NỘI DUNG

CÁC LOẠI UPS

LỰA CHỌN UPS

CÁC LOẠI ẮC QUY

SƠ ĐỒ NỐI ĐẤT

CHỌN CB BẢO VỆ

THIẾT BỊ PHỤ TRỢ

CÁC LOẠI UPS

CÓ 3 LOẠI UPS

UPS OFLINE

UPS OFLINE VỚI CÔNG NGHỆ INTERACTIVE

UPS ONLINE

CÁC LOẠI UPS

UPS OFLINE

NGUỒN ĐIỆN QUA SWITCH ĐẾN NGUỒN

ĐẦU RA, VÀ NẠP CHO ẮC QUY QUA HỆ

THÔNG CHARGER

KHI MẤT ĐIỆN LƯỚI HỆ THỐNG ẮC QUY

CUNG CẤP MỘT DÒNG MỘT CHIỀU CHO

BỘ INVERTER CHUYỂN THÀNH DÒNG

XOAY CHIỀU CUNG CẤP CHO MẠNG

LƯỚI

UPS OFLINE

CÁC LOẠI UPS

CÁC LOẠI NÀY THƯỜNG SỬ DỤNG CHO TẢI <=2.5KVA

UPS OFLINE VỚI CÔNG NGHỆ INTERACTIVE

CÁC LOẠI UPS

ĐIỆN ÁP LƯỚI VÀO BÌNH THƯỜNG THÌ

UPS HOẠT ĐỘNG GIỐNG NHƯ UPS OFLINE

ĐIỆN ÁP LƯỚI THẤP HƠN HAY CAO HƠN

ÁP RA THÌ MBA AT SẼ HOẠT ĐỘNG ĐIỀU

CHỈNH ĐIỆN ÁP LẠI SAO CHO NGÕ RA OK

NHẤT

MẤT ĐIỆN BỘ ẮC QUY SẼ CẤP ĐIỆN CHO

TẢI

GIÁ THÀNH CAO HƠN UPS OFLINE

CÁC LOẠI UPS

UPS ONLINE

ĐIỆN VÀO TRƯỢC TIẾP CẤP CHO BỘ

CHỈNH LƯU VÀ BỘ SẠC VÀ BIẾN ĐỔI

THÀNH ĐIỆN MỘT CHIỀU NẠP CHO ẮC

QUY VÀ BIẾN ĐỔI THÀNH ĐIỆN AC CUNG

CẤP CHO TẢI

NÊN BẤT CỨ TRƯỜNG HỢP NÀO THÌ TẢI

VẪN LUÔN CÓ ĐIỆN LIÊN TỤC TRỪ HƯ

HỎNG UPS THÌ TA SẼ SỬ DỤNG MẠCH

BYPASS LẤY ĐIỆN TRỰC TIẾP TỪ NGUỒN

CÁC LOẠI UPS

UPS ONLINE

CÁC LOẠI NÀY THƯỜNG ÁP DỤNG CHO TẢI > 2.5KVA

CÁC LOẠI UPS

CÁC BỘ PHẬN KHÁC KHÔNG ĐẢM BẢO SỰ LIÊN TỤC NHƯNG LẠI BẢO VỆ TẢI

NHẠY CẢM KHỎI CÁC NHIỄU THƯỜNG XẢY RA TRÊN MẠNG PHÂN PHỐI:

BÔ LỌC PHÍCH CẮM: PHÍCH CẮM AC DÙNG NỐI TẢI NHƯNG BÊN TRONG

TRONG CÓ MỘT BỘ LỌC CAO TẦN (HF) ĐỂ GIẢM CÁC NHIỄU KÍ SINH. DÙNG

CHO MÁY TÍNH 250 ĐẾN 1000 VA

BỘ LỌC ĐIỀU HÒA HỢP CHUẨN: ĐẢM BẢO NGUỒN AC CUNG CẤP VỚI CHỨC

NĂNG:

LỌC KÍ SINH

GIỮ ĐIỆN ÁP KHÔNG ĐỔI

CÁCH LI TẢI KHỎI MẠNG ĐIỆN AC

DÙNG CHO VĂN PHÒNG HAY CÔNG NGHIỆP LÊN TỚI 5000VA

LỰA CHỌN HỆ THỐNG UPS

CÔNG SUẤT

MỨC ĐIỆN THẾ ĐẦU VÀO ĐẦU RA

THỜI GIAN TỰ HÀNH

TẦN SỐ ĐẦU VÀO ĐẦU RA

TÍNH KHẢ DỤNG

CÁC CHỨC NĂNG KHÁC

LỰA CHỌN HỆ THỐNG UPS

CÔNG SUẤT

CHỌN CÔNG SUẤT CỦA UPS PHẢI TÍNH ĐẾN:

GIÁ TRỊ ĐỈNH CỦA DÒNG ĐIỆN KHỞI ĐỘNG

KHẢ NĂNG ĐẶT THÊM THIẾT BỊ

KHẢ NĂNG QUÁ TẢI CỦA UPS

LỰA CHỌN HỆ THỐNG UPS

CÔNG SUẤT

GIÁ TRỊ TỐI ĐA CỦA NHU CẦU KVA DỰ KIẾN

GIÁ TRỊ TỐI ĐA CỦA DÙNG QUÁ ĐỘ (KHỞI ĐỘNG ĐỘNG CƠ, TẢI TRỞ, MBA,…)

Sups >= 𝑆𝑑 1.2 ÷2 +𝑆𝑞

𝑘

Sd: công suất yêu cầu tối đa của tải

Sq: công suất quá độ của tải

K: hệ số quá tải

k=1.5 quá tải trong 1 phút

k=1.25 quá tải trong 10 phút

LỰA CHỌN HỆ THỐNG UPS

CÔNG SUẤT

NHU CẦU TỔNG CỦA CÁC TẢI THƯỜNG XUYÊN CỦA THIẾT BỊ ĐƯỢC HIỆU CHỈNH MỞ

RỘNG TRONG TƯƠNG LAI 20%, CÓ NGHĨA NHÂN CHO (1.2 ĐẾN 2)

BỘ NGHỊCH LƯU DO MERLIN GERLIN SẢN XUẤT CÓ THỂ CHỊU QUÁ TẢI:

1.5In TRONG 1 PHÚT

1.25In TRONG 10 PHÚT

VỚI SỰ THAY ĐỔI TỨC THỜI KHI CẮT HAY MỞ MỘT LÚC NHIỀU THIẾT BỊ, ĐIỆN ÁP ĐẦU

RA THÔNG THƯỜNG CÒN TỪ 10% ĐẾN -8% GIÁ TRỊ ĐỊNH MỨC CỦA NÓ.

VÍ DỤ

LỰA CHỌN HỆ THỐNG UPS

MẠCH 4 CÓ DÒNG QUÁ ĐỘ 4In TRONG THỜI GIAN 200MS KHI KHỞI ĐỘNG. HOẠT

ĐỘNG NÀY ÍT NHẤT 1 LẦN TRONG NGÀY

1:80kva

2:10kva

3:20kva

4:20kva

5:30kva

HÃY CHỌN UPS CHO

CÁC CUNG CẤP ĐIỆN

CHO CÁC MẠCH TẢI

ĐÓ????

LỰA CHỌN HỆ THỐNG UPS

GIẢI VÍ DỤ

VẤN ĐỀ LÀ XÁC ĐỊNH CÔNG SUẤT QUÁ ĐỘ CỦA TẢI

CÔNG SUẤT TỐI ĐA CỦA TẢI: Sd=80+10+20+20+30=160KVA

KHẢ NĂNG MỞ RỘNG TRONG TƯƠNG LAI: 160*1.2=192

CÔNG SUẤT QUÁ ĐỘ CỦA TẢI: 3*20=60 KVA (DO MẠCH 4 CÓ DÒNG QUÁ ĐỘ BẰNG 4In,

TÍNH 1 LẦN Ở TRÊN RỒI, NÊN Ở DƯỚI CÒN 3 LẦN)

TỔNG CÔNG SUẤT LÀ: 252 KVA

CHỌN QUÁ TẢI TRONG 1 PHÚT LÀ 1.5In NÊN HỆ SỐ QUÁ TẢI BẰNG 1.5

NÊN CÔNG SUẤT CỦA UPS CẦN CHỌN LÀ:

Sups>=252/1.5=168 KVA

NÊN CHỌN BỘ UPS 200 KVA LÀ HỢP LÍ NHẤT.

ĐIỆN ÁP ĐẦU VÀO VÀ ĐẦU RA

LỰA CHỌN HỆ THỐNG UPS

MỨC ĐIỆN ÁP VÀO PHỤ THUỘC LƯỚI ĐIỆN, CHO PHÉP SAI SỐ ±25% ĐIỆN ÁP LƯỚI

THẤP NHẤT TẠI ĐÓ

ĐIỆN ÁP ĐẦU RA PHỤ THUỘC MỨC ĐIỆN ÁP TẢI, CHỈ CHO PHÉP ±1% ĐIỆN ÁP TẢI

LỚN NHẤT

THỜI GIAN TỰ HÀNH

LỰA CHỌN HỆ THỐNG UPS

THỜI GIAN TỰ HÀNH CỦA UPS PHỤ THUỘC VÀO BỘ ẮC QUY.

