06612758

Embed Size (px)

Citation preview

  • 8/12/2019 06612758

    1/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    IEEE TRANSACTIONS ON POWER DELIVERY 1

    An Interphase Distance Relaying Algorithm for

    Series-Compensated Transmission LinesZ. Y. Xu, Senior Member, IEEE, Z. P. Su, J. H. Zhang, A. Wen, and Q. X. Yang

    AbstractA new interphase distance relaying algorithm for se-ries-compensated transmission lines is proposed in this paper. Thefault impedance can be correctively calculated using the proposedalgorithm without requirement of the parameters of series capac-

    itor device. The series capacitor can be simplified as a linearizedimpedance during the fault period, but its parameters can be usedas variables in fault loop equations. The real-time digital simulatortests show that the proposed algorithm can obtain more accurateresults than other traditional distance relaying algorithms for se-ries-compensated transmission lines.

    Index TermsDistance relay, interphase faults, series-compen-sated transmission lines.

    I. INTRODUCTION

    S ERIES capacitors (SCs) have been widely used in powertransmission to increase power transfer capability, improvetransient stability and damp power oscillations. The metal oxide

    arrestor (MOV) was applied as an overvoltage protection de-

    vice on the series capacitors itself for years. Distance relay is

    widely used as main or backup protection of transmission lines

    including series-compensated transmission lines, but the relia-

    bility of traditional distance relay is affected by the incorrectly

    measured fault impedance caused by highly nonlinear charac-

    teristic of MOV[1].To eliminate the influence of nonlinearity caused by MOV a

    series of simplified and approximated models of SC/MOV de-

    vice for distance relay have been discussed[2][6]. However, in

    the methods based on the calculation of voltage across SC/MOV

    to eliminate the effect of series capacitor discharging gap (GAP)

    was not considered, which must be set to discharge in order to

    protect the SC/MOV in severe internal faults on the protected

    lines. Actually, GAP is an important part of modern SC/MOV

    devices and it is impossible to accurately calculate the voltage

    across SC/MOV without considering GAP discharging.

    The enhancement for directional and pilot protection on

    series-compensated lines has been proposed in [7], [8], but itcannot be used in fault impedance calculation of step distance

    Manuscript received April 07, 2013; revised July 07, 2013, August 16, 2013;accepted September 02, 2013. Date of publication September 26, 2013; date of

    current version nulldate. Paper no. TPWRD-00382-2013.Z. Y. Xu, Z. P. Su, J. H. Zhang, and Q. X. Yang are with the School of Elec-

    trical Electronic Engineering, North China Electric Power University, Chang-ping, Beijing 102206, China.

    Z. Y. Xu and Q. X. Yang are also with Beijing Sifang Automation Co. Ltd.,

    Haidian, Beijing 100085, China (e-mail: [email protected]).A. Wen is with China Southern Power Grid Co. Ltd., Guangzhou 510623,

    ChinaColor versions of one or more of the figures in this paper are available online

    at http://ieeexplore.ieee.org.

    Digital Object Identifier 10.1109/TPWRD.2013.2281067

    relay. The wavelet transform technique [9], [10] has also

    been presented to improve the performance of protection on

    series-compensated transmission lines; in [11] a neural net-

    work scheme has been suggested. However, their performance

    needs further evaluation and improvement. A scheme based on

    high-frequency signals have been proposed in [12], in which

    a specialized measurement unit consisting of stack tuner and

    line trap is used to capture the high-frequency components of

    the fault signal. In order to evaluate the performance of this

    scheme more test cases were required.

    In this paper a new algorithm is proposed for the distance

    relay on series-compensated transmission lines, which is de-

    duced from time domain fault location method [13], [14]. In

    the proposed algorithm, the effect of series capacitor on mea-

    sured fault impedance is avoided because the series capacitor

    parameters are only used as variables in the fault loop equations,

    which are not required to be known. A significant merit of pro-

    posed algorithm is that all operating states of series capacitance

    device can be modeled as a linearized equivalent impedance.

    Meanwhile, the operating states of SC/MOV/GAP, the parame-

    ters of SC/MOV/GAP, the relative fault position with respect to

    SC/MOV/GAP and the iterative calculations are unnecessary.

