Upload
walter-ge
View
219
Download
0
Embed Size (px)
Citation preview
7/27/2019 1000038
http://slidepdf.com/reader/full/1000038 1/7
Compressor suction drums
T his happens in petrochemical plants, ren-
eries and anywhere else where the gas
approaching a compressor is wet. Traces of
aqueous or organic liquid escape the inlet knock-
out drum, often intermittently, and silently
damage the compressor. Telltale signs include
pitting corrosion, salt deposits and diluted
lubricants.
Instead of trying to repair symptoms, look forthe root cause, which usually involves the mist
eliminator in the knockout drum (see Figures 1
and 2). Problems may include improper mist
eliminator specications, overloading, uneven
velocity proles, incorrect installation, high
liquid viscosity, waxy deposits, liquid slugs,
foaming and several other possibilities.
The trouble may even be that no mist elimina-
tor was provided in the rst place, or perhaps no
knockout drum at all. But wherever free liquid
drops out in a suction drum, it generates somemist that can damage the compressor unless it is
removed by a mist eliminator. Even in cases
where the feed gas never has any free liquid,
there are often ne mist droplets that coalesce
into large drops on the walls of the inlet pipe or
inside the compressor. For all but the driest gas,
a compressor should be protected by an inlet
mist eliminator. New high-capacity, high-
efciency mist eliminator technologies pay off
the rst time you avoid a shutdown.
For optimum separation performance,compressor knockout drums must be properly
designed and sized with appropriate mist elimi-
nator elements in correct congurations, taking
into account many factors. In multistage
compressor installations, the proper knockout
drum design is seldom the same for all stages.
To maintain good performance, the design of
each drum should be reviewed whenever there
are signicant changes in the process, such as
increases or decreases in throughput, shifts in
Amistco
composition of the gas or mist droplets, altera-
tions in upstream equipment, or revisions to
operating and control procedures. In addition,
mist eliminator elements should be visually
inspected occasionally (especially after major
process upsets) to make sure they are intact and
free of excessive solid deposits.
A thorough understanding of the relevant
considerations will help you avoid common
www.digitalrefining.com/article/1000038 May 2004 1
I think I have got liquid carryover. What can I do about it?
Figure 1 Typical compressor suction drums
Figure 2 Typical multistage compressor installation
7/27/2019 1000038
http://slidepdf.com/reader/full/1000038 2/7
suction-drum pitfalls and some not-so-commonones that could severely damage your compres-
sors due to liquid carryover. For detailed
explanations of mist eliminator selection, sizings
and vessel design for a wide range of applica-
tions, see Amistco’s literature such as Amistco
Mesh & Vane Mist Eliminators, Bulletin 106.
This paper provides information that applies
specically to compressor inlet knockout drums.
Designing for droplet size distribution
There are many different types of mist elimina-tor elements, and the variety has greatly
increased through the years. Not understanding
the liquid source in the upstream process can
cause you to select the wrong type of mist elimi-
nator, or to keep a given type when process
changes make it inappropriate.
Understanding the process allows you to
design for the most efcient mist collection.
Most important, selection should not be made
2 May 2004 www.digitalrefining.com/article/1000038
until the droplet size distribution is dened, in
terms of the proportion of droplets of each size.
Assuming an incorrect droplet size distribution
can mean that you have designed for a less ef-
cient mist eliminator and liquid carryover may
occur.
See Tables 1 and 2 for some points of refer-
ence and rough guidelines in this respect. Be
aware that the capture efciency of a given mist
eliminator element does not depend only ondroplet size. It is also inuenced by gas velocity
through the element and mist load in terms of
liquid ow rate per unit of cross-sectional area.
Then there are variables such as density and
viscosity that depend on temperature, pressure,
and liquid and gas composition. All else being
equal, efciency generally goes up with higher
velocity, ner mesh strands, closer packing of
mesh (greater density), closer spacing of vanes,
Figure 3 Typical multistage compressor installation
Figure 4 Typical multistage compressor installation
Tables 1 and 2
7/27/2019 1000038
http://slidepdf.com/reader/full/1000038 3/7
and greater thickness of the mist eliminator
element.
