8/10/2019 By CY Series
1/36
Air Handling UnitsDirect Expansion
BY Series(Matching with CY series Condensing units)
BY07 thru BY25
6 TR thru 30 TR
20 kW thru 105 kW
8/10/2019 By CY Series
2/36
Company Business
Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabiaand today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.
Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.
The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product andservice brands as well as a number of international brands under the OEM sales.
The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.
The four SBUs are:1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance,
retrofit & operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHUs.
The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operationsfrom the corporate headquarters in Dammam, Saudi Arabia.
Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.
All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.
Factories and Productions
Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facilityin Italy operated by Geoclima.
The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.
Quality & Product Certificates
The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.
Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization)
Certificate for Room Air Conditioners. ZACs products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (Certified Performance)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)7. ASME (American Quality of Mechanical Engineers)
Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammedbin Fahd Al Saud Award for Factory Safety.
Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Condition-ers manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from theConcealed Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin
Air Handling Units up to 138,316 CFM and the Water Chillers up to 500 TR cooling capacity.
8/10/2019 By CY Series
3/36
Contents Page
Outstanding features ................................................................................................................................ 2
Model decoding ........................................................................................................................................ 3
Blower drive options ................................................................................................................................. 4
Standard specifications ......................................................................................................................... 4-5
Options and accessories ....................................................................................................................... 5-6
Physical data ............................................................................................................................................ 7
Cooling capacities ............................................................................................................................... 8-14
Fan performance data ....................................................................................................................... 15-16
Electrical data .................................................................................................................................... 17-19
Dimensions, indoor units ................................................................................................................... 20-23
Dimensions, heater box .......................................................................................................................... 24
Dimensions, outdoor units ................................................................................................................. 25-27
Typical schematic wiring diagram ...................................................................................................... 28-31
Controls and sequence of operation ....................................................................................................... 32
Installation instructions ........................................................................................................................... 33
INDEX
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.
THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
1
8/10/2019 By CY Series
4/36
*HIGH EER (ENERGY EFFICIENCY RATIO)
*INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS
*LOW CEILING HEIGHT REQUIREMENTS
*MICROPROCESSOR BASED CONTROLS
*ONE SIDE TOTAL SERVICE ACCESSIBILITY
*SINGLE POINT POWER ENTRY
*UV FLOW LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY)
*NUMBERED CODED WIRES
*INSULATED DRAIN PAN
*FACTORY INSTALLED OPTIONS UPON REQUEST
*SMALL FOOTPRINT
*LIGHT WEIGHT
*PRE-PAINTED CABINETS WITH FIBERGLASS INSULATION
*LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTALLATION
*STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTALLATION
*ALUMINUM OR SYNTHETIC FILTERS
*UL LISTED MAJOR COMPONENTS
OUTSTANDING FEATURES
2
8/10/2019 By CY Series
5/36
MO
DELDECODING
1&2
BASIC
3&4
FACEAREA
(SQ.FT.)
7
REFRIGERATION
CIRCUIT
6
ELECTRICAL
SUPPLY
(V-Ph-Hz)
9
BLOWER
MOTOR
12
EV
APORATOR
COIL
13
FILTER
11
HEATER
OPTIONS
(kW/STAGE)
14
OTHEROPTIONS
BY
AIR
HANDLING
UNIT
07
10
14
18
25
S:SINGLE
D:DUAL
H:208/230-3-60
M:380-3-60
(4WIRE)
F:460-3-60
D:2HPODP
E:3HPODP
D:2HPODP
E:3HPODP
G:5HPODP
J:7.5HPODP
J:7.5HPODP
L:10HPODP
A:ALUMINUM
FIN
B:COATED
ALUMINUM
FIN
C:COPPERFIN
FORBY07-BY14
N
:NOHEATER
A
:5/1
B
:6/1
C
:7.5/1
D
:10/2
E
:12/2
F
:15/2
G
:20/2
H
:25/2
J
:30/2
FORBY18-BY25
N
:NOHEATER
E
:12/2
F
:15/2
G
:20/2
H
:25/2
J
:30/2
K
:35/2
L
:40/2
N:NOOPTION
V:VOLTFREE
CONTACTS*
8
MODE
C:COOLON
LY
J:ALT.I
K:ALT.II
10
DRIVE
OPTIONS
15
THERMOSTAT
OPTION
S
:UNITWITH
THERMOSTAT
D
:UNITWITHOUT
THERMOSTAT
5
ARRANGEMENT
H
:HORIZONTAL
V
:VERTICAL
FORBY07
N:NOFILTER
E:1/2"ALUMINUM
F:1/2"SYNTHETIC
A:1"ALUMINUM
C:1"SYNTHETIC
N:NOFILTER
A:1"ALUMINUM
B:2"ALUMINUM
C:1"SYNTHETIC
D:2"SYNTHETIC
N:NOFILTER
B:2"ALUMINUM
D:2"SYNTHETIC
MODELS:BY07-BY25
FORBY07
FORBY10
FORBY14/18
FORBY25
NOTE:*BlowermotorRUN/TRIPindication.
FORBY18-BY25
FORBY07-BY14
D:DUAL
FORBY10,14&18
FORBY25
3
8/10/2019 By CY Series
6/36
STANDARD SPECIFICATIONS
A. GeneralThese Zamil Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with
blower motor, DX coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applications.
The unit is ready to operate when piped to a suitable condensing unit, connected to power/controls and air ducts or
plenums.
They should be ordered separately as horizontal air discharge or vertical air discharge units as per application require-
ments.
B. Unit EnclosureCasing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1/2" thick fiberglass insulation to prevent condensation from
forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and
errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality conform-
ing to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.
C. CoilsCoils are of the enhanced louvered fin-and-tube type, constructed of copper tubes, mechanically bonded to aluminum
fins.As an opt ion, corrugated copper or enhanced coated aluminum fins may be provided. End plates and tube support
sheets are 18 gauge galvanized steel, formed to provide structural strength. Each coil is pressure tested in the factory at
not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.
D. Drain PansDrain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional
corrosion protection. Drain outlets of 3/4" NPT is provided for field connection.
E. Evaporator FanEvaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor is
mounted on an adjustable base and secured by a locking device. Fan drive is through adjustable motor pitch pulley and
belt-driven. Fan shafts are designed to operate at less than 2/3rds of the first critical speed when the unit comes up to
rated revolutions per minute (RPM). Units have sealed, permanently lubricated ball or sleeve fan bearing and are stati-
cally / dynamically balanced in the fan housing during final assembly. Fan motors are of the open drip-proof type(totally
enclosed types are optional)and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-the-
line type.
4
BLOWER DRIVE OPTIONS
MODELNUMBER OPTION
MOTOR BLOWER APPROX. SPEEDCHANGE PER
PULLEYTURN (RPM)
PULLEYPITCH DIA.
(INCH)
SPEED RANGE (RPM)
MINIMUM MAXIMUM
PULLEYPITCH DIA.
(INCH)HP RPM
BY07
BY10
BY14
BY18
BY25
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
2
3
23
5
7.5
5
7.5
7.5
10
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
2.7 - 3.7
2.7 - 3.7
3.1 - 4.1
3.1 - 4.1
3.7 - 4.7
4.3 - 5.5
3.7 - 4.7
4.3 - 5.5
4.3 - 5.5
4.3 - 5.5
893
964
733
875
809
940
809
875
685
800
1156
1321
970
1157
1028
1203
1028
1120
880
1023
5.6
4.9
7.4
6.2
8.0
8.0
8.0
8.6
11
9.4
62
71
40
47
37
44
37
40
38
44
8/10/2019 By CY Series
7/36
F. Microprocessor ControlThese air handling units are provided with a microprocessor control board incorporating the following features:
- BALANCE LOADING OF COMPRESSORS:The units electronic control automatically operates lead/lag sequenceof compressors. This is to load the compressors evenly over long periods of operation. If required however, compres-
sor-1 can also be set to always lead. In this case, compressor-1 always starts first and stops last. (Selectable throughdip switch setting on control board).
- PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoids opening and compressor starting to equalize the pressure in the system necessary for compressor to start-up. (Selectable through dip switch setting on control board).
- COMPRESSOR ANTI-RECYCLING PROTECTION:The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermo-stat due to load demand.
- COMPRESSOR LOCK-OUT FUNCTION: If any of the units safety control trips due to abnormal conditions, theelectronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system condi-tions.
- FAULT DIAGNOSTICS: In case of system fault, LEDs on the board emits a flashing signal indicating where the faultis. This is to guide the service technician in identifying the fault.
- DIGITAL I/Os: The units control board is compatible to operate with a DDC controller or any standard 24V a.c.thermostat commercially available.
- SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequen-
tial order: supply fan condenser fan compressor; at a pre-determined timings.
G. Control PanelA complete factory-wired control panel is provided to ensure safe and proper operation.
OPTIONS AND ACCESSORIESA. Electric HeatersElectric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical
characteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switchesare provided to shut-off power to heaters in case of airflow failure.
B. FiltersFilters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminumtype (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units.
C. Discharge Air Plenum & Return Air GrilleAs an accessory, discharge air plenum with return air grilles can be provided on vertical units.
D. UV Flow Light EmittersThe damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The
UV flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growthof these microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow.
To order the UV flow use the kit numbers in the table below.
MODEL NUMBER BY07 BY10 BY14 BY18 BY25
KIT PART NUMBER 700-391-18 700-391-19 700-391-20 700-391-21 700-391-22
5
8/10/2019 By CY Series
8/36
6
E. Electronic ThermostatGeneral information:Electronic thermostat shall control one or two stage heating and cooling applications. The thermo-
stat normally displays room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to
select continuous fan operation, or have the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and
should not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers/diffusers.
Single/dual stage - Cooling & heating.
Low voltage control - 24 VAC (nominal).
Room temperature display - in 0C or 0F.
Mode of operation - FAN/COOL/HEAT/AUTO.
Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.
Heating & cooling setpoint is permissible.
Temperature set button - Up for increasing & down for decreasing temperature.
Built-in compressor fault & clogged filter indication led lights.
Remote sensing function as an option. Duct sensor is provided with the thermostat.
800-652-61 1 & 2 1 & 2 OFF-HEAT/COOL ON - AUTO
TYPICAL THERMOSTAT
Part No.Heating
Stages
Cooling
Stages
Selector Switch Positions
Mode Switch Fan Switch
8/10/2019 By CY Series
9/36
Corrugated Fin & Tube
PHYSICAL DATA
MODEL NUMBER BY07 BY10 BY14 BY18 BY25
EVAPORATOR BLOWER Type Centrifugal
Nominal airflow CFM (L/S) 2800 (1321) 4600 (2171) 5500 (2596) 7000 (3303) 9000 (4247)
Motor HP (Std/Alt) 2/3 3/2 5/7.5 5/7.5 7.5/10
Drive type Belt Belt Belt Belt Belt
Blower size 12x12 15x15 15x15 15x12 18x18
Quantity 1 1 1 2 2
EVAPORATOR COIL Type
Tube dia. - Rows - FPI 3/8 - 3 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14
Face area, Sq. ft. (Sq. m.) 7 (0.65) 10 (0.93) 14 (1.3) 17.4 (1.62) 25 (2.32)
REFRIGERANT LINES Suction line size O.D. (inch) 1-1/8 1-3/8 1-3/8 - -
SINGLE COMPRESSOR Liquid line size O.D. (inch) 5/8 5/8 5/8 - -
REFRIGERANT LINES Suction line size O.D. (inch) 7/8 7/8 1-1/8 1-3/8 1-3/8
DUAL COMPRESSORLiquid line size O.D. (inch) 1/2 1/2 5/8 5/8 7/8
RETURN AIR FILTER Size (inch) 20 x 20 x 1/2 18 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 2
Quantity 3 3 3 3 3
SHIPPING WEIGHT kg. (approx.) 165 225 300 340 420
7
8/10/2019 By CY Series
10/36
NOTES: 1. Direct interpolation is permissible Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.
TC Total Capacity (1000 Btuh) GrossSC Sensible Heat Capacity (1000 Btuh) Gross
DBE Dry Bulb Temp. (0F) of Air Entering CoilWBE Wet Bulb Temp. (0F) of Air Entering Coil
DBL Dry Bulb Temp. (0F) of Air Leaving CoilWBL Wet Bulb Temp. (0F) of Air Leaving Coil
kW Total unit power inputDR Wet Bulb depression ratio
BY07 INDOOR UNIT WITH CY075 OUTDOOR UNIT
BY07 INDOOR UNIT WITH CY090 OUTDOOR UNIT
62 67 72 62 67 72 62 67 72
68.38 74.46 80.91 71.74 78.24 85.14 74.17 80.84 88.13
61.94 51.99 41.85 70.48 58.38 46.06 72.69 64.18 49.84
6.55 6.74 6.88 6.83 7 7.14 7.33 7.49 7.64
65.49 71.41 77.72 68.6 74.91 81.72 70.89 77.45 84.5
60.59 50.71 40.64 67.23 57.03 44.83 69.47 62.89 48.58
7.21 7.41 7.57 7.49 7.66 7.83 7.98 8.15 8.32
62.34 68.12 74.28 65.25 71.38 78 67.22 73.67 80.63
59.15 49.34 39.35 63.95 55.63 43.5 65.88 61.42 47.24
7.94 8.14 8.32 8.21 8.4 8.59 8.7 8.89 9.09
59.03 64.66 70.68 61.7 67.73 74.17 63.56 69.9 76.63
57.63 47.91 38.01 60.47 54.21 42.14 62.29 60.01 45.87
8.66 8.88 9.09 8.93 9.13 9.35 9.42 9.62 9.87
55.63 61.12 67.07 58.14 63.99 70.24 59.9 65.88 72.63
54.52 46.47 36.71 56.98 52.76 40.77 58.7 58.44 44.54
9.38 9.61 9.85 9.63 9.86 10.14 10.12 10.36 10.66
CONDENSER
ENTERING AIR
TEMP. (0
F)
EVAPORATOR AIRFLOW, CFM/DR
1900/0.102 2400/0.126 2900/0.148
EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
74.41 81.45 89.03 77.72 85.21 93.05 80.14 87.86 96.17
69.27 57.95 46.47 76.16 64.68 50.79 78.53 70.74 54.78
7.79 8.02 8.23 8.33 8.53 8.74 8.82 9.02 9.24
70.98 77.94 85.25 74.06 81.33 89.07 76.34 83.8 91.98
