Protection Systems
Answers for infrastructure.
SIPROTEC 5 Line ProtectionDevices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86Catalog SIPROTEC 5.02 Edition 2
8/2/2019 7SA87
2/64
2 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
System catalog
The system catalog describes the SIPROTEC 5 system features.
Device catalogs
The device catalogs describe device-specific features such asfunctional scope, hardware and applications.
Device manuals
The device manuals describe the functions and applications ofa specific SIPROTEC 5 device. The printed manual and the onlinehelp for the device have the same informational structure.
Hardware manual
The hardware manual describes the hardware componentsand device combinations of the SIPROTEC 5 device family.
Operating manual
The operating manual describes the basic principles andprocedures for operating and assembling the devices of theSIPROTEC 5 device family.
Communication protocol manuals
The communication protocol manuals include a description ofspecific protocols for communication within the SIPROTEC 5device family and to higher-level control centers.
Product information
The product information includes general information aboutdevice installation, technical data, limiting values for input andoutput modules, and conditions when preparing for operation.
This document is delivered with each SIPROTEC 5 device.DIGSI 5 online help
The DIGSI 5 online help contains a help package for DIGSI 5 andCFC. The help package for DIGSI 5 includes a description of thebasic operation of software, the DIGSI principles and editors. Thehelp package for CFC includes an introduction to CFC program-ming, basic examples of CFC handling, and a reference chapterwith all CFC blocks available for the SIPROTEC 5 device family.
Online help devices
The online help for devices has the same information structureas the device manual.
SIPROTEC 5 / DIGSI 5 Tutorial
The tutorial on the DVD contains brief information aboutimportant product features, more detailed information about theindividual technical areas, as well as operating sequences withtasks based on practical operation and a brief explanation.
System catalog
Manuals
Devicemanuals
Device catalogsCommunication
protocol manualsProduct
information
SIP
G-0
043.E
N.a
i
Hardwaremanual
Operatingmanual
Online help DIGSI 5Online help devices
SIPROTEC 5/DIGSI 5Tutorial
SoftwareCatalogs
Overview of documentation for the SIPROTEC 5 system
8/2/2019 7SA87
3/64
Introduction 5
Line Protection Devices 6
Overview 6
Distance Protection Devices 7
Applications, application examples, functions andapplication templates
Distance protection 7SA84 7Distance protection 7SA86 10Distance protection 7SA87 14
Differential Protection Devices 18
Applications, application examples, functions and
application templates
Differential protection 7SD84 18Differential protection 7SD86 21Differential protection 7SD87 25
Differential and Distance Protection Devices 29
Applications, application examples, functions andapplication templates
Differential protection and distance protection 7SL86 29Differential protection and distance protection 7SL87 33
Circuit-Breaker Management 37
Applications, application examples, functions and
application templates
Circuit-breaker management device 7VK87 37
Overcurrent Protection for Overhead Line 40
Applications, application examples, functions and
application templates
Overcurrent protection for line 7SJ86 40
Description of the Device Functions 43
Functional integration, protection 43Control & automation 56Monitoring, field data acquisition & recording 57Recorder 58Communication 59Cyber Security, test 60
Overview of the Standard Variants 61
Legal Notice 63
The products and systems described in this catalogare manufactured and sold according to a certifiedmanagement system (acc. to ISO 9001, ISO 14001and BS OHSAS 18001).DNV Certificate No.: 92113-2011-AHSO-GER-TGAand Certificate No.: 87028-2010-AHSO-GER-TGA.
3SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Contents
SIPROTEC 5 Line Protection
Devices 7SA8, 7SD8,7SL8, 7VK8, 7SJ86Energy Automation
Catalog SIPROTEC 5.02 Edition 2
Invalid: Catalog SIP 5.02 V1.0
8/2/2019 7SA87
4/64
4 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Editorial
SIPROTEC has been a recognized brand leader in digitalprotection and field devices on the energy market for decades.The Siemens high-performance SIPROTEC devices cover theentire power spectrum and can be implemented in a wide rangeof fields from power generation to very high voltage transmis-
sion and distribution network applications.Smart automation for transmission grids is the Siemensresponse to the present and future challenges to achieve areliable and efficient energy supply. SIPROTEC 5 is an activecomponent of the energy-efficient smart grid and animportant building block in the complex distributed energysupply systems and networks solutions.
The next generation of SIPROTEC devices, SIPROTEC 5, is basedon the proven features of SIPROTEC 4 to provide you with a new,modern platform including both hardware and software.This platform offers an excellent solution to the challengesassociated with evolving grid structures and workflows.The quality, reliability and proven functions of the former
system have been preserved. Innovative approaches includingholistic workflow, safety and security, and network stabilitymonitoring (PMU functionality) have been added.
The pioneering system architecture places you in full controlof switchgear communications. A powerful, reliable communica-tion infrastructure, combined with the flexible engineeringcapabilities serves as the basis for monitoring and controlling ofdistributed, decentralized systems. Seamless communicationsis the central component of the SIPROTEC 5 system architectureto provide flexibility, safety and security in the automateddistributed network solutions.
With SIPROTEC 5, you are at the beginning of a new generationof intelligent, digital multifunction field devices. The new oper-
ating tool DIGSI 5 offers individual support for you handlesyour specific workflow requirements, from system designto device selection and testing, covering the entire device life-cycle. The new tool offers cost savings over the entire lifecyclewithout compromising safety and system availability.
With the new SIPROTEC 5 generation, you are well equippedto meet the growing economic and reliability demandsimposed on your networks. The philosophy of SIPROTEC 5is reflected in the modularity and flexibility of its hardware andsoftware components. Perfectly tailored fit the custom fitfor your switchgear and specifications for the application andstandardization of energy automation.
Ingo Erkens
General ManagerInfrastructure and Cities SectorSmart Grid DivisionEnergy Automation
8/2/2019 7SA87
5/64
5SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Introduction
SIPROTEC 5 Line protection devices
SIPROTEC 5 line protection devices are part of the modularsystem of SIPROTEC 5. They support all SIPROTEC 5 systemfeatures, and can be used individually as well as universallyin the framework of system solutions. In the following, thespecific properties of the SIPROTEC 5 line protection devices are
described. The description of the SIPROTEC 5 system features isfound in the system catalog.
In the system catalog, the following properties of SIPROTEC 5 areintroduced in detail:
The SIPROTEC 5 system
Areas of use
Hardware
Engineering
Communication
IEC 61850 Simply usable
Test and diagnostics
Safety concept DIGSI 5
The system catalog can be ordered free of chargefrom your Siemens contact partner under order numberE50001-K4605-A011-A1-7600.
SIPROTEC 5 line protection devices are based on the distanceprotection and differential protection principles. They protectoverhead lines and cables of all voltage levels with the highestpossible degree of selectivity and security. A large number ofadditional protection and automation functions makes use in allareas of line protection possible.
The devices also contain important auxiliary functions thatare necessary for safe network operation today. This includesfunctions for control, measurement and monitoring. The largenumber of communication interfaces and communicationprotocols satisfies the requirements of communication-basedselective protection, as well as automated operation.
Commissioning and maintenance work can be completed safely,quickly and thus cost-effectively with high-performance testfunctions. Because of a modular structure design, SIPROTEC 5line protection devices can always be flexibly adapted to specificrequirements.
SIPROTEC 5 system catalog
Order No. E50001-K4605-A011-A1-7600
Answers for energy.
Energy Automation
Cataog SIP 5.01 V1.
SIPROTEC 5 System OverviewProtection, Automation and Monitoring
8/2/2019 7SA87
6/64
6 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Features
The device types are defined by their main protection functionsand by essential distinguishing features.
Definition of device types based on designation
For devices with flexible configurability of the hardware quantitystructure, you can select various standard variants whenordering. Expandability through supplemental modules allowsfor individual adaptation to specific applications such as moreanalog channels for breaker-and-a-half schemes, or more binarycontacts (see Overview of the standard variants, page 58).
