MAXIMIZING PERFORMANCE, ENERGY SAVINGS & COMFORT 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 to 2000 CFM) 42DF 42DE 42CG 42DC 42CE Turn to the Experts

42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

Embed Size (px)

Citation preview

Page 1: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

MAXIMIZING PERFORMANCE, ENERGY SAVINGS & COMFORT

42C/D SERIES

Ducted Chilled Water Fan Coil UnitWith District Cooling Application(200 to 2000 CFM)

42DF

42DE

42CG

42DC

42CE

Turn to the Experts

Page 2: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

2

MODEL NUMBER NOMENCLATURE

TABLE OF CONTENTSPage

Model Number Nomenclature……………………………………………………………………………………..……... 2 ‐ 3Product Features………………………………………………………………………………………………………………………. 4Technical Data………………………………………………………………………………………………………………….…. 5 – 9Unit Dimension and Weight……………………………………………………………………………………………...10 – 14Performance Rating…………………………………………………………………………………………………………..15 – 17Electrical Data………………………………………………………………………………………………………………………… 18Wiring Diagram……………………………………………………………………………………………………………………….. 19Guide Specifications………………………………………………………………………………………………………………… 20

COMPUTER SELECTION

We  have made  available  a  computer  program  to  finalize  your  selections.  Please contact your Carrier representative for a computer selection based on your “Quick Selection” plus the design parameters of your application.

4 2 C E T 0 0 3 4 ‐ ‐ 7 0 1 2 5

42 series CISB CodeFan Coil Unit 25

Model Packing method

CET 1

DC‐CED ∆T District Development Series

DCD Cooling 0  :  42CET / 42CED3  :  42DC / 42DCD

Model No.

42CET & CED 42DC & DCD Electrical Characteristic

003 010 7  ‐  220/240V‐1PH‐50Hz004 012005 014006 016008 018010 020

012 3  :  3 row coil (42CET)014 4  :  4 row coil (42CET, CED, DC, DCD)

Std

R  :  Right Handling‐   :  Left Handling

Not used

Page 3: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

3

MODEL NUMBER NOMENCLATURE (cont’)

4 2 D E ‐ 0 6 ‐ 4 R L 7 2 1 2 5

42 series CISB CodeFan Coil Unit 25

Packing methodModel 1

CG‐DE‐DF‐ Development Series

2  :  42CG, DE/DFModel No.

42CG 42DE/DF Electrical Characteristic

02 06 7  ‐  220/240V‐1PH‐50Hz03 0804 1006 12

08 14 4  :  4 row coil (42CG, 42DE, DF)10 16 6  :  6 row coil (42DE, 42DF)12 18

20 ‐ : Not used

RR  :  Right HandlingRL   :  Left Handling

Page 4: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

4

PRODUCT FEATURES

If fan coil terminals are the answer to your job requirements, you can’t afford to passover Carrier’s versatile and extensive range of fan coil units.

With Carrier’s 42 series  fan coil units, you can select  furred‐in or cabinet  style,  in capacities  from 200  to 2,000  cfm.   Units  are  ideal  for  installations  in  residential,  hotels, motels,  apartments,  offices,  hospitals, schools and other multi‐room buildings.

Carrier  room  fan coil  terminals provide unsurpassed year  round comfort, with high cooling performance.  Carrier  42  series  terminal  requires  very  little  space  and  is  easy  to  install.    Piping,  drain  and  wiring connections are readily accessible to save installation time and field labor expense.

Forget about expensive ductwork, forget about complex system controls, forget the aggravation and choose Carrier’s easy  to  install  room  fan coil units – in pipe  systems.   Opt  for quiet.   Carrier  room  fan coil units operate at exceptionally  low  sound  levels.   Generous amount of  insulation absorbs operating  sound and rugged, rigid construction ensures vibration free operation at all fan speeds.

Carrier room fan coil units are economical.  Three speed fans deliver just the right amount of conditioned air for your comfort needs at any load.  And each individual unit can be shut off when not in use.  Shaded‐pole motors deliver peak operating efficiency.   In choosing Carrier units, you can match your application with a wide range of custom‐designed options and accessories.

When you go for Carrier 42 series, the advantages to owner, installer and the room occupants are too great to ignore.

