KEPCO(SI, VI)
Bigger value between 5% of setting value or 35ms
Current
Rated Current(In)
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Fundamental wave of ground current(Remove harmonic & DC offset)
5A
1.0In~10.0In/0.1In unit adjustment
0.05s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Operate within 0.05s when the operating time is set as 0.05s
Bigger value between 5% of setting value or 35ms
Current
Rated Current(Io)
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Fundamental wave of ground current(Remove harmonic & DC offset)
5A
0.02In~2.00In/0.01In unit adjustment
0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Definite(Definite Time)
Bigger value between 5% of setting value or 35ms
GroundOver-CurrentRelay DefiniteTime Element
GroundOver-CurrentRelayInstantaneousElement
Directional
GroundOver-CurrentRelay InverseTime Element
DirectionalGroundOver-CurrentRelay DefiniteTime Element
OCGR(51G)
Item Area
Item Area
OCGR(50G)
DOCGR(67N)
Item Area
Current
Rated Current(Io)
Operating Value Setting Range
Standard Voltage
Rated Voltage(Vo)
Standard Voltage Setting Range
Operating Time Setting(Delay)
Recovery Level
Standard Sensitivity Phase Angle
Accuracy of Phase AngleOperating Characteristic
Accuracy of Operating Time
Fundamental wave of ground current(Remove harmonic & DC offset)
5A
0.02In~2.00In/0.01In unit adjustment
Fundamental wave of zero-phase voltage(Remove harmonic & DC offset)
110V, 190V
0.07Vo~1.00Vo/0.01Vo unit adjustment
0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
0~359/1unit adjustment
3Definite(Definite Time)
Bigger value between 5% of setting value or 35ms
Item Area
DOCGR(67N)
Dig
italMultifunction
Inte
gratedProtectionRelay
8/13/2019 VIPAM 3000
8/24
Current
Rated Current(Iz)
Operating Value Setting Range
Standard Voltage
Rated Voltage(Vo)
Standard Voltage Setting RangeOperating Time Setting(Delay)
Recovery Level
Standard Sensitivity Phase Angle
Accuracy of Phase Angle
Operating Characteristic
Accuracy of Operating Time
Current
Rated Current(Io)
Operating Value Setting Range
Standard Voltage
Rated Voltage(Vo)
Standard Voltage Setting Range
Operating Time Setting(Delay)
Recovery Level
Standard Sensitivity Phase Angle
Accuracy of Phase AngleInstantaneous Operation
Accuracy of Operating Time
Fundamental wave of ground current(Remove harmonic & DC offset)
1.5mA
0.60Iz~4.00Iz/0.01Iz unit adjustment
Fundamental wave of zero-phase voltage(Remove harmonic & DC offset)
110V, 190V
0.07Vo~1.00Vo/0.01Vo unit adjustment0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
0~359/1unit adjustment
3
Definite(Definite Time)
Bigger value between 5% of setting value or 35ms
Fundamental wave of ground current(Remove harmonic & DC offset)
5A
1.0In~10.0In/0.1In unit adjustment
Fundamental wave of zero-phase voltage(Remove harmonic & DC offset)
110V, 190V
0.07Vo~1.00Vo/0.01Vo unit adjustment
0.05s~100.00s/0.01s unit adjustment
97% of operating value setting
0~359/1unit adjustment
3Operate within 0.05s when the operating time is set as 0.05s
Bigger value between 5% of setting value or 35ms
Operating Characteristic
D3-8 VITZROTECH
Item Area
Item Area
DOCGR(67N)
SGR(67G)
DirectionalGroundOver-CurrentRelayInstantaneousElement
SelectiveGround RelayDefinite TimeElement
Over-VoltageRelay DefiniteTime Element
Voltage
Rated Voltage(Vn)
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Fundamental wave of phase voltage or phase-phase voltage(Remove harmonic & DC offset)
110V, 63.5V
0.80Vn~ 1.60Vn/ 0.01Vn unit adjustment
0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Definite(Definite Time)
