AE1299

Embed Size (px)

Citation preview

  • 7/28/2019 AE1299

    1/15

    1 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Application Guidelines for

    K4 Refrigeration Copeland Scroll Compressors 2 - 6 Horsepower

    AE4-1299 R9 March 2011

    Application Engineering

    B U L L E T I N

    Introduction

    The Copeland Scroll K4 represents the secondgeneration of compliant scroll technology for therefrigeration industry. Four major changes have beenincorporated compared to the previous K3 offering:

    Revised scroll form - Specifically designed toachieve the higher compression ratios typicallyfound in refrigeration applications

    Addition of Dynamic Discharge Valve - Provides

    improved energy efficiency when operating at highcompression ratio conditions

    Modified Injection System - Enables the scroll toaccept either liquid or vapor injection dependingon system design

    DU Drive Bearing - This Teflon impregnated bronzebearing provides improved reliability

    These changes result in a compressor that is suitablefor the most demanding refrigeration applications withefficiencies comparable to the industry standard Discuscompressor.

    NomenclatureThe Copeland Scroll compressor model numbersinclude the nominal capacity at standard 60Hz ARIrating conditions. Please refer to product literature formodel number details.

    Operating Envelope

    K4 models can be used with a variety of refrigerantsdepending on the model selected and the lubricantused:

    Table 1

    Model Refrigerant Lubricant

    ZS, ZF R-22 MO

    ZS, ZFR-404A, R-507,R-134A, R-22

    POE

    ZF R-407C, R-404A POE

    See Form 93-11 for a complete list of all Emersonapproved refrigerants and lubricants.

    The ZF and ZS model families are intended forrefrigeration type duty. The approved operatingenvelopes for these models are depicted in Figures1A through 1F.

    It must be noted that the ZF model when operatedat low evaporator temperatures requires some formof injection to prevent overheating. Either liquid orvapor injection is sufficient for moderate condensingtemperatures. However, depending on the refrigerantused, evaporating temperature and condensing

    temperature, liquid injection is required.

    Evaporating Temperature

    CondensingTem

    perature

    R-134a ZF**K4E Envelope(Includes Liquid Injection)

    Conditions: 65F Return Gas; 0F Subcooling, 95F Ambient

    Figure 1B

    Evaporating Temperature

    C

    ondensingTemperature

    R-22 ZF**K4 Envelope(Includes Liquid Injection)

    Conditions: 65F Return Gas; 0F Subcooling, 95F Ambient

    Figure 1A

  • 7/28/2019 AE1299

    2/15

    2 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    ZS**K4/K4E Envelope (R-22)

    Figure 1F

    ZS**K4E Envelope (R-134A)

    Figure 1D

    Conditions: 65F Return Gas; 0F Subcooling, 95F Ambient

    ZS**K4E Envelope (R-404A/R-507)

    Figure 1E

    Conditions: 65F Return Gas; 0F Subcooling, 95F Ambient

    Conditions: 65F Return Gas; 0F Subcooling, 95F Ambient

    R-404A / R-507/ R-407A / R-407C ZF**K4E

    Envelope (Includes Liquid Injection)

    Conditions: 65F Return Gas; 0F Subcooling, 95F Ambient

    Figure 1C

    Evaporating Temperature

    CondensingTemperature

    Low Condensing

    Temperature

    Region

    C F

    Liquid Injection

    The low temperature scroll compressor is provided withan injection port suitable for connection to a source ofliquid refrigerant. Internally, this port is connected to aninner pocket of the scroll mechanism. Since this pocketis separated from the suction inlet, no loss of capacityor mass flow results from injecting at this point.

    Refrigerant injected in this manner must include thesystem components listed on the next page. Failure toprovide these components can result in liquid refrigerant

    completely filling the scroll during an off cycle. Whenpower is reapplied in this condition, the hydraulic effectproduced can result in pressures high enough to causepermanent damage to the compressor. It is a conditionof warranty that these components are properlyinstalled, whenever liquid or vapor injection is used.

    Capillary Tube - Liquid must be fed through anappropriate capillary tube as defined in Table 2.NOTE: Not required if DTC valve is used

    Solenoid Valve - A solenoid valve with a minimum.109 inch orifice must be provided in the injectioncircuit that opens whenever the compressor is

    operative or cooling is required during pumpdown.The solenoid must be closed when the compressoris cycled off. NOTE: Not required if DTC valve isused.