Carrier 42 series fan coils give you design and equipment location flexibility• Wide range of popular capacities, 200 – 2000 cfm• Available up to 8 sizes.• Cabinet or furred‐in units• Choose from numerous control systems• Select 3 row coils (42CE), 4 row coils (42CE & DC) and 6 row coils (42DE & DF)

• Accommodates 2 pipe systems• Fully insulated/low fan speed means quiet operation• Draw outside air for odor dilution• Uses only minimal space

Select Carrier fan coils for easy, low cost installation• Easy wiring, piping connections• Mounting holes, slots speed hanging• Requires no expensive ductwork• Ideal for new construction or renovation

Save operating costs with Carrier fan coils• Individual unit shut‐off when not in use• Efficient, 3 speed centrifugal fans• Shaded pole motors• High efficiency heat transfer surface

Carrier fan coils save you service and maintenance expense• Nationwide Carrier service• Insulated drain pan• Easy access to components• Rugged construction• Factory leak test for coil• Cleanable filters• Long life, heavy duty bearings

tekchand
Highlight
tekchand
Highlight
tekchand
Highlight
tekchand
Highlight
Page 5: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

5

TECHNICAL DATA

42CET Furred‐in Ceiling FCU with Plenum3 Rows at nominal CFM

MODEL:  42CETPERFORMANCE

49.942.837.734.125.523.221.918.8KgNet Weight

¾” MPTCondensate Drain

¾” FPTIn‐OutConnections

1.72MPaWorking Pressure

3RowCoil

Permanent Split CapacitorMotor Type

Centrifugal Forward‐curved bladesFan Type

23.714.931.923.623.814.811.922.5kPaWater Drop

0.4710.3830.3310.2870.2060.1630.1500.120L/sWater Flow

40.140.839.836.237.836.134.733.4Low

41.742.741.539.340.036.738.236.0Med

44.943.743.941.841.241.340.039.0

dB(A)

High

Noise *

2.041.301.101.020.650.550.440.37AmpMotor nominal current

78w x 375w x 268w x 258w x 275684835WMotor nominal power output

373613036726307227921634312966118749519Btu/hr

10.958.907.716.684.793.803.482.79kWCooling Capacity (Fluid)*

661566472378283236189142L/s

140012001000800600500400300CFMHigh

Nominal 

Air Volume

014012010008006005004003

NOTE:* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air 

temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.** Sound measurement in accordance with Standard JIS8616‐2006 (1.5m below the unit bottom).

Performance AssuranceRated in accordance withARI Standard 440‐1998(50Hz only)

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 6: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

6

TECHNICAL DATA (cont’)

42CET Furred‐in Ceiling FCU with Plenum4 Rows at nominal CFM

MODEL:  42CETPERFORMANCE

52.445.139.735.926.524.523.119.9KgNet Weight

¾” MPTCondensate Drain

¾” FPTIn‐OutConnections

1.72 MPaWorking Pressure

4RowCoil

Permanent Split CapacitorMotor Type

Centrifugal Forward‐curved bladesFan Type

37.323.825.317.97.422.218.19.8kPaWater Drop

0.5510.4540.3650.3120.2090.1830.1680.124L/sWater Flow

40.140.839.836.237.836.134.733.4Low

41.742.741.539.340.036.738.236.0Med

44.943.743.941.841.241.340.039.0

dB(A)

High

Noise *

2.041.301.101.020.650.550.440.37AmpMotor nominal current

78w x 375w x 268w x 258w x 275684835WMotor nominal power output

437083596228797247371661614603134779792Btu/hr

12.8110.548.447.254.874.283.952.87kWCooling Capacity (Fluid)*

661566472378283236189142L/s

140012001000800600500400300CFMHigh

Nominal

Air Volume

014012010008006005004003

NOTE:* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air 

temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.** Sound measurement in accordance with Standard JIS8616‐2006 (1.5m below the unit bottom).