67.71 56.54 45.07 72.58 63.13 49.38 74.82 69.16 53.35
8.67 8.89 9.1 9.18 9.39 9.61 9.67 9.87 10.11
67.35 74.13 81.27 70.27 77.32 84.97 72.25 79.73 87.65
66.08 54.99 43.62 68.87 61.57 47.96 70.81 67.67 51.88
9.58 9.79 10 10.08 10.28 10.52 10.55 10.76 11.01
63.63 70.23 77.3 66.25 73.2 80.62 68.17 75.37 83.17
62.35 53.42 42.2 64.92 59.98 46.45 66.8 66.01 50.38
10.47 10.68 10.91 10.95 11.16 11.42 11.42 11.64 11.9259.8 66.23 73.03 62.22 68.95 76.16 63.93 71.02 78.55
58.61 51.85 40.67 60.98 58.36 44.91 62.66 64.43 48.84
11.34 11.55 11.81 11.82 12.03 12.33 12.29 12.51 12.84
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
2250/0.118 2800/0.144 3350/0.168
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kWTC
125 SC
kW
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
COOLING CAPACITIES(Single compressor units)
BY10 INDOOR UNIT WITH CY100 OUTDOOR UNIT
TC
85 SC
kW
TC
95 SC
kW
TC105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
62 67 72 62 67 72 62 67 72
93.7 101.72 110.43 97.19 105.68 114.75 99.69 108.38 118.1
84.45 69.89 55.2 91.35 77.72 60.21 93.71 85.01 65.01
8.88 9.09 9.34 9.11 9.32 9.62 9.49 9.72 10.05
90.53 98.45 106.93 93.78 102.15 111.09 96.21 104.74 114.14
83.14 68.66 54.01 88.15 76.41 59.02 90.44 83.72 63.74
9.72 9.92 10.16 9.94 10.14 10.43 10.3 10.53 10.86
86.75 94.68 103.07 89.93 98.17 106.98 92.2 100.75 11081.54 67.26 52.71 84.53 74.97 57.68 86.67 82.36 62.44
10.64 10.85 11.14 10.85 11.08 11.42 11.22 11.46 11.85
82.96 90.68 99.09 85.78 94.04 102.88 88.02 96.42 105.69
77.99 65.75 51.38 80.63 73.49 56.36 82.74 80.8 61.08
11.57 11.81 12.14 11.78 12.04 12.44 12.15 12.43 12.89
78.57 86.31 94.62 81.33 89.47 98.19 83.31 91.73 100.86
73.86 64.17 49.9 76.45 71.88 54.86 78.31 79.2 59.56
12.61 12.87 13.27 12.81 13.11 13.59 13.18 13.51 14.06
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
2800/0.05 3400/0.066 4000/0.076
EVAPORATOR ENTERING AIR, WBE (0F)
8
8/10/2019 By CY Series
11/36
NOTES: 1. Direct interpolation is permissible Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.
TC Total Capacity (1000 Btuh) GrossSC Sensible Heat Capacity (1000 Btuh) Gross
DBE Dry Bulb Temp. (0F) of Air Entering CoilWBE Wet Bulb Temp. (0F) of Air Entering Coil
DBL Dry Bulb Temp. (0F) of Air Leaving CoilWBL Wet Bulb Temp. (0F) of Air Leaving Coil
kW Total unit power inputDR Wet Bulb depression ratio
BY10 INDOOR UNIT WITH CY120 OUTDOOR UNIT
BY10 INDOOR UNIT WITH CY150 OUTDOOR UNIT
62 67 72 62 67 72 62 67 72
112.8 122.36 132.41 117.12 127.11 137.76 120.05 130.47 141.72
106.89 88.89 70.55 114.78 99.61 77.42 117.65 109.78 83.96
11.14 11.44 11.76 11.62 11.92 12.29 12.25 12.57 12.98
104.71 113.62 123.17 108.58 118.09 128.1 111.48 121.11 131.79
101.14 83.56 65.79 106.41 94.18 72.55 109.25 104.12 79
11.88 12.18 12.52 12.34 12.65 13.06 12.98 13.3 13.77
96.63 105.02 113.93 100.04 108.9 118.45 102.69 111.75 121.66
91.8 76.15 59.36 95.04 86.1 65.79 97.56 95.63 71.82
12.58 12.87 13.24 13.03 13.35 13.8 13.66 14 14.5
91.61 99.75 108.41 94.81 103.35 112.59 97.05 105.92 115.66
87.03 74.19 57.52 90.07 84.12 63.91 92.19 93.56 69.98
13.25 13.56 13.96 13.7 14.03 14.51 14.33 14.68 15.23
85.33 93.09 101.38 88.37 96.42 105.17 90.35 98.84 108
81.07 71.74 55.21 83.95 81.68 61.56 85.84 91.19 67.62
14.04 14.35 14.8 14.48 14.83 15.36 15.11 15.48 16.09
CONDENSER
ENTERING AIR
TEMP. (0
F)
EVAPORATOR AIRFLOW, CFM/DR
3200/0.059 4000/0.076 4800/0.092
EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
130.72 141.5 152.59 133.69 144.78 156.04 135.29 146.53 157.97
121.42 100.28 78.76 129.68 107.7 83.43 131.24 112.45 86.44
13.6 13.95 14.33 14.07 14.42 14.82 14.43 14.78 15.2
125.32 135.95 146.9 128.08 139 150.29 129.63 140.68 152.16
119.09 98.14 76.77 124.24 105.5 81.48 125.74 110.26 84.5
14.91 15.27 15.68 15.37 15.73 16.17 15.73 16.09 16.55
119.22 129.71 140.69 121.86 132.62 143.95 123.31 134.18 145.69
115.64 95.74 74.65 118.21 103.13 79.37 119.61 107.86 82.36
16.35 16.73 17.17 16.8 17.18 17.67 17.15 17.54 18.05
113.64 123.99 135 116.05 126.83 138.2 117.43 128.32 139.87
110.23 93.55 72.7 112.57 101 77.45 113.91 105.74 80.45
17.63 18.03 18.52 18.08 18.48 19.02 18.43 18.84 19.41107.89 118.27 129.48 110.24 121.05 132.45 111.55 122.47 134.27
104.65 91.39 70.85 106.93 98.89 75.55 108.2 103.63 78.67
18.9 19.32 19.87 19.34 19.77 20.38 19.69 20.13 20.77
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
4000/0.076 4600/0.088 5000/0.095
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kWTC
125 SC
kW
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
COOLING CAPACITIES(Single compressor units)
BY14 INDOOR UNIT WITH CY150 OUTDOOR UNIT
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
62 67 72 62 67 72 62 67 72
141.18 152.95 164.83 145.99 157.94 170.28 149.86 162.43 175.25
132.88 110.4 87.29 143.07 121.29 94.24 146.87 134.31 102.5
13.72 14.07 14.51 14.23 14.6 15.1 15.12 15.52 16.09
135.25 146.88 158.79 139.71 151.7 164.07 143.55 155.9 168.75
130.17 107.9 85.06 136.92 118.83 92.04 140.68 131.77 100.23
15.04 15.41 15.89 15.54 15.93 16.48 16.42 16.85 17.48
128.63 140.12 152.07 132.81 144.62 157.24 136.47 148.6 161.75
127.21 105.14 82.6 130.15 116.02 89.65 133.74 128.95 97.85
16.49 16.89 17.41 16.99 17.41 18.03 17.86 18.32 19.03
122.53 133.87 146.03 126.33 138.38 151.03 129.9 142.32 155.5
120.08 102.58 80.42 123.8 113.62 87.47 127.3 126.67 95.74
17.79 18.21 18.79 18.28 18.73 19.42 19.15 19.65 20.44
116.43 127.8 140 120.05 131.93 145.03 123.33 135.78 149.5
114.1 100.19 78.24 117.65 111.07 85.42 120.86 124.17 93.79
19.07 19.52 20.18 19.57 20.05 20.82 20.43 20.98 21.85
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
4000/0.050 4800/0.062 5800/0.076
EVAPORATOR ENTERING AIR, WBE (0F)
9
8/10/2019 By CY Series
12/36
8/10/2019 By CY Series
13/36
NOTES: 1. Direct interpolation is permissible Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.
