06239625

Embed Size (px)

Citation preview

  • 8/12/2019 06239625

    1/8

    IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012 2133

    A New Digital Distance Relaying Scheme forCompensation of High-Resistance Faults on

    Transmission LineVijay H. Makwana and Bhavesh R. Bhalja, Senior Member, IEEE

    AbstractPerformance of the conventional ground distancerelaying scheme is adversely affected by different types of groundfaults, such as single line to ground, double line to ground, andsimultaneous open conductor and ground. This effect is morepronounced due to the considerable value of fault resistance anddirection and magnitude of power flow. The work presented in thispaper addresses the aforementioned problems encountered by theconventional ground distance relaying scheme when protectingdoubly fed transmission lines. Further, a new digital distancerelaying scheme is proposed which compensates the errors pro-

    duced by the conventional ground distance relaying schemeusing local-end data only. The detailed analysis of the apparentimpedance as seen from the relaying point by the conventionalground distance relaying scheme and the proposed scheme duringdifferent types of ground faults is also presented in this paper.The feasibility of the proposed scheme has been tested usingMATLAB/SIMULINK software. The simulation results demon-strate the effectiveness of the proposed scheme since it providesaccuracy on the order of 98%.

    Index TermsDoubly fed transmission line, ground distancerelay, high resistance fault, simultaneous open conductor andground fault, single-line-to-ground fault.

    I. INTRODUCTION

    DIGITAL distance relays, used to protect extremely high

    voltage (EHV) and ultra-high voltage (UHV) transmis-

    sion lines, can realize some very useful functions which were

    not possible with previous generation relays, such as long-term

    storage of prefault data, multiple setting groups, programmable

    logic, adaptive logic, and sequence-of-events recording [1], [2].

    However, these relays do not have successful solutions to the

    cumbersome problems, such as the presence of high fault path

    resistance during different types of ground faults and remote in-

    feed [3]. Under these conditions, part of the fault resistance is

    translated into inductance or capacitance, causing over-reach orunder-reach of the distance relay [4], [5].

    The performance of the digital ground distance relay is also

    affected by a typical type of ground fault called a simultaneous

    Manuscript received November 29, 2011; revised April 21, 2012; acceptedMay 27, 2012. Date of publication July 13, 2012; date of current versionSeptember 19, 2012. Paper no. TPWRD-01014-2011.

    V. H. Makwana is with the Department of Electrical Engineering, G. H. PatelCollege of Engineering and Technology, Vallabh Vidyanagar-388 120, Gujarat,India (e-mail: [email protected]).

    B. R. Bhalja is with the Department of Electrical Engineering, A. D. PatelInstitute of Technology, New Vidyanagar, Karamsad-388121, Gujarat, India(e-mail: [email protected]).

    Digital Object Identifier 10.1109/TPWRD.2012.2202922

    open conductor and ground fault. This type of fault may occur

    on an overhead transmission line because of the breaking of a

    phase conductor at a point close to the transmission tower. The

    breaking conductor on the tower side is being held by the sus-

    pension insulators and that on the other side falling to ground.

    Severe power system disturbances are often caused during this

    type of simultaneous fault condition, which are the sources of

    erroneous operation of the conventional digital distance relays

    [6][8].Daros et al. [4] presented a technique of fault resistance

    compensation in the phase coordinate. The fault impedance

    was obtained in an iterative manner with improved accuracy.

    However, the performance of the technique is not validated

    for multi-infeed transmission lines. Subsequently, Xuet al. [5]

    proposed a fault impedance estimation algorithm for ground

    distance relaying. This scheme is based on the selection of three

    different types/combinations of sequence current components,

    namely, negative-, zero-, and comprehensive negative-zero-se-

    quence current components. However, in this scheme, the

    procedure has not been clearly mentioned for the selection of a

    particular sequence current component, which is required for

    the impedance estimation algorithm.Eissa [9] proposed a fault impedance compensation method

    for the two-terminal transmission line which is based on fault

    resistance calculation. However, the effect of remote infeed and

    variations in active and reactive power have not been considered

    by the said scheme. To enhance the capability against fault re-

    sistance, Liuet al.[10] developed an adaptive impedance relay

    with a composite polarizing voltage which comprises memo-

    rized prefault compensated voltage and the voltage during fault.