Function library and application templates
A common function library makes all protection, automation,monitoring and auxiliary functions for the SIPROTEC 5 lineprotection devices available. Thus, the same functions are trulythe same for all devices. Once established, configurations canbe transferred from device to device. This results in substantiallyreduced engineering effort.
On the following pages of this catalog, the selection of functionsavailable from the library is shown in table format. Pre-definedtemplates are available in DIGSI for standard applications. Thesetemplates contain basic configurations, required functions anddefault settings for standard applications.
7 XX YY
Main protection:
7 SA Distance protection
7 SD Differential protection
7 SL Distance and differential protection
7 SJ Overcurrent protection7 VK Circuit-breaker management
Essential distinguishing features:
7 84 exclusively 3-pole tripping Hardware quantity structure fixed
7 86 exclusively 3-pole tripping Hardware quantity structure flexibly configurable
7 87 1- and 3-pole tripping Hardware quantity structure flexibly configurable
Type designation 7SA84 7SA86 7SA87 7SD84 7SD86 7SD87 7SL86 7SL87 7VK87 7SJ86
Distance protection
Differential protection
Overcurrent protection for overhead line
Circuit-breaker management
3-pole trip command
1-/3-pole trip command
Flexibly configurable hardware
Table 1 Overview of the various distinguishing features of the main protection types
7SS8*
6MD8
7KE8*
7SD87
7SL87
7VK87
7SA87
7UT8*
7SJ86
7SS8*
7KE85*
7SA84
7SA86
7SJ86
7SD84
7SD86
7SL86
7UT8*
7SJ86
Distribution
Generation
Fig. 1 Areas of application of the SIPROTEC 5 devices in the power transmission system
Overview
Line Protection Devices
XX
Main protection functions
Distinguishing features
YY7
SIP5-0010a.E
N.a
i
8/2/2019 7SA87
7/64
7SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA84 Applications
Distance Protection 7SA
Properties
Main protection function: Distance protection
Tripping: 3-pole, min. tripping time 25 ms
Inputs and outputs: 4 current transformers, 4 voltage transform-ers, 5 binary inputs, 8 binary outputs(1 standard, 7 fast relays). TheI/O quantity structure for 7SA84 is fixed;it cannot be changed with other modules ofthe SIPROTEC 5 modular system
Width of housing: 1/319"
Line protection for all voltage levels with 3-pole tripping
Selective protection of overhead lines and cables with single-and multi-ended feeders
Time-graded backup protection for differential protectionequipment
Suitable for radial, ring or any type of meshed systems of anyvoltage level with grounded, compensated or isolated neutralpoint
Main protection function: 6-system distance protection
Various additional functions
Protection of lines with capacitive series compensation
Suitable for protection of long and short lines
Adaptive power-swing blocking
Detection of CT saturation for fast tripping and high accuracyat the same time
Secure serial protection data communication, also over greatdistances and all available physical media (fiber-optic cable,2-wire connections and communication networks)
Control of switching devices
Measurement of operating values and synchrophasors Powerful fault recording
Consistent monitoring concept
Auxiliary functions for simple tests and commissioning.
Applications
The distance protection 7SA84 is a universal protection, controland automation device on the basis of the SIPROTEC 5 system.Due to its high flexibility, it is suitable as selective protectionequipment for overhead lines and cables with single- and multi-ended infeeds as well as time-graded backup protection forcomparison protection schemes. The device is delivered with theaforementioned number of analog and binary inputs and out-
puts. Apart from that, the device supports all SIPROTEC 5 systemcharacteristics. It enables future-oriented system solutions withhigh investment security and low operating costs.
Functions
Table 2 on page 9 shows all functions that are available in the7SA84. Basically, all functions can be configured freely withDIGSI 5. For the application of some of the functions, yourequire the appropriate number of free function points withinthe device. The function point calculator in the online configura-tor provides support in determining the required number offunction points for your device.
Application templates
Application templates are available in DIGSI for standardapplications. They comprise all basic configurations and defaultsettings. Table 2 on page 9 shows the functional scope andthe function point requirement for the application templatesdescribed. The following application templates are available:
7SA84 basic distance protection
Distance protection with 3-pole tripping for networks with allkinds of neutral point treatment
Non-directional overcurrent protection as emergency orbackup function
Teleprotection functions
Fault locator.
7SA84 distance protections for compensated/isolated systems
with AR
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesand cables in networks with compensated and isolated neutral
point.
7SA84 distance protection for overhead line for grounded
systems, with AR
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with grounded neutral point (Fig. 3).
7SA84 distance protection with MHO distance zone
characteristics for overhead line for grounded systems, with AR
Comprises the basic functions with MHO distance zonecharacteristics as well as additional functions that are typicallyrequired for the protection of overhead lines in networks withgrounded neutral point.
Fig. 2 Distance protection 7SA84
8/2/2019 7SA87
8/64
8 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA84 Application examples
Distance Protection 7SA
Busbar with line feeder
V4
I1
I2
I3
I4
V1
V2
V3
CI
FG Circuit breaker
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
QA
Power line
Com.
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
BI Binary input
BO Binary output
FG Line
27 59 81
50/51
21 67N
68
PI
FL85
21 Distance protection
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protection
67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
79 Automatic reclosing
81 Frequency protect ion
85 Teleprotection schemesCtrl Control
FL Fault locator
Teleprotection (85) can use
conventional signalling or serial
protection interface
V-1ph
V-3ph
25
50BF
79
Ctrl
CB BIBO
I-3phV-3ph
I-3ph
50HS
7SA84
Fig. 3 Application example: Distance protection for overhead line
SIP5
G-0025a.E
N
8/2/2019 7SA87
9/64
9SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA84 Functions, application templates
Distance Protection 7SA
Application templates
ANSI Function Abbr. Ava
ilable
in7
SA84
DIS
Basic
DIS
comp./isol.