Mesh pad fouling In some cases, liquid carryover to the compres-
sor is caused by fouling of a mesh-type mist
eliminator, on account of the resulting restric-
tion to gas ow and extra holdup of liquid in
the pad. Vane-type mist eliminators are a better
choice for fouling applications. Due to the rela-
tively wide open spaces between blades, vanes
are much less likely to plug. If the fouling
deposit can be readily dissolved by a suitable
solvent, as might be the case with viscous oils
or waxes or certain caked solids, consider
installing a spray system, as shown in Figure 3,
to clean the vanes on-line whenever necessary.
Adding a high-efciency mesh mist eliminator
downstream of the vane unit (also shown
in Figure 3) can help make up for theinherently lower droplet capture efciency of
the vanes. Figure 5 Typical multistage compressor installation
Figure 6 Typical multistage compressor installation
www.digitalrefining.com/article/1000038 May 2004 3
7/27/2019 1000038
http://slidepdf.com/reader/full/1000038 4/7
6 illustrates guidelines for sufcient distance
between the mist eliminator and the gas inlet
and outlet.
If spacing is too close, the gas will pass though
only part of the mist eliminator. This causes
localised high velocities with liquid re-entrain-
ment and low velocities with poor efciency, as
shown in Figure 7.
In an existing conventional drum where the
mist eliminator is too close to the gas outlet,
there may not be enough room to lower the mist
eliminator. The solution then might be a prop-
erly designed ow distribution device located
above the mist eliminator to create a more
uniform velocity prole.
Overcoming pressure-drop constraintsProcesses that operate under vacuum or very low
pressure immediately upstream of the compres-
sor can be very tricky for suction drum design, because the pressure drop across the mist elimi-
nator must be kept low. However, generally
speaking, the lower the pressure-drop character-
istics of a mist eliminator type, the lower its
efciency in removing mist. Liquid carryover
from the suction drum may be a result of select-
ing a low-efciency mist eliminator for the sake
of low pressure drop.
When high efciency is not required, a vane
unit or low-density mesh pad (Amistco TM-1105)
may be recommended to achieve low pressuredrop. To gain higher efciency without much
cost in terms of pressure drop, a possible solu-
tion is a dual-density mesh pad. In such a pad,
the downstream layer has higher density than
the upstream layer. The result is higher separa-
tion efciency with only a slight increase in
pressure drop.
Throughput exceeding design capacity
In designing compressor knockout drums, like
other gas liquid separator vessels, conventionalmist eliminators are generally selected and sized
with a margin of about 10% above the design
throughput. Flow rates beyond the upper operat-
ing limit may allow liquid carryover due to high
velocities that cause re-entrainment from the
mist eliminator element.
More specically, mist eliminators are typically
sized for a cross-sectional area to achieve a
design velocity according to the Souders-Brown
vapour load factor K:
Liquid slugs and high liquid loading
In some applications, liquid slugs occasionally
come in with the gas feed. These surges can
temporarily overwhelm the slug-catching capa-
bility of the inlet knockout drum and ood a
mesh-type mist eliminator, causing liquid carry-over (see Figure 4).
When liquid slugs or generally high liquid
loading are expected, it is recommended to use a
vane-type mist eliminator upstream of the mesh
pad, as shown before in Figure 3. Vanes can
generally handle up to 10 times more liquid load
than mesh pads.
Breaking inlet foam
If liquid in the gas approaching the compressor
knockout drum is subject to foaming, it canreadily ood a mesh pad and, in severe cases,
even a vane unit. The end result is massive liquid
carryover from the vessel and damage to the
compressor. A vortex-tube cyclone device (see
Figure 5) can break up foam in the incoming
feed.
Dealing with high liquid viscosity
There are applications in which high viscosity
impedes liquid drainage so severely that a mesh
pad would ood at prohibitively low velocitiesand liquid loading. In these applications, a vane
unit is the better choice. For high efciencies,
consider Amistco’s double-pocket vanes, which
handle high-viscosity liquids with an efciency
of 99.9% for 8-micron and larger droplets.