    However, the accuracy of the estimation of the compensated

    voltage need not be guaranteed at the time of fault.

    Hence, none of these papers have analyzed the impact of dif-

    ferent types of ground faults including a simultaneous open con-ductor and ground fault on transmission lines, thereby leaving

    a scope of research for improvements in this area. Therefore, in

    order to solve the problem of maloperation of the conventional

    digital distance relaying scheme during aforementioned types

    of ground faults, the authors have proposed a new digital dis-

    tance relaying scheme in this paper. The discussions have been

    supported with MATLAB/SIMULINK software validation.

    II. GROUNDFAULTS ONDOUBLYFEDTRANSMISSIONLINE

    Fig. 1 shows a single-line diagram of a portion of the power

    system network containing a transmission line between two

    buses. A single-line-to-ground fault, having fault resistance

    0885-8977/$31.00 2012 IEEE

  • 8/12/2019 06239625

    2/8

    2134 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012

    Fig. 1. Modeling of the single-line-to-ground fault.

    Fig. 2. Modeling of the open conductor and ground fault.

    , occurs at fault location which is at percentage of the

    transmission line from bus . Since part of the fault current

    supplied from bus is not measurable at the relaying point

    , the conventional ground distance relay measures an incor-

    rect value of fault impedance. Consequently, the relay may

    over-reach/under-reach depending upon the forward/backward

    direction of power flow and the magnitude of fault resistance.

    Further, Fig. 2 shows a simultaneous open conductor and

    ground fault condition on the doubly fed transmission line at

    fault location , which is at percentage of the transmission

    line from bus . During a simultaneous open conductor and

    ground fault, the Bus S side phase A of the transmission line hasbeen broken and fallen to ground. Whereas, Bus side phase

    of the transmission line has broken, but is held by the suspension

    insulators. In this situation, the conventional ground distance

    relay at Bus measures an incorrect value of fault impedance

    and it may over-reach/under-reach. Furthermore, the conven-

    tional phase and ground distance relays at Bus completely

    fail to detect an open conductor fault on the transmission line

    [6].

    III. ANALYSIS OFGROUNDFAULTS ONDOUBLYFEDTRANSMISSIONLINE

    For all analyses, positive- and negative-sequence impedances

    ( and ) of the transmission line are assumed to be equal.

    The voltage and current of phase of the transmission line mea-

    sured at the relaying point are represented by and ,

    respectively. Throughout the entire analysis, , , and

    represent the actual magnitude of resistance, reactance, and

    impedance of the faulted portion of the transmission line. Con-

    sequently, and represent fault impedance measured by

    the conventional ground distance relaying scheme and the pro-

    posed scheme, respectively. In the equations throughout the en-

    tire discussion, the positive-, negative-, and zero-sequence com-

    ponents are specified by subscripts 1, 2, and 0, respectively. Fur-

    ther, the sequence (positive, negative, and zero) components ofvoltages and currents of the transmission line measured at buses

    and are indicated by , and , , re-

    spectively. Similarly, the sequence (positive, negative, and zero)

    components of impedances of the sources and (connected

    at buses and ) are indicated by and , respec-

    tively. Furthermore, since the ground path is involved in both

    types of faults, the magnitude of fault resistance plays a key role

    in the measurement of impedance of the faulted portion of thetransmission line. Hence, the authors have considered wide vari-

    ations in the magnitude of fault resistance up to 200 .

    A. Impedance Measured by the Conventional Ground Distance

    Relaying Scheme

    Referring to Figs. 1 and 2, for a single-line-to-ground fault

    as well as a simultaneous open conductor and ground fault oc-

    curring in phase of a doubly fed transmission line, the fault

    impedance seen by the conventional ground distance re-

    laying scheme located at relaying point is given by [1]

    (1)

    where

    It is clearly indicated by (1) that for both types of faults, the

    conventional ground distance relay measures the impedance of

    the faulted portion of the transmission line along with some ad-

    ditional impedance . Hence, appropriate compensation is re-

    quired in order to eliminate and to measure the correct valueof impedance of the faulted portion of the transmis-

    sion line. The proposed scheme does the function of elimination

    of during different types of ground faults considering wide

    variations in fault resistances.