systems,withAR
DIS
overheadline,
groundedsystems
DIS
MHO,overhead
line
,grounded
systems
Protection functions for 3-pole tripping 3-pole
21, 21N Distance protection Z<
25 Synchrocheck, synchronizing function Sync
27 Undervoltage protection, 3-phase V<
27 Undervoltage protection, positive-sequence system V1<
27 Undervoltage protection, 1-phase, Vx * Vx<
32, 37 Power protection active/reactive power P, Q
46 Negative-sequence system overcurrent protection with direction I2>, (V2,I2)
49 Thermal overload protection , It
50HS High speed instantaneous overcurrent protection I>>>
50BF Circuit-breaker failure protection CBFP
50/51 Overcurrent protection, phases I>,Ip>
50N/51N Overcurrent protection, ground faults IN>, INP>
59 Overvoltage protection, 3-phase V>
59 Overvoltage protection, positive-sequence system V1>
59 Overvoltage protection, compounding V1comp>
59 Overvoltage protection, negative-sequence system V2>
59N Overvoltage protection, zero-sequence system V0>
59 Overvoltage protection, 1-phase, Vx * Vx>
67 Directional overcurrent protection, phases I>, Ip (V,I)
67N Directional overcurrent protection for ground faults IN>, INP (V,I)
67Ns Sensitive ground-fault detection for systems with resonant or isolated neutral * IN>, (V,I)
68 Power-swing blocking Z/t
74TC Trip-circuit supervision TCS
78 Out-of-step protection Z/t
79 Automatic reclosing AR
81O Overfrequency protection f>
81U Underfrequency protection f<
85/21 Teleprotection for distance protection
85/27 Weak or no infeed: Echo and tripping WI
85/67N Teleprotection for directional ground-fault protection
86 Lockout
FL Fault locator FL
FL Fault locator, two-ended measurement* FL-two
PMU Synchrophasor measurement PMU
Operational measured values, standard
Measured values, extended: Min, Max, Avg (function points per type)
Switching-statistic counters
CFC standard
CFC arithmetic
CFC switching sequences
Inrush current detection
External trip initiation
Control for 4 switching devices
Control for more than 4 switching devices (function points per switching device)
Fault recording of analog and binary signals
Monitoring and supervision
Protection interface, serial
Function points: 0 125 225 225
* Currently under development
Table 2 7SA84 functions, application templates
8/2/2019 7SA87
10/64
10 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA86 Applications
Distance Protection 7SA
Properties
Main protection function: Distance protection
Tripping: 3-pole, min. tripping time 9 ms
Inputs and outputs:
Hardware flexibility:
12 predefined standard variants with 4/4 or8/8 current/voltage transformers, 5 to 31
binary inputs,8 to 46 binary outputs or flexibly adjustableI/O quantity structure within the scope of theSIPROTEC 5 modular system
Width of housing: 1/3 19" to 1/1 19"
Line protection for all voltage levels with 3-pole tripping
Very short tripping time
Also used in switchgear with breaker-and-a-half scheme
Selective protection of overhead lines and cables with single-and multi-ended feeders
Time-graded backup protection for differential protectionequipment
Suitable for radial, ring or any type of meshed systems of anyvoltage level with grounded, compensated or isolated neutralpoint
Main protection function: 6-system distance protection
Various additional functions
Protection of lines with capacitive series compensation
Suitable for the protection of long and short lines
Adaptive power-swing blocking
Detection of CT saturation for fast tripping and high accuracyat the same time
Secure serial protection data communication, also over greatdistances and all available physical media (fiber-optic cable,
2-wire connections and communication networks) Control of switching devices
Measurement of operating values and synchrophasors
Powerful fault recording
Consistent monitoring concept
Auxiliary functions for simple test and commissioning.
Applications
The distance protection 7SA86 is a universal protection, controland automation device on the basis of the SIPROTEC 5 system.Due to its high flexibility, it is suitable as selective, fast protec-tion equipment for overhead lines and cables with single- and
multi-ended infeeds as well as time-graded backup protectionfor comparison protection schemes. The device supports allSIPROTEC 5 system characteristics. It enables future-orientedsystem solutions with high investment security and low operat-ing costs.
Functions
Table 3 on page 13 shows all functions that are available in the7SA86. Basically, all functions can be configured freely withDIGSI 5. For the application of some of the functions, yourequire the appropriate number of free function points withinthe device. The function point calculator in the online configura-tor provides support in determining the required number offunction points for your device.
Application templates
Application templates are available in DIGSI for standardapplications. They comprise all basic configurations and defaultsettings. Table 3 on page 13 shows the functional scope andthe function point requirement for the application templatesdescribed. The following templates are available:
7SA86 basic distance protection
Distance protection with 3-pole tripping for networks with allkinds of neutral point treatment
Non-directional overcurrent protection as emergency orbackup function
Teleprotection functions
Fault locator.
7SA86 distance protections for compensated/isolated systems
with AR
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesand cables in networks with compensated and isolated neutral
point.
7SA86 distance protection for overhead line for grounded
systems, with AR
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with grounded neutral point (Fig. 5).
Fig. 4 Distance protection 7SA86
8/2/2019 7SA87
11/64
11SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA86 Application examples
Distance Protection 7SA
7SA86 distance protection with MHO distance zone
characteristics for overhead line for grounded systems, with AR
Comprises the basic functions with MHO distance zonecharacteristics as well as additional functions that are typicallyrequired for the protection of overhead lines in networks withgrounded neutral point
7SA86 distance protection for overhead line for grounded
systems, with AR for applications with breaker-and-a-half
scheme
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with grounded neutral point; prepared for applica-tions with breaker-and-a-half schemes (Fig. 6).
7SA86 distance protection with MHO distance zone
characteristics for overhead line for grounded systems, with AR
for applications with breaker-and-a-half schemes
Comprises the basic functions with MHO distance zonecharacteristics as well as additional functions that are typicallyrequired for the protection of overhead lines in networks
with grounded neutral point; prepared for applications withbreaker-and-a-half schemes (Fig. 6).
Fig. 5 Application example: Distance protection for overhead line
Busbar with line feeder
V4
I1
I2
I3
I4
V1
V2
V3
CI
FG Circuit breaker
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
QA
Power line
Com.
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
BI Binary input
BO Binary output
FG Line
27 59 81
50/51
21 67N
68
PI
FL85
21 Distance protection
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protection67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
79 Automatic reclosing
81 Frequency protect ion
85 Teleprotection schemes
Ctrl Control
FL Fault locator
Teleprotection (85) can use
conventional signalling or serial
protection interface
V-1ph
V-3ph
25
50BF
79
Ctrl
CBBI
BO
I-3phV-3ph
I-3ph
50HS
7SA86
SIP5
G-0033a.E
N
8/2/2019 7SA87
12/64
12 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA86 Application examples
Distance Protection 7SA
V1
V2
V4
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
A-QA
V3
I1
I2
I3
I4
V1V2
V3
I1
I2
I3
I4
V4
MP
CT-3ph 2
Power line 1
Busbar 1
Busbar 2
B-QA
C-QA
Power line 2
Com.
CI
MP
VT-1ph 2
52
52
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
Summation of currents
BI Binary input
BO Binary output
27 59 81
50/51
21 67N
68
PI
FL85
FG Line
21 Distance protection
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protection
67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
79 Automatic reclosing
81 Frequency protection
85 Teleprotection schemes
87STUB STUB Differential protection
Ctrl ControlFL Fault locator
Teleprotection (85) can use
conventional signalling or serial
protection interface
87STUB
FG Circuit breaker B-QA
FG Circuit breaker A-QA
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
I-3ph
V-3ph
50HS
7SA86
Fig. 6 Application example: Distance protection for overhead line with breaker-and-a-half scheme
SIP5
G-0034a
.EN
8/2/2019 7SA87
13/64
13SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA86 Functions, application templates
Distance Protection 7SA
Application templates
ANSI Function Abbr. Available
in7SA86
DIS
Basic
DIS
comp./isol.