    This makes the algorithm simpler and more accurate than other

    algorithms. This paper mainly investigates the algorithm for in-

    terphase faults. The algorithm for single phase to ground faults

    is being reviewed in another paper. Validation tests have been

    performed using RTDS to demonstrate the accuracy of the pro-

    posed algorithm.

    II. MODEL ANALYSIS

    The voltage-current characteristics of MOV are designed as

    highly nonlinear. This can significantly affect the traditional dis-

    tance relaying. The general characteristics of MOV conduction

    by IEC standard[15]is expressed by a single exponential curve

    as given in theAppendix.Fig. 1shows the structure of modern SC/MOV/GAP device

    and its equivalent circuit. Three different operating states incor-

    porate the SC/MOV/GAP different protection functions for dif-

    ferent fault conditions. The three operating states are as follows:

    1) SC/MOV is bypassed by GAP discharging in 23 ms after

    fault inception.

    2) Capacitor operates without MOV and GAP action.

    3) Capacitor operates with MOVaction and without GAP dis-

    charging.

    Actually, all these three operating states can be represented

    as a linearized equivalent circuit in series with resistance

    and capacitive reactance for the SC/MOV/GAP as shown

    0885-8977 2013 IEEE

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/12/2019 06612758

    2/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    2 IEEE TRANSACTIONS ON POWER DELIVERY

    Fig. 1. SC/MOV/GAP equivalent circuit for analysis. (a) FSC, (b) Equivalentcircuit.

    Fig. 2. Series-compensated transmission line.

    Fig. 3. SC/MOV equivalent circuit for interphase fault.

    inFig. 1(b). This is the basis of the proposed algorithm in this

    study as shown below:

    For thefirst state the fault location is always internal in series-

    compensated transmission lines and the fault is severe. The GAP

    is set to discharge in order to protect SC/MOV as quickly as

    possible after fault inception. It is easy to understand that

    and are equal to zero and the linearized model is applicable.

    For the second state, the fault is not severe and it is always ex-

    ternal. The voltage of SC is below the designed protective level

    andthustheMOVdoesnotconduct.The iszeroand isstill

    constant during the fault period. Obviously the SC/MOV/GAP

    can be represented by a linearized impedance in such state.

    For the third state, various simulations on RTDS were carried

    out to confirm that a linearized equivalent impedance model is

    reasonable for the SC/MOV coordination action during fault pe-

    riod. The test model used is a 500 kV 300 km long series-com-

    pensated transmission line as shown in Fig.2. The line reactance

    of 60% is compensated by two series capacitors C1 (30%) and

    C2 (30%) that are located at two ends of protected line. MOVs

    are simulated in detail with a single exponential model [15].

    Faults are initiated at 0.4 s. The three-line equivalent circuit of

    an interphase fault is also indicated in Fig. 3.

    Fig. 4. SC/MOV device waveform under CA solid fault at 180 km away frombus M with MOV cond uction. (a) SC voltage. (b) R elay cur rent. (c) MOV cur-

    rent. (d) SC current. (e) Calculated SC/MOV equivalent impedance.

    Fig. 4shows the current and voltage waveforms in SC/MOV

    device for a solid CA fault located at 180 km away from bus

    M. In this case the series capacitor operates with corresponding

    MOV conducting during fault period, and the GAP is set not to

    discharge. As shown inFig. 4(b)(d), the following character-

    istics can be found: 1. Voltage across SC is lagging 90 degrees

    from its current. When voltage reaches its protective level the

    phase angle of current flowing through SC is always in 90 to

    180 degree or 270 to 360 degree; 2. For every power frequency

    period when MOV conducts the initial phase-angle and magni-

    tude of fault current of SC/MOV have already appeared, so that

    the initial phase-angle and magnitude of power frequency fault

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/12/2019 06612758

    3/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    XUet al.: AN INTERPHASE DISTANCE RELAYING ALGORITHM FOR SERIES-COMPENSATED TRANSMISSION LINES 3