    B. Impedance Measured by the Proposed Scheme

    Fig. 3 shows an equivalent circuit for a single-line-to-ground

    fault occurring in phase of the doubly fed transmission line.

    With reference to Fig. 3

    (2)

    Generally, the magnitudes of and are negligible

    with respect to . Further, is in the numerator and

    is in the denominator side. Therefore, and

    can be safely removed from (2). Hence, (2) can be written

    as

    (3)

    Now, since the sequence current components during a single-

    line-to-ground fault at point are equal ,

    the total fault current is given by

    (4)

  • 8/12/2019 06239625

    3/8

    MAKWANA AND BHALJA: NEW DIGITAL DISTANCE RELAYING SCHEME FOR COMPENSATION 2135

    Fig. 3. Equivalent circuit for the single-line-to-ground fault in phase .

    Fig. 4. Impedanceseen at therelayingpoint for a single-line-to-ground fault.

    Hence, (1) now can be written as

    (5)

    During a single-line-to-ground fault, if the voltage at the re-

    laying point leads with respect to the voltage at the remote end,

    thentheimpedance providedby (5) isas shownin Fig. 4(a).

    Conversely, when the voltage at the relaying point lags with re-

    spect to the voltage at the remote end, impedance provided

    by (5) is as shown in Fig. 4(b).

    It is to be noted from Fig. 4 that the value of fault impedance

    measured at the relaying point is the vector addition of

    actual impedance of the faulted portion of the transmis-

    sion line and fault impedance . The deviation angle

    can be determined using the second part of (5) since that partcontains gradients of all known current and impedance vectors.

    Only is unknown, but it is not required to find the deviation

    angle.

    In Fig. 4, can be determined with the help of the apparent

    impedance measured at the relaying point and the devia-

    tion angle [11]. It is given by

    (6)

    Hence, the actual impedance is determined by the inter-

    section oftwo straight lines, namely and . Here, and

    represent the impedance vectors of the transmission line. Now,

    assuming and as resistance km) and reactance km)

    of the transmission line, the impedance of the faulted portion of

    the transmission line is given by [11]

    (7)

    (8)

    The same algorithm is applicable to a simultaneous open

    conductor and ground fault as well as to a double-line-to-ground

    fault. Further, during a triple-line-to-ground fault, is either

    zero or negligible since the fault is symmetrical in nature.

    Therefore, referring to (1) and (5), it can be concluded that

    the impedance is either zero or negligible. As a result, the

    conventional scheme and proposed scheme measure the same

    and correct value of impedance of the faulted portion

    of the transmission line.

    The flowchart for determining the impedance values using the

    proposed scheme is shown in Fig. 5. The proposed algorithm

    uses the Half Cycle Modified Discrete Fourier Transform algo-

    rithm, as suggested by [12], for phasor computation. This willhelp to reduce the fault detection time to a large extent, which

    is required these days for digital relays available from different

    manufacturers at voltage levels of 400 kV and above. In addi-

    tion, the proposed algorithm uses the sampling rate of 20 sam-

    ples/cycle which helps to reduce not only the computation time

    but also reduces hardware requirements.

    IV. RESULTS ANDDISCUSSIONS

    This section describes the performance of the conventional

    ground distance relaying scheme and the proposed scheme for

    different types of faults (a single-line-to-ground fault, a double-line-to-ground fault, a triple-line-to-ground fault, and a simul-

    taneous open conductor and ground fault) on 400-kV, 300-km-

    long doubly fed transmission line. The source and transmission-

    line parameters are given in Tables X and XI. The faults are sim-

    ulated considering wide variations in fault location (0% to 80%

    in steps of 10%), with different values of fault resistance (5 ,

    50 , 100 , and 200 ) and having different values of a power

    transfer angle (20 , 10 , 10 and 20 ). Throughout the en-

    tire discussion, , , and , represent the magni-

    tudes of resistance and reactance measured by the conventional

    ground distance relaying scheme and the proposed scheme, re-

    spectively. represents the percentage error in the measure-

    ment of reactance given by the conventional ground distance re-laying scheme. and represent the percentage errors in

