CÁC LOẠI UPS
UPS OFLINE
NGUỒN ĐIỆN QUA SWITCH ĐẾN NGUỒN
ĐẦU RA, VÀ NẠP CHO ẮC QUY QUA HỆ
THÔNG CHARGER
KHI MẤT ĐIỆN LƯỚI HỆ THỐNG ẮC QUY
CUNG CẤP MỘT DÒNG MỘT CHIỀU CHO
BỘ INVERTER CHUYỂN THÀNH DÒNG
XOAY CHIỀU CUNG CẤP CHO MẠNG
LƯỚI
UPS OFLINE VỚI CÔNG NGHỆ INTERACTIVE
CÁC LOẠI UPS
ĐIỆN ÁP LƯỚI VÀO BÌNH THƯỜNG THÌ
UPS HOẠT ĐỘNG GIỐNG NHƯ UPS OFLINE
ĐIỆN ÁP LƯỚI THẤP HƠN HAY CAO HƠN
ÁP RA THÌ MBA AT SẼ HOẠT ĐỘNG ĐIỀU
CHỈNH ĐIỆN ÁP LẠI SAO CHO NGÕ RA OK
NHẤT
MẤT ĐIỆN BỘ ẮC QUY SẼ CẤP ĐIỆN CHO
TẢI
GIÁ THÀNH CAO HƠN UPS OFLINE
CÁC LOẠI UPS
UPS ONLINE
ĐIỆN VÀO TRƯỢC TIẾP CẤP CHO BỘ
CHỈNH LƯU VÀ BỘ SẠC VÀ BIẾN ĐỔI
THÀNH ĐIỆN MỘT CHIỀU NẠP CHO ẮC
QUY VÀ BIẾN ĐỔI THÀNH ĐIỆN AC CUNG
CẤP CHO TẢI
NÊN BẤT CỨ TRƯỜNG HỢP NÀO THÌ TẢI
VẪN LUÔN CÓ ĐIỆN LIÊN TỤC TRỪ HƯ
HỎNG UPS THÌ TA SẼ SỬ DỤNG MẠCH
BYPASS LẤY ĐIỆN TRỰC TIẾP TỪ NGUỒN
CÁC LOẠI UPS
CÁC BỘ PHẬN KHÁC KHÔNG ĐẢM BẢO SỰ LIÊN TỤC NHƯNG LẠI BẢO VỆ TẢI
NHẠY CẢM KHỎI CÁC NHIỄU THƯỜNG XẢY RA TRÊN MẠNG PHÂN PHỐI:
BÔ LỌC PHÍCH CẮM: PHÍCH CẮM AC DÙNG NỐI TẢI NHƯNG BÊN TRONG
TRONG CÓ MỘT BỘ LỌC CAO TẦN (HF) ĐỂ GIẢM CÁC NHIỄU KÍ SINH. DÙNG
CHO MÁY TÍNH 250 ĐẾN 1000 VA
BỘ LỌC ĐIỀU HÒA HỢP CHUẨN: ĐẢM BẢO NGUỒN AC CUNG CẤP VỚI CHỨC
NĂNG:
LỌC KÍ SINH
GIỮ ĐIỆN ÁP KHÔNG ĐỔI
CÁCH LI TẢI KHỎI MẠNG ĐIỆN AC
DÙNG CHO VĂN PHÒNG HAY CÔNG NGHIỆP LÊN TỚI 5000VA
LỰA CHỌN HỆ THỐNG UPS
CÔNG SUẤT
MỨC ĐIỆN THẾ ĐẦU VÀO ĐẦU RA
THỜI GIAN TỰ HÀNH
TẦN SỐ ĐẦU VÀO ĐẦU RA
TÍNH KHẢ DỤNG
CÁC CHỨC NĂNG KHÁC
LỰA CHỌN HỆ THỐNG UPS
CÔNG SUẤT
CHỌN CÔNG SUẤT CỦA UPS PHẢI TÍNH ĐẾN:
GIÁ TRỊ ĐỈNH CỦA DÒNG ĐIỆN KHỞI ĐỘNG
KHẢ NĂNG ĐẶT THÊM THIẾT BỊ
KHẢ NĂNG QUÁ TẢI CỦA UPS
LỰA CHỌN HỆ THỐNG UPS
CÔNG SUẤT
GIÁ TRỊ TỐI ĐA CỦA NHU CẦU KVA DỰ KIẾN