    current flowing through SC/MOV is not affected by MOV con-

    duction; 3. When MOV conducts the voltage across SC/MOV is

    limited to a constant value and the fault current is transferred to

    MOV branch. In this stage because of the nonlinear character-

    istic of MOV, the fault current is still a part of sinusoidal wave-

    form, as shown in Fig. 4(c), and the power frequency component

    of fault current measured by relay is completely sinusoidal due

    to that. As shown inFig. 4(a), the initial phase-angle and mag-

    nitude of fault voltage across SC are also constant during fault

    period. According to the analysis above, the SC/MOV can also

    be represented by a linearized impedance regardless of the high

    nonlinear characteristics of MOV. Fig. 4(e) shows the calcu-

    lated SC/MOV equivalent impedance during such fault period.

    It is apparent that the equivalent impedance is a capacitive con-

    stant. The transient process of impedanceinFig. 4(e)is caused

    by the transient current and voltage.

    Meanwhile,Fig. 5shows the current and voltage waveforms

    of SC/MOV device for the same fault without MOV conduction.

    It is clear from Figs. 4(e) and 5(d) that the transient process

    with MOV conduction after fault inception is much shorter than

    that of fault without MOV conduction. This is the reason of the

    attenuation of MOV/SC equivalent resistance.

    In summary, all three operating states of SC/MOV/GAP de-

    vice can be represented with a linearized impedance, which is

    the basis of the algorithm proposed in this paper.

    III. ALGORITHM FORSERIES-COMPENSATED LINES

    Based on the analysis above, a new interphase distance relay

    algorithm for series-compensated transmission line is proposed

    below. The following analysis neglects the shunt capacitance of

    transmission lines to simplify the algorithm. The error causedby this will be discussed later. As shown in Fig. 3, when an

    interphase fault occurs on the series-compensated transmission

    line, the interphase voltage of fault phase at relay location

    can be obtained as

    (1)

    where are resistance and inductance of fault line.

    Combining the resistance items,(2)can be obtained

    (2)

    where .

    Differentiating(2)with respects to t, (3)can be obtained

    (3)

    by applying a simplified notation as follows:

    Fig. 5. SC/MOV waveform under CA solid fault at 180 km away from bus M

    without MOV and GAP conduction. (a) Relay current. (b) SC voltage. (c) SCcurrent. (d) Calculated SC/MOV equivalent impedance.

    Equation(3) can be rewritten as(4)

    (4)

    where N is a sequence sampling number, (4) should be satis-

    fied for each sampling instant. In (4), there are three unknown

    variables. It means that arbitrary three discontinuous sampling

    points can be selected to satisfy the(5) as follows:

    (5)

    According to the(5), and because , and are constant

    during the fault period, the fault reactance and resistance

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/12/2019 06612758

    4/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    4 IEEE TRANSACTIONS ON POWER DELIVERY

    can be obtained from (6) and (7), without any requirement of se-

    ries capacitor parameters. is a variable, which is not required

    to be solved, and is any phase of AB, BC, or CA.

    IV. DIGITAL VERIFICATION

    A test model of a 500 kV series-compensated transmission

    line is shown inFig. 2. The detailed parameters are presented

    in theAppendixof this paper. The studiedfirst-zone interphase

    distance relay is set to protect 85% of the 300 km transmission

    line (i.e., 255 km). RTDS is used for the simulation of power

    system, series-compensated transmission line, CTs and CVTs.

    MATLAB is used for the calculations of the new algorithm.

    Source M leads source N by the angles between 0 (no load) and

    30 (heavy load). Faults are initiated at 0.4 s. The sampling rate

    of 80 samples per cycle (for 50 Hz system) is used and Butter-

    worth low-pass filter with 120 Hz cut-off frequencies is selected

    to filter out the high order harmonic components. Equations(6)

    and(7), shown at the bottom of the page, are employed to cal-

    culate the fault impedance from the relay location to the faultpoint for interphase faults.