    Current Sensing Relay - To prevent the solenoidfrom remaining open during a motor protectortrip a current sensing relay must be provided thatsenses whenever the compressor is off and closesthe solenoid to stop injection. NOTE: Not requiredif DTC valve is used

  • 7/28/2019 AE1299

    3/15

    3 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    this condition and will dilute the oil in the compressorcrankcase.

    NOTE: Use of R-407a and R-407c with capillary tubes

    is not approved see Discharge Temp Control Valvesection for proper use.

    Vapor Injection

    Emerson has developed the ZF**KVE low temperaturemodels to take advantage of the system efficiencybenefit due to subcooling the liquid being feed to theevaporator. Figure 3 is a representation of this type ofsystem. However, it is beyond the scope of this bulletinto provide details of the proper application of vapor-injected systems. Please refer to AE 4-1327 for additionalinformation on "Economized Vapor Injection" systems.

    DISCHARGE TEMPERATURE CONTROL VALVEIntroduction

    The purpose of the DTC valve is to eliminate the needfor a capillary tube on the 2 through 6 horsepower "ZF"scroll model family.

    The DTC valve is approved for all refrigerants in thisproduct range. A DTC valve must be used for ZF**K4Eapplications with R-407C and R-407A.

    Valve Specifications

    Opening Setpoint: 193F 5F

    Liquid Line Connection: 3/8 (9.5mm)

    Installation of Valve (see Figure 4)

    The valve bulb must be installed in the top cap thermalwell to adequately control scroll temperatures. The valveshould be tightened on the injection fitting to a torque of216-245 in. lbs. (24.4 - 27.7 Nm). A 90 orientation on thevalve is recommended, however it will function properlyin any orientation. The capillary tube connecting thevalve to the bulb should be positioned such that it doesnot contact the compressor during operation. Do notbend the capillary tube within 1 (25.4mm) of the valve.

    The DTC Valve comes with an insulating cap. If thisadditional height from the cap is an issue, the valve

    cap could be replaced with high temperature insulation.This should be applied to insulate and protect the valvesremote bulb assembly. This will reduce the total heightrequirement by 0.5 (12.7mm).

    Suggested Application Techniques

    For the most efficient thermal sensing, spread a thin filmof thermal grease around the DTC Valve bulb beforeinstalling into the top cap well. However for properfunctioning of the valve this is not required.

    The following components are not required, but theyare recommended for liquid injection.

    Sight Glass - A sight glass just before the capillary

    tube inlet is recommended to allow visual inspectionfor the presence of liquid refrigerant.

    Filter/Drier - A filter/drier installed in the injectioncircuit is recommended to avoid the possibility ofcapillary tube blockage due to contaminants.

    Table 2Capillary Tubes For Liquid Injection

    Model

    Cap TubeEmerson

    Kit NumberI.D.(Inches)

    Length(Inches)

    R-22

    ZF06K4 0.042 70 998-1583-00

    ZF08K4 0.042 70 998-1583-00

    ZF09K4 0.042 30 998-1583-03

    ZF11K4 0.042 30 998-1583-03

    ZF13K4 0.042 10 998-1583-05

    ZF15K4 0.042 5 998-1583-06

    ZF18K4 0.050 5 998-1586-00

    R-404A/R-507/R-134A

    ZF06K4E 0.042 70 998-1583-00

    ZF08K4E 0.042 70 998-1583-00

    ZF09K4E 0.042 70 998-1583-00

    ZF11K4E 0.042 50 998-1583-01

    ZF13K4E 0.042 40 998-1583-02

    ZF15K4E 0.042 30 998-1583-03

    ZF18K4E 0.042 20 998-1583-04

    Figure 2 is a representation of a typical system withthese components.

    The advantage of this type of injection system is thatit tends to be self regulating i.e., as the pressure

    differential across the capillary tube increases, theamount of liquid fed to the compressor also increases.Since more cooling is needed at high compression ratioconditions, this automatic increase in liquid feed isexactly what is needed.