GIÁ TRỊ TỐI ĐA CỦA DÙNG QUÁ ĐỘ (KHỞI ĐỘNG ĐỘNG CƠ, TẢI TRỞ, MBA,…)
Sups >= 𝑆𝑑 1.2 ÷2 +𝑆𝑞
𝑘
Sd: công suất yêu cầu tối đa của tải
Sq: công suất quá độ của tải
K: hệ số quá tải
k=1.5 quá tải trong 1 phút
k=1.25 quá tải trong 10 phút
LỰA CHỌN HỆ THỐNG UPS
CÔNG SUẤT
NHU CẦU TỔNG CỦA CÁC TẢI THƯỜNG XUYÊN CỦA THIẾT BỊ ĐƯỢC HIỆU CHỈNH MỞ
RỘNG TRONG TƯƠNG LAI 20%, CÓ NGHĨA NHÂN CHO (1.2 ĐẾN 2)
BỘ NGHỊCH LƯU DO MERLIN GERLIN SẢN XUẤT CÓ THỂ CHỊU QUÁ TẢI:
1.5In TRONG 1 PHÚT
1.25In TRONG 10 PHÚT
VỚI SỰ THAY ĐỔI TỨC THỜI KHI CẮT HAY MỞ MỘT LÚC NHIỀU THIẾT BỊ, ĐIỆN ÁP ĐẦU
RA THÔNG THƯỜNG CÒN TỪ 10% ĐẾN -8% GIÁ TRỊ ĐỊNH MỨC CỦA NÓ.
VÍ DỤ
LỰA CHỌN HỆ THỐNG UPS
MẠCH 4 CÓ DÒNG QUÁ ĐỘ 4In TRONG THỜI GIAN 200MS KHI KHỞI ĐỘNG. HOẠT
ĐỘNG NÀY ÍT NHẤT 1 LẦN TRONG NGÀY
1:80kva
2:10kva
3:20kva
4:20kva
5:30kva
HÃY CHỌN UPS CHO
CÁC CUNG CẤP ĐIỆN
CHO CÁC MẠCH TẢI
ĐÓ????
LỰA CHỌN HỆ THỐNG UPS
GIẢI VÍ DỤ
VẤN ĐỀ LÀ XÁC ĐỊNH CÔNG SUẤT QUÁ ĐỘ CỦA TẢI
CÔNG SUẤT TỐI ĐA CỦA TẢI: Sd=80+10+20+20+30=160KVA
KHẢ NĂNG MỞ RỘNG TRONG TƯƠNG LAI: 160*1.2=192
CÔNG SUẤT QUÁ ĐỘ CỦA TẢI: 3*20=60 KVA (DO MẠCH 4 CÓ DÒNG QUÁ ĐỘ BẰNG 4In,
TÍNH 1 LẦN Ở TRÊN RỒI, NÊN Ở DƯỚI CÒN 3 LẦN)
TỔNG CÔNG SUẤT LÀ: 252 KVA
CHỌN QUÁ TẢI TRONG 1 PHÚT LÀ 1.5In NÊN HỆ SỐ QUÁ TẢI BẰNG 1.5
NÊN CÔNG SUẤT CỦA UPS CẦN CHỌN LÀ:
Sups>=252/1.5=168 KVA
NÊN CHỌN BỘ UPS 200 KVA LÀ HỢP LÍ NHẤT.
ĐIỆN ÁP ĐẦU VÀO VÀ ĐẦU RA
LỰA CHỌN HỆ THỐNG UPS
MỨC ĐIỆN ÁP VÀO PHỤ THUỘC LƯỚI ĐIỆN, CHO PHÉP SAI SỐ ±25% ĐIỆN ÁP LƯỚI
THẤP NHẤT TẠI ĐÓ
ĐIỆN ÁP ĐẦU RA PHỤ THUỘC MỨC ĐIỆN ÁP TẢI, CHỈ CHO PHÉP ±1% ĐIỆN ÁP TẢI
LỚN NHẤT
THỜI GIAN TỰ HÀNH
LỰA CHỌN HỆ THỐNG UPS
THỜI GIAN TỰ HÀNH CỦA UPS PHỤ THUỘC VÀO BỘ ẮC QUY.