    In order to verify and evaluate the new algorithm, some

    comparison results are shown between the new algorithm and

    the traditional distance relaying algorithm[16]which is widely

    used in distance relay of transmission lines. The traditional

    algorithm for interphase fault is given as

    (8)

    Fig. 6 shows the current waveform flowing through

    SC/MOV/GAP, the phase voltages, currents and the inter-

    phase fault impedance loci measured at two ends for a solidBC fault located at 240 km away from bus M which is inside

    the reach offirst-zone. As shown inFig. 6(a), in this case the

    series capacitor operates corresponding to MOV conduction

    during fault period and the GAP is not triggered. As shown in

    Fig. 6(b), for the relay at end M, the calculated fault reactance

    using traditional algorithm(8)reached to 28 ohm (100 km) and

    instable due to the series capacitor in the fault loop.

    For the new algorithm the accurate fault impedance is ob-

    tained within a cycle (20 ms) following the fault occurrence.

    As shown inFig. 6(c), for the relay at end N MOV/SC is by-

    passed by GAP triggering discharge, the series capacitor is not

    in the fault loop and the calculated fault impedance with the tra-

    ditional algorithm (8) had an error of 10%. However,for thenew

    algorithm the accurate fault impedance is obtained in 18 ms fol-

    lowing the fault occurrence.Fig. 7shows the currents flowing

    through SC/MOV, the impedance loci and the comparison re-

    sults between the new algorithm and traditional algorithm(8)

    for an ABC three-phase fault, which occurs at 150 km away

    from end M within the reach offirst-zone of the distance relay

    at both ends. As shown inFig. 7(a), in this test the SC/MOV is

    bypassed by GAP discharging in 2.5 ms after fault occurs. As

    shown inFig. 7(b)the calculated fault impedances with tradi-

    tional algorithm are nearly the same as the proposed algorithm.

    This is because the series capacitor in fault loop is bypassed by

    GAP. The proposed algorithm can always correctly calculate

    the fault impedance.

    Fig. 8 shows the currents flowing through SC/MOV, the

    impedance loci and the comparison results between the new

    algorithm and the traditional algorithm (8) when an ACG

    two-phase to ground solid fault occurs at 270 km away from

    end N. This point is beyond the reach offirst-zone of the dis-tance relay at end N. As shown inFig. 8(a), the series capacitor

    operates with MOV action during fault period, because the

    voltage across SC/MOV is too small to conduct MOV in deep

    nonlinear zone. As shown in Fig. 8(b) the calculated fault

    impedance with traditional algorithm is instable and inside

    the first-zone due to the series capacitors in fault loop. The

    proposed algorithm can correctly calculate the fault impedance.

    The error of the calculated fault reactance is derived by using

    (9)

    % (9)

    where is the actual fault reactance of the line. is the cal-

    culated fault reactance.

    To further verify the new algorithm, the comparisons between

    the new algorithm and the traditional algorithm are given under

    various typical fault conditions. Fig. 9shows the comparison

    results between the new algorithm and the traditional algorithm

    (8), when BCG solid grounded faults occur along the series ca-

    pacitor compensated transmission line with MOV conduction.

    The faults are simulated with (heavy load, source

    M leads source N) under different fault locations. As shown

    (6)

    (7)

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/12/2019 06612758

    5/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    XUet al.: AN INTERPHASE DISTANCE RELAYING ALGORITHM FOR SERIES-COMPENSATED TRANSMISSION LINES 5

    Fig. 6. SC/MOV/GAP waveform and estimated fault impedance under BCsolid fault at 240 km from bus M. (a) Current waveform through SC/MOV at

    end M. (b) Current and impedance loci measured at end M. (c) Current throughSC/GAP and impedance loci measured at end N.

    in Fig. 9, the errors of new algorithm are much smaller than

    Fig. 7. SC waveform and estimated fault impedance under ABC fault at 150km away from bus M. (a) Current waveform though SC/MOV/GAP and relay.