  • 8/12/2019 06239625

    4/8

    2136 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012

    Fig. 5. Flowchart of the proposed scheme.

    the measurement of resistance and reactance given by the pro-

    posed scheme, respectively. These errors are defined as

    (9)

    and

    (10)

    A. Single-Line-to-Ground Fault

    For a single-line-to-ground fault, the simulation results ob-

    tained using MATLAB/SIMULINK software are as follows.1) Effect of Change in the Fault Location and Power Transfer

    Angle: Tables I and II represent the performance of the con-

    ventional ground distance relaying scheme and the proposed

    scheme, respectively, in terms of error in the measurement of re-

    sistance and reactance of the faulted portion of the transmission

    line for a single-line-to-ground fault at different fault locations

    (0% to 80% in steps of 10%), with 100 and having

    different values of (20 and 20 ).

    It is to be noted from Table I that the percentage error in the

    measurement of reactance of the faulted portion of the trans-

    mission line given by the conventional ground distance relaying

    scheme increases as the fault location moves away from the re-

    laying point irrespective of the direction of power flow. Fur-thermore, the percentage error increases gradually up to 50%

    TABLE IEFFECT OFCHANGE INFAULT LOCATION ANDPOWERTRANSFERANGLEON THECONVENTIONALGROUNDDISTANCE RELAYINGSCHEMEDURING

    100

    TABLE IIEFFECT OFCHANGE INFAULTLOCATION ANDPOWERTRANSFERANGLE ON

    THEPROPOSEDSCHEMEDURING 100

    in case of the power flow from bus to bus (positive sign of

    ) whereas it increases very rapidly up to about 410% during

    the power flow from bus to bus (negative sign of ).

    On the other hand, it is to be noted from Table II that the per-centage error in the measurement of resistance and reactance

    of the faulted portion of the transmission line given by the pro-

    posed scheme is negligible for a single-line-to-ground fault at all

    fault locations even with different values of the power transfer

    angle. Even though the percentage error increases as the fault

    location moves away from the relaying point and the direction

    of power flow changes (the sign of changes from negative to

    positive), it still remains within 1.43%.

    Fig. 6 represents the loci of fault impedance provided by the

    conventional ground distance relaying scheme and the proposed

    scheme for a single-line-to-ground fault at different fault loca-

    tions (0% to 80% in steps of 10%), with a fault resistanceof 100 having different values of the power transfer angle

    .

    It has been observed from Fig. 6 that the conventional

    ground distance relay completely fails to detect high-resistance

    single-line-to-ground faults having 100 since its loci

    of impedance is outside the first zone boundary. Further, it

    is to be noted from Fig. 6 that the locus of impedance of the

    conventional relay moves very far away from the first zone

    boundary since the location of fault moves away from the

    relaying point during the reversal of power (power flowing

    from bus to bus ). This clearly indicates that the percentage

    error in the measurement of impedance of the faulted portion

    of the transmission line increases very rapidly. Conversely,the proposed scheme measures the correct value of impedance

  • 8/12/2019 06239625

    5/8

    MAKWANA AND BHALJA: NEW DIGITAL DISTANCE RELAYING SCHEME FOR COMPENSATION 2137

    Fig. 6. Impedance seen by the conventional and the proposed scheme withvarying fault location and power transfer angle.

    TABLE III

    EFFECT OFCHANGE INFAULTRESISTANCE ON THECONVENTIONALSCHEME

    of the faulted portion of the transmission line since the locus

    of the fault impedance gets superimposed on the locus of the

    actual value of fault impedance for all fault locations even with

    different values of power transfer angles .

    2) Effect of Change in the Fault Resistance: Tables III and

    IV show the performance of the conventional ground distance

    relaying scheme and the proposed scheme in terms of error in

    the measurement of resistance and reactance of the faulted por-

    tion of the transmission line for a single-line-to-ground fault at

    different fault locations (0% to 80% in steps of 10%) having

    10 with different values of (100 and 200 ). It is to

    be noted from Table III that the percentage error in the mea-surement of reactance of the faulted portion of the transmission

    line given by the conventional ground distance relaying scheme

    increases as the value of increases. Further, as the fault lo-

    cation moves away from the relaying point, the percentage error

    also increases. Conversely, it is to be noted from Table IV that

    the proposed scheme measures the correct values of resistance

    and reactance of the faulted portion of the transmission line.