NẾU DUNG LƯỢNG ẮC QUY CÀNG CAO THÌ THỜI GIAN TỰ HÀNH LÂU CÒN THẤP THÌ

NGƯỢC LẠI

HỆ SỐ TẢI (SỐ TẢI NỐI VÀO BỘ LƯU ĐIỆN) TẢI NHIỀU SỬ DỤNG NHIỀU NĂNG LƯỢNG

ĐỂ DUY TRÌ )

TẦN SỐ ĐẦU VÀO VÀ ĐẦU RA

LỰA CHỌN HỆ THỐNG UPS

CÁC UPS NGÀY NAY CÓ TẦN SỐ ĐẦU VÀO 50/60 HZ VỚI SAI SỐ ±10%

TẦN SỐ ĐẦU RA VỚI SAI SỐ NGHIÊM NGẶT 50/60 HZ SAI SỐ ±0.5 HZ VỚI

VẬN HÀNH KHI CÓ TẢI VÀ 0.005HZ KHI VẬN HÀNH KHÔNG TẢI

TÍNH KHẢ DỤNG

LỰA CHỌN HỆ THỐNG UPS

MTBF(MEAN TIME BETWEEN FAILURES): THỜI GIAN TRUNG BÌNH GIỮA 2 LẦN

HƯ HỎNG

THƯỜNG LÀ 50000H

NẾU NGUỒN ĐÔI LÀ 70000H ĐẾN 200000H NẾU LÀ NGUỒN ĐÔI UPS ĐI KÈM VỚI

MÁY PHÁT DỰ PHÒNG

CÁC CHỨC NĂNG KHÁC

LỰA CHỌN HỆ THỐNG UPS

TÙY VÀO MỨC ĐỘ TIỆN ÍCH, UPS SẼ TRANG BỊ THÊM CÁC CHỨC NĂNG KHÁC:

CHỨC NĂNG BẢO VỆ: NGẮN MẠCH, QUÁ TẢI, LỌC XUNG EMI/RF

CHỨC NĂNG BÁO TÌNH TRẠNG: CẠN ẮC QUY, QUÁ TẢI,…

CHỨC NĂNG GIÁM SÁT VÀ ĐIỀU KHIỂN TỪ XA

CHỨC NĂNG THAY ẮC QUY NÓNG

CHỨC NĂNG VẬN HÀNH TIẾT KIÊM ĐIỆN: CHỨC NĂNG THƯỜNG ĐI KÈM THEO LOẠI

UPS, CHỈ CẤP NGUỒN TỪ ẮC QUY KHI ĐIỆN NĂNG KHÔNG ỔN ĐỊNH VÀ NGUỒN

CHÍNH HƯ HỎNG

ẮC QUY

CÓ 2 LOẠI ĂC QUY ĐƯỢC DÙNG KÈM VỚI UPS

ẮC QUY THƯỜNG

ẮC QUY LOẠI KÍN

ẮC QUY

ẮC QUY HỞ (NON-SEALED UNITS)

DÙNG CHÓ THIẾT BỊ CÔNG SUẤT LỚN CÓ 2 LOẠI ẮC QUY ƯA CHUỘNG: ẮC QUY

MỞ (OPEN-TYPE) VÀ ĂC QUY KIỀM (CAMIUM-NICKET)

ẮC QUY YÊU CẦU HỆ THỐNG GIÓ, CƯỠNG BỨC HAY TỰ NHIÊN

TỈ LỆ THÔNG GIÓ KHUYẾN CÁO 0.05NI (N LÀ SỐ NGĂN TRONG ẮC QUY VÀ I LÀ

DÒNG NẠP LỚN NHẤT CỦA BỘ NẠP ẮC QUY)

ẮC QUY THƯỜNG (MAINTENANCE-FREE SEALED UNITS)