TC Total Capacity (1000 Btuh) GrossSC Sensible Heat Capacity (1000 Btuh) Gross
DBE Dry Bulb Temp. (0F) of Air Entering CoilWBE Wet Bulb Temp. (0F) of Air Entering Coil
DBL Dry Bulb Temp. (0F) of Air Leaving CoilWBL Wet Bulb Temp. (0F) of Air Leaving Coil
kW Total unit power inputDR Wet Bulb depression ratio
BY10 INDOOR UNIT WITH CY120 OUTDOOR UNIT
BY10 INDOOR UNIT WITH CY150 OUTDOOR UNIT
62 67 72 62 67 72 62 67 72
114.47 125.97 138.9 119.74 132.31 146.38 123.61 136.72 151.86
105.56 88.62 71.58 117.34 99.74 78.98 121.14 109.99 85.79
11.43 12 12.59 12.01 12.6 13.21 12.73 13.32 13.95
108.48 119.86 132.55 113.46 125.72 139.66 116.92 130.06 144.83
102.83 86.12 69.21 111.19 97.12 76.6 114.58 107.51 83.38
11.98 12.66 13.37 12.59 13.29 14.04 13.33 14.04 14.83
102.34 113.48 125.93 106.84 118.96 132.59 110.01 122.98 137.38
100.13 83.53 66.79 104.7 94.51 74.13 107.81 104.87 80.86
12.52 13.3 14.14 13.16 13.96 14.86 13.91 14.74 15.67
96.63 107.51 119.86 100.74 112.72 126.03 103.95 116.32 130.34
96.63 81.11 64.61 98.73 92.12 71.87 101.87 102.33 78.47
13.04 13.92 14.88 13.7 14.61 15.64 14.47 15.41 16.48
90.07 100.72 112.69 93.77 105.43 118.28 96.63 108.83 122.28
88.27 78.45 62.06 91.89 89.37 69.21 94.69 99.64 75.8
13.67 14.67 15.79 14.35 15.4 16.59 15.12 16.22 17.45
CONDENSERENTERING AIR
TEMP. (0
F)
EVAPORATOR AIRFLOW, CFM/DR
3200/0.059 4000/0.076 4800/0.092
EVAPORATOR ENTERING AIR, WBE (0F)
62 67 72 62 67 72 62 67 72
131.07 143.06 155.86 134.29 146.58 160.01 136.17 148.7 162.28
121.55 100.91 79.91 130.26 108.33 84.78 132.08 113.24 87.87
14.08 14.41 14.73 14.54 14.86 15.2 14.9 15.22 15.56
124.62 136.3 148.97 127.68 139.79 152.87 129.41 141.76 154.96
118.74 98.25 77.51 123.85 105.81 82.37 125.53 110.7 85.42
15.52 15.88 16.26 15.98 16.33 16.74 16.33 16.68 17.1
118.17 129.54 141.72 120.86 132.62 145.34 122.44 134.39 147.41
114.62 95.68 74.99 117.24 103.1 79.81 118.77 107.93 82.93
16.95 17.35 17.79 17.4 17.8 18.28 17.75 18.15 18.65
111.37 122.43 134.48 113.85 125.44 137.8 115.25 127.02 139.66
108.03 92.97 72.55 110.43 100.5 77.32 111.79 105.28 80.39
18.38 18.81 19.34 18.83 19.27 19.85 19.18 19.63 20.23105.1 116.01 127.76 107.43 118.66 130.86 108.71 120.3 132.54
101.95 90.58 70.28 104.21 97.97 75.05 105.45 102.89 78.08
19.64 20.12 20.74 20.09 20.59 21.26 20.44 20.95 21.65
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
4000/0.076 4600/0.088 5000/0.095
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kWTC
125 SC
kW
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
COOLING CAPACITIES(Dual compressor units)
BY14 INDOOR UNIT WITH CY150 OUTDOOR UNIT
TC
85 SC
kW
TC
95 SC
kW
TC105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
62 67 72 62 67 72 62 67 72
136.47 149.13 162.76 141.39 154.82 169.24 145.82 159.92 175.25
125.59 104.51 83.1 137.14 115.31 90.16 141.45 128.04 98.44
14.32 14.64 15 14.82 15.14 15.54 15.7 16.03 16.48
129.67 142.02 155.34 134.27 147.33 161.59 138.49 152.12 167
122.62 101.7 80.47 130.25 112.45 87.58 134.34 125.19 95.7
15.8 16.15 16.59 16.29 16.66 17.15 17.16 17.55 18.1
122.7 134.74 147.76 126.95 139.63 153.52 130.66 144.08 158.75119.02 98.86 77.82 123.15 109.55 84.84 126.74 122.24 93.04
17.26 17.67 18.18 17.75 18.18 18.77 18.63 19.09 19.75
115.56 127.28 140 119.42 131.93 145.24 122.82 136.03 150
112.09 96.01 75.15 115.84 106.76 82.07 119.14 119.43 90.17
18.73 19.19 19.8 19.22 19.71 20.43 20.09 20.63 21.43
109.11 120.52 132.93 112.52 124.65 137.79 115.75 128.49 142.25
105.83 93.47 72.76 109.15 104.03 79.63 112.27 116.7 87.72
20.02 20.54 21.27 20.52 21.08 21.92 21.4 22.02 22.97
CONDENSERENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
4000/0.05 4800/0.062 5800/0.076
EVAPORATOR ENTERING AIR, WBE (0F)
11
8/10/2019 By CY Series
14/36
NOTES: 1. Direct interpolation is permissible Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.