sys
tems,withAR
DIS
overheadline,
gro
undedsystems
DIS
MHO,overhead
line,grounded
sys
tems
DIS
overheadline,
gro
undedsystems
bre
aker-and-a-half
DIS
MHO,overhead
line
,groundedsystems
bre
aker-and-a-half
Protection functions for 3-pole tripping 3-pole
Hardware quantity structure expandable I/O
21, 21N Distance protection Z<
25 Synchrocheck, synchronizing function Sync 2 227 Undervoltage protection, 3-phase V<
27 Undervoltage protection, positive-sequence system V1<
27 Undervoltage protection, 1-phase, Vx * Vx<
32, 37 Power protection active/reactive power P, Q
46 Negative-sequence system overcurrent protection with direction I2>, U2/I2
49 Thermal overload protection
50HS High speed instantaneous overcurrent protection I>>>
50BF Circuit-breaker failure protection CBFP 2 250/51 Overcurrent protection, phases I>, Ip>
50N/51N Overcurrent protection, ground faults IN>, INP> 59 Overvoltage protection, 3-phase V>
59 Overvoltage protection, positive-sequence system V1>
59 Overvoltage protection, compounding V1comp>
59 Overvoltage protection, negative-sequence system V2>
59N Overvoltage protection, zero-sequence system V0>
59 Overvoltage protection, 1-phase, Vx * Vx>
67 Directional overcurrent protection, phases I>, Ip (V,I)
67N Directional overcurrent protection for ground faults IN>, INP (V,I)
67Ns Sensitive ground-fault detection for systems with resonant orisolated neutral *
IN>, (V,I)
68 Power-swing blocking Z/t
74TC Trip-circuit supervision TCS
78 Out-of-step protection Z/t
79 Automatic reclosing AR 2 281O Overfrequency protection f>
81U Underfrequency protection f<
85/21 Teleprotection for distance protection
85/27 Weak or no infeed: Echo and tripping WI
85/67N Teleprotection for directional ground-fault protection
86 Lockout
87STUB STUB differential protection (for breaker-and-a-half schemes) I
FL Fault locator FL
FL Fault locator, two-ended measurement* FL-two
PMU Synchrophasor measurement PMU
Operational measured values, standard
Measured values, expanded: Min, Max Middle(function points per type)
Switching-statistic counters
CFC standard CFC arithmetic
CFC switch sequences
Inrush current detection
External trip initiation
Control for 4 switching devices
Control for more than 4 switching devices (function pointsper switching device)
Fault recording of analog and binary signals
Monitoring and supervision
Protection interface, serial
Function points: 0 125 225 225 375 375* Currently under development
Table 3 7SA86 functions, application templates
8/2/2019 7SA87
14/64
14 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA87 Applications
Distance Protection 7SA
Properties
Main protection function: Distance protection
Tripping: 1- and 3-pole, min. tripping time 9 ms
Inputs and outputs:
Hardware flexibility:
12 predefined standard variations with 4/4or 8/8 current/voltage transformers, 5 to31 binary inputs, 8 to 46 binary outputs orflexibly adjustable I/O quantity structurewithin the scope of the SIPROTEC 5 modularsystem
Width of housing: 1/3 19" to 1/1 19"
Line protection for all voltage levels with 1- and 3-pole tripping
Very short tripping time
Also used in switchgear with breaker-and-a-half schemes
Selective protection of overhead lines and cables with single-and multi-ended feeders
Time-graded backup protection for differential protectionequipment
Suitable for radial, ring or any type of meshed systems of anyvoltage level with grounded, compensated or isolated neutralpoint
Main protection function: 6-system distance protection
Various additional functions
Protection of lines with capacitive series compensation
Suitable for protection of long and short lines
Adaptive power-swing blocking
Detection of CT saturation for fast tripping and high accuracyat the same time
Secure serial protection data communication, also over greatdistances and all available physical media (fiber-optic cable,
2-wire connections and communication networks) Control of switching devices
Measurement of operating values and synchrophasors
Powerful fault recording
Consistent monitoring concept
Auxiliary functions for simple tests and commissioning.
Applications
The distance protection 7SA87 is a universal protection, controland automation device on the basis of the SIPROTEC 5 system.Due to its high flexibility, it is suitable as selective, fast protec-tion equipment for overhead lines and cables with single- andmulti-ended infeeds as well as time-graded backup protection
for comparison protection schemes. The device supports allSIPROTEC 5 system characteristics. It enables future-orientedsystem solutions with high investment security and low operat-ing costs.
Functions
Table 4 on page 17 shows all functions that are available in the7SA87. Basically, all functions can be configured freely withDIGSI 5. For the application of some of the functions, yourequire the appropriate number of free function points withinthe device. The function point calculator in the online configura-tor provides support in determining the required number offunction points for your device.
Application templates
Application templates are available in DIGSI for standardapplications. They comprise all basic configurations and defaultsettings. Table 4 on page 17 shows the functional scope andthe function point requirement for the application templatesdescribed. The following application templates are available:
7SA87 basic distance protection
Distance protection with 1-/3-pole tripping for networks withall kinds of neutral point treatment
Non-directional overcurrent protection as emergency orbackup function
Teleprotection functions
Fault locator.
7SA87 distance protection for compensated/isolated systems
with AR
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with compensated and isolated neutral point.
7SA87 distance protection for overhead line for grounded
systems, with AR
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with grounded neutral point (Fig. 8).
Fig. 7 Distance protection 7SA87
8/2/2019 7SA87
15/64
15SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA87 Application examples
Distance Protection 7SA
7SA87 distance protection for overhead line in grounded
systems, with AR for applications with breaker-and-a-half
schemes
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with grounded neutral point; prepared for applica-
tions with breaker-and-a-half schemes (Fig. 9).
Busbar with line feeder
V4
I1
I2
I3
I4
V1
V2
V3
CI
FG Circuit breaker
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
QA
Power line
Com.
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
BI Binary input
BO Binary output
FG Line
27 59 81
50/51
21 67N
68
PI
FL85
21 Distance protection
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protect ion
67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
79 Automatic reclosing
81 Frequency protect ion
85 Teleprotection schemes
Ctrl Control
FL Fault locator
Teleprotection (85) can use
conventional signalling or serial
protection interface
V-1ph
V-3ph
25
50BF
79
Ctrl
CBBI
BO
I-3phV-3ph
I-3ph
50HS
7SA87
Fig. 8 Application example: Distance protection for overhead line
SIP5G
-0026a.E
N
8/2/2019 7SA87
16/64
16 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA87 Application examples
Distance Protection 7SA
V1
V2
V4
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
A-QA
V3
I1
I2
I3
I4
V1V2
V3
I1
I2
I3
I4
V4
MP
CT-3ph 2
Power line 1
Busbar 1
Busbar 2
B-QA
C-QA
Power line 2
Com.
CI
MP
VT-1ph 2
52
52
52
FG Function group
MP Measuring point
PI Protect ion interface
CI Communicat ion interface
CB Circuit breaker
Summation of currents
BI Binary input
BO Binary output
27 59 81
50/51
21 67N
68
PI
FL85
FG Line
21 Distance protection
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protection
67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
79 Automatic reclosing
81 Frequency protection
85 Teleprotection schemes
87STUB STUB Differential protection
Ctrl Control
FL Fault locator
Teleprotection (85) can use
conventional signalling or serial
protection interface
87STUB
FG Circuit breaker B-QA
FG Circuit breaker A-QA
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
I-3ph
V-3ph
50HS
7SA87
Fig. 9 Application example: Distance protection for overhead line with breaker-and-a-half scheme
SIP5
G-0035a.E
N
8/2/2019 7SA87
17/64
17SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Distance protection 7SA87 Functions, application templates
Distance Protection 7SA
Application templates
ANSI Function Abbr. Available
in7SA87
DIS
Basic
DIS
comp./isol.
sys
tems,withAR
DIS
overheadline,
gro
undedsystems
DIS
overheadline,
gro
undedsystems
bre
aker-and-a-half
Protection functions for 3-pole tripping 3-pole
Protection functions for 1-pole tripping 1-pole
Hardware quantity structure expandable I/O
21, 21N Distance protection Z<
25 Synchrocheck, synchronizing function Sync 2
27 Undervoltage protection, 3-phase V<
27 Undervoltage protection, positive-sequence system V1<
27 Undervoltage protection, 1-phase, Vx * Vx<
32, 37 Power protection active/reactive power P, Q
46 Negative-sequence system overcurrent protection with direction I2>, (V2,I2)
49 Thermal overload protection , It
50 HS High speed instantaneous overcurrent protection I>>>
50BF Circuit-breaker failure protection CBFP 250/51 Overcurrent protection, phases I>, IP
50N/51N Overcurrent protection, ground faults IN>, INP>
59 Overvoltage protection, 3-phase V>
59 Overvoltage protection, positive-sequence system V1>
59 Overvoltage protection, compounding V1comp>
59 Overvoltage protection, negative-sequence system V2>
59N Overvoltage protection, zero-sequence system V0>
59 Overvoltage protection, 1-phase, Vx * Vx>
67 Directional overcurrent protection, phases I>, Ip (V,I)
67N Directional overcurrent protection for ground faults IN>, INP (V,I)
67Ns Sensitive ground-fault detection for systems with resonant or isolated neutral * IN>, (V,I)
68 Power-swing blocking Z/t
74TC Trip-circuit supervision TCS
78 Out-of-step protection Z/t
79 Automatic reclosing AR 2
81O Overfrequency protection f>
81U Underfrequency protection f<
85/21 Teleprotection for distance protection
85/27 Weak or no infeed infeed: Echo and tripping WI
85/67N Teleprotection for directional ground-fault protection
86 Lockout
87STUB STUB differential protection (for breaker-and-a-half schemes) I
FL Fault locator FL
FL Fault locator, two-ended measurement* FL-two
PMU Synchrophasor measurement PMU
Operational measured values, standard
Measured values, extended: Min, Max, Avg (function points per type Switching-statistic counters
CFC standard
CFC arithmetic
CFC switching sequences
Inrush current detection
External trip initiation
Control for 4 switching devices
Control for more than 4 switching devices (function points per switching device)
Fault recording of analog and binary signals
Monitoring and supervision
Protection interface, serial
Function points: 0 150 250 425* Currently under development
Table 4 7SA87 functions, application templates
8/2/2019 7SA87
18/64
18 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD84 Applications
Differential Protection 7SD
Properties
Main protection function: Differential protection
Tripping: 3-pole, min. tripping time 14 ms
Inputs and outputs: 4 current transformers,4 voltage transformers,
5 binary inputs, 8 binary outputs(1 standard, 7 fast relays)The I/O quantity structure for 7SD84 is fixed;it cannot be changed with the other modulesof the SIPROTEC 5 modular system.
