Jornada Técnica

MATERIALES DE CONSTRUCCION

Los componentes que hacen un rociador son: Cuerpo Deflector Elemento Fusible o Ampolla (bulbo) Pip Cap (Gorra) Pintle Screw (Tornillo) Resorte Belleville Los Rociadores Viking utilizan latón de bajo contenido de zinc para suministrar un cuerpo mas “elástico”. Este contenido de zinc bajo protege al rociador de de-zincaficacion. El Resorte Bellville sella la salida del rociador. Este asiento metal-metal permite que el rociador opere aunque no halla presión en la tubería/rociador.

Aprobaciones

UL & c-UL (ULC) NFPA & Requerimientos UL

FM Requerimientos FM

(NFPA = mínimo)

LPC LPC Standard

VDS VDS Standard

NYC & LA Aprobaciones Especificas

Agencia Norma

Tipos de Rociadores

Tipo Control – Respuesta Standard y Respuesta Rápida

Cobertura Standard

Montante

Pendiente

Pared (Sidewall)

Cobertura Extendida

Montante

Pendiente

Pared (Sidewall)

Tipo Control Aplicación Especial

Rociador Gota Gorda (Large Drop)

Supresión

ESFR – Montante y Pendiente

Residencial

Rociadores Tipo Control

Rociadores Tipo Control están separados en las siguientes categorías:

Cobertura Standard - Respuesta Standard

Cobertura Standard - Respuesta Rápida

Cobertura Extendida – Respuesta Standard

Cobertura Extendida – Respuesta Rápida

Tubería Seco – Respuesta Standard/Respuesta Rápida

Almacenamiento – Respuesta Standard/Respuesta Rápida

Identificación de Rociadores

Índice de Temperatura de

Activación

155°F 175°F 200or212°F 286°F 360°F 500°F

(68°C) (79°C) (93or100°C) (141°C) (182°C) (260°C)

Ordinario Intermedio Alto Extra Ultra

Alto Alto

Máx Temp Máx Temp Máx Temp Máx Temp Máx Temp

Techo Techo Techo Techo Techo

100°F 150°F 225°F 300°F 465°F

(38°C) (65°C) (107°C) (149°C) (240°C)

Rojo Amarillo Verde Azul Malva Negro

Respuesta Standard – Ampolla de 5 mm

155°F 175°F 200or212°F 286°F

(68°C) (79°C) (93or100°C) (141°C)

Ordinario Intermedio Alto

Max Temp Max Temp Max Temp

Techo Techo Techo

100°F 150°F 225°F

(38°C) (65°C) (107°C)

Rojo Amarillo Verde Azul

Respuesta Rapida – Ampolla de 3 mm bulb

Instalado encima de la tuberia

Rociadores Montantes

Rociador Pendiente

Instalado en un techo

falso

Rociador Pendiente

Montado en tuberia

expuesta

Rociadores Pendientes son instalados de bajo de la tuberia o en un techo falso

Rociadores de Pared normalmente son instalados en la paredl

Horizontal Sidewall Sprinkler

Factor K del Rociador Los factores K son conocidos como los coeficiente de

descarga. Lo mas grande el factor K, la mayor descarga

de agua bajo una presion en particular. Hay (3)

tamanos de roscas actualmente utilizadas, ½”, ¾” y 1”.

No solamente utilice el diametro de la rosca cuando

Este reemplazando un rociador. Identifique la

orientacion, Factor K y Temperatura antes de

remplazar el rociador.