    (b) Fault impedance loci measured at end M and N.

    those of the traditional algorithm. The relay with the new algo-

    rithm can operate correctly under this condition; however, the

    http://-/?-http://-/?-
  • 8/12/2019 06612758

    6/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    6 IEEE TRANSACTIONS ON POWER DELIVERY

    Fig. 8. SC/MOV waveform and estimated fault impedance under CAG solid

    fault at 270 km from bus N. (a). Current waveform though SC/MOV. (b) Fault

    impedance loci measured at both ends.

    relay with the traditional algorithm may over-reach. As shown

    inFig. 9, the maximum error of the new algorithm is less than

    3.0%, while the traditional algorithms error reaches 80%. As

    shown inFigs. 6(b),8(b)the impedance loci of traditional al-

    gorithm is instable in early 0.6 s after the fault occurs due tothe impact of SC/MOV. For the proposed algorithm, the errors

    exist due to that the shunt capacitance of transmission lines is

    neglected, while the test used the distributed parameter model.

    V. REACH SETTINGS FORRESISTANCECOMPONENT

    As (1) concerning an interphase fault on a series-compen-

    sated transmission line, the measured fault resistance R is ex-

    pressed as follows.

    (10)

    According to the [5], the maximum equivalent resistance

    Rcmax equals 0.34Xco when MOV acts. Xco is the original

    capacitive reactance of series capacitance. If k is the series

    Fig. 9. Estimated fault reactance errors for BCG solid grounded fault with the

    condition of under different fault locations.

    compensation degree, we have . As for the solid

    interphase fault occurring at the end of the series-compensated

    line, following equations can be obtained.

    (11)

    (12)

    Here, is the increasing resistance due to the series com-

    pensation capacitor.

    According to the typical parameters of 500 kV line in the

    Appendix, is6.6 ohm. Substituting the parameters into(12)

    the increasing resistance can be expressed as

    (13)

    Even the series compensation degree is 70%, the increasing

    maximum resistance willbe 15.7 ohm. The increasing re-

    sistance of interphase distance relay should not be neglected for

    the reach settings of resistance component when MOV acts in

    practical engineering. However, the arc resistance of interphasefault is much smallerthan that of single-phase to ground faults

    and 20 ohm interphasearc resistance is the limitation value in

    practical engineering[17]. So that 50100 ohm is the suitable

    valuefor the reach settings of interphase distance relay. As to the

    other two cases theincreasing resistance is zero like singe phase

    to ground faults. The equivalent resistance shown in Fig. 4(e)

    demonstrates the correct analysis here.

    VI. SENSITIVITY ANALYSIS

    It is necessary to analyze the sensitivity of the proposed al-

    gorithm for the influential factors.

    A. Impact of Shunt Capacitance

    The proposed algorithm is derived based on neglecting the

    shunt capacitance of transmission lines. As shown in Figs.6to9,

    the simulation is carried out using distributed parameter line

    models. The maximum relative error is less than 3.0%. The re-

    sult shows the errors of proposed algorithm including the im-

    pact of shunt capacitance is less than 3.0% for the 500 kV typ-

    ical series-compensated transmission line, therefore the shunt

    capacitance impact on proposed algorithm can be neglected for

    practical applications.

    B. Impact of Fault Resistances and Load Currents

    It can be concluded that the accuracy of the new algorithm can

    be affected by the fault resistance and load current according to

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/12/2019 06612758

    7/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    XUet al.: AN INTERPHASE DISTANCE RELAYING ALGORITHM FOR SERIES-COMPENSATED TRANSMISSION LINES 7

    Fig. 10. Estimated fault reactance errors under CA faults with fault resistance

    030 at 150 km away from bus M.

    Fig. 11. Estimated fault reactance errors under BC solid faults at 80% away of

    series-compensated line length from bus M.

    the derived formulas(6)(7).Figs. 6 to 8 show the new algo-

    rithm functions perfectly for a solid interphase fault. In prac-

    tice the fault resistance for the two phases fault may be rela-

    tively smaller. A simulation is given under the extreme condi-

    tions of (heavy load) and fault resistance 030 for

    CA inter-phases fault. As shown in Fig. 10, the errors of the

    new algorithm are much smaller than those of the traditional

    algorithm.