TC Total Capacity (1000 Btuh) GrossSC Sensible Heat Capacity (1000 Btuh) Gross
DBE Dry Bulb Temp. (0F) of Air Entering CoilWBE Wet Bulb Temp. (0F) of Air Entering Coil
DBL Dry Bulb Temp. (0F) of Air Leaving CoilWBL Wet Bulb Temp. (0F) of Air Leaving Coil
kW Total unit power inputDR Wet Bulb depression ratio
BY14 INDOOR UNIT WITH CY180 OUTDOOR UNIT
62 67 72 62 67 72 62 67 72
167.37 182.36 198.38 174.95 190.75 207.91 180.31 196.86 214.78
148.38 124.49 100.23 168.42 139.28 109.92 178.51 153.29 118.92
15.98 16.38 16.77 16.88 17.26 17.69 18.16 18.53 19.01
160.47 175.3 190.98 167.52 183.36 200.09 172.55 189.13 206.53
145.18 121.57 97.46 165.1 136.42 107.15 170.82 150.41 116.08
17.54 17.94 18.35 18.42 18.8 19.27 19.68 20.07 20.59
152.99 167.48 183.02 159.61 175.01 191.55 164.5 180.55 197.72
141.81 118.35 94.53 158.01 133.12 104.14 162.85 147.16 113.09
19.27 19.66 20.12 20.12 20.52 21.04 21.37 21.78 22.38
145.32 159.66 174.86 151.46 166.67 183.02 155.87 171.68 188.9
138.4 115.22 91.56 149.95 129.91 101.2 154.31 143.77 110.17
20.96 21.37 21.88 21.81 22.22 22.83 23.04 23.49 24.18
137.46 151.46 166.71 143.31 158.09 174.25 147.24 162.81 179.79
134.94 111.91 88.66 141.88 126.61 98.19 145.77 140.48 107.15
22.64 23.07 23.65 23.46 23.92 24.63 24.69 25.19 26
CONDENSER
ENTERING AIR
TEMP. (0
F)
EVAPORATOR AIRFLOW, CFM/DR
4400/0.056 5500/0.073 6600/0.088
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
COOLING CAPACITIES(Dual compressor units)
BY18 INDOOR UNIT WITH CY180 OUTDOOR UNIT
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kWTC
125 SC
kW
62 67 72 62 67 72 62 67 72
176.47 192.66 209.84 183.92 201.29 219.69 189.49 207.19 226.5
163.61 136.38 108.63 182.08 153.4 119.75 187.6 169.31 129.96
16.72 17.13 17.59 17.44 17.85 18.39 18.38 18.81 19.42
168.99 185 202 176.24 193.1 211.27 181.27 198.68 217.71
160.21 133.27 105.79 174.47 150.21 116.83 179.45 166.1 127.02
18.34 18.75 19.26 19.04 19.47 20.06 19.96 20.43 21.1
161.07 176.68 193.29 167.73 184.36 202.03 172.38 189.51 208.28
156.79 129.94 102.63 166.05 146.89 113.62 170.66 162.68 123.87
20.14 20.57 21.14 20.81 21.28 21.97 21.73 22.24 23.03
152.71 168.14 184.59 158.94 175.34 192.8 163.5 180.35 198.84
151.18 126.55 99.54 157.35 143.44 110.47 161.87 159.36 120.79
21.92 22.37 23.03 22.58 23.09 23.9 23.49 24.06 24.98144.35 159.6 175.88 150.16 166.33 183.57 154.29 170.86 189.08
142.91 123.25 96.51 148.66 140.1 107.38 152.75 155.86 117.58
23.68 24.17 24.95 24.33 24.9 25.85 25.23 25.88 26.98
CONDENSER
ENTERING AIRTEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
5050/0.052 6300/0.067 7550/0.082
EVAPORATOR ENTERING AIR, WBE (0F)
BY18 INDOOR UNIT WITH CY220 OUTDOOR UNIT
62 67 72 62 67 72 62 67 72
201.12 217.84 235.74 210 227.78 246.84 216.47 235.01 254.49
176.71 148.27 119.48 199.83 165.44 130.66 212.14 181.79 140.9
20.12 20.64 21.14 20.89 21.39 21.94 21.82 22.32 22.94
193.86 210.39 227.69 202.31 219.59 238.15 208.24 226.17 245.7
173.3 145.15 116.4 196.46 162.12 127.49 204.08 178.24 137.87
22.01 22.55 23.08 22.76 23.27 23.88 23.69 24.2 24.88
186.38 202.51 219.63 194.35 211.4 229.46 200.02 217.66 236.59169.81 141.82 113.38 192.94 158.9 124.38 196.02 175.04 134.72
23.89 24.43 25.01 24.61 25.15 25.81 25.53 26.07 26.82
178.68 194.63 211.36 186.12 202.93 220.77 191.46 208.83 227.48
166.24 138.58 110.3 182.4 155.56 121.34 187.63 171.68 131.65
25.76 26.3 26.93 26.46 27.01 27.75 27.35 27.94 28.78
170.09 185.43 201.78 177.06 193.37 210.72 181.92 198.68 216.74
162.39 134.77 106.76 173.52 151.86 117.82 178.29 167.8 127.96
27.8 28.37 29.06 28.49 29.07 29.92 29.37 30.01 30.97
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
5050/0.054 6300/0.069 7550/0.085
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
12
8/10/2019 By CY Series
15/36
NOTES: 1. Direct interpolation is permissible Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.
TC Total Capacity (1000 Btuh) GrossSC Sensible Heat Capacity (1000 Btuh) Gross
DBE Dry Bulb Temp. (0F) of Air Entering CoilWBE Wet Bulb Temp. (0F) of Air Entering Coil
DBL Dry Bulb Temp. (0F) of Air Leaving CoilWBL Wet Bulb Temp. (0F) of Air Leaving Coil
kW Total unit power inputDR Wet Bulb depression ratio
BY18 INDOOR UNIT WITH CY240 OUTDOOR UNIT
62 67 72 62 67 72 62 67 72
221.8 240.1 259.48 231.81 250.97 271.25 238.64 258.55 279.88
188.82 158.41 127.52 213.75 176.76 139.28 231.48 193.93 150.34
21.87 22.51 23.08 22.83 23.42 24.02 24.01 24.48 25.24
214.24 232.09 251.03 223.57 242.47 262.5 230.22 249.45 270.47
185.37 155.11 124.39 210.14 173.46 136.25 223.32 190.44 147.14
23.87 24.49 25.06 24.8 25.37 25.99 25.75 26.37 27.2
206.19 223.84 242.34 215.03 233.37 253.15 221.07 240.35 260.69
181.79 151.81 121.22 206.56 169.9 132.99 214.44 187.14 143.85
26.1 26.69 27.26 26.98 27.53 28.18 27.85 28.46 29.39
197.89 215.1 233.41 206.19 224.26 243.79 211.92 230.88 250.91
178.1 148.26 117.99 200 166.42 129.79 205.56 183.65 140.62
28.29 28.86 29.43 29.13 29.67 30.35 29.9 30.58 31.56
188.37 205.39 223.28 196.12 213.95 232.93 201.67 219.95 240.05
173.88 144.41 114.37 190.24 162.52 126.07 195.62 179.56 137.11
30.69 31.22 31.83 31.48 32.01 32.75 32.25 32.85 33.99
CONDENSER
ENTERING AIR
TEMP. (0
F)
EVAPORATOR AIRFLOW, CFM/DR
5600/0.061 7000/0.078 8400/0.094
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
COOLING CAPACITIES(Dual compressor units)
62 67 72 62 67 72 62 67 72
228.24 247.37 267.41 239.54 259.47 281.25 247.06 268.05 290.56
195.68 163.58 130.77 223.35 183.85 144.21 234.71 203.1 156.42
22.42 23 23.62 23.09 23.66 24.39 23.95 24.54 25.38
220.39 238.79 258.62 230.72 250.69 271.88 238.04 258.68 280.86
192.32 160.12 127.63 219.18 180.62 141.03 226.14 199.73 153.27
24.38 24.95 25.58 25.01 25.59 26.35 25.85 26.45 27.36
211.76 229.94 249.57 221.57 240.93 261.85 228.24 248.54 270.78
188.54 156.65 124.45 210.49 176.85 137.61 216.82 195.94 150.02
26.56 27.11 27.77 27.15 27.72 28.54 27.95 28.57 29.55
203.14 221.1 240.26 212.42 231.5 252.16 218.82 238.79 260.3
184.87 153.26 121.2 201.8 173.41 134.43 207.88 192.55 146.63
28.7 29.25 29.94 29.25 29.83 30.73 30.05 30.68 31.77193.2 210.95 229.66 201.96 220.77 240.84 207.84 227.47 248.66
180.61 149.37 117.53 191.86 169.51 130.69 197.45 188.51 142.95
31.05 31.59 32.36 31.57 32.16 33.18 32.34 33.01 34.24
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
6000/0.041 7500/0.054 9000/0.067
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kWTC
125 SC
kW
BY25 INDOOR UNIT WITH CY240 OUTDOOR UNIT
BY25 INDOOR UNIT WITH CY300 OUTDOOR UNIT
62 67 72 62 67 72 62 67 72
275.76 298.09 321.21 287.45 310.97 334.78 295.53 319.32 344.02
246.81 206.13 164.71 279.95 230.66 180.24 289.62 253.39 194.65
26.05 26.75 27.47 27.03 27.71 28.55 28.38 29.09 30.03
264.78 286.86 309.72 275.69 298.87 323.15 283.76 307.14 332.38
241.71 201.43 160.37 274.69 225.75 176.12 278.09 248.71 190.73
28.39 29.1 29.87 29.35 30.05 30.95 30.68 31.42 32.44
252.24 274.06 297 262.75 285.61 309.57 269.65 293.57 318.41235.98 196.17 155.69 262.75 220.63 171.3 264.25 243.7 185.92
31.2 31.94 32.78 32.12 32.87 33.88 33.45 34.24 35.38
240.63 262.2 285.21 250.59 273.12 297.54 257.41 280.92 306.31
230.7 191.29 151.34 250.59 215.66 167.1 252.26 238.89 181.87
33.71 34.47 35.39 34.61 35.4 36.51 35.91 36.76 38.04
229.02 250.65 273.72 238.04 261.03 285.52 244.71 268.28 294.21
225.57 186.71 147.21 233.28 211.06 162.92 239.81 234.12 177.83
36.19 36.99 38.02 37.07 37.91 39.16 38.36 39.29 40.72
CONDENSER
ENTERING AIR
TEMP. (0F)
EVAPORATOR AIRFLOW, CFM/DR
7200/0.052 9000/0.067 10800/0.082
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC105 SC
kW
TC
115 SC
kW
TC
125 SC
` kW
13
8/10/2019 By CY Series
16/36
COOLING CAPACITIES(Dual compressor units)
BY25 INDOOR UNIT WITH CY360 OUTDOOR UNIT
NOTES: 1. Direct interpolation is permissible Do not extrapolate.2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.