NẾU DUNG LƯỢNG ẮC QUY CÀNG CAO THÌ THỜI GIAN TỰ HÀNH LÂU CÒN THẤP THÌ
NGƯỢC LẠI
HỆ SỐ TẢI (SỐ TẢI NỐI VÀO BỘ LƯU ĐIỆN) TẢI NHIỀU SỬ DỤNG NHIỀU NĂNG LƯỢNG
ĐỂ DUY TRÌ )
TẦN SỐ ĐẦU VÀO VÀ ĐẦU RA
LỰA CHỌN HỆ THỐNG UPS
CÁC UPS NGÀY NAY CÓ TẦN SỐ ĐẦU VÀO 50/60 HZ VỚI SAI SỐ ±10%
TẦN SỐ ĐẦU RA VỚI SAI SỐ NGHIÊM NGẶT 50/60 HZ SAI SỐ ±0.5 HZ VỚI
VẬN HÀNH KHI CÓ TẢI VÀ 0.005HZ KHI VẬN HÀNH KHÔNG TẢI
TÍNH KHẢ DỤNG
LỰA CHỌN HỆ THỐNG UPS
MTBF(MEAN TIME BETWEEN FAILURES): THỜI GIAN TRUNG BÌNH GIỮA 2 LẦN
HƯ HỎNG
THƯỜNG LÀ 50000H
NẾU NGUỒN ĐÔI LÀ 70000H ĐẾN 200000H NẾU LÀ NGUỒN ĐÔI UPS ĐI KÈM VỚI
MÁY PHÁT DỰ PHÒNG
CÁC CHỨC NĂNG KHÁC
LỰA CHỌN HỆ THỐNG UPS
TÙY VÀO MỨC ĐỘ TIỆN ÍCH, UPS SẼ TRANG BỊ THÊM CÁC CHỨC NĂNG KHÁC:
CHỨC NĂNG BẢO VỆ: NGẮN MẠCH, QUÁ TẢI, LỌC XUNG EMI/RF
CHỨC NĂNG BÁO TÌNH TRẠNG: CẠN ẮC QUY, QUÁ TẢI,…
CHỨC NĂNG GIÁM SÁT VÀ ĐIỀU KHIỂN TỪ XA
CHỨC NĂNG THAY ẮC QUY NÓNG
CHỨC NĂNG VẬN HÀNH TIẾT KIÊM ĐIỆN: CHỨC NĂNG THƯỜNG ĐI KÈM THEO LOẠI
UPS, CHỈ CẤP NGUỒN TỪ ẮC QUY KHI ĐIỆN NĂNG KHÔNG ỔN ĐỊNH VÀ NGUỒN
CHÍNH HƯ HỎNG
ẮC QUY
ẮC QUY HỞ (NON-SEALED UNITS)
DÙNG CHÓ THIẾT BỊ CÔNG SUẤT LỚN CÓ 2 LOẠI ẮC QUY ƯA CHUỘNG: ẮC QUY
MỞ (OPEN-TYPE) VÀ ĂC QUY KIỀM (CAMIUM-NICKET)
ẮC QUY YÊU CẦU HỆ THỐNG GIÓ, CƯỠNG BỨC HAY TỰ NHIÊN
TỈ LỆ THÔNG GIÓ KHUYẾN CÁO 0.05NI (N LÀ SỐ NGĂN TRONG ẮC QUY VÀ I LÀ
DÒNG NẠP LỚN NHẤT CỦA BỘ NẠP ẮC QUY)
ẮC QUY THƯỜNG (MAINTENANCE-FREE SEALED UNITS)
ẮC QUY SỬ DỤNG CHO HỆ THỐNG UPS CÔNG SUẤT < 250KVA
ĐẢM BẢO HOẠT ĐỘNG TỰ HÀNH ĐẾN 30 PHÚT
TRƯỜNG HỢP ẮC QUY CƯỠNG BỨC BỘ PHẬN ẮC QUY PHẢI TỰ ĐỘNG TẮT KHI
QUẠT NGỪNG CHẠY
SƠ ĐỒ NỐI ĐẤT