Width of housing: 1/3 19"
Line protection for all voltage levels with 3-pole tripping
Phase-selective protection of overhead lines and cables withsingle- and multi-ended infeeds of all lengths with 2 line ends
Transformers and compensating coils in the protection zoneare possible
Suitable for radial, ring or any type of meshed systems of any
voltage level with grounded, compensated or isolated neutralpoint
Protection of lines with capacitive series compensation
Main protection function is differential protection withadaptive algorithm for maximum sensitivity and stability evenat different CT errors, CT saturation and capacitive chargingcurrents
Directional backup protection and various additional functions
Secure serial protection data communication, also over greatdistances, and all available physical media (fiber-optic cable,2-wire connections and communication networks)
Control of switching devices
Measurement of operating values and synchrophasors
Powerful fault recording
Consistent monitoring concept
Auxiliary functions for simple tests and commissioning.
Applications
The differential protection device 7SD84 is a universalprotection, control and automation device on the basis of theSIPROTEC 5 system. Due to its high flexibility, it is suitable asselective protection equipment for overhead lines and cableswith single- and multi-ended infeeds with two ends. Transform-ers and compensating coils in the protection zone are also pos-sible. The device is delivered with the aforementioned numberof analog and binary inputs and outputs. Apart from that, thedevice supports all SIPROTEC 5 system characteristics. It enablesfuture-oriented system solutions with high investment securityand low operating costs.
Functions
Table 5 on page 20 shows all functions that are available in the7SD84. Basically, all functions can be configured freely withDIGSI 5. For the application of some of the functions, yourequire the appropriate number of free function points withinthe device. The function point calculator in the online configura-tor provides support in determining the required number offunction points for your device.
Application templates
Application templates are available in DIGSI for standardapplications. They comprise all basic configurations and defaultsettings. Table 5 on page 20 shows the functional scope andthe function point requirement for the application templatesdescribed. The following application templates are available:
7SD84 basic differential protection
Phase-selective differential protection with 3-poletripping
Non-directional overcurrent protection as emergency orbackup function
Fault locator.
7SD84 differential protection for overhead line
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overheadlines: Circuit-breaker failure protection, AR, synchronizationfunction, voltage and frequency protection, thermal overloadprotection (Fig. 11).
7SD84 differential protection for overhead line with
transformer in the protection range
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overheadlines: Circuit-breaker failure protection, AR, synchronizationfunction, voltage and frequency protection, thermal overloadprotection
Considers a transformer in the protection range.
Fig. 10 Differential protection device 7SD84
8/2/2019 7SA87
19/64
19SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD84 Application examples
Differential Protection 7SD
Busbar with line feeder
V4
I1
I2
I3
I4
V1
V2
V3
CI
FG Line FG Circuit breaker
MP
VT-1ph 1
27 59 81
FL
50/51
MP
CT-3ph 1
MP
VT-3ph 1
87L
PI
QA
25 Synchrocheck, synchronizing function
27 Undervoltage protect ion
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protect ion
79 Automatic reclosing
81 Frequency protection
87L Differential protection, line
Ctrl Control
FL Fault locator
Power line
Com.
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
BI Binary input
BO Binary output
V-1ph
V-3ph
25
50BF
79
Ctrl
CB BIBO
I-3ph
I-3ph
V-3ph
50HS
7SD84
Fig. 11 Application example: Line differential protection for overhead line
SIP5
G-0022a.E
N
8/2/2019 7SA87
20/64
20 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD84 Functions, application templates
Differential Protection 7SD
Application templates
ANSI Function Abbr. Ava
ilable
in7
SD84
DIFFBasic
DIFFOverheadline
DIFFOverheadline
withtransformer
Protection functions for 3-pole tripping 3-pole
87L Differential protection, line I
25 Synchrocheck, synchronizing function Sync
27 Undervoltage protection, 3-phase V<
27 Undervoltage protection, positive-sequence system V1<
27 Undervoltage protection, 1-phase, Vx * Vx<
32, 37 Power protection active/reactive power P, Q
46 Negative-sequence system overcurrent protection with direction I2>, (V2,I2)
49 Thermal overload protection , It
50HS High speed instantaneous overcurrent protection I>>>
50BF Circuit-breaker failure protection CBFP
50/51 Overcurrent protection, phases I>, IP>
50N/51N Overcurrent protection, ground faults IN>, INP>
59 Overvoltage protection, 3-phase V>
59 Overvoltage protection, positive-sequence system V1>
59 Overvoltage protection, compounding V1comp>
59 Overvoltage protection, negative-sequence system V2>
59N Overvoltage protection, zero-sequence system V0>
59 Overvoltage protection, 1-phase, Vx * Vx>
67 Directional overcurrent protection, phases I>, Ip (V,I)
67Ns Sensit ive ground-fault detection for systems with resonant or isolated neutral * IN>, (V,I)
74TC Trip-circuit supervision TCS
79 Automatic reclosing AR
81O Overfrequency protection f>
81U Underfrequency protection f<
86 Lockout
87L/87T Option for line differential protection: including power transformer I
Option for line differential protection:charging-current compensation
Broken-wire detection for differential protection
FL Fault locator FL
FL Fault locator, two-ended measurement * FL-two
PMU Synchrophasor measurement PMU
Operational measured values, standard
Measured values, extended: Min, Max, Avg (function points per type)
Switching-statistic counters
CFC standard
CFC arithmetic
CFC switching sequences
Inrush current detection
External trip initiation
Control for 4 switching devices
Control for more than 4 switching devices (function points per switching device)
Fault recording of analog and binary signals
Monitoring and supervision
Protection interface, serial
Function points: 0 175 275
* Currently under development
Table 5 7SA84 functions, application templates
8/2/2019 7SA87
21/64
21SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD86 Applications
Differential Protection 7SD
Properties
Main protection function: Differential protection
Tripping: 3-pole, min. tripping time 9 ms
Inputs and outputs: 12 predefined standard variants with 4/4or 8/8 current/voltage transformers, 5 to31 binary inputs, 8 to 46 binary outputs orflexibly adjustable I/O quantity structurewithin the scope of the SIPROTEC 5 modularsystem
Width of housing: 1/3 19" to 1/1 19"
Line protection for all voltage levels with 3-pole tripping
Phase-selective protection of overhead lines and cables withsingle- and multi-ended infeeds of all lengths with up to 6 lineends
Also used in switchgear with breaker-and-a-half schemes
Transformers and compensating coils in the protection zoneare possible
Suitable for radial, ring or any type of meshed systems of anyvoltage level with grounded, compensated or isolated neutralpoint
Protection of lines with capacitive series compensation
Main protection function is differential protection withadaptive algorithm for maximum sensitivity and stability evenat different CT errors, CT saturation and capacitive chargingcurrents
Directional backup protection and various additional functions
Secure serial protection data communication, also over greatdistances, and all available physical media (fiber-optic cable,2-wire connections and communication networks)
Control of switching devices
Measurement of operating values and synchrophasors Powerful fault recording
Consistent monitoring concept
Auxiliary functions for simple tests and commissioning.