TC Total Capacity (1000 Btuh) GrossSC Sensible Heat Capacity (1000 Btuh) Gross
DBE Dry Bulb Temp. (0
F) of Air Entering CoilWBE Wet Bulb Temp. (0F) of Air Entering Coil
DBL Dry Bulb Temp. (0
F) of Air Leaving CoilWBL Wet Bulb Temp. (0F) of Air Leaving Coil
kW Total unit power inputDR Wet Bulb depression ratio
62 67 72 62 67 72 62 67 72
334.9 364.81 396.08 344.97 375.54 407.78 352.94 383.93 417.41
304.4 255.21 204.79 331.8 275.15 217.53 345.88 294.2 229.85
35.79 36.73 37.61 36.92 37.83 38.74 38.21 39.09 40.05
321.57 350.77 381.72 330.78 360.98 393.3 338.3 369.36 402.41
298.38 249.32 199.36 325.48 269.25 212.3 331.53 288.61 224.57
38.58 39.51 40.42 39.7 40.58 41.54 40.96 41.84 42.87
305.49 334.38 365.43 314.31 344.59 376.55 321.57 352.2 385.34
290.83 242.41 193.28 308.03 262.75 206.27 315.14 281.85 218.6
41.69 42.59 43.56 42.76 43.65 44.7 44 44.9 46.04
289.8 318.38 348.75 297.84 327.75 359.35 304.31 335.03 367.76
283.9 235.95 187.09 291.89 256.06 200.09 298.23 275.23 212.44
44.74 45.64 46.7 45.78 46.69 47.87 47 47.94 49.23
273.33 301.99 332.46 280.92 310.9 342.61 287.06 317.86 350.69
267.87 229.35 181.21 275.3 249.51 194.25 281.32 268.75 206.66
47.74 48.66 49.85 48.76 49.71 51.05 49.97 50.96 52.44
CONDENSER
ENTERING AIR
TEMP. (0
F)
EVAPORATOR AIRFLOW, CFM/DR
9000/0.065 10500/0.079 12000/0.092
EVAPORATOR ENTERING AIR, WBE (0F)
TC
85 SC
kW
TC
95 SC
kW
TC
105 SC
kW
TC
115 SC
kW
TC
125 SC
kW
14
8/10/2019 By CY Series
17/36
FAN PERFORMANCE DATABELT DRIVEN MOTORS
MODEL No.: BY07
NOTES : 1. Values include losses for filters, unit casing and wet coils.2. 2 HP motor and alternative drive I to be used for the unshaded portion.3. 3 HP motor and alternative drive II to be used for the shaded portion.
2800 (1321)
3000 (1416)
3200 (1510)
3400 (1605)
3600 (1699)
3800 (1793)
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2170)4800 (2265)
5000 (2360)
Ai rfl ow,CFM (L/S)
0.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
610 0.62 710 0.75 745 0.87 760 0.95 850 1.2
625 0.69 720 0.80 760 0.95 810 1.12 865 1.25
636 0.77 734 0.92 780 1.06 820 1.26 870 1.38
660 0.88 746 1.01 805 1.18 833 1.34 881 1.5
675 1.0 760 1.16 820 1.32 848 1.48 900 1.66
700 1.13 778 1.3 840 1.43 868 1.63 913 1.8
727 1.28 790 1.45 865 1.62 882 1.8 926 1.96
772 1.41 843 1.62 880 1.78 921 1.96 968 2.16
791 1.58 864 1.79 887 1.94 934 2.14 979 2.34
840 1.79 890 1.96 931 2.2 975 2.38 1017 2.59857 1.95 906 2.17 947 2.4 988 2.57 1035 2.76
876 2.15 920 2.38 961 2.6 1005 2.76
External Static Pressure (inch wg.)0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
905 1.32 965 1.5 1000 1.6 1054 1.8 1100 2.0
915 1.4 970 1.6 1013 1.75 1065 2.0 1115 2.15
925 1.51 978 1.73 1023 1.86 1073 2.1 1122 2.28
939 1.67 983 1.84 1033 2.02 1083 2.25 1128 2.44
950 1.82 995 1.98 1043 2.21 1090 2.41 1131 2.6
966 2.0 1006 2.18 1056 2.39 1100 2.58 1143 2.78
980 2.18 1023 2.4 1066 2.6 1108 2.77
1011 2.36 1054 2.56 1096 2.76
1024 2.54 1067 2.77
1058 2.77
MODEL No.: BY10
I
II
15
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
820* 0.62* 900 0.71 965 0.82 1020 0.88 1102 1.03
824* 0.7* 905 0.79 970 0.91 1026 1.0 1107 1.12
853 0.81 927 0.91 986 1.02 1041 1.13 1111 1.25
950 0.94 1004 1.05 1059 1.21 1132 1.27 1155 1.38
968 1.1 1032 1.22 1086 1.33 1150 1.45 1194 1.57
1054 1.4 1106 1.5 1160 1.61 1216 1.76 1261 1.88
1066 1.55 1133 1.7 1180 1.82 1234 1.94 1276 2.09
1091 1.75 1157 1.91 1202 2.02 1255 2.2 1307 2.33
1116 1.96 1171 2.1 1228 2.3 1276 2.45 1329 2.6
1800 (849)
2000 (944)
2200 (1038)
2400 (1133)
2600 (1227)
2800 (1321)
3000 (1416)
3200 (1510)
3400 (1605)
Ai rfl ow,CFM (L/S)
External Static Pressure (inch wg.)1.0 1.2 1.4
RPM BHP RPM BHP
1145 1.14 1220 1.26
1152 1.25 1225 1.35
1160 1.36 1237 1.48
1244 1.5 1297 1.65
1250 1.69 1305 1.82
1323 2.02 1380* 2.2*
1334* 2.23* 1400* 2.3*
1359* 2.47*
1368* 2.73*
0.80.60.40.2
I
II
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2170)
4800 (2265)5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)
Air flo w,CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
694* 1.21* 743* 1.3* 797 1.52 845 1.66 890 1.83
705* 1.33* 761* 1.45* 811 1.67 857 1.81 903 2.0
719* 1.43* 774 1.6 823 1.8 869 1.97 918 2.17
735* 1.57* 787 1.75 835 1.95 885 2.17 929 2.34
748* 1.72* 800 1.92 846 2.09 897 2.35 935 2.52761* 1.87* 812 2.09 862 2.30 904 2.52 948 2.70
778 2.06 823 2.27 873 2.48 917 2.70 959 2.91
800 2.31 846 2.5 894 2.72 934 2.94 979 3.15
808 2.46 858 2.7 903 2.90 945 3.12 987 3.38
826 2.68 869 2.9 917 3.12 955 3.4 1000 3.65
837 2.90 885 3.12 927 3.37 965 3.64 1009 3.9
850 3.12 900 3.41 940 3.65 980 3.92 1021 4.17
879 3.41 920 3.70 962 3.96 1000 4.2 1040 4.45
894 3.76 933 4.0 973 4.24 1013 4.44 1050 4.68
0.2
External Static Pressure (inch wg.)