Bigger value between 5% of setting value or 35ms
OVR(59P)
Item Area
8/13/2019 VIPAM 3000
9/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-9VIPAM 3000
VIPAM 3000
Voltage
Rated Voltage(Vo)
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Voltage
Setting Characteristic
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Fundamental wave of phase voltage or phase-phase voltage(Remove harmonic & DC offset)
3-Phase Voltage Unbalance Factor[%] = ((Vmax-Vmin) /Vaverage)100
5~100%/1% unit adjustment
0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Definite
Bigger value between 5% of setting value or 35ms
Voltage
Rated Voltage(Vn)
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Fundamental wave of zero-phase voltage(Remove harmonic & DC offset)
110V, 190V
0.05Vo~0.80Vo/0.01Vo unit adjustment
0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Definite
Bigger value between 5% of setting value or 35ms
Item Area
Item Area
Item Area
Low-VoltageRelay DefiniteTime Element
GroundOver-VoltageRelay DefiniteTime Element
Open-PhaseRelay DefiniteTime Element
UVR(27P)
OVGR(64G)
POR(47P)
Fundamental wave of phase voltage or phase-phase voltage(Remove harmonic & DC offset)
110V, 63.5V
0.20Vn~1.00Vn/ 0.01Vn unit adjustment
0.10s~100.00s/0.01s unit adjustment
103% of operating value setting
5%
Definite
From 1.05times the operating value setting, Bigger value between5% of setting value or 35ms
Voltage
Operating Value Setting Range
Operating Time Setting(Delay)
Recovery Level
Accuracy
Operating Characteristic
Accuracy of Operating Time
Fundamental wave of negative-phase calculated using the 3-phase voltage
5~100%/1% unit adjustment
0.10s~100.00s/0.01s unit adjustment
97% of operating value setting
5%
Definite
Bigger value between 5% of setting value or 35ms
Negative-PhaseOver VoltageDefinite TimeElement
NSOVR(47)
Item Area
8/13/2019 VIPAM 3000
10/24
Characteristic Curve
D3-10 VITZROTECH
Here, t : Operating Time
M : Multiplier Setpoint(Time Tab Range:0.05-10.00
(Adjustment of 0.01unit))
I : Input Current
Ipu : Setting Value
K = 0.11
= 0.02
C = 0.42
Here, t : Operating Time
M : Multiplier Setpoint
(Time Tab Range:0.05-10.00
(Adjustment of 0.01unit))
I : Input Current
Ipu : Setting Value
K = 39.85
= 1.95
C = 1.084
KEPCOStandardInverse
KEPCO VeryInverse
8/13/2019 VIPAM 3000
11/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-11VIPAM 3000
VIPAM 3000
Here, t : Operating Time
M : Multiplier Setpoint
(Time Tab Range:0.05-10.00
(Adjustment of 0.01unit))
I : Input Current
Ipu : Setting Value
K = 0.14
= 0.02
C = 0
Here, t : Operating TimeM : Multiplier Setpoint
(Time Tab Range:0.05-10.00
(Adjustment of 0.01unit))
I : Input Current
Ipu : Setting Value
K = 13.5
= 1.00
C = 0
IECInverse TimeStandardInverse
IEC VeryInverse
8/13/2019 VIPAM 3000
12/24
Characteristic Curve
D3-12 VITZROTECH
Here, t : Operating Time
M : Multiplier Setpoint(Time Tab Range:0.05-10.00
(Adjustment of 0.01unit))
I : Input Current
Ipu : Setting Value
K = 80
= 2.00
C = 0
Here, t : Operating Time
M : Multiplier Setpoint
(Time Tab Range:0.05-10.00
(Adjustment of 0.01unit))
I : Input Current
Ipu : Setting Value
K = 120
= 1.00
C = 0
IEC ExtremelyInverse
IEC LongInverse
8/13/2019 VIPAM 3000
13/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-13VIPAM 3000
VIPAM 3000
It is operated when it meets thefollowing conditions at the same time.
Condition 1) |Vo| Voset
Condition 2) |Io| Io set
Condition 3) The phase difference ofzero-phase current withzero-phase voltage is within
the shaded area in the picture.