Applications
The differential protection device 7SD86 is a universalprotection, control and automation device on the basis of theSIPROTEC 5 system. Due to its high flexibility, it is suitable asselective protection equipment for overhead lines and cableswith single- and multi-ended infeeds with up to 6 ends.Transformers and compensating coils in the protection zone arealso possible. The device is delivered with the aforementioned
number of analog and binary inputs and outputs. Apart fromthat, the device supports all SIPROTEC 5 system characteristics.It enables future-oriented system solutions with high investmentsecurity and low operating costs.
Functions
Table 6 on page 24 shows all functions that are available in the7SD86. Basically, all functions can be configured freely withDIGSI 5. For the application of some of the functions, yourequire the appropriate number of free function points withinthe device. The function point calculator in the online configura-tor provides support in determining the required number offunction points for your device.
Application templates
Application templates are available in DIGSI for standardapplications. They comprise all basic configurations and defaultsettings. Table 6 on page 24 shows the functional scope andthe function point requirement for the application templatesdescribed. The following application templates are available:
7SD86 basic differential protection
Phase-selective differential protection with 3-pole tripping
Non-directional overcurrent protection as emergency orbackup function
Fault locator.
7SD86 differential protection for overhead line
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overheadlines: Circuit-breaker failure protection, AR, synchronizationfunction, voltage and frequency protection, thermal overloadprotection (Fig. 13).
7SD86 differential protection for overhead line with transformerin the protection range
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overheadlines: Circuit-breaker failure protection, AR, synchronizationfunction, voltage and frequency protection, thermal overloadprotection.
Considers a transformer in the protection range.
Fig. 12 Differential protection device 7SD86
8/2/2019 7SA87
22/64
22 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD86 Application examples
Differential Protection 7SD
7SD86 differential protection for overhead line, for applications
with breaker-and-a-half schemes
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overheadlines: Circuit-breaker failure protection, AR, synchronizationfunction, voltage and frequency protection, thermal overload
protection.
Prepared for applications with breaker-and-a-half schemes(Fig. 14).
Busbar with line feeder
V4
I1
I2
I3
I4
V1
V2
V3
CI
FG Line FG Circuit breaker
MP
VT-1ph 1
27 59 81
FL
50/51
MP
CT-3ph 1
MP
VT-3ph 1
87L
PI
QA
25 Synchrocheck, synchronizing function
27 Undervoltage protect ion
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protection
79 Automatic reclosing
81 Frequency protect ion
87L Differential protection, line
Ctrl Control
FL Fault locator
Power line
Com.
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
BI Binary input
BO Binary output
V-1phV-3ph
25
50BF
79
Ctrl
CBBI
BO
I-3ph
I-3ph
V-3ph
50HS
7SD86
Fig. 13 Application example: Line differential protection for overhead line
S
IP5
G-0037a.E
N
8/2/2019 7SA87
23/64
23SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD86 Application examples
Differential Protection 7SD
V1
V2
V4
FG Line
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
A-QA
V3
I1
I2
I3
I4
V1V2
V3
I1
I2
I3
I4
V4
MP
CT-3ph 2
Power line 1
Busbar 1
Busbar 2
B-QA
C-QA
27 59 81
50/51
FL87L
PI
Power line 2
Com.
CI
MP
VT-1ph 2
52
52
52
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage p rotection
79 Automatic reclosing
81 Frequency protection
87L Differential protection, line
87STUB STUB Differential protection
Ctrl Control
FL Fault locator
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
Summation of currents
BI Binary input
BO Binary output
87STUB
FG Circuit breaker B-QA
FG Circuit breaker A-QA
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
I-3ph
V-3ph
7SD86
50HS
Fig. 14 Application example: Line differential protection for overhead line with breaker-and-a-half scheme
SIP5
G-0023a
.EN
8/2/2019 7SA87
24/64
24 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD86 Functions, application templates
Differential Protection 7SD
Application templates
ANSI Function Abbr. Ava
ilable
in7
SD86
DIFFBasic
DIFFOverheadline
DIFFOverheadline
withtransformer
DIFFOverheadline,
breaker-and-a-half
Protection functions for 3-pole tripping 3-pole
Hardware quantity structure expandable I/O
87L Line differential protection for 2 line ends Z<
87L Line differential protection for 3 to 6 line ends I
25 Synchrocheck, synchronizing function Sync 2
27 Undervoltage protection, 3-phase V<
27 Undervoltage protection, positive-sequence system V1<
27 Undervoltage protection, 1-phase, Vx * Vx<
32, 37 Power protection active/reactive power P, Q
46 Negative-sequence system overcurrent protection with direction I2>, (V2,I2)
49 Thermal overload protection , It
50 HS High speed instantaneous overcurrent protection I>>>
50BF Circuit-breaker failure protection CBFP 2
50/51 Overcurrent protection, phases I>, IP>
50N/51N Overcurrent protection, ground faults IN>, INP>
59 Overvoltage protection, 3-phase V>
59 Overvoltage protection, positive-sequence system V1>
59 Overvoltage protection, compounding V1comp>
59 Overvoltage protection, negative-sequence system V2>
59N Overvoltage protection, zero-sequence system V0>
59 Overvoltage protection, 1-phase, Vx * Vx>
67 Directional overcurrent protection, phases I>, Ip (V,I)
67Ns Sensitive ground-fault detection for systems with resonant or isolated neutral * IN>, (V,I)
74TC Trip-circuit supervision TCS
79 Automatic reclosing AR 2
81O Overfrequency protection f>
81U Underfrequency protection f<
86 Lockout
87L/87T Option for line differential protection: including power transformer I
Option for line dif ferential protection:charging-current compensation
87STUB STUB differential protection (for breaker-and-a-half schemes) I
Broken-wire detection for differential protection
FL Fault locator FL
FL Fault locator, two-ended measurement* FL-two
PMU Synchrophasor measurement PMU
Operational measured values, standard
Measured values, expanded: Min, Max, Avg (function points per type)
Switching-statistic counters
CFC standard CFC arithmetic
CFC switching sequences
Inrush current detection
External trip initiation
Control for 4 switching devices
Control for more than 4 switching devices (function points per switching device)
Fault recording of analog and binary signals
Monitoring and supervision
Protection interface, serial
Function points: 0 175 275 325
* Currently under development
Table 6 7SD86 functions, application templates
8/2/2019 7SA87
25/64
25SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD87 Applications
Differential Protection 7SD
Properties
Main protection function: Differential protection
Tripping: 1- and 3-pole, min. tripping time 9 ms
Inputs and outputs: 12 predefined standard variants with 4/4or 8/8 current/voltage transformers, 5 to
31 binary inputs, 8 to 46 binary outputs orflexibly adjustable I/O quantity structurewithin the scope of the SIPROTEC 5 modularsystem
Width of housing: 1/3 19" to 1/1 19"
Line protection for all voltage levels with 1- and 3-pole tripping
Phase-selective protection of overhead lines and cables withsingle- and multi-ended infeeds of all lengths with up to 6 lineends
Also used in switchgear with breaker-and-a-half schemes
Transformers and compensating coils in the protection zoneare possible
Suitable for radial, ring or any type of meshed systems of anyvoltage level with grounded, compensated or isolated neutralpoint
Protection of lines with capacitive series compensation
Main protection function is differential protection with adap-tive algorithm for maximum sensitivity and stability even inthe most varied transformer errors, CT saturation and capaci-tive charging currents
Directional backup protection and various additional functions
Secure serial protection data communication, also over greatdistances and all available physical media (fiber-optic cable,2-wire connections and communication networks)
Control of switching devices
Measurement of operating values and synchrophasors
Powerful fault recording
Consistent monitoring concept
Auxiliary functions for simple tests and commissioning.