MODEL No.: BY14
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
937 2.03 975 2.25 992 2.4 1075 2.64 1102 2.85
951 2.19 992 2.43 1002 2.6 1080 2.82 1110 3.05
963 2.33 1006 2.58 1010 2.78 1093 2.97 1133 3.2
971 2.55 1013 2.75 1053 2.93 1100 3.17 1138 3.41
979 2.72 1023 2.91 1065 3.14 1107 3.4 1144 3.62989 2.91 1032 3.11 1068 3.37 1113 3.6 1150 3.86
1001 3.11 1038 3.34 1070 3.59 1119 3.85 1159 4.08
1019 3.38 1056 3.64 1098 3.88 1133 4.10 1171 4.36
1028 3.65 1063 3.83 1106 4.14 1139 4.35 1176 4.57
1041 3.9 1078 4.13 1114 4.37 1150 4.6 1186 4.78
1047 4.13 1088 4.35 1123 4.59 1157 4.85 1194 5.05
1061 4.38 1100 4.66 1133 4.85 1167 5.1 1205 5.41078 4.69 1114 4.92 1150 5.2 1183 5.45 1218 5.76
1091 4.92 1125 5.2 1161 5.51 1194 5.8 1229 6.08
I II
NOTES : 1. Values include losses for filters, unit casing and wet coils.2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
NOTES : 1. Values include losses for filters, unit casing and wet coils.2. 2 HP motor and alternative drive I to be used for the unshaded portion.3. 3 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
8/10/2019 By CY Series
18/36
FAN PERFORMANCE DATABELT DRIVEN MOTORS
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
955 2.66 1005 2.96 1057 3.3 1104 3.6 1153* 3.88
961 2.83 1010 3.15 1060 3.46 1107 3.76 1155* 4.04
966 2.96 1012 3.23 1062 3.57 1109 3.88 1157* 4.27
968 3.07 1015 3.38 1065 3.73 1110 4.07 1158* 4.4*
970 3.23 1020 3.53 1066 3.84 1113 4.18 1159* 4.59
980 3.4 1025 3.69 1070 4.0 1118 4.4 1162* 4.72
985 3.56 1030 3.84 1080 4.27 1120 4.63 1163* 4.95
990 3.72 1036 4.04 1082 4.45 1126 4.82 1165* 5.09
1000 3.88 1045 4.23 1083 4.6 1127 5 1170* 5.3*
1004 4.14 1050 4.47 1090 4.83 1134 5.16 1175* 5.51
1012 4.28 1054 4.66 1095 5.04 1135 5.39 1179* 5.72
1017 4.47 1059 4.85 1100 5.19 1141* 5.58* 1183* 5.95
1021 4.68 1065 5.09 1108 5.47 1150* 5.8* 1185* 6.12
1026 4.85 1069 5.23 1112 5.66 1154* 6* 1193* 6.42
1041 5.14 1083 5.47 1125 5.9 1158* 6.36* 1200* 6.78
1046 5.33 1087 5.75 1128 6.12 1164* 6.6*1054 5.56 1100 6 1132 6.36 1172* 6.84*
1066 5.85 1107 6.24 1140 6.72
5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)
6800 (3209)
7000 (3303)
7200 (3398)
7400 (3492)
7600 (3587)
7800 (3681)
8000 (3775)8200 (3870)
8400 (3964)
Air flo w,CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
715* 1.33* 731* 1.56* 787* 1.82* 850 2.07 902 2.4
718* 1.42* 737* 1.68* 793* 1.96* 856 2.26 905 2.53
721* 1.53* 750* 1.81* 802* 2.07* 860 2.35 911 2.66
725* 1.68* 756* 1.92* 807 2.21 866 2.5 916 2.79
729* 1.81* 762* 2.03* 816 2.35 872 2.64 921 2.9
733* 1.9* 775* 2.14* 833 2.42 877 2.78 930 3.02
738* 2.03* 788* 2.35* 839 2.57 888 2.92 935 3.24
745* 2.15* 795* 2.5* 850 2.71 900 3.08 940 3.41
753* 2.38* 800* 2.64* 855 2.92 905 3.25 950 3.58
761* 2.5* 810 2.78 863 3.08 910 3.41 960 3.75
772* 2.69* 820 2.92 875 3.33 918 3.58 967 3.95
777* 2.84* 830 3.08 880 3.41 927 3.75 976 4.14
794* 2.96* 845 3.3 890 3.62 936 3.95 985 4.4
805 3.18 850 3.5 900 3.83 941 4.2 990 4.57
820 3.36 870 3.69 909 4.1 954 4.5 1002 4.9
830 3.59 880 3.86 922 4.25 963 4.65 1008 5.05867 3.77 890 4.1 936 4.5 972 4.9 1016 5.25
890 4.05 904 4.42 945 4.75 986 5.1 1025 5.45
0.2External Static Pressure (inch wg.)
MODEL No.: BY18
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
NOTES : 1. Values include losses for filters, unit casing and wet coils.2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
I II
16
BHP RPM BHP RPM BHP RPM BHP RPM BHP4.5 940 5.0 980 5.46 1010 6.0 1059* 6.6*
4.73 942 5.23 981 5.71 1011 6.3 1060* 6.92
4.96 944 5.45 982 5.97 1013 6.6 1062* 7.22
5.2 945 5.68 983 6.23 1014 6.95 1063* 7.51
5.45 947 5.9 985 6.5 1016 7.25 1064* 7.78
5.65 948 6.12 986 6.8 1018 7.5 1065* 8.05
5.97 949 6.48 988 7.2 1019 7.8 1066* 8.35
6.3 951 6.8 990 7.6 1020 8.1 1067* 8.65
6.75 953 7.15 992 8.0 1021 8.45 1068* 9.0*
7.1 955 7.6 994 8.35 1022 8.75 1069* 9.45
7.4 957 8.06 996 8.71 1023 9.25 1070* 9.8*
7.85 965 8.4 1003 9.1 1034* 9.7*
8.3 973 8.8 1009 9.5
8.7 981 9.25 1014 9.9
9.15 989 9.6
9.6 996 10.1
NOTES: 1. Values include losses for filters, unit casing and wet coils.2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.
