AE1294

Embed Size (px)

Citation preview

  • 7/28/2019 AE1294

    1/2

    1 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1294

    Application Engineering

    B U L L E T I N

    For years servicemen have used megohmeters toevaluate compressor motor windings. However, mostmegohmeter manufacturers publish guidelines thatapply to open motors. For this reason, Emerson ClimateTechnologies has investigated the use of megohmeterson hermetic and semi-hermetic compressors.

    When using megohmeters to evaluate the motorinsulation of compressors, it is important to understandthat they should not be used as one would a volt-ohmmeter. A single megohmeter reading gives little insightinto the condition of a motors insulation.

    Megohmeters are best used as a part of a regularmaintenance program to monitor trends (over severalmonths). For example, one might record a megohm valueand compare it to a previous reading. If subsequentreadings show a trend of lower and lower values, thencorrective action (such as system clean up) should betaken.

    Emerson does not incorporate the megohmeter intoany of its quality checks. All Copeland compressorsmust pass U.L. required tests using hi-potential currentleakage testers (hi-pot). Studies performed by Emersonhave found that compressors with megohmeter readingsas low as 0.5 megohms still pass the hi-pot.

    There are many factors that affect megohm readingsincluding contaminated refrigerant, oil level, refrigerantin oil and current leakage through electrical fusites orterminal plates.

    Any external electrical components connected to thecompressor terminals also affect megohm readings.Wires, contactors and relays all leak current and willdecrease compressor megohmeter readings if notdisconnected.

    As mentioned earlier a single megohm reading cannotbe used to condemn a compressor since many otherfactors are involved. However, limits can be placed onmegohm values that dictate action be taken. Emersonhas found that these limits are related to the rated voltageof the compressor. Megohm values equal to or greaterthan 1000 ohms per volt are probably acceptable. Forexample, a 460 volt compressor might show a megohmreading of 460,000 ohms or 0.46 megohm. Compressorswith rated voltages of 208 to 230 volts would then beoperable at megohm values of 0.208 to 0.230 megohms;for simplicity, Emerson has set the limit at 0.5 megohmsbefore a compressor is condemned. Figure 1 showsthe required procedure for checking compressors witha megohmeter.

    New compressors that have never been installed will notneed any system clean-up procedures so long as themegohm reading is above 0.5. A baseline reading mustbe established for comparison purposes and since thisis its first reading this will be its baseline value.

    Megohm Values of Copeland Compressors

    AE4-1294 August 1992Reformatted November 2010

    Application Engineering

    B U L L E T I N

  • 7/28/2019 AE1294

    2/2

    2 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1294

    Application Engineering

    B U L L E T I N

    Figure 1Megohmeter Test Procedure