Factor Knominal(USA)

gpm/(psi)1/2

Intervalo devalores de K

(USA)gpm/(psi)1/2

Intervalo devalores de K

(Métrico)l/min/bar1/2

Porcentaje dedescarga con

relación al estándar K = 5.6

Tipo de

Rosca

1.41.92.84.25.68.0

11.214.016.819.622.425.228.0

1.3-1.51.8-2.02.6-2.94.0-4.45.3-5.87.4-8.2

11.0-11.513.5-14.516.0-17.618.6-20.621.3-23.523.9-26.526.6-29.4

19-2226-2938-4259-6476-84

107-118159-166195-209231-254272-301311-343349-387389-430

2533.35075

100140200250300350400450500

½” NPT½” NPT½” NPT½” NPT½” NPT

¾” o ½” NPT¾” o ½” NPT

¾” NPT¾” NPT1” NPT1” NPT1” NPT1” NPT

Factores K estándar (USA y métricos)

SENSIBILIDAD TÉRMICA

Índice de tiempo de respuesta

(RTI)

SENSIBILIDAD DE LOS

SPRINKLERS

• RESPUESTA ESTANDAR

– 3 Min. 51 Sec. Room Fire Test

– 100 Sec. Plunge Test

• RESPUESTA RÁPIDA

– 75 Sec. Room Fire Test

– 14 Sec. Plunge Test

• RESIDENCIALES

– Special Fire Test

– 14 Sec. Plunge

Plunge Oven

Índice de tiempo de

respuesta

(RTI)

• Respuesta rápida RTI < 50

• Respuesta especial 50 <RTI < 80

• Respuesta normal RTI > 80

Strut – 110 m-s½

Glass Bulb (5mm) - 105 m-s½ Fusible Link – 26 m-s½

Glass Bulb (3mm) - 36 m-s½ Glass Bulb (2.5mm) - 22 m-s½

Heat Fin - 26 m-s½

Rociadores de Cobertura Estandar

Pendiente y Montante

Rociadores de Cobertura Estandar

Pendiente o Montante

• Distribution 16 ft (4,9 m) dia @ 4 ft (1,2 m) debajo del deflector

15 gpm (0.95 L/s) for 1/2” (15 mm) “orificio estandar”

21 gpm (1,3 L/s) for 3/4” (20 mm) “orificio grande”

Rociadores Cobertura

Estandar

Rociadores de Cobertura Estandar

Pendiente o Montante

Espacio Rociadores Estandar (Area de Cobertura)

Riesgo Liviano (definido por NFPA 13) : 225 sq. ft. max

Riesgo Ordinario (definido por NFPA 13) : 130 sq. ft. max

Riesgo Extra (as defined by NFPA 13) : 100 sq. ft. max

(Nota: areas para sistemas calculados hidraulicamente)

15’-0”

(4,57m) 15’-0”

(4,57m)

15’-0”

(4,57m)

NFPA 13 limita la area de cobertura para Riesgos Livianos

a 225 sq. ft. por rociador

Rociadores de Cobertura Estandar

*Plan View

Classification of Occupancies

Upright and pendent spray sprinklers shall be permitted in all

occupancy hazard classifications and building construction types.

5.1* Classification of Occupancies.

5.1.1 Occupancy classifications for this standard shall relate to

sprinkler design, installation, and water supply requirements only.

5.1.2 Occupancy classifications shall not be intended to be a general

classification of occupancy hazards.

5.2* Light Hazard Occupancies.

Light hazard occupancies shall be defined as occupancies or portions

of other occupancies where the quantity and/or combustibility of

contents is low and fires with relatively low rates of heat release are

expected.

EXAMPLES: Churches, Clubs, Hospitals, Museums, Offices,

Restaurant Seating Areas

10’-0”

(3,04m)

10’-0”

(3,04m)

13’-0”

(3,97m)

NFPA 13 limita la area maxima de cobertura para riesgo

Ordinario a 130 sq. ft. por rociador

Rociadores Cobertura Estandar

*Plan View

Classification of Occupancies Upright and pendent spray sprinklers shall be permitted in all occupancy hazard

classifications and building construction types.

5.1* Classification of Occupancies.

5.1.1 Occupancy classifications for this standard shall relate to sprinkler design,

installation, and water supply requirements only.

5.1.2 Occupancy classifications shall not be intended to be a general classification of

occupancy hazards.

5.3.1* Ordinary Hazard (Group 1).