ẮC QUY SỬ DỤNG CHO HỆ THỐNG UPS CÔNG SUẤT < 250KVA

ĐẢM BẢO HOẠT ĐỘNG TỰ HÀNH ĐẾN 30 PHÚT

TRƯỜNG HỢP ẮC QUY CƯỠNG BỨC BỘ PHẬN ẮC QUY PHẢI TỰ ĐỘNG TẮT KHI

QUẠT NGỪNG CHẠY

SƠ ĐỒ NỐI ĐẤT

UPS ĐƯỢC NUÔI TỪ HAI MẠCH, MỖI MẠCH ĐƯỢC BẢO VỆ RIÊNG BIỆT

MẠCH 1 NỐI VÀO BỘ NGHỊCH LƯU 3 PHA 3 DÂY

MẠCH 2 4 DÂY 3 PHA NỐI VÀO BỘ CÔNG TẮC TƠ TỈNH

TỦ PHÂN PHỐI PHÍA SAU ĐƯỢC CUNG CẤP ĐIỆN ÁP 230/400V

SƠ ĐỒ NỐI ĐẤT

BIỆN PHÁP CHỐNG GIẬT PHỤ THUỘC VÀO HỆ THÔNG NỐI ĐẤT

DO ĐÓ SẼ PHỤ THUỘC VÀO SỰ TỒN TẠI CÁCH LY MẠCH PHÍA TRƯỚC

VÀ SAU UPS

NẾU KHÔNG CÓ CÁCH LY THÌ SƠ ĐỒ NỐI ĐẤT TẠI HAI ĐẦU UPS PHẢI

GIỐNG NHAU

NẾU CÓ SỰ CÁCH LY THÌ KHÔNG YÊU CẦU NỐI ĐẤT ĐẦU VÀO VÀ ĐẦU

RA UPS GIỐNG NHAU

SƠ ĐỒ NỐI ĐẤT

SƠ ĐỒ TT/TT

D1 D2

C/S

SO DO TT/TT

SƠ ĐỒ NỐI ĐẤT

SƠ ĐỒ TT/TT

ĐIỂM TRUNG TÍN CỦA BỘ NGHỊCH LƯU KHÔNG THỂ NỐI ĐẤT THƯỜNG

TRỰC

SỬ DỤNG TIẾP ĐIỂM THƯỜNG ĐÓNG CỦA CONTACTOR

KHI CB D2 MỞ THÌ TIẾP ĐIỂM TRUNG TÍN BỘ NGHỊCH LƯU-ĐẤT ĐÓNG

KHI CB D2 ĐÓNG THÌ TIẾP ĐIỂM ĐÓ HỞ

MẤT ĐIỆN CONTACTOR QUAY VỀ BAN ĐẦU TIẾP ĐIỂM ĐÓNG ẮC QUY CẤP

ĐIỆN CHO TẢI VỚI SƠ ĐỒ TT

ĐẢM BẢO MỘT TRONG 2 MẠCH HOẠT ĐỘNG HIỆU QUẢ

LỘ RA SỬ DỤNG RCD 30MMA

SƠ ĐỒ TN-C/IT

SƠ ĐỒ NỐI ĐẤT

D1 D2

C/S

SO DO TT/TT

SƠ ĐỒ NỐI ĐẤT

SƠ ĐỒ TN-C/IT

KHI ĐÓNG D2 THÌ DÒNG CHẠY CẤP NGUỒN ĐỒNG THỜI TRUNG TÍN CỦA BỘ

NGHỊCH LƯU.

SỬ DỤNG TIẾP ĐIỂM THƯỜNG HỞ CỦA CONTACTOR

KHI MẤT ĐIỆN CÔNG TẮC TƠ NHẢY VỀ TRẠNG THÁI BAN ĐẦU LÀM CẶP TIẾP

ĐIỂM TRUNG TÍN VỚI ĐẤT HỞ. ĐỒNG THỜI ẮC QUY CUNG CẤP ĐIỆN CHO TẢI

LÚC NÀY ĐẦU RA ĐIỆN ÁP HOẠT ĐỘNG VỚI SƠ ĐỒ IT

BẢO VỆ Ổ ĐIỆN BẰNG RCD VÀ CB VỚI DÒNG CẮT NGẮN MẠCH CHỈNH ĐỊNH

THẤP.

SƠ ĐỒ NỐI ĐẤT

SƠ ĐỒ IT/IT

C/S

SO DO IT/IT

CIC1

CIC2

SƠ ĐỒ NỐI ĐẤT

SƠ ĐỒ IT/IT

SỬ DỤNG TIẾP ĐIỂM HỞ CỦA CÔNG TẮC TƠ ĐỂ KẾT NỐI TRUNG TÍN BỘ NGỊCH

LƯU VỚI ĐẤT NHƯNG CONTACTOR LIÊN KẾT VỚI CB TRONG MẠCH UPS

CÓ ĐIỆN TIẾP ĐIỂM ĐÓNG, MẤT ĐIỆN TIẾ ĐIỂM HỞ>>> ẮC QUY CẤP ĐIỆN VỚI SƠ

ĐỒ IT

DO SƠ ĐỒ IT NÊN NGÕ RA ĐƯỢC BẢO VỆ BẰNG CÁC CB. RCD KHÔNG ĐƯỢC SỬ

DỤNG