    For the liquid injection system to be effective, aminimum of 5F sub-cooled liquid at the capillary inletis required. However, DO NOT use mechanically cooledsubcooled liquid. The cap tube will be oversized under

  • 7/28/2019 AE1299

    4/15

    4 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    No crankcase heaters are required on single phasescroll compressors.

    Three Phase - Outdoor Only

    Crankcase heaters are required on three phasecompressors when the system charge exceeds10 lbs. See Table 3A.

    Table 3A Crankcase Heaters

    Model

    ZF 06, 08, 09, 11, 13, 15, 18

    ZS 15, 19, 21, 26, 30, 38, 45

    Part Number Volts WattsLead

    Length(in)

    GroundingWire

    Length (in)

    018-0095-00 240 70 21.7 28.5

    018-0095-01 480 70 21.7 28.5

    018-0095-02 575 70 21.7 28.5

    018-0095-03 240 70 31.5 28.5

    018-0095-04 240 70 48.2 47.5

    018-0095-05 480 70 48.2 47.5

    018-0095-06 575 70 48.2 47.5

    018-0095-07 120 70 48.2 47.5

    018-0095-08 400 70 48.2 47.5

    018-0095-09 277 70 21.7 28.5

    The listed crankcase heaters are intended for useonly where there is limited access. The heaters arenot equipped for use with electrical conduit. Whereapplicable electrical safety codes require heater leadprotection, a crankcase terminal box should be used.Recommended crankcase heater terminal box andcover kit numbers are listed in Table 3B. If there are anyquestions concerning their application, contact EmersonClimate Technologies Application Engineering.

    Table 3BConduit Ready Heater Terminal Box Kits

    Models Part Number

    ZF06, 08, 09, 11ZS15, 19, 21, 26 998-7026-00

    ZF13, 15, 18ZS30, 38, 45

    998-7024-00

    Discharge Line Thermostat

    A discharge line thermostat is required in thecompressor control circuit. The thermostats have a cutout setting that will insure discharge line temperatures

    At your discretion, field serviceability can be improvedby installing a shut-off valve in the liquid line just beforethe DTC Valve.

    The valve requires a solid column of liquid. A liquid linesightglass could be applied to visually insure liquid flow.

    Compressor Or Valve Service

    Replacing a ZF compressor using capillary tube, liquidinjection solenoid, and current sensing relay:

    The ZF compressor and DTC Valve eliminates theneed for the solenoid and current sensing relay. Thesedevices may be left on if desired, but they are notrequired.

    Replacing a ZF compressor using the DTC Valve:

    We recommend replacing both the DTC Valve and thecompressor at the same time. If you wish to use theexisting DTC Valve, the valve filter (pn 013-0119-00)should be cleaned and/or replaced.

    Replacing a capillary tube on a ZF compressor:

    The DTC Valve is not backward compatible oncompressors with no thermal well in the top cap.Replacement capillary tubes will be available throughour PrimeSourceSM network.

    Replacing a DTC Valve on a ZF compressors:

    Before replacing the DTC Valve, clean and/or change

    the filter to verify there is an unobstructed column ofliquid to the valve.

    Accumulators

    Due to the scrolls inherent ability to handle liquidrefrigerant in flooded start and defrost cycle operationconditions, accumulators may not be required. Anaccumulator is required on single compressor systemswith charges over 10 lbs. On systems with defrostschemes or transient operations that allow prolonged,uncontrolled liquid return to the compressor, anaccumulator is required unless a suction header ofsufficient volume to prevent liquid migration to thecompressor is used.

    Excessive liquid flood back or repeated flooded startswill dilute the oil in any compressor causing inadequatelubrication and bearing wear. Proper system design willminimize liquid floodback thereby ensuring maximumcompressor life.

    Crankcase Heaters

    Single Phase

  • 7/28/2019 AE1299

    5/15

    5 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    observed a potential short cycling condition on the 2,2 , 3, & 3 Horsepower models. This phenomenoncan be attributed to several factors:

    1. Location of low-pressure control sensor. If it islocated right at the suction inlet of the compressor,it will be more sensitive to pressure spikes.

    2. Actual low-pressure setting. Refer to ourrecommended setting in Table 5. If the differentialpressure setting is too close, this will increase thepossibility of short cycling.