Performance AssuranceRated in accordance withARI Standard 440‐1998(50Hz only)

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 7: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

7

TECHNICAL DATA (cont’)

42CED Furred‐in Ceiling FCU with Plenum (District Cooling Application)4 Rows at nominal CFM

MODEL:  42CEDPERFORMANCE

52.445.139.735.926.524.523.119.9KgNet Weight

¾” MPTCondensate Drain

¾” FPTIn‐OutConnections

1.72MPaWorking Pressure

4RowCoil

Permanent Split CapacitorMotor Type

Centrifugal Forward‐curved bladesFan Type

15.223.313.520.27.722.718.58.8kPaWater Drop

0.2450.2330.1750.1510.0970.0950.0860.060L/sWater Flow

40.140.839.836.237.836.134.733.4Low

41.742.741.539.340.036.738.236.0Med

44.943.743.941.841.241.340.039.0

dB(A)

High

Noise *

2.041.301.101.020.650.550.440.37AmpMotor nominal current

78w x 375w x 268w x 258w x 275684835WMotor nominal power output

310492821722178192101231712044109877609Btu/hr

9.108.276.505.633.613.533.222.23kWCooling Capacity (Fluid)*

661566472378283236189142L/s

140012001000800600500400300CFMHigh

Nominal

Air Volume

014012010008006005004003

NOTE:* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air 

temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.** Sound measurement in accordance with Standard JIS8616‐2006 (1.5m below the unit bottom).

Performance AssuranceRated in accordance withARI Standard 440‐1998(50Hz only)

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 8: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

8

TECHNICAL DATA (cont’)

42DC Furred‐in Ceiling FCU with Plenum4 Rows at nominal CFM

1 1/8”1 1/8”1 1/8”1 1/8”7/8”7/8”In‐Out (Sweat conn.)Connections

7/8”Condensate Drain

MODEL:  42DCPERFORMANCE

1008881797666KgNet Weight

1.72 MPaWorking Pressure

4RowCoil

Permanent Split CapacitorMotor Type

Centrifugal Forward‐curved bladesFan Type

30.825.250.529.841.523.8kPaWater Drop

0.80.80.80.60.50.4L/sWater Flow

45.245.347.641.042.440.6Low

49.449.552.844.844.545.5Med

52.151.854.347.647.647.6

dB(A)

High

Noise *

2.39x22.39x22.39x21.15x21.15x22.39AmpMotor nominal current

200x2200x2200x2120x2120x2200WMotor nominal power output

661966107760054467464196931733Btu/hr

19.417.917.613.712.39.3kWCooling Capacity (Fluid)*

943852755661566472L/s

200018001600140012001000CFMHigh

Nominal

Air Volume

020018016014012010

NOTE:* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air 

temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.** Sound measurement in accordance with Standard JIS8616‐2006 (1.5m below the unit bottom).

Performance AssuranceRated in accordance withARI Standard 440‐1998(50Hz only)

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 9: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

9

TECHNICAL DATA (cont’)

42DCD Furred‐in Ceiling FCU with Plenum (District Cooling Application)4 Rows at nominal CFM

1 1/8”1 1/8”1 1/8”1 1/8”7/8”7/8”In‐Out (Sweat conn.)Connections

7/8”Condensate Drain

MODEL:  42DCDPERFORMANCE

1008881797666KgNet Weight

1.72 MPaWorking Pressure

4RowCoil

Permanent Split CapacitorMotor Type

Centrifugal Forward‐curved bladesFan Type

30.825.250.529.841.523.8kPaWater Drop

0.80.80.80.60.50.4L/sWater Flow

45.245.347.641.042.440.6Low

49.449.552.844.844.545.5Med

52.151.854.347.647.647.6

dB(A)

High

Noise *

2.39x22.39x22.39x21.15x21.15x22.39AmpMotor nominal current

200x2200x2200x2120x2120x2200WMotor nominal power output

661966107760054467464196931733Btu/hr

19.417.917.613.712.39.3kWCooling Capacity (Fluid)*

943852755661566472L/s

200018001600140012001000CFMHigh

Nominal

Air Volume

020018016014012010

NOTE:* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air 

temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.** Sound measurement in accordance with Standard JIS8616‐2006 (1.5m below the unit bottom).