    Even though the percentage error increases as the fault location

    moves away from the relaying point and with the increase in

    the values of , the maximum percentage error still remains

    within a limit of 1.71%.

    Fig. 7 shows the performance of the conventional ground dis-

    tance relaying scheme and the proposed scheme in terms oferror in the measurement of impedance of the faulted portion

    TABLE IVEFFECT OFCHANGE INFAULTRESISTANCE ON THEPROPOSEDSCHEME

    Fig. 7. Impedance seen by the conventional and the proposed scheme withvarying fault resistance.

    of the transmission line for a single-line-to-ground fault at dif-

    ferent fault locations (0% to 80% in steps of 10%), with dif-ferent values of (5, 50, 100, and 200 ) and . It has

    been observed from Fig. 7 that the locus of fault impedance mea-

    sured by the conventional ground distance relaying scheme lies

    within its first zone boundary for a single-line-to-ground fault

    having a low value of fault resistance (say 5 ). However, as the

    values of fault resistance increase, the locus of fault impedance

    moves away from the first zone boundary. In the worst case, that

    is, for a single-line-to-ground fault having very high values of

    fault resistance (100 and 200 ), the loci of fault impedance lie

    completely outside the first zone boundary. This clearly indi-

    cates that the conventional ground distance relaying scheme is

    unable to provide adequate protection to the transmission lineagainst high-resistance single-line-to-ground faults. In contrast,

    the locus of the proposed scheme always lies within the first

    zone boundary even with wide variations in the values of fault

    resistance and fault locations.

    3) Effect of Change in the Magnitude of the Source Short-Cir-

    cuit Capacity: Tables V and VI show the performance of the

    conventional ground distance relaying scheme and the proposed

    scheme, respectively, in terms of error in the measurement of re-

    sistance and reactance of the faulted portion of the transmission

    line for a single-line-to-ground fault at different fault locations

    (0% to 80% in steps of 10%), with different short-circuit ca-

    pacity of sources and (5 and 20 GVA) with 100

    and 10 . It is to be noted from Table V that the percentageerror in the measurement of reactance of the faulted portion of

  • 8/12/2019 06239625

    6/8

    2138 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012

    TABLE VEFFECT OF CHANGE IN SHORT-CIRCUIT CAPACITY OF

    SOURCES ON THECONVENTIONALSCHEME

    TABLE VIEFFECT OF CHANGE IN SHORT-CIRCUIT CAPACITY

    OFSOURCES ON THEPROPOSEDSCHEME

    the transmission line provided by the conventional ground dis-

    tance relaying scheme increases as the short-circuit capacity of

    source decreases. This clearly indicates that the conventionalground distance relaying scheme performs inadequately during

    weak infeed conditions. On the other hand, it is to be noted from

    Table VI that the proposed scheme measures correct values of

    resistance and reactance of the faulted portion of the transmis-

    sion line during strong and weak infeed conditions (for high and

    low values of short-circuit capacities of sources and ). In

    all of these situations, the maximum percentage error remains

    within 1.61%.

    B. Double-Line-to-Ground Fault

    Table VII shows the performance of the conventional grounddistance relaying scheme and the proposed scheme

    in terms of error in the measurement of resistance and reac-

    tance of the faulted portion of the transmission line for a double-

    line-to-ground fault at different fault locations (0% to 80% in

    steps of 10%), with 100 and 10 .

    It is to be noted from Table VII that the percentage error in

    the measurement of reactance of the faulted portion of the trans-

    mission line provided by the conventional ground distance re-

    laying scheme is above 20% for all fault locations. Further, as

    the fault location moves away from the relaying point, the per-

    centage error decreases marginally. Conversely, the percentage

    error in the measurement of resistance and reactance given by

    the proposed scheme is very low for close-in faults and increasesmarginally as the fault location moves toward the remote end.