    3. Type of Low-pressure control can have an effecton cycling. The encapsulated non-adjustable typeis more susceptible to causing excessive cyclingdue to tolerances.

    4. If short cycling cannot be avoided, using a 3-minutetime delay will limit the cycling of the compressor toan acceptable level.

    IPR Valve

    Refrigeration scroll compressors (up to 6 HP size) haveinternal pressure relief valves which open at a dischargeto suction differential pressure of 375 to 450 psi. Thisaction will trip the motor protector and remove the motorfrom the line.

    Motor Protection

    Conventional inherent internal line break motorprotection is provided.

    Compressor Oil Charge

    See Table 6 for the properfield oil recharge values.

    The oil level of scroll compressors should be adjustedto the mid-point of the sight glass.

    below the 260F maximum limit. It should be installedapproximately 7 inches from the discharge tube outlet.If a service valve is installed at the discharge tube, thethermostat should be located 5 inches from the valvebraze. For proper functioning in extremely low outdoorambient conditions, it is recommended the thermostatshould be insulated to protect it from a direct air stream.

    Kits have been set up to include the TOD thermostat,retainer, and installation instructions. These thermostatsmust be used with 1/2 O.D. discharge lines to ensureproper thermal transfer and temperature control.They work with either 120 or 240 volt circuits, and areavailable with or without an alarm circuit capability.See Table 4 for a list of discharge line thermostat kitnumbers.

    Pressure Controls

    Both high and low pressure controls are required andthe following set points are the minimum and maximumlimits. See Table 5 for setpoints.

    Pump Down Recommendations

    Refrigeration scroll compressors use a low-leakdischarge valve to prevent high-pressure backflow intothe low side. Typically, this check valve prevents systempressures from equalizing and pump down can beachieved. However, during laboratory testing, we have

    ApplicationControl

    TypeR-404A /

    R-507R-22 R-407A R-407C

    Medium Temp(ZF)

    LOW 17.1 PSIG Min. 10PSIG Min. 8 PSIG Min. 6 PSIG Min.

    HIGH 445 PSIG Max. 381 PSIG Max. 428 Max. 402 PSIG Max.

    Medium Temp(ZS)

    LOW 8 PSIG Min. 24 PSIG Min.N/A N/A

    HIGH 445 PSIG Max. 381 PSIG Max.

    Low Temp(ZF)

    LOW 0 PSIG Min. 2 in. Hg Min. 4 in. Hg Min. 5 in. Hg Min.

    HIGH 400 PSIG Max. 335 PSIG Max. 375 PSIG Max. 352 PSIG Max

    Table 5Low and High Pressure Control Settings for ZF*K4(E) & ZS*K4(E)

    Table 4

    Discharge Line Thermostat Kits

    Kit NumberConduit

    ConnectorAlarm Contact

    Lead

    998-7022-02 Yes No

    998-0540-00 No No

    998-0541-00 No Yes

  • 7/28/2019 AE1299

    6/15

    6 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Discharge Mufflers

    Flow through scroll compressors is continuous withrelatively low pulsations. External mufflers applied

    to piston compressors may not be required on theCopeland Scroll compressor. Due to system variabilityindividual tests should be conducted by the systemmanufacturer to verify acceptable levels of sound andvibration.

    Compressor Tubing and Mounting

    Compressor mounting must be selected based onapplication. Consideration must be given to soundreduction and tubing reliability. Some tubing geometryor shock loops may be required to reduce vibrationtransferred from the compressor to external tubing.

    Mounting for Rack Systems - Specially designed rubber

    grommets are available for Copeland Scroll 2-6 H.P.scroll rack applications. These grommets are formulatedfrom a high durometer material specifically designedfor refrigeration applications. The high durometerlimits the compressors motion thereby minimizingpotential problems of excessive tubing stress. Sufficientisolation is provided to prevent vibration from beingtransmitted to the mounting structure. This mountingarrangement is recommended for multiple compressorrack installations. See Figure 6A for a detail of thismounting system.

    Note: The use of standard soft grommets is notrecommended for most Copeland Scroll Rack

    installations. These softer mounts allow for excessivemovement that will result in tube breakage unless theentire system is properly designed.

    Condensing Units- For 2-6 H.P. Copeland ScrollCondensing unit applications soft mounts arerecommended. See Figure 6B.