Performance AssuranceRated in accordance withARI Standard 440‐1998(50Hz only)

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 10: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

10

UNIT DIMENSIONS AND WEIGHT

42CET/CED Furred‐in Ceiling FCU with Plenum

52.449.9184020101876014

45.142.8160017701636012

39.737.7136015301396010

35.934.1124014101276008

26.525.59201090956006

24.523.2800970836005

23.121.9720890756004

19.918.8600770636003

4 Rows3 RowsCBA

WEIGHT (kg)DIMENSIONS (mm)MODEL42CET/CED

Page 11: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

11

UNIT DIMENSIONS AND WEIGHT (cont’)

42CG Furred‐in Ceiling FCU with Plenum

11130517115715462681546208312

9730517116713242781324188010

80305171155991267991152408

76305171122879233879134606

57279146114768281657121904

5427914694657260546106703

442791469854626543596502

GFEDCBAWEIGHT (kg)

DIMENSIONS (mm)UNIT SIZE42CG

Page 12: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

12

UNIT DIMENSIONS AND WEIGHT (cont’)

42DC/DCD Furred‐in ceiling FCU with Plenum

100147913721270121911941422020

88137812701168117810921321018

811251114310419919651194016

79112410169148648381067014

76997889787737711940012

68870762660610584813010

FEDCBAWEIGHT (kg)

DIMENSION (mm)UNIT SIZE

42DC/DCD

Page 13: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

13

UNIT DIMENSIONS AND WEIGHT (cont’)

42DE Furred‐in ceiling FCU with Plenum

110203121912192031219162620

105203111811182031118152418

98203991991203991139716

90203837837203837127014

83203737737203737114312

75203610610203610101610

7020350850820350891408

6120338138120338178706

FEDCBAWEIGHT (kg)

DIMENSIONS (mm)UNIT SIZE42DE

Page 14: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

14

UNIT DIMENSIONS AND WEIGHT (cont’)

42DF Furred‐in ceiling FCU with Plenum

117203121912192221181162620

113203111811182221078152418

104216991991222953139716

98203864864222826127014

90216737737222699114312

80203610610222572101610

7620350850822247091408

7121635638122234378706

FEDCBAWEIGHT (kg)

DIMENSIONS (mm)UNIT SIZE

42DF

Page 15: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

15

PERFORMANCE RATING

42CET (3‐ROWS)

42CET (4‐ROWS)

10.40.13512.914.12.363.13150Medium14.80.16313.514.92.943.80199

50High

005

4.80.08812.413.31.532.0591Low8.30.12013.314.52.182.83142Medium11.90.15013.915.42.773.48194

50High

004

9.80.07011.812.71.251.7372Low16.30.10012.713.81.742.33108Medium22.50.12013.314.62.142.79141

50High

003

31.90.33113.615.25.897.7140850

High

010

11.00.18912.413.53.224.39194Low19.00.25513.214.64.485.94295Medium23.60.28713.615.15.146.68352

50High

008

13.70.15012.613.82.573.48159Low18.90.18113.114.53.184.22208Medium23.80.20613.515.03.684.79251

50High

006

6.00.09912.213.11.702.30100Low

13.60.34013.014.35.977.99385Low17.20.39113.314.86.919.10464Medium23.70.47113.915.68.5310.95610

50High

014

9.30.29213.214.55.156.79336Low12.30.34213.615.16.147.95422Medium14.90.38313.915.66.998.90500

50High

012

15.20.22012.513.73.745.11230Low22.10.27013.014.44.666.27302Medium

WBDBSensibleTotal

Water Pressure

(kPa)

Water Flow

(L/s)

Air off FCU

(°C)

Capacity

(kW)Air Flow

(L/s)

ESP

PaSpeed

Model

42CET

16.4400.07910.811.42.182.92143Medium22.7170.09511.412.22.693.53188

50High

005

7.2930.05110.410.81.411.9188Low12.7040.07111.211.81.992.62135Medium18.5320.08611.8312.72.523.22183

50High

004

2.5110.03710.911.21.071.3969Low6.5460.05011.612.21.471.87103Medium8.7880.06012.112.91.802.23133

50High

003

13.4510.17512.113.05.166.5038550

High

010

9.7440.10011.011.82.763.73187Low16.6490.13511.712.73.835.03281Medium20.1760.15112.013.24.365.63332

50High

008

4.4840.07111.912.72.092.64153Low6.1870.08612.313.32.563.19198Medium7.7420.09712.613.72.953.61237