    C. Impact of SIR (System Impedance Ratio)

    SIR reflects the ratio of the system equivalent impedance and

    the relay reach impedance. For a fault on a series-compensated

    transmission line, lower SIR means a larger fault current, which

    will cause different equivalent impedance and resistance

    . This section will illustrate the impact of SIR for the pro-

    posed algorithm. A series of solid interphase faults at 80% away

    from end M of the series-compensated transmission line under

    different SIRs are simulated. Errors of fault reactance for pro-

    posed algorithm are shown inFig. 11. Fig. 11 shows that the

    proposed algorithm performances soundly when a solid inter-

    phase fault occurs under different SIRs. The simulation is given

    under the extreme conditions of (the series ca-

    pacitor is included in the line impedance) and (heavy

    load). As shown inFig. 11, the maximum errors of the proposed

    algorithm is less than %, therefore the SIR impact on pro-

    posed algorithm is insignificant.

    D. Impact of Low Frequency Components

    The proposed algorithm is based on the power frequency

    components that satisfy the differential equation (1). In se-

    ries-compensated transmission system, sub-harmonic, low

    frequency, and sub-synchronous components may appear.

    For instance, the capacitance series oscillation with line re-

    actance may introduce low frequency transient component,

    the capacitance series oscillation with transformer reactance

    may introduce sub-harmonic component; and the capaci-

    tance series oscillation with turbine generator may introduce

    sub-synchronous component. The sub-harmonic, low frequency

    transient and sub-synchronous components including decayed

    d.c. component also satisfy the differential equation (1). It is

    still valid to solve the fault impedance with (6) and (7). Such

    kinds of low frequency components have no impact on the

    algorithm proposed in this paper. As explained in Section IV

    only a butterworth low-pass filter is needed to filter out the

    high-order harmonics.

    VII. CONCLUSION

    A new algorithm has been developed for the distance relay of

    interphase faults on series-compensated transmission lines. The

    algorithm can eliminate the effect of nonlinear characteristics of

    MOV and can satisfy all the operating states of series capacitordevices. The advantage of the proposed algorithm is that it does

    not requireany parametersof series capacitor device,and it is not

    necessary to know the operating state of SC/MOV/GAP during

    fault period. The overreach and under-reach of distance relaying

    caused by MOV conduction are eliminated. Another advantage

    of the algorithm is that its calculation is simple and non-iterative.

    Thestudy hasshown thatthe shunt capacitance does nothave any

    impact on proposed algorithm. Theother influential factors such

    as fault resistance, load level and SIR effect are also investigated

    in this paper. Numerical simulations are carried out on RTDS,

    showing that the accuracy and reliability of the new algorithm

    proposed in this paper are satisfactory.

    APPENDIX

    1) Parameters of 300 km, 500 kV Bergeron Model lines:

    Positive/negative sequence parameters

    Zero sequence parameters

    System parameters

    Source M parameters: 500 kV

    Source N parameters 500 kV

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
  • 8/12/2019 06612758

    8/8

    This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

    8 IEEE TRANSACTIONS ON POWER DELIVERY

    2) MOV parameters:

    -

    REFERENCES

    [1] M. Adamiak and R. Patterson, Protection requirements for flexibleAC transmission system, inProc. CIGRE, Paris, France, 1992.

    [2] F. Ghassemi, J. Goodarzi, and A. T. Johns, Method to improve digitaldistance relay impedance measurement when used in series compen-

    sated lines protected by a metal oxide varistor, in Proc. Inst. Elect.

    Eng., Gen. Transm. Distrib., Jul. 1998, vol. 145, no. 4, pp. 403508.

    [3] A. Girgis, A. Sallam, and A. K. Ei-Din, An adaptive protection

    scheme for advanced series compensated (ASC) transmission lines,

    IEEE Trans. Power Del., vol. 13, no. 2, pp. 414420, Apr. 1998.

    [4] M. M. Saha, B. Kasztenny, E. Rosolowski, and J. Izykowski, First

    zone algorithm for protection of series compensated lines, IEEE

    Trans. Power Del., vol. 16, no. 2, pp. 200207, Apr. 2001.[5] D. L. Goldsworthy, A linearized model for MOV-protected series ca-

    pacitors,IEEE Trans. Power Syst., vol. PWRS-2, no. 4, pp. 953958,

    Nov. 1987.