    Tubing Considerations - Proper tube design must betaken into consideration when designing the tubingconnecting the scroll to the remaining system. Thetubing should provide enough flexibility to allownormal starting and stopping of the compressorwithout exerting excessive stress on the tube joints.In addition, it is desirable to design tubing with anatural frequency different from the normal runningfrequency of the compressor. Failure to do this canresult in tube resonance and unacceptable tubing life.Figures 7A and 7B are examples of acceptable tubingconfigurations.

    Oil Management for Rack Applications

    Copeland refrigeration scroll compressors may beused on multiple compressor parallel rack applications.

    This requires the use of an oil management system tomaintain proper oil level in each compressor crankcase.The sight glass connection supplied can accommodatethe mounting of the oil control devices.

    Unlike semi-hermetic compressors, scroll compressorsdo not have an oil pump with accompanying oil pressuresafety controls. Therefore, an external oil level controlis required.

    The OMB Oil Level Management Control combines thefunctions of level control and timed compressor shut-offshould the level not come back to normal within a setperiod of time. This device has been found to provide

    excellent performance infield tests on scroll compressorsand is recommended for parallel system applications.

    Note: Due to issues that have been experienced withthe Trax Oil level control, Emerson recommendsthat OEMs not use Trax Oil on future new scrollcompressor rack applications. We may considerdenial of warranty for lubrication related failureswhen the Trax Oil control is used on new systemsin the future.

    Immediately after system start-up the oil reservoir levelwill fluctuate until equilibrium is reached. It is advisableto monitor the oil level during this time to assure sufficient

    oil is available. This will prevent unnecessary trips ofthe oil control system.

    Note: If oil management problems are occuring,please refer to AE17-1320 or contact EmersonClimate Technologies Application Engineering.

    Table 6Oil Charges

    Model Family Initial Recharge

    ZF06K/ZS15K 44 40

    ZF08K/ZS19K 50 46

    ZF09K/ZS21K 49 45

    ZF11K/ZS26K 49 45

    ZF13K/ZS30K 64 60

    ZF15K/ZS38K 64 60

    ZF18K/ZS45K 64 60

  • 7/28/2019 AE1299

    7/15

    7 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Three phase scrolls however, will rotate in eitherdirection depending on the power phasing. Sincethere is a 50/50 chance of connected power beingbackwards, contractors should be warned of this.

    Appropriate instructions or notices should be providedby the OEM.

    Verification of proper rotation can be made by observingthat suction pressure drops and discharge pressurerises when the compressor is energized. Additionally,if operated in reverse the compressor is noisier andits current draw is substantially reduced compared totabulated values.

    Although operation of the scroll in the reverse directionfor brief periods of time is not harmful, continuedoperation could result in a failure.

    All three phase compressors are wired identicallyinternally. Once the correct phasing is determined fora specific system or installation, connecting properlyphased power leads to the same Fusite terminals willmaintain proper rotation.

    Brief Power Interruptions

    Brief power interruptions (less than 1/2 second) mayresult in powered reverse rotation of single phaseCopeland Scroll compressors. High pressure dischargegas expands backwards through the scrolls at powerinterruption, causing the scroll to orbit in the reversedirection. If power is re-applied while this reversal isoccurring, the compressor may continue to run noisily

    in the reverse direction for several minutes until thecompressors internal protector trips. This has nonegative impact on durability. When the protector resetsthe compressor will start and run normally.

    Emerson strongly encourages use of a timer which cansense brief power interruptions and lock the compressorout of operation for two minutes. A typical timer is shownin Figure 9.

    No time delay is required on three phase models toprevent reverse rotation due to power interruptions.

    Deep Vacuum Operation

    WARNING: Do not run a Copeland Scroll compressorin a deep vacuum. Failure to heed this advice can resultin arcing of the Fusite pins and permanent damage tothe compressor.

    A low pressure control is required for protection againstdeep vacuum operation. See section on PressureControls for the proper set points.

    Caution: These examples are intended only asguidelines to depict the need for flexibility in tubedesigns. In order to properly determine if a design isappropriate for a given application, samples should betested and evaluated for stress under various conditionsof use including voltage, frequency, load fluctuations,and shipping vibration. The guidelines above may behelpful; however, testing should be performed for eachsystem designed.