50High

006

9.2960.05810.110.51.572.1596Low

8.6680.18011.712.65.126.69370Low10.8500.20412.013.05.897.59442Medium15.2140.24512.413.67.239.10576

50High

014

14.5570.17111.111.84.786.35323Low18.7710.19911.512.45.687.41402Medium23.2850.22311.812.86.438.27472

50High

012

6.7250.11711.111.73.314.34221Low9.5650.14311.512.24.115.31287Medium

WBDBSensibleTotal

Water Pressure

(kPa)

Water Flow

(L/s)

Air off FCU

(°C)

Capacity

(kW)Air Flow

(L/s)

ESP

(Pa)Speed

Model

42CET

NOTE: Air Conditions: EDB/EWB  27/19°C Water Conditions: EWT/LWT  7.2/12.8˚C ∆T: 5.6˚C

NOTE: Air Conditions: EDB/EWB  27/19°C Water Conditions: EWT/LWT  7.2/12.8˚C ∆T: 5.6˚C

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 16: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

16

PERFORMANCE RATING (cont’)

16.4400.07910.811.42.182.92143Medium

22.7170.09511.412.22.693.53188

50

High

005

7.2930.05110.410.81.411.9188Low

12.7040.07111.211.81.992.62135Medium

18.5320.08611.8312.72.523.22183

50

High

004

2.5110.03710.911.21.071.3969Low

6.5460.05011.612.21.471.87103Medium

8.7880.06012.112.91.802.23133

50

High

003

13.4510.17512.113.05.166.5385

50

High

010

9.7440.10011.011.82.763.73187Low

16.6490.13511.712.73.835.03281Medium

20.1760.15112.013.24.365.63332

50

High

008

4.4840.07111.912.72.092.64153Low

6.1870.08612.313.32.563.19198Medium

7.7420.09712.613.72.953.61237

50

High

006

9.2960.05810.110.51.572.1596Low

8.6680.18011.712.65.126.69370Low

10.8500.20412.013.05.897.59442Medium

15.2140.24512.413.67.239.10576

50

High

014

14.5570.17111.111.84.786.35323Low

18.7710.19911.512.45.687.41402Medium

23.2850.22311.812.86.438.27472

50

High

012

6.7250.11711.111.73.314.34221Low

9.5650.14311.512.24.115.31287Medium

WBDBSensibleTotal

Water Pressure

(kPa)

Water Flow

(L/s)

Air off FCU

(°C)

Capacity

(kW)Air Flow

(L/s)

ESP

PaSpeed

Model

42CED

42CED (4‐ROWS) – District Cooling Application

NOTE: Air Conditions: EDB/EWB  23.9/17.2°C Water Conditions:  EWT/LWT 5.5/14.4˚C ∆T: 8.9˚C

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 17: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

17

PERFORMANCE RATING (cont’)

42DC (4‐ROWS)

42DCD (4‐ROWS) – District Cooling Applications

NOTE: Air Conditions: EDB/EWB  27/19°C Water Conditions: EWT/LWT  7.2/12.8˚C ∆T: 5.6˚C

NOTE: Air Conditions: EDB/EWB  23.9/17.2°C Water Conditions: EWT/LWT  5.5/14.4˚C ∆T: 8.9˚C

22.7770.50612.513.58.811.8531Medium

29.7710.58913.114.210.513.7671

50

High

014

21.8800.36611.912.66.28.5352Low

32.9990.46412.713.78.110.8500Medium

41.4580.52913.214.49.512.3613

50

High

012

12.3750.28112.012.84.86.5277Low

19.8770.36212.913.96.48.4401Medium

23.7630.40213.314.47.39.3470

50

High

010

30.8470.83613.114.214.919.4947

50

High

020

14.4070.56412.112.99.713.1563Low

20.9830.69812.913.912.416.2772Medium

25.1680.77213.314.413.917.9901

50

High

018

28.7850.55812.213.19.613.0560Low

42.3550.68813.014.012.216.0767Medium

50.4850.75813.314.613.617.6894

50

High

016

15.3940.40911.812.56.99.5392Low

17.0380.59811.812.610.113.9575Low

24.7790.74312.613.613.017.3790Medium

WBDBSensibleTotal

Water Pressure

(kPa)

Water Flow

(L/s)

Air off FCU

(°C)