Applications
The differential protection device 7SD87 is a universalprotection, control and automation device on the basis of theSIPROTEC 5 system. Due to its high flexibility, it is suitable asselective protection equipment for overhead lines and cableswith single- and multi-ended infeeds with up to 6 ends.Transformers and compensating coils in the protection zone are
also possible. The device is delivered with the aforementionednumber of analog and binary inputs and outputs. Apart fromthat, the device supports all SIPROTEC 5 system characteristics.It enables future-oriented system solutions with high investmentsecurity and low operating costs.
Functions
Table 7 on page 28 shows all functions that are available in the7SD87. Basically, all functions can be configured freely withDIGSI 5. For the application of some of the functions, yourequire the appropriate number of free function points withinthe device. The function point calculator in the online configura-tor provides support in determining the required number offunction points for your device.
Application templates
Application templates are available in DIGSI for standardapplications. They comprise all basic configurations and defaultsettings. Table 7 on page 28 shows the functional scope andthe function point requirement for the application templatesdescribed. The following application templates are available:
7SD87 basic differential protection
Phase-selective differential protection with 1- and 3-poletripping
Non-directional overcurrent protection as emergency orbackup function
Fault locator.
7SD87 differential protection for overhead line
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead lines:Circuit-breaker failure protection, synchronization function,voltage and frequency protection, thermal overload protection(Fig. 16).
7SD87 differential protection for overhead line with transformer
in the protection range
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead lines:Breaker failure protection, AR, synchronization function, volt-age and frequency protection, thermal overload protection.
Considers a transformer in the protection range.
Fig. 15 Differential protection device 7SD87
8/2/2019 7SA87
26/64
26 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD87 Application examples
Differential Protection 7SD
7SD87 differential protection for overhead line, for applications
with breaker-and-a-half schemes
Comprises the basic functions as well as additional functions thatare typically required for the protection of overhead lines: Circuit-breaker failure protection, AR, synchronization function, voltageand frequency protection, thermal overload protection.
Prepared for applications with breaker-and-a-half schemes(Fig. 17).
Busbar with line feeder
V4
I1
I2
I3
I4
V1
V2
V3
CI
FG Line FG Circuit breaker
MP
VT-1ph 1
27 59 81
FL
50/51
MP
CT-3ph 1
MP
VT-3ph 1
87L
PI
QA
25 Synchrocheck, synchronizing function
27 Undervoltage protect ion
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protection
79 Automatic reclosing
81 Frequency protect ion
87L Differential protection, line
Ctrl Control
FL Fault locator
Power line
Com.
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
BI Binary input
BO Binary output
V-1phV-3ph
25
50BF
79
Ctrl
CBBI
BO
I-3ph
I-3ph
V-3ph
50HS
7SD87
Fig. 16 Application example: Line differential protection for overhead line
S
IP5
G-0032a.E
N
8/2/2019 7SA87
27/64
27SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD87 Application examples
Differential Protection 7SD
V1
V2
V4
FG Line
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
A-QA
V3
I1
I2
I3
I4
V1V2
V3
I1
I2
I3
I4
V4
MP
CT-3ph 2
Power line 1
Busbar 1
Busbar 2
B-QA
C-QA
27 59 81
50/51
FL87L
PI
Power line 2
Com.
CI
MP
VT-1ph 2
52
52
52
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage p rotection
79 Automatic reclosing
81 Frequency protection
87L Differential protection, line
87STUB STUB Differential protection
Ctrl Control
FL Fault locator
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
Summation of currents
BI Binary input
BO Binary output
87STUB
FG Circuit breaker B-QA
FG Circuit breaker A-QA
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
I-3ph
V-3ph
7SD87
50HS
Fig. 17 Application example: Line differential protection for overhead line with breaker-and-a-half scheme
SIP5
G-0024a
.EN
8/2/2019 7SA87
28/64
28 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection 7SD87 Functions, application templates
Differential Protection 7SD
Application templates
ANSI Function Abbr. Available
in7SD87
DIF
FBasic
DIF
FOverheadline
DIF
FOverheadline
withtransformer
DIF
FOverheadline,
bre
aker-and-a-half
Protection functions for 3-pole tripping 3-pole
Protection functions for 1-pole tripping 1-pole
Hardware quantity structure expandable I/O
87L Line differential protection for 2 line ends I
87L Line differential protection for 3 to 6 line ends I
25 Synchrocheck, synchronizing function Sync 2
27 Undervoltage protection, 3-phase V<
27 Undervoltage protection, positive-sequence system V1<
27 Undervoltage protection, 1-phase, Vx * Vx<
32, 37 Power protection active/reactive power P, Q
46 Negative-sequence system overcurrent protection with direction I2>, (V2,I2)
49 Thermal overload protection , It
50HS High speed instantaneous overcurrent protection I>>>
50BF Circuit-breaker failure protection CBFP 2
50/51 Overcurrent protection, phases I>, Ip>
50N/51N Overcurrent protection, ground faults IN>, INP>
59 Overvoltage protection, 3-phase V>
59 Overvoltage protection, positive-sequence system V1>
59 Overvoltage protection, compounding V1comp>
59 Overvoltage protection, negative-sequence system V2>
59N Overvoltage protection, zero-sequence system V0>
59 Overvoltage protection, 1-phase, Vx * Vx>
67 Directional overcurrent protection, phases I>, Ip (V,I)
67Ns Sensitive ground-fault detection for systems with resonant or isolated neutral * IN>, (V,I)
74TC Trip-circuit supervision TCS
79 Automatic reclosing AR 2
81O Overfrequency protection f>
81U Underfrequency protection f<
86 Lockout
87L/87T Option for line protection: including power transformer I
Option for line differential protection: charging-current compensation
87STUB STUB differential protection (for breaker-and-a-half schemes) I
Broken-wire detection for differential protection
FL Fault locator FL
FL Fault locator, two-ended measurement* FL-two
PMU Synchrophasor measurement PMU
Operational measured values, standard
Measured values, expanded: Min, Max, Avg (function points per type)
Switching-statistic counters
CFC standard
CFC arithmetic
CFC switching sequences
Inrush current detection
External trip initiation
Control for 4 switching devices
Control for more than 4 switching devices (function points per switching device)
Fault recording of analog and binary signals
Monitoring and supervision
Protection interface, serial
Function points: 0 175 275 350
* Currently under development
Table 7 7SD87 functions, application templates
8/2/2019 7SA87
29/64
29SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection and distance protection 7SL86 Applications
Differential Protection and Distance Protection 7SL
Properties
Main protection function: Differential protection and distance protec-tion
Tripping: 3-pole, min. tripping time 9 ms
Inputs and outputs:
Hardware flexibility:
12 predefined standard variants with 4/4 or8/8 current/voltage transformers, 5 to 31binary inputs,8 to 46 binary outputs or
flexibly adjustable I/O quantity structurewithin the scope of the SIPROTEC 5 modularsystem
Width of housing: 1/3 19" to 1/1 19"
Line protection for all voltage levels with 3-pole tripping
Phase-selective protection of overhead lines and cables withsingle- and multi-ended infeeds
Used on lines of all lengths with up to 6 line ends
Also used in switchgear with breaker-and-a-half schemes
Transformers and compensating coils in the protection zoneare possible
Suitable for radial, ring or any type of meshed systems of anyvoltage level with grounded, compensated or isolated neutralpoint
Protection of lines with capacitive series compensation
Two independent main protection functions with variousprotection algorithms
Main 1 protection: Differential protection with very shorttripping time. The adaptive algorithm guarantees maximumsensitivity and stability, even in case of di fferent CT errors,CT saturation and capacitive charging currents.