    Starting Characteristics

    Single phase scrolls are designed with PSC type motorsand therefore will start without the need of start assistdevices in most applications. However, if low voltageconditions exist at start-up, protector trips can result.Therefore start assist devices (start capacitors & relays)are available to maximize starting characteristics under

    abnormal conditions.Fusite

    Fusite pin orientation for single phase and three phaseCopeland Scroll compressors are shown in Figure 8and inside the terminal box.

    Shell Temperature

    System component failure may cause the top shelland discharge line to briefly reach temperaturesabove 300F. Wiring or other materials which could bedamaged by these temperatures should not come incontact with the shell.

    Connection FittingsScroll compressors are provided either with stubconnections or Rotalock adapters depending on the billof material selected (consult your District Sales Manageror Application Engineer for details).

    As of April 1, 1998 stub tube models have copper platedsteel suction, discharge, and injection fittings for a morerugged, leak resistant connection. Prior to April 1, 1998discharge connections were 100% copper.

    Brazing procedures for copper plated steel fittings areinherently different than brazing pure copperfittings. Seesection on Field Service (see Figure 10) for suggestions

    on how to properly make these connections.

    Three Phase Scroll Compressors -Directional Dependence

    Scroll compressors are directional dependent; i.e. theywill compress in one rotational direction only. On singlephase compressors this is not an issue since they willalways start and run in the proper direction (except asdescribed in the section Brief Power Interruptions).

  • 7/28/2019 AE1299

    8/15

    8 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Scroll compressors (as with any refrigerant compressor)should never be used to evacuate a refrigeration or airconditioning system. See AE24-1105 for proper systemevacuation procedures.

    Assembly Line System Charging Procedure

    Rapid charging only on the suction side of a scrollsystem can occasionally result in a temporary no-startcondition for the compressor. If the flanks of the scrollhappen to be in a sealed position, rapid pressurizationof the low side without opposing high side pressurecan cause the scrolls to seal axially. Until the pressureseventually equalize, the scrolls can be held tightlytogether, preventing rotation.

    The best way to avoid this situation is to charge onboth the high and low sides simultaneously at a ratewhich does not result in axial loading of the scrolls. Themaximum charging rate can be determined throughsimple tests.

    Should a scroll fail to start and this sealing conditionis suspected, reverse the three phase leads andmomentarily(1-2 seconds) power the compressor inthe reverse direction. This should free the scroll flanksand allow for normal operation.

    Unbrazing System Components

    If the refrigerant charge is removed from a scroll unitby bleeding the high side only, it is sometimes possiblefor the scrolls to seal, preventing pressure equalization

    through the compressor. This may leave the low sideshell and suction line tubing pressurized. If a brazingtorch is then applied to the low side, the pressurizedrefrigerant and oil mixture could ignite as it escapesand contacts the brazing flame. It is important to checkboth the high and low sides with manifold gauges beforeunbrazing, or in the case of assembly line repair, removerefrigerant from both the high and low sides. Instructionsshould be provided in appropriate product literature andassembly (line repair) areas.

    HiPot Testing

    Scroll compressors are configured with the motor inthe bottom of the shell. Unlike most other hermetic

    compressors, the scroll motor can be immersed inrefrigerant when liquid is present in the shell. In thisrespect, the scroll is more like semi hermetic compressorswhich have horizontal motors partially submerged in oiland refrigerant. HiPot tests with liquid refrigerant in theshell can show higher levels of current leakage due tohigher electrical conductivity of liquid refrigerant vs.refrigerant vapor and oil. This phenomenon can occurwith any compressor when the motor is immersed inrefrigerant and does not present any safety issue. To

    lower the current leakage reading operate the systemfor a brief period of time, redistributing the refrigerant toa more normal configuration, and test again.

    Copeland Scroll Functional Check

    Copeland Scroll compressors do not have internalsuction valves. It is not necessary to perform functionalcompressor tests to check how low the compressor willpull suction pressure. This type of test may damage ascroll compressor. The following diagnostic procedureshould be used to evaluate whether a scroll compressoris functioning properly.