SGR PhaseCharacteristics
8/13/2019 VIPAM 3000
14/24
Item Specification Relevant Standard
Insulated Resistance
Power Frequency Withstand Voltage
Lightning Impulse Withstand Voltage
Oscillatory Surge
Surge Susceptibility
Fast Transient Burst
Electrostatic Discharge(ESD)Radio FrequencyRadiated Susceptibility
Radio FrequencyConducted Susceptibility
500V, 10Mor above
AC 2000V, 1min
5kV(3kV)
2.5kV ~ 3kV
Control Power, Transformer:2kV / Signal:1kV
Control Power, Transformer:4kV / Signal:4kV
Air:8kV / Contact: 6kV
10V/m
10V
KEMC 1120
IEC 60255-5
IEC 60255-5
IEC 60255-22-1
IEC 60255-22-5
IEC 60255-22-4
IEC 60255-22-2
IEC 60255-22-3
IEC 60255-22-6
LED Type Color Display Condition & State
POWER
RUN
SYS FAIL
TX
RX
6types other thanOCR, OCGR
R
ST
N
TIME
INST
TRIP
Local
Remote
CB ON
CB OFF
Green
Yellow
Red
Yellow
Yellow
Red
Red
RedRed
Red
Red
Red
Red
Red
Green
Red
Green
Lighted when control power is supplied
Flickering when the system is normally operating
Lighted when the result of system self-diagnosis is Fail
Display of transmitted state during RS422 /485 communication
Display of received state during RS422 /485 communication
Lighted when it is in Alarm or Trip state due to a failure whileLED flashes at Pickup State after the relay element is set asan operating state
Turned on during the Phase(R) Trip; flickering at Pickup status
Turned on during the Phase(S) Trip; flickering at Pickup statusTurned on during the Phase(T) Trip; flickering at Pickup status
Turned on during the Phase(N) Trip; flickering at Pickup status
Lighted when time delay failure is generated
Lighted when instantaneous failure is generated
Lighted when Trip (Failure) is generated
Lighted when CB control condition is Local
Lighted when CB control condition is Remote
Lighted when CB state is ON(Close)
Lighted when CB state is OFF(Open)
Communication
RelayOperationDisplay
Operating Characteristic & Terminal Marks
D3-14 VITZROTECH
OperatingCharacteristic
Input/Output Channel
C/B State & Run Display
Noise Rating
Type Item Form Rating
Dry contacta,bContacts
Input
Output
AC/DC110,125[V]Source Applied Voltage & Current
AC/DC110, 125V, 5mA
(R/Y Auxiliary Contact Capacity)
Resistance Load : AC 250V,16A DC30V16A COS=1.0
Resistance Load : AC 250V,5A DC30V5A COS=1.0
DI1(CB-ON)
DI2(CB-OFF)DI3DI16
CB-ON(DO 01)CB-OFF(DO 02)
DO03DO14(For L/R, For Buzzer,For System Fail)
8/13/2019 VIPAM 3000
15/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-15VIPAM 3000
VIPAM 3000
Terminal Block
Terminal Marks
8/13/2019 VIPAM 3000
16/24
D3-16 VITZROTECH
Connecting Method
3P4WConnection3CT /3PT
3P4WConnection3CT /4PT
8/13/2019 VIPAM 3000
17/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-17VIPAM 3000
VIPAM 3000
3P3WConnection3CT /GPT
3P3WConnection2CT /2PT
8/13/2019 VIPAM 3000
18/24
External Structure & Each Part Name
D3-18 VITZROTECH
ExternalStructure
1 Power LED(Green)
2 RUN LED(Yellow)
3 System Fail LED(Red)
4 Communication LED(Yellow)
5 Relay Operation Display LED(Red)
6 CB ON/OFF State Display LED(Red/Green)
7 Local/Remote State Display LED(Red/Green)
8 Function Key
9 Fault Reset Key
10 ESC Key
11 Local/Remote Selection Key
12 CB ON Key
13 CB OFF Key
14 Left Key
15 Right Key
16 Up Key
17 Down Key
18 Enter Key
19 LCD Display
20 RS-232 Port
8/13/2019 VIPAM 3000
19/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-19VIPAM 3000
VIPAM 3000
Block Diagram
PC HMI Program
8/13/2019 VIPAM 3000
20/24
External Dimensions & Diagram
D3-20 VITZROTECH
Fault Wave
ExternalDimensions
8/13/2019 VIPAM 3000
21/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-21VIPAM 3000
VIPAM 3000
MMI Block Diagram
8/13/2019 VIPAM 3000
22/24
Control Circuit Diagram & Development Test Report
D3-22 VITZROTECH
VIPAM3000-FISequenceDrawing(ExampleDrawing)
8/13/2019 VIPAM 3000
23/24
Dig
italMultifunction
Inte
gratedProtectionRelay
D3
D3-23VIPAM 3000
VIPAM 3000
8/13/2019 VIPAM 3000
24/24
Development Test Report