Ordinary hazard (Group 1) occupancies shall be defined as occupancies or portions of

other occupancies where combustibility is low, quantity of combustibles is moderate,

stockpiles of combustibles do not exceed 8’-0”, and fires with moderate rates of heat

release are expected.

Examples:Restaurant Service Areas, Bakeries, Automobile Parking and

Showrooms, Laundries

5.3.2* Ordinary Hazard (Group 2). Ordinary hazard (Group 2) occupancies shall be defined

as occupancies or portions of other occupancies where the quantity and combustibility of

contents are moderate to high, stockpiles do not exceed 12’, and fires with moderate to

high rates of heat release are expected.

Examples: Dry Cleaners, Horse Stables, Machine Shops, Library

Stack Rooms, Mercantile, Confectionary Products

10’-0”

(3,04m) 10’-0”

(3,04m)

10’-0”

(3,04m)

NFPA 13 limita la area maxima de cobertura para riesgo

Extra a 100 sq. ft. por rociador

Standard Coverage Sprinklers

*Plan View

Classification of Occupancies Upright and pendent spray sprinklers shall be permitted in all occupancy hazard

classifications and building construction types.

5.1* Classification of Occupancies.

5.1.1 Occupancy classifications for this standard shall relate to sprinkler design,

installation, and water supply requirements only.

5.1.2 Occupancy classifications shall not be intended to be a general classification of

occupancy hazards.

5.4.1* Extra Hazard (Group 1). Extra hazard (Group 1) occupancies shall be defined as

occupancies or portions of other occupancies where the quantity and combustibility of

contents are very high and dust, lint, or other materials are present, introducing the

probability of rapidly developing fires with high rates of heat release but with little or no

combustible or flammable liquids.

Examples: Combustible Hydraulic Fluid Use Areas, Metal Extruding,

Saw Mills, Upholstering with Plastic Foams, Rubber Reclaiming

5.4.2* Extra Hazard (Group 2). Extra hazard (Group 2) occupancies shall be defined as

occupancies or portions of other occupancies with moderate to substantial amounts of

flammable or combustible liquids or occupancies where shielding of combustibles is

extensive.

Examples: Flammable Liquids Spraying, Open Oil Quenching,

Plastics Processing, Solvent Cleaning, Varnish and Paint Dipping

Rociadores Cobertura Estandar

Pendientes o Montantes

Presion Minima de operacion es 7 psi. Flujo por rociador

Es determinado por area x densidad o presion minima

Multiplicada por la raiz cuadrada de la presion minima

(cual sea la mayor)

Flujo Minimo Rociador

Q = Area x Densidad

Q = K x P

P = (Q/K)2

K = Q/ P

Q = Flujo Agua

K = Coefficiente de

Descarga

P = Presion

15’-0”

(4,57m) 15’-0”

(4,57m)

15’-0”

(4,57m)

Densidad requerida para Riesgo Ligero es .10 gpm per sq. ft.

Descarga Minima por rociador espacio 225 sq. ft. es

Determinado por area x densidad = Q

EJemplo: .10 gpm per sq. ft. x 225 sq. ft. = 22.5 gpm

*Plan View

10’-0”

(3,04m) 10’-0”

(3,04m)

13’-0”

(3,96m)

Densidad req. para Riesgo Ordinario 1 es .15 gpm per sq. ft.

Descarga Minima por rociador espacio 130 sq. ft. es

Determinado por area x densidad = Q

Ejemplo: .15 gpm per sq. ft. x 130 sq. ft. = 19.5 gpm

*Plan View

10’-0”

(3,04m)

10’-0”

(3,04m)

13’-0”

(3,96m)

Densidad req. para Riesgo Ordinario 2 es .20 gpm per sq. ft.

Descarga Minima por rociador espacio 130 sq. ft. es

Determinado por area x density = Q

Ejemplo: .20 gpm per sq. ft. x 130 sq. ft. = 26 gpm

*Plan View

10’-0”

(3,04m)

10’-0”

(3,04m)

10’-0”

(3,04m)

Densidad Req. para Riesgo Extra 1 is .30 gpm per sq. ft.