    1. Verify proper unit voltage.

    2. Normal motor winding continuity and short to groundchecks will determine if the inherent overload motorprotector has opened or if an internal short to ground

    has developed. If the protector has opened, thecompressor must cool sufficiently to reset.

    3. With service gauges connected to suction anddischarge pressure fittings, turn on the compressor.If suction pressure falls below normal levels thesystem is either low on charge or there is a flowblockage.

    4. Single Phase Compressors

    If the suction pressure does not drop and thedischarge pressure does not rise to normal levelsthe compressor is faulty.

    5. Three Phase Compressors

    If the suction pressure does not drop and thedischarge pressure does not rise, reverse any twoof the compressor power leads and reapply powerto make sure the compressor was not wired to runin the reverse direction.

    The compressor current draw must be compared topublished compressor performance curves at thecompressor operating conditions (pressures andvoltages). Significant deviations (15%) from publishedvalues may indicate a faulty compressor.

    New Installation

    The copper-coated steel suction, discharge, andinjection tubes on scroll compressors can bebrazed in approximately the same manner as anycopper tube.

    Recommended brazing material - Any Silfosmaterial is recommended, preferably with aminimum of 5% silver. However, 0% silver isacceptable.

  • 7/28/2019 AE1299

    9/15

    9 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Use of a dry nitrogen purge to eliminate possibilityof carbon buildup on internal tube surfaces isrecommended.

    Be sure process tube fitting I.D. and process tubeO.D. are clean prior to assembly.

    Apply heat in Area 1. As tube approaches brazingtemperature, move torch flame to Area 2.

    Heat Area 2 until braze temperature is attained,moving torch up and down and rotating aroundtube as necessary to heat tube evenly. Add brazematerial to the joint while moving torch aroundcircumference.

    After braze material flows around joint, move torchto heat Area 3. This will draw the braze material

    down into the joint. The time spent heating Area 3should be minimal.

    As with any brazed joint, overheating may bedetrimental to the final result.

    Field Service

    To disconnect:

    Reclaim refrigerant from both the high and low sideof the system. Cut tubing near compressor.

    To reconnect:

    Recommended brazing materials; Silfos withminimum 5% silver or silver braze material withflux.

    Reinsert tube fitting.

    Heat tube uniformly in Area 1, moving slowly toArea 2. When joint reaches brazing temperature,apply brazing material.

    Heat joint uniformly around the circumference toflow braze material completely around the joint.

    Slowly move torch in Area 3 to draw braze materialinto the joint.

    Do not overheat joint.

    Scroll Tube BrazingFigure 10

  • 7/28/2019 AE1299

    10/15

    10 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Copeland Scroll K4

    Liquid Injection*

    Figure 3

    Figure 2

    Copeland Scroll K4Vapor Injection*

    * See catalog 1.401 for part information

  • 7/28/2019 AE1299

    11/15

    11 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Figure 4

  • 7/28/2019 AE1299

    12/15

    12 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    FEATURES

    Self contained unit with oil level sensor

    and integral solenoid to manage oillevel supply

    Hall-effect sensor for precisemeasurement of oil level

    Alarm and status indication by LEDs

    SPDT output contact for compressorshutdown or alarming

    Easy installation by sightglassreplacement

    Adapters suitable for various types ofcompressors including conventionaland scroll compressors

    Signal generated by gravity basedfloat-not prone to errors from foaming

    like optical sensors

    Sacrificial magnet for reliable operation

    SAFETY INSTRUCTIONS

    WARNING: Before opening any system,make sure the pressure in the system isbrought to and remains at atmosphericpressure. Failure to comply can result inpersonal injury and/or system damage.

    1. Read installation instructionsthoroughly. Failure to followinstructions may result in productfailure, system damage, or personal

    injury.

    2. Do not open system under pressure.

    3. Ensure supply voltage is withinspecified OMB limits.

    4. Disconnect supply voltage fromsystem/OMB before installation/service. Comply with local electricalregulations when wiring OMB.