Main 2 protection: 6-system distance protection with very
short tripping time and high accuracy also when detectingCT saturation.
Adaptive power-swing blocking
Various additional functions
Secure serial protection data communication, also over greatdistances, and all available physical media (fiber-optic cable,2-wire connections and communication networks)
Control of switching devices
Measurement of operating values and synchrophasors
Powerful fault recording
Consistent monitoring concept
Auxiliary functions for simple tests and commissioning.
Applications
The combined differential and distance protection 7SL86 is auniversal protection, control and automation device on the basisof the SIPROTEC 5 system.
Due to its high flexibility, it is suitable as selective protectionequipment for overhead lines and cables with single- and multi-ended infeeds of all lengths with up to 6 ends. Transformers andcompensating coils in the protection zone are also possible. Thedevice is delivered with the aforementioned number of analogand binary inputs and outputs. Apart from that, the devicesupports all SIPROTEC 5 system characteristics. It enables future-oriented system solutions with high investment security and lowoperating costs.
Functions
Table 8 on page 32 shows all functions that are available in the7SL86. Basically, all functions can be configured freely withDIGSI 5. For the application of some of the functions, yourequire the appropriate number of free function points withinthe device. The function point calculator in the online configura-tor provides support in determining the required number of
function points for your device.Application templates
Application templates are available in DIGSI for standardapplications. They comprise all basic configurations and defaultsettings. Table 8 on page 32 shows the functional scope andthe function point requirement for the application templatesdescribed. The following application templates are available:
7SL86 basic differential and distance protection
Phase-selective differential protection with 3-pole tripping
Distance protection with 3-pole tripping for networks with allkinds of neutral point treatment
Non-directional overcurrent protection as emergency orbackup function
Teleprotection functions
Fault locator.
7SL86 differential and distance protection for overhead line in
grounded systems
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with grounded neutral point: Circuit-breakerfailure protection, AR, synchronization function, voltage andfrequency protection, thermal overload protection.
Fig. 18 Differential protection and distance protection 7SL86
8/2/2019 7SA87
30/64
30 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection and distance protection 7SL86 Application examples
Differential Protection and Distance Protection 7SL
7SL86 differential and distance protection with MHO distance
zone characteristic for overhead line in grounded systems
Comprises the basic functions with MHO distance zonecharacteristics as well as additional functions that are typicallyrequired for the protection of overhead lines in networks withgrounded neutral point (Fig. 19).
7SL86 differential and distance protection for overhead line
in grounded systems, with AR for applications with
breaker-and-a-half schemes
Comprises the basic functions as well as additional functionsthat are typically required for the protection of overhead linesin networks with grounded neutral point
Prepared for applications with breaker-and-a-half schemes(Fig. 20).
7SL86 differential and distance protection with MHO distance
zone characteristics for overhead line in grounded systems,
with AR for applications with breaker-and-a-half schemes
Comprises the basic functions with MHO distance zonecharacteristics as well as additional functions that are typicallyrequired for the protection of overhead lines in networks with
grounded neutral point Prepared for applications with breaker-and-a-half schemes
(Fig. 20).
Busbar with line feeder
V4
I1
I2
I3
I4
V1
V2
V3
FG Circuit breaker
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
QA
Power line
Com.
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
BI Binary input
BO Binary output
FG Line
V-3ph
27 59 81
50/51
21 67N
6887L
PI
FL85
CI
21 Distance protection
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection59 Overvoltage protect ion
67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
79 Automatic reclosing
81 Frequency protection
85 Teleprotection schemes for 21 and/or 67 N
Ctrl Control
FL Fault locator
Teleprotection (85) can use
conventional signalling or serial
protection interface
I-3ph V-1ph
V-3ph
25
50BF
79
Ctrl
CBBI
BO
I-3ph
7SL86
50HS
Fig. 19 Application example: Combined line differential and distance protection for overhead line
SIP5
G-0036a.E
N
8/2/2019 7SA87
31/64
31SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection and distance protection 7SL86 Application examples
Differential Protection and Distance Protection 7SL
V1
V2
V4
MP
VT-1ph 1
MP
CT-3ph 1
MP
VT-3ph 1
A-QA
V3
I1
I2
I3
I4
V1V2
V3
I1
I2
I3
I4
V4
MP
CT-3ph 2
Power line 1
Busbar 1
Busbar 2
B-QA
C-QA
Power line 2
Com.
CI
MP
VT-1ph 2
52
52
52
FG Function group
MP Measuring point
PI Protection interface
CI Communication interface
CB Circuit breaker
Summation of currents
BI Binary input
BO Binary output
FG Line
I-3ph
27 59 81
50/51
21 67N
6887L
PI
Teleprotection (85) can use
conventional signalling or serial
protection interface
FL85
87STUB
FG Circuit breaker B-QA
FG Circuit breaker A-QA
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
25
50BF
79
Ctrl
CBBI
BO
V-1ph
V-3ph
I-3ph
V-3ph
7SL86
50HS
21 Distance protection
25 Synchrocheck, synchronizing function
27 Undervoltage protection
50/51 Overcurrent protection, phases, ground
50HS High speed instantaneous overcurrent protection
50BF Circuit-breaker failure protection
59 Overvoltage protection
67N Directional overcurrent protection for ground-faults
68 Power-swing blocking
79 Automatic reclosing
81 Frequency protection
85 Teleprotection schemes for 21 and/or 67N
87L Differential protect ion, l ine
87STUB STUB Differential protectionCtrl Control
FL Fault locator
Fig. 20 Application example: Combined line differential and distance protection for overhead line with breaker-and-a-half scheme
SIP5
G-0027a
.EN
8/2/2019 7SA87
32/64
32 SIPROTEC 5 Line Protection, Devices 7SA8, 7SD8, 7SL8, 7VK8, 7SJ86 Siemens SIPROTEC 5.02 Edition 2
Differential protection and distance protection 7SL86 Functions, application templates
Differential Protection and Distance Protection 7SL
Application templates
ANSI Function Abbr. Available
in
7SL86
DIFF/DISBasic
DI
FF/DISoverhead
lin
e,
grounded
sy
stems
DI
FF/DISMHO
,
ov
erheadline
,
gr
oundedsystems
DI
FF/DISoverhead
lin
e,
groundedsyst.
br
eaker-and-a-h
alf
DI
FF/DISMHO
,over-
he
adline
,grounded
br
eaker-and-a-h
alf
Protection functions for 3-pole tripping 3-pole
Hardware quantity structure expandable I/O
21, 21N Distance protection Z<
87L Line differential protection for 2 line ends I
87L Line differential protection for 3 to 6 line ends I 25 Synchrocheck, synchronizing function Sync 2 227 Undervoltage protection, 3-phase V< 27 Undervoltage protection, positive-sequence system V1< 27 Undervoltage protection, 1-phase, Vx * Vx< 32, 37 Power protection active/reactive power P, Q 46 Negative-sequence system overcurrent protection with direction I2>, (V2,I2) 49 Thermal overload protection , It 50HS High speed instantaneous overcurrent protection I>>>
50BF Circuit-breaker failure protection CBFP 2 250/51 Overcurrent protection, phases I>, Ip>
50N/51N Overcurrent protection, ground faults IN>, INP>
59 Overvoltage protection, 3-phase V>
59 Overvoltage protection, positive-sequence system V1> 59 Overvoltage protection, compounding V1comp> 59 Overvoltage protection, negative-sequence system V2>