    TABLE VIIEFFECT OFCHANGE INFAULTLOCATION ON THECONVENTIONALGROUND

    DISTANCERELAYINGSCHEME AND THEPROPOSEDSCHEME

    TABLE VIIIEFFECT OFCHANGE INFAULTLOCATION ON THEPROPOSEDSCHEME

    However, for all situations, the maximum percentage error re-

    mains within 1.84%.

    C. Triple-Line-to-Ground Fault

    Table VIII shows the performance of the proposed scheme

    in terms of error in the measurement of resistance andreactance of the faulted portion of the transmission line for a

    triple-line-to-ground fault at different fault locations (0% to

    80% in steps of 10%), with 200 and 10 . It

    is mentioned in Section III that during a triple-line-to-ground

    fault, the conventional ground distance relaying scheme and the

    proposed scheme measure the same and correct value of fault

    impedance. Hence, no separate results for the conventional

    ground distance relaying scheme are shown.

    It is to be noted from Table VIII that as the fault location

    moves away from the relaying point, the percentage error in the

    measurement of resistance and reactance of the faulted portion

    of the transmission line provided by the proposed scheme in-

    creases. However, the rate of increase in the percentage error is

    very less and the maximum percentage error remains within

    1.96%.

    D. Simultaneous Open Conductor and Ground Fault

    Table IX shows the performance of the conventional ground

    distance relaying scheme and the proposed scheme in terms

    of error in the measurement of resistance and reactance of the

    faulted portion of the transmission line for a simultaneous open

    conductor and ground fault at different fault locations (0% to

    80% in steps of 10%) with 50 and 20 . It is to

    be noted from Table IX that the percentage error in the measure-

    ment of reactance of the faulted portion of the transmission lineprovided by the conventional ground distance relaying scheme

  • 8/12/2019 06239625

    7/8

    MAKWANA AND BHALJA: NEW DIGITAL DISTANCE RELAYING SCHEME FOR COMPENSATION 2139

    TABLE IXEFFECT OFCHANGE INFAULTLOCATION ON THE CONVENTIONALSCHEME

    AND THEPROPOSEDSCHEME

    Fig. 8. Impedance seen by the conventional and the proposed scheme withvarying fault resistance.

    is more than 5% for all fault locations. Conversely, the per-

    centage error in the measurement of resistance and reactance

    given by the proposed scheme is below 1.90%.

    Fig. 8 shows the performance of the conventional ground dis-

    tance relaying scheme and the proposed scheme on the

    plane for a simultaneous open conductor and ground fault at

    different fault locations (0% to 80% in steps of 10%), having

    different values of , with 50 .

    It has been observed from Fig. 8 that even though the loci of

    fault impedance measured by the conventional ground distance

    relaying scheme lie within its first zone boundary for differentvalues of the power transfer angle, they are far away from the

    locus of the actual fault impedance. This clearly indicates that

    the conventional ground distance relaying scheme measures the

    fault impedance with a very high percentage of error whereas the

    proposed scheme does the same task with very good accuracy

    even with wide variations in fault locations and power transfer

    angles.

    V. CONCLUSION

    In this paper, the authors have proposed a new digital distance

    relaying scheme for a doubly fed transmission line which effec-tively compensates the errors given by the conventional ground

    TABLE XTRANSMISSION-LINEPARAMETERS

    TABLE XISOURCEPARAMETERS

    distance relaying scheme during different types of high-resis-

    tance ground faults. Further, the proposed scheme measures cor-

    rect values of resistance and reactance with an average accuracyof 98% for different types of high-resistance ground faults in-

    cluding a simultaneous open conductor and ground fault. More-

    over, it maintains the same accuracy during wide variations in

    system and fault conditions. At the end, it utilizes sequence

    components of voltage and current phasors at the local end only

    and, hence, it is very simple and more reliable compared to other

    techniques which use remote-end data.

    REFERENCES

    [1] Protective relay engineers, inProc. 61st Annu. Conf. Fundamentalsof Distance Protection,, College Station, TX,Apr. 13, 2008,pp. 134.[2] A.G. PhadkeandJ. S.Thorp, Computer Relaying for Power Systems.

    Taunton, U.K.: Research Studies Press, 1998.[3] B. Bhalja and R. P. Maheshwari, An adaptive distance relaying

    scheme using radial basis function neural network, Elect. PowerCompon. Syst., vol. 35, no. 3, pp. 245259, Mar. 2007.