    5. Do not exceed maximum workingpressure.

    6. Keep temperature within nominallimits.

    7. Work should be performed by qualifiedservice personnel or a licensed

    contractor

    SPECIFICATIONS

    Maximum WorkingPressure:

    500 psig

    Solenoid MOPD: 350 psig

    Supply Voltage: 24 VAC,50/60 Hz

    Solenoid Coil:ASC2L

    24 VAC,50/60 Hz

    Current Consumption: 0.6A

    Time Delay for Low LevelSignal:

    10 seconds

    Time Delay After SetpointRecovery:

    5 seconds

    Alarm Delay Time:(including alarm contact)

    120 seconds

    Alarm Switch:SPDT

    Alarm Contact Rating:10A-125V,5A-250V

    Refrigerant Compatibility:(not for use withflammablerefrigerants or ammonia)

    HFC, HCFC,CFC

    Refrigerant Temperature: -40F TO 180FStorage and AmbientTemp.:

    -40F TO 120F

    Ambient Temp. (Housing): -40F TO 120F

    Oil Supply fitting: Male SAE

    Compressor Adapter: See Table 1

    Table 1

    Mounting Adapter Kit

    Applications

    Adapter KitACA

    Compressor TypeCopeland Glaciers,

    ZF, ZS, ZB

    INSTALLATION INSTRUCTIONS

    1. Read installation instructions thoroughly.

    2. Assure that you have the appropriate

    mounting adapter kit for the compressor.

    See Table 1. For semi-hermetic

    compressors see steps 1A through 5A

    below. For Copeland compressors using

    adapter kit ACA see steps 1B through

    6B. For Copeland compressors using

    adapter kit ACB see steps 1C through

    6C.

    Kit ACA (Pipe Thread) for Scroll

    Compressors

    1. Assure there is no pressure in thecompressor crankcase and unscrew the pipe thread attaching the original sightglass to the compressor. Take note ofthe original oil level since oil may be lostwhen the sight glass is removed. Tip thecompressor to avoid oil loss if possible.

    2. Using PTFE tape as a sealant, threadthe adapter into the compressor withthe three hole flange installed on theadapter to capture in the assembly.The chamfered side of the threaded boltholes should face outward. Torque thepipe thread to 30-40 ft.-lbs. Take carenot to scratch the o-ring seal surface ofthe adapter.

    3. Using the O-ring and bolts provided,install the control unit to the adapterflange. The top of the control unit mustbe perfectly horizontal with the oil inletfitting to the left. Torque the bolts to 120in.-lbs.

    4. Connect the oil supply line to the inchmale flare fitting. A clean-able strainer isincorporated into the fitting.

    5. Make wiring connections in accordancewith Figure 1. Important: The screwclamp style connector plugs used for thepower supply and solenoid coil must beunplugged from the circuit board to gainaccess to the wire clamp screws. Use asmall screwdriver to pry them outward.

    6. Assure there is a proper oil level in the

    crankcase.

    Figure 5OMB Electronic Oil Level Management System Installation and Service Instructions

  • 7/28/2019 AE1299

    13/15

    13 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Figure 6B

    2-6 HP Copeland Scroll Condensing Unit Mounting

    Kit 527-0116-00

    2-6 HP Copeland Scroll Rack Mounting

    Figure 6A

    Kit 527-0157-00

  • 7/28/2019 AE1299

    14/15

    14 2010 Emerson Climate Technologies

    Printed in the U.S.A.

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Typical Suction Tubing Typical Injection Tubing

    Figure 7A Figure 7B

    NOTES:

    (1) The above tubing configurations are guidelines to minimize tube stress.

    (2) Follow similar guidelines for discharge tubing and oil return tubing as needed.

    (3) If a run of over 20 is required, intermediate clamps may be necessary.

    (4) Do not hang weights on tubing (e.g. filter drier on suction tubing) except after clamps or close to the header.

    (5) Tube runs of less than 8 are not recommended.

    (6) This dimension should be made as short as possible (e.g. 2 or less) but still insuring a proper braze joint.

    (7) The above tubing recommendations are based on no elbow joints. The use of continuous tubing is

    preferred.

    Motor Terminal (Fusite) Connections for

    Single Phase and Three Phase Scrolls

    Figure 8

  • 7/28/2019 AE1299

    15/15

    15 2010 Emerson Climate Technologies

    AE4-1299 R9

    Application Engineering

    B U L L E T I N

    Scroll Wiring Schematic

    Figure 9

    Tranformer if Required

    VAC Line Voltage

    Compressor

    Contactor

    Coil