Mist eliminator spacing in the vessel
An often overlooked but very important aspect
of suction drum design that can lead to liquid
carryover is proper spacing in the vessel. Figure
Figure 7 Typical multistage compressor installation
4 May 2004 www.digitalrefining.com/article/1000038
7/27/2019 1000038
http://slidepdf.com/reader/full/1000038 5/7
VG = Gas velocity (volume ow divided by
cross-section)
PL = Liquid density
PG = Gas density
Conventional horizontal mesh pads are tradi-
tionally sized for a K factor of 0.35 ft per second,
which corresponds to a velocity of 10 ft per
second in the reference case of water and air at
room conditions. When a knockout drum’s throughput has
grown to exceed its capacity, there are generally
two options:
• Replace the vessel with a larger one to allow a
mist eliminator with greater cross-sectional area,
thus reducing the velocity
• Replace the mist eliminator in the existing
vessel with one using the latest technology to
maintain efciency with higher throughput.
Option 2 is generally much more cost-effective
and often does not require prohibitive downtime.In a traditional vertical cylindrical vessel, the
traditional horizontal orientation is no longer the
only solution. Compressor knockout drums can
be retrotted for capacity increases using any of
the following techniques:
• Vertical mist eliminator elements with hori-
zontal ow (K= 0.42 for mesh pads, K = 0.65 for
vane units)
• Properly engineered bafing for even velocity
proles with close spacing
• Horizontal mesh pads with drainage layers or
multiple zones that can increase capacity by 10-
12% (K = 0.40)• Amistco double-pocket vanes that can double
the capacity of a conventional vane unit (K =
0.8–1.1)
• Mesh-vane combinations that can increase
efciency and capacity by 10–25% (K =
0.5–0.65)
• Mesh agglomerator followed by double-pocket
vanes for highest efciency (99.9% of 2-micron
droplets) and greatest capacity increase
• Two- or four-bank congurations that allow
Figure 8 Typical multistage compressor installation
Figure 9 Typical multistage compressor installation
Figure 10 Typical multistage compressor installation
www.digitalrefining.com/article/1000038 May 2004 5
7/27/2019 1000038
http://slidepdf.com/reader/full/1000038 6/7
mist eliminator elements of greater cross-
sectional areas.
Figure 8 illustrates several of these possibilities:
horizontal ow through vertical mist eliminator
elements, use of mesh pads to agglomerate ne
mist into large droplets that are removed by vaneunits, and a double-bank conguration. Amistco’s
design specialists can help apply such advanced
means of optimising the efciency and capacity of
existing knockout drums to create optimal solu-
tions for particular applications.
Retrofit without recertifying for ASME codeRetrotting an existing vessel for any of the fore-
going suggested remedies has one drawback: it
often requires the welding of new support rings,
beams, clips and other structures to the vessel wall. Most vessels are ASME code certied. Thus,
after welding to the vessel wall, the welded area
must be heat-treated, and the vessel must be
recertied. It is generally desirable to avoid this
cumbersome procedure. Amistco offers expan-
sion rings that are made in sections that can be
passed through a manway (see Figure 9).
The rings are then bolted together and wedged
against the vessel wall without welding. The
unique double expansion design ensures that the
installed ring does not move during operation.
Once the rings are installed either in vertical or
horizontal vessels, beams can be bolted to the
rings and complete housings can be built up
inside the vessel.
Using inlet diffusers to relieve carryover
Inlet design is one of the most commonly
neglected aspects of a compressor knockout
drum design, thus often the cause of poorperformance. In the example shown in Figure
10, a half-pipe inlet deector projecting into the
vessel reduces the gas ow area of that position,
with the following results:
• Gas jets to the back wall of the vessel
• Without enough space to diffuse the jet, gas
utilises only part of the mist eliminator. Due to
an uneven velocity prole, liquid carryover
occurs, as in Figure 7
• The gas jet agitates the accumulated liquid
below, generating droplets• Turbulence spoils normal gravity settling of
larger liquid droplets below the mist eliminator.
Additional liquid load increases the likelihood of
ooding the mist eliminator.
A properly selected inlet diffuser added to an
existing knockout drum (see Figure 11) provides
more effective separation of liquid coming in
with the gas and distributes the gas evenly
throughout the vessel diameter before the gas
moves upwards.