    [6] V. H. Makwana and B. R. Bhalja, A new digital relaying scheme

    for series-compensated double-circuit line during open conductor and

    ground fault, IEEE Trans. Power Del., vol. 27, no. 2, pp. 910917,

    Apr. 2012.[7] T. S. Sidhu and M. Khederzadeh, Series compensated line protection

    enhancement by modified pilot relaying scheme,IEEETrans. Power

    Del., vol. 21, no. 3, pp. 11911198, Jul. 2006.

    [8] P. Jena and A. K. Pradhan, A positive-sequence directional relaying

    algorithm for series compensated line,IEEE Trans. Power Del., vol.

    25, no. 4, pp. 22882297, Oct. 2010.

    [9] U. B. Parikh,B. Das,and R. P. Maheshwari, Combined wavelet-SVM

    technique for fault zone detection in a series compensated transmission

    line, IEEE Trans. Power Del., vol. 23, no. 4, pp. 17891794, Oct.

    2008.

    [10] A. I. Megahed, A. M. Moussa, and A. E. Bayoumy, Usage of wavelet

    transform in the protection of series-compensated transmission line,

    IEEE Trans. Power Del., vol. 21, no. 3, pp. 12131221, Jul. 2006.

    [11] Q. Y. Xuan, Y. H. Song, A. T. Johne, R. Morgan, and D. Willians,Performance of an adaptive protection scheme for series compensated

    EHV transmission system using neural networks, Elect. Power Syst.

    Res., vol. 36, no. 1, pp. 5766, Jan. 1966.

    [12] J. A. S. B. Jayasinghe, R. K. Aggarwal, A. T.Johns, and Z. Q. Bo, A

    novel non-unit protection for series compensated EHV transmission

    line based on fault generated high frequency voltage signals, IEEE

    Trans. Power Del., vol. 13, no. 1, pp. 405413, Jan. 1998.

    [13] McInnes and Morrison, Real time calculation of resistance and reac-

    tance for transmission line protection by digital computer,Inst. Elect.

    Eng. Trans. EE, vol. EE7, no. 1, pp. 1623, 1971.

    [14] M. S. Sachdev and M. A. Baribeau, A new algorithm for digitalimpedance relays,IEEE Trans. Power App. Syst., vol. PAS-8, no. 6,

    pp. 22322240, Nov. 1979.

    [15] Series Capacitor for Power SystemPart 2 Protective Equipment forSeries Capacitor Banks, IEC International Standard, 1994-07, IEC

    60143-2.[16] User Manual of SF-Auto. CSC101 Distance Protection,2011.

    [17] Z. Y. Xu, S. F. Huang, L. Ran, J. F. Liu, Q. X. Yang, and J. L. He,A distance relay for a 1000-kV UHV transmission line, IEEE Trans.

    Power Del., vol. 23, no. 4, pp. 17951804, Oct. 2008.

    Z. Y. Xu (M08SM10) was born in 1963. He received the Ph.D. degree in

    electrical engineering from North China Electric Power University, Beijing,

    China, in 1996.

    Currently, he is a Professor at North China Electric Power University. When

    he was with Sifang Automation Co. Ltd., he designed a series of extremely

    high voltage/ultra-high voltage transmission-line protection relays, which have

    been widely used on 220 kV1000 kV transmissio n lines in China. His research

    interests include power system protection and control.

    Z. P. Su was born in China in 1987. He received the M.Sc. degree in electrical

    engineering from North China Electrical University and is an Engineer with

    Wuhu Power Supply Company, Anhui Electric Power Company, Wuhu, China.

    His research interests include power system protection and control.

    J. H. Zhangwas born in China in 1983. He is currently pursuing the Ph.D. de-

    gree in electrical engineering at North China Electric Power University, Beijing,

    China.His research interests include power system protection and control.

    A. Wen was born in China in 1965. He received the Ph.D. degree in electrical

    and electronics engineering from the University of Manchester, Manchester.

    U.K., in 1992.Currently, he is a Senior Technical Specialist with China Southern Power

    Grid Co. Ltd., Guangzhou, China. His research interests include power system

    protection and control.

    Q. X. Yang was born in China in 1937.

    Currently, he is a Chinese academician of Engineering and a Professor at

    North China Electric Power University, Beijing, China. His research interests

    include power system protection and control, and substation automation.