    [4] A. D. Filomena, R. H. Salim, M. Resener, and A. S. Bretas, Grounddistance relaying with fault-resistance compensation for unbalancedsystems,IEEE Trans. Power Del., vol. 23, no. 3, pp. 13191326, Jul.2008.

    [5] Z. Y. Xu, S. J. Jiang, Q. X. Yang, and T. S. Bi, Ground distance re-laying algorithm for high resistance fault,IET Gen., Transm. Distrib.,vol. 4, no. 1, pp. 2735, 2010.

    [6] V. Cook, Distance protection performance during simultaneousfaults,Proc. Inst. Elect. Eng., vol. 124, no. 2, pp. 141146, Feb. 1977.

    [7] F. M. Abouelenin, A complete algorithm to fault calculation due to

    simultaneous faultsCombination of short circuits and open lines,in Proc. IEEE MELCON Electrotech. Conf., Cairo, Egypt, May 79,2002, pp. 522526.

    [8] D. R. Smith, Digital simulation of simultaneous unbalances involvingopen and faulted conductors, IEEE Trans. Power App. Syst., vol.PAS-89, no. 8, pp. 18261835, Nov./Dec. 1970.

    [9] M. M. Eissa, Ground distance relay compensation based on faultresistance calculation, IEEE Trans. Power Del., vol. 21, no. 4, pp.18301835, Oct. 2006.

    [10] Q. K. Liu, S. F. Huang, H. Z. Liu, and W. S. Liu, Adaptive impedancerelay with composite polarizing voltage against fault resistance,IEEETrans. Power Del., vol. 23, no. 2, pp. 586592, Apr. 2008.

    [11] Y.-J. Ahn, S.-H. Kang, S.-J. Lee, and Y.-C. Kang, An adaptive dis-tance relaying algorithm immune to reactance effect for double-circuittransmission line systems, in Proc. IEEE Power Eng. Soc. Summer

    Meeting, Vancouver, BC, Canada, Jul. 19, 2001, vol. 1, pp. 599604.

    [12] S.-L. Yu and J.-C. Gu, Removal of decaying dc in current and voltagesignals using a modified Fourier filter algorithm, IEEE Trans. PowerDel., vol. 16, no. 3, pp. 372379, Jul. 2001.

  • 8/12/2019 06239625

    8/8

    2140 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012

    Vijay H. Makwana received the B.E. degree in elec-trical engineering and the M.E. degree in electricalpower systems from B.V.M. Engineering College,Sardar Patel University, Vallabh Vidyanagar, India,in 1999 and 2002, respectively, and is currentlypursuing the Ph.D. degree in electrical engineeringat SICART, Sardar Patel University.

    Currently, he is an Associate Professor in the

    Department of Electrical Engineering, G. H. PatelCollege of Engineering and Technology, VallabhVidyanagar. He has published four papers in inter-

    national journals. He has also written a book Power System Protection andSwitchgear (Tata Mc-Graw Hill, 2010). His research interests include powersystem protection, planning and design, system modeling, and simulation.

    Bhavesh R. Bhalja (M07SM10) received theB.E. degree in electrical engineering and the M.E.degree in power system engineering from B.V.M.Engineering College, Sardar Patel University,Vallabh Vidyanagar, India, in 1999 and 2001, respec-tively, and the Ph.D. degree from the Indian Instituteof Technology Roorkee in 2007.

    Currently, he is a Professor and Head of the De-

    partment of Electrical Engineering, A. D. Patel Insti-tute of Technology, New Vidyanagar, India. He haspublished more than 60 papers in journals and con-

    ferences at international and national levels. He is also involved in many re-search-and-development projects with the Government of India. He has alsowritten a bookProtection and Switchgear(Oxford University Press, 2011). Hisresearch interests include power system protection, automation, planning anddesign, system modeling and simulation, and artificial intelligence.

    Prof. Bhalja received the Young Engineers Award and Merit Award from theInstitution of Engineers, India in 2009 and 2007, respectively. He also receivedthe Hariom Ashram Prerit Bhaikaka Interuniversity Smarak Trust Award fromSardar Patel University in 2009.