Figure 11 Typical multistage compressor installation
Figure 12 Typical multistage compressor installation
6 May 2004 www.digitalrefining.com/article/1000038
7/27/2019 1000038
http://slidepdf.com/reader/full/1000038 7/7
Damage by sudden pressure changes
Carefully review the transient pressures that
occur at the knockout drum and mist eliminator
during all phases of operations. The suction
drum could see a sudden surge of ow in either
direction due to compressor recycle or opening
an anti-surge valve.
Pads and vanes can also be damaged by freez-
ing liquids in cold climates. In natural gas
production and pipelining, hydrate formation is
known to destroy mesh pads and vanes.
To cope with any of these scenarios, as shown
in Figure 12, any or all of the following remedies
can be applied to mist eliminator elements:
• Reinforce with heavy-duty material
• Fasten with bolts instead of traditional tie
wires, or provide an upper support ring in addi-
tion to the lower one
• Provide a pressure relief door in the case of
mesh.
Compressor knockout drum casesEthylene plant debottleneck
A large ethylene producer needed to debottle-
neck its six-stage compressor train to increase
throughout. This project needed to be accom-
plished with minimal cost and downtime.
Using conventional mist eliminators mesh
pads or horizontal ow vanes, the knockout
drum before each compressor stage would have
to be enlarged. For instance, the drum at theinlet to the rst stage, 8 ft in diameter, would be
replaced by a 14 ft vessel.
Amistco thoroughly reviewed the process
conditions and internal geometry of each knock-
out drum. We then customised each existing
drum with double-pocket vanes and mesh
agglomerators, arranged as in Figure 8, using
one, two or four banks, as required. To ensure
proper gas distribution, we added inlet diffusers
as in Figure 11 and ow distribution plates on
the downstream side of the vane units. The result was 35% increased capacity, while achieving an
efciency of 99.9% of 1-micron and larger mist
droplets.
Fertilizer plant capacity boost and amine loss cut
A four-train fertilizer plant needed more ammo-
nia gas processing capacity in one of the trains to
increase production capacity. The bottleneck was
the overhead knockout drum in two of four
carbon dioxide absorber towers in that train.
Those vessels also served as suction drums for the
compressors that followed. In addition, it was
desired to reduce excessive loss of valuable amine
in the form of mist escaping the knockout drums.
Amistco reviewed the absorber process condi-
tions and the available space in the knockout
drums. Although the space in one of the drums
was very tight, we were able to solve this problem
by retrotting both drums with a double-bank
system, as in Figure 8. In each bank, a mesh
agglomerator is followed by an double-pocket
vane unit. The result was a 30% capacity increase.
In addition, the rate of amine loss fell to 0.05
gallon per million standard cubic feet, which
corresponds to savings on the order of $75 000
per year. Another benet was elimination of a
cause of pitting corrosion in the compressors.
Gas production and condensate recovery increase
A large oil and gas company wanted to revampseveral dozen of its 30-year-old two-phase eld
separators (sizes 2–5 ft OD). The purpose was to
increase capacity and improve recovery of
condensate. As in the preceding case, the separa-
tors were also suction drums for compressors.
Joining with a local fabrication shop, Amistco
brought the separators from the eld, removed
the old internals, enlarged the inlet and outlet
nozzles, and retrotted the vessels with Amistco
double-pocket vane units. The separators were
ASME code recertied, painted and reinstalledin the eld with new instrumentation. This reju-
venation saved the company thousands of dollars
per unit as compared to purchasing new separa-
tors. Gas capacity increased by up to 50%, and
condensate recovery went up by many thousands
of barrels per year.
These cases are typical of many applications
where Amistco’s separation technology made a
big difference. Similar results can be achieved
for a wide variety of compressor knockout drums
in reneries, gas plants, oil and gas explorationand production, and petrochemical plants.
www.digitalrefining.com/article/1000038 May 2004 7
Links
More artcle from: ACs-AMisTCO ic
More artcle from the followg categore:
Ma Trafer & separato Alterate Fuel
Petrochemcal Preure Drop Cotrol
Revamp, shutdow ad Turaroud LnG/GTL