Capacity

(kW)Air Flow

(L/s)

ESP

PaSpeed

Model

42DC

17.7550.23612.213.07.18.8531Medium

23.3750.27512.613.68.410.2671

50

High

014

8.2800.16012.012.74.86.0352Low

12.5240.20312.713.66.37.6500Medium

16.0210.23213.014.17.38.6613

50

High

012

24.6600.14111.312.04.05.3277Low

39.2470.18212.013.05.46.8422Medium

46.9580.20312.413.46.17.5470

50

High

010

34.7030.40812.313.412.215.2947

50

High

020

28.6950.28411.412.28.110.6563Low

41.8170.35212.013.010.313.1772Medium

49.7380.38912.313.411.614.5901

50

High

018

23.9430.26811.812.67.79.9559Low

34.5840.33012.413.49.912.3767Medium

41.1600.36312.713.811.013.5894

50

High

016

12.1360.19111.612.35.67.1391Low

18.9510.29111.412.18.310.8575Low

28.1870.36212.012.910.613.5790Medium

WBDBSensibleTotal

Water Pressure

(kPa)

Water Flow

(L/s)

Air off FCU

(°C)

Capacity

(kW)Air Flow

(L/s)

ESP

PaSpeed

Model

42DCD

‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐

Page 18: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

18

ELECTRICAL DATA

NOTE:1.) Total motor amps and watts shown for units with 2 motors (size 10 and 12)2.) Motor name plate amps may vary.

42CG MOTOR DATA

NOTE:1.) Total motor amps and watts shown for units with 2 motors (size 12 to 20)2.) Motor name plate amps may vary.

220/240‐1‐50V‐Ph‐HzPower Supply

1.551.180.800.690.560.420.42AmpMotor nominal current

2802481521501188787WattsMotor nominal power output

56647237828318914294ℓ/s12001000800600400300200CFMHighNominal Air Volume

12100806040302

MODEL: 42CGPERFORMANCE

4.504.504.352.402.202.401.501.23AmpMotor nominal current

950960920490445500295250WattsMotor nominal power output

220/240‐1‐50V‐Ph‐HzPower Supply

943850755661566472378283ℓ/s200018001600140012001000800600CFMHighNominal Air Volume

2018161412100806

MODEL: 42DE, DFPERFORMANCE

42DE, DF MOTOR DATA

220/240‐1‐50V‐Ph‐HzPower Supply

MODEL:  42CED/CETPERFORMANCE

2.041.301.101.020.650.550.440.37AmpMotor nominal current

78w x 375w x 268w x 258w x 275684835WMotor nominal power output

661566472378283236189142L/s

140012001000800600500400300CFMHigh

Nominal Air Volume

014012010008006005004003

42CED/CET MOTOR DATA

220/240‐1‐50V‐Ph‐HzPower Supply

MODEL:  42DC/DCDPERFORMANCE

2.39x22.39x22.39x21.15x21.15x22.39AmpMotor nominal current

200x2200x2200x2120x2120x2200WMotor nominal power output

943852755661566472L/s

200018001600140012001000CFMHigh

Nominal

Air Volume

020018016014012010

42DC/DCD MOTOR DATA

NOTE:  Motor name plate amps may vary.

NOTE:  Motor name plate amps may vary.

Page 19: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

19

WIRING DIAGRAM

42CET/CED Wiring Diagram

42DC/DCD Wiring Diagram

NOTE: 1. CAUTION – DISCONNECT POWER BEFORE SERVICING.2. USE 14 AWG, 75˚C MIN, COPPER CONDUCTOR.3. MOTOR(S) THERMALLY PROTECTED.4. PROVIDE DISCONNECT MEANS & OVERCURRENT PROTECTION AS REQUIRED.5. 002 TO 006 ARE SINGLE MOTOR; 008 TO 012 ARE DOUBLE MOTORS & 014 IS THREE FAN MOTORS.6. SNAP APART CAREFULLY AT HINGLE TO SEPARATE COVER FROM THE CONTROL BOX.

NOTE: 1. CAUTION – DISCONNECT POWER BEFORE SERVICING.2. USE 14 AWG, 75˚C MIN, COPPER CONDUCTOR.3. MOTOR(S) THERMALLY PROTECTED.4. PROVIDE DISCONNECT MEANS & OVERCURRENT PROTECTION AS REQUIRED.5. UNIT 42DC012 AND ABOVE HAVE 2 FAN MOTORS.