Descarga Minima por rociador espacio 100 sq. ft. is

Determinado por area x density = Q

Ejemplo: .30 gpm per sq. ft. x 100 sq. ft. = 30 gpm

*Plan View

10’-0”

(3,04m)

10’-0”

(3,04m)

10’-0”

(3,04m)

Densidad Req. para Riesgo Extra 2 is .40 gpm per sq. ft.

Descarga Minima por rociador espacio 100 sq. ft. es

Determinado por area x density = Q

Ejemplo: .40 gpm per sq. ft. x 100 sq. ft. = 40 gpm

*Plan View

Rociadores Cobertura Estandar

Pared

Debe cumplir con los requeriminetos medios de distribucion

sobre la area de 100 ft2 (9,3 m2) entre dos rociadores a un

espacio de 10 ft. (3,05 m) de separacion para rociadores

estandar de 1/2” (15 mm): 0.05 gpm/ft2 (0.034 L/s/m2) o

0.07gpm/ft2 (0.048 L/s/m2) para rociadores de grande orificios

17/32” (20 mm) : Y todavia proporcionar 3.5% contra la pared en

donde estan instalados los rociadores, para ambos 1/2” and L/O.

DISTRIBUCION ROCIADOR DE PARED

Rociadores Cobertura

Estandar de Pared

Rociadores Cobertura Estandar de

Pared

Espacio Rociador Estandar (Area de Cobertura)

Riesgo Ligero (acuerdo a la NFPA 13) : 196 sq. ft. max

(18,2 sq. m)

Riesgo Ordinario (acuerdo a la NFPA 13) : 100 sq. ft. max

(9,29 sq. m) (Nota: Debe ser listado para Riesgo Ordinario)

14’-0”

(4,27m)

14’-0”

(4,27m)

14’-0”

(4,27m)

Densidad Req. para Riesgo Ligero es .10 gpm

per sq. ft.

Descarga Minima por rociador espacio 196 sq. ft. es

Determinado por area x density = Q

Ejempl: .10 gpm per sq. ft. x 196 sq. ft. = 19.6 gpm

*Plan View

10’-0”

(3,04m) 10’-0”

(3,04m)

10’-0”

(3,04m)

Densidad Req. para Riesgo Ordinario Groupo 1

es .15 gpm per sq. ft.

Descarga Minima por rociador espacio 100 sq. ft. es

Determinado por area x density = Q

Ejemploe: .15 gpm per sq. ft. x 100 sq. ft. = 15 gpm

*Plan View

10’-0”

(3,04m)

10’-0”

(3,04m)

10’-0”

(3,04m)

Densidad Req. para Riesgo Ordinario Group 2

es .20 gpm per sq. ft.

Descarga Minima por rociador espacio 100 sq. ft. es

Determinado por area x density = Q

Ejemplo: .20 gpm per sq. ft. x 100 sq. ft. = 20 gpm

*Plan View

Rociadores Cobertura Extendida

Pendiente y Montante

Rociadores Cobertura Extendida Solo se permiten en areas de Riesgo Ligero

A menos que esten listados especificamente para

areas listadas para Riesgo Ordinario

Rociadores Cobertura Extendida Tienen areas de cobertura maxima de 400 sq. ft.

de acuerdo a NFPA 13. El Espacio esta en

incrementos de 2’-0”, ejemplo: 12’x12’, 14’x14’

16’x16’, 18’x18’, 20’x20’

DISTRIBUCION ROCIADORES • COVERTURA EXTENDIDA

– AREA DEL PISO MAS MOJAR LA PARED

30” (762 mm) ENCIMA DEL PISO ABADO

Model M ECOH-

ELO Pendent

VK534

Model M ECLH-

ELO Pendent

VK608

Model M ECOH-

ELO Upright

VK532

ECOH-K14

Cobertura Extendida- Pendiente

ECLH-ELO Pendiente

Espacio y Descarga Minima