UPS ĐƯỢC NUÔI TỪ HAI MẠCH, MỖI MẠCH ĐƯỢC BẢO VỆ RIÊNG BIỆT
MẠCH 1 NỐI VÀO BỘ NGHỊCH LƯU 3 PHA 3 DÂY
MẠCH 2 4 DÂY 3 PHA NỐI VÀO BỘ CÔNG TẮC TƠ TỈNH
TỦ PHÂN PHỐI PHÍA SAU ĐƯỢC CUNG CẤP ĐIỆN ÁP 230/400V
SƠ ĐỒ NỐI ĐẤT
BIỆN PHÁP CHỐNG GIẬT PHỤ THUỘC VÀO HỆ THÔNG NỐI ĐẤT
DO ĐÓ SẼ PHỤ THUỘC VÀO SỰ TỒN TẠI CÁCH LY MẠCH PHÍA TRƯỚC
VÀ SAU UPS
NẾU KHÔNG CÓ CÁCH LY THÌ SƠ ĐỒ NỐI ĐẤT TẠI HAI ĐẦU UPS PHẢI
GIỐNG NHAU
NẾU CÓ SỰ CÁCH LY THÌ KHÔNG YÊU CẦU NỐI ĐẤT ĐẦU VÀO VÀ ĐẦU
RA UPS GIỐNG NHAU
SƠ ĐỒ NỐI ĐẤT
SƠ ĐỒ TT/TT
ĐIỂM TRUNG TÍN CỦA BỘ NGHỊCH LƯU KHÔNG THỂ NỐI ĐẤT THƯỜNG
TRỰC
SỬ DỤNG TIẾP ĐIỂM THƯỜNG ĐÓNG CỦA CONTACTOR
KHI CB D2 MỞ THÌ TIẾP ĐIỂM TRUNG TÍN BỘ NGHỊCH LƯU-ĐẤT ĐÓNG
KHI CB D2 ĐÓNG THÌ TIẾP ĐIỂM ĐÓ HỞ
MẤT ĐIỆN CONTACTOR QUAY VỀ BAN ĐẦU TIẾP ĐIỂM ĐÓNG ẮC QUY CẤP
ĐIỆN CHO TẢI VỚI SƠ ĐỒ TT
ĐẢM BẢO MỘT TRONG 2 MẠCH HOẠT ĐỘNG HIỆU QUẢ
LỘ RA SỬ DỤNG RCD 30MMA
SƠ ĐỒ NỐI ĐẤT
SƠ ĐỒ TN-C/IT
KHI ĐÓNG D2 THÌ DÒNG CHẠY CẤP NGUỒN ĐỒNG THỜI TRUNG TÍN CỦA BỘ
NGHỊCH LƯU.
SỬ DỤNG TIẾP ĐIỂM THƯỜNG HỞ CỦA CONTACTOR
KHI MẤT ĐIỆN CÔNG TẮC TƠ NHẢY VỀ TRẠNG THÁI BAN ĐẦU LÀM CẶP TIẾP
ĐIỂM TRUNG TÍN VỚI ĐẤT HỞ. ĐỒNG THỜI ẮC QUY CUNG CẤP ĐIỆN CHO TẢI
LÚC NÀY ĐẦU RA ĐIỆN ÁP HOẠT ĐỘNG VỚI SƠ ĐỒ IT
BẢO VỆ Ổ ĐIỆN BẰNG RCD VÀ CB VỚI DÒNG CẮT NGẮN MẠCH CHỈNH ĐỊNH
THẤP.
SƠ ĐỒ NỐI ĐẤT
SƠ ĐỒ IT/IT
SỬ DỤNG TIẾP ĐIỂM HỞ CỦA CÔNG TẮC TƠ ĐỂ KẾT NỐI TRUNG TÍN BỘ NGỊCH
LƯU VỚI ĐẤT NHƯNG CONTACTOR LIÊN KẾT VỚI CB TRONG MẠCH UPS
CÓ ĐIỆN TIẾP ĐIỂM ĐÓNG, MẤT ĐIỆN TIẾ ĐIỂM HỞ>>> ẮC QUY CẤP ĐIỆN VỚI SƠ
ĐỒ IT
DO SƠ ĐỒ IT NÊN NGÕ RA ĐƯỢC BẢO VỆ BẰNG CÁC CB. RCD KHÔNG ĐƯỢC SỬ
DỤNG