Page 20: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

20

GUIDE SPECIFICATIONS

HVAC Guide SpecificationsSize range: 200 to 1400 Nominal Cfm

Part 1 – GENERAL

1.1 System DescriptionHorizontal,  room  fan  coil  unit  with  furred‐in, above  ceiling  for  ducting,  or with  cabinet  for exposed ceiling installations.

1.2 Quality AssuranceUnit  shall  be  tested  in  accordance  with  ARI Standard 440.   Each coil shall be factory tested for  leakage  at  400  psig  air  pressure with  coil submerge  in  water,  insulation  and  adhesive shall meet  NFPA‐90A  requirements  for  flame spread  and  smoke  generation.   All  equipment wiring shall comply with NEC requirements.Factory is ISO‐9001 certified.

1.3 Delivery storage and handlingEach  unit  shall  be  individually  packaged  from point  of manufacture.    Unit  shall  be  handled and  stored  in  accordance  with  the manufacturer’s instructions.

Part 2 ‐ PRODUCTS

Equipment2.1 General

Factory  assembled,  horizontal,  blow‐thru  type fan coil for furred‐in, exposed ceiling or ducted installations.  Unit shall be complete with water coil(s), fan(s), motor(s), drain pan, filters and all required wiring, collars for ducted units.

2.2 42CET, CED Furred‐in UnitsBase  42CET,  CED  unit  with  factory  installed plenum  section  and  cleanable  filter  as  shown on equipment drawings.   The plenum  shall be  rear  air  return.    Shall  enclose  the  fan/motor assemblies,  and  shall  be  lined  with  PU insulation  18kg/m³ density.   Unit  shall  have  a removable  panel  to  provide  access  to fan/motor  assemblies  and  unit  identification label.

2.3 FansDirect  driven,  double  width  fan  wheels  with forward  curved  blades  shall  be  statically  and dynamically  balanced.    Scrolls  shall  be constructed  of  galvanized  steel.    Fan  wheels shall be constructed of galvanized steel.

2.4 CoilsDrain pan covers entire  length & width of  coil till the headers.Standard base unit shall be equipped with a 3‐row, 4‐row or 6‐row coil for  installation  in a 2‐pipe  system.    Coils  shall  have  3/8‐in  (or  ½”) copper  tubes,  aluminium fins  bonded  to  the tubes by mechanical expansion.   Each coil shall have a manual air vent and threaded or sweat  connections field piping.

2.5 Operating CharacteristicsA one coil unit installed in a 2‐pipe system shall be capable of providing cooling as determined by  the  operating  mode  of  the  central  water supply system.

2.6 Electrical RequirementsStandard unit shall operate on 220/240v, single phase, 50Hz electric power.   All  internal wiring shall be in flexible conduit.

2.7 Motor(s)Fan motors  shall be 3‐speed, 220/240v,  single phase,  50Hz,  permanent  split  capacitor  type, with  sleeve  type  bearings  and  oversized  oil reservoirs to ensure lubrication.The  fan  motor(s)  shall  be  equipped  with integral automatic temperature reset for motor protection.

Page 21: 42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application ·  · 2014-03-04Ducted Chilled Water Fan Coil Unit With District Cooling Application (200 ... With

Manufacturer reserves the right to discontinue, or change at anytime, specifications or designs without notice and without incurring obligations.

42CD‐H08‐1PD

Carrier International Sdn Bhd, Malaysia

Turn to the Experts

As the world leader in heating, ventilation and air conditioning, Carrier is committed to continually improving the quality of comfort we provide to our customers.  But our level of responsibility extends well beyond…

Carrier  Corporation  has  identified  six  specific  areas which  directly  impact  how we,  as  a world manufacturer, balance our customers’ needs for comfort with the environment’s needs for responsible consumption.

These  symbols  graphically  represent  our  six  areas  of  concentration  and will  serve  as  visual  reminders  of  the importance of managing our finite resources.

Each of us at Carrier Corporation believes that, for generations to come, success will not only be measured by the quality of our products and systems, but also by how we have improved the quality of life.