*For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
6000 (2832)
6400 (3020)
6800 (3209)
7200 (3398)
7600 (3587)
8000 (3775)
8400 (3964)
8800 (4152)
9200 (4341)
9600 (4530)
10000 (4719)
10400 (4907)
10800 (5096)
11200 (5286)
11600 (5474)
12000 (5663)
Air flo w,CFM (L/S)
0.4External Static Pressure (inch wg.)
MODEL No.: BY25
0.6 0.8 1.0 1.2 1.4 2.01.81.6
I II
RPM BHP RPM BHP RPM BHP RPM BHP RPM700 2.6 762 3.12 812 3.6 847 4.0 870
706 2.8 764 3.3 813 3.78 848 4.22 871
716 3.05 766 3.5 814 4.0 849 4.42 872
722 3.24 768 3.7 815 4.19 850 4.64 873
732 3.4 770 3.82 816 4.35 851 4.88 874
740 3.6 772 4.0 818 4.56 852 5.18 875
751 3.9 778 4.35 821 4.85 853 5.5 876
759 4.2 784 4.65 824 5.16 857 5.81 878
770 4.5 790 5.0 828 5.5 862 6.14 880
779 4.9 796 5.35 832 5.84 870 6.45 900
790 5.2 806 5.67 838 6.15 878 6.7 915
801 5.55 813 6.1 849 6.6 890 7.1 920
809 5.9 825 6.5 870 7.0 898 7.5 928
821 6.4 856 6.9 876 7.4 906 7.95 936
852 6.8 872 7.3 885 7.9 914 8.45 944
870 7.2 885 7.8 892 8.5 925 9.0 952
8/10/2019 By CY Series
19/36
ELECTRICAL DATA
MIN. MAX. HP FLA kW FLA
8.3 155 12.6 24 25
208/230-3-60 187 253
2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35
10*/12* 25.1/30.1 39.6/45.9 40/5015*/20* 37.7/50.2 55.4/71 60/8025*/30* 62.8/75.3 86.8/102.4 90/110
11 20
5 12.6 26.8 30
3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35
10*/12* 25.1/30.1 42.4/48.6 45/5015*/20* 37.7/50.2 58.1/73.8 60/8025*/30* 62.8/75.3 89.5/105.1 90/110
5 15
5 7.6 14.5 15
380-3-60 342 418
2 4 6/7.5 9.1/11.4 16.4/19.3 20/20
10*/12* 15.2/18.2 24/27.8 25/3015*/20* 22.8/30.4 33.5/43 35/4525*/30* 38/45.6 52.5/62 60/70
6.4 15
5 7.6 15.9 20
3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25
10*/12* 15.2/18.2 25.4/29.2 30/3015*/20* 22.8/30.4 34.9/44.4 40/4525*/30* 38/45.6 53.9/63.4 60/70
4.4 15
5 6.3 12.3 15
460-3-60 414 506
2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20
10*/12* 12.6/15.1 20.1/23.3 25/2515*/20* 18.8/25.1 27.9/35.8 30/4025*/30* 31.4/37.7 43.6/51.5 45/60
5.1 15
5 6.3 13 15
3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20
10*/12* 12.6/15.1 20.9/24 25/2515*/20* 18.8/25.1 28.6/36.5 30/4025*/30* 31.4/37.7 44.4/52.3 45/60
POWER
SUPPLY
(V-Ph-Hz)
VOLTAGE
RANGE
BLOWER
MOTOR ELECTRIC HEATERMCA MOCP
MODEL No.: BY07
(4 WIRE)
(STD.)
(STD.)
(ALT.)
(ALT.)
LEGEND
FLA Full Load Amps
HP Horse Power
MCA Minimum Circuit Amps
MOCP Maximum Over Current Protection
*Combination of 2 heater modules
(STD.)
(ALT.)
17
MIN. MAX. HP FLA kW FLA
8.3 155 12.6 24 25
208/230-3-60 187 253
2 6.6 6/7.5 15.1/18.8 27.1/31.8 30/35
10*/12* 25.1/30.1 39.6/45.9 40/50
15*/20* 37.7/50.2 55.4/71 60/80
25*/30* 62.8/75.3 86.8/102.4 90/110
11 20
5 12.6 26.8 30
3 8.8 6/7.5 15.1/18.8 29.9/34.5 35/35
10*/12* 25.1/30.1 42.4/48.6 45/50
15*/20* 37.7/50.2 58.1/73.8 60/80
25*/30* 62.8/75.3 89.5/105.1 90/110
5 15
5 7.6 14.5 15
380-3-60 342 418
2 4 6/7.5 9.1/11.4 16.4/19.3 20/20
10*/12* 15.2/18.2 24/27.8 25/30
15*/20* 22.8/30.4 33.5/43 35/45
25*/30* 38/45.6 52.5/62 60/70
6.4 15
5 7.6 15.9 20
3 5.14 6/7.5 9.1/11.4 17.8/20.7 20/25
10*/12* 15.2/18.2 25.4/29.2 30/30
15*/20* 22.8/30.4 34.9/44.4 40/45
25*/30* 38/45.6 53.9/63.4 60/70
4.4 15
5 6.3 12.3 15
460-3-60 414 506
2 3.5 6/7.5 7.5/9.4 13.8/16.1 15/20
10*/12* 12.6/15.1 20.1/23.3 25/25
15*/20* 18.8/25.1 27.9/35.8 30/40
25*/30* 31.4/37.7 43.6/51.5 45/60
5.1 15
5 6.3 13 15
3 4.1 6/7.5 7.5/9.4 14.5/16.9 15/20
10*/12* 12.6/15.1 20.9/24 25/25
15*/20* 18.8/25.1 28.6/36.5 30/40
25*/30* 31.4/37.7 44.4/52.3 45/60
POWER
SUPPLY
(V-Ph-Hz)
VOLTAGE
RANGE
BLOWER
MOTORELECTRIC HEATER
MCA MOCP
MODEL No.: BY10
(ALT.)
(STD.)
(ALT.)
(STD.)
(ALT.)
(STD.)
(4 WIRE)
8/10/2019 By CY Series
20/36
ELECTRICAL DATA
LEGEND
FLA Full Load Amps
HP Horse Power
MCA Minimum Circuit Amps
MOCP Maximum Over Current Protection
*Combination of 2 heater modules
MIN. MAX. HP FLA kW FLA
17.3 305 12.6 33 40
208/230-3-60 187 253
5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45
10*/12* 25.1/30.1 48.6/54.9 50/60
15*/20* 37.7/50.2 64.4/80 70/90
25*/30* 62.8/75.3 95.8/111.4 100/125
24.4 40
5 12.6 40.1 50
7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60
10*/12* 25.1/30.1 55.8/62 60/70
15*/20* 37.7/50.2 71.5/87.1 80/90
25*/30* 62.8/75.3 102.9/118.5 110/125
11.3 20
5 7.6 20.8 25
380-3-60 342 418
5 9 6/7.5 9.1/11.4 22.6/25.5 25/30
10*/12* 15.2/18.2 30.3/34 35/35
15*/20* 22.8/30.4 39.8/49.3 45/50
25*/30* 38/45.6 58.8/68.3 60/70
15.6 25
5 7.6 25.1 35
7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35
10*/12* 15.2/18.2 34.6/38.4 40/45
15*/20* 22.8/30.4 44.1/53.6 50/60
25*/30* 38/45.6 63.1/72.6 70/80
8.6 15
5 6.3 16.5 20
460-3-60 414 506
5 6.9 6/7.5 7.5/9.4 18/20.4 20/25
10*/12* 12.6/15.1 24.4/27.5 30/30
15*/20* 18.8/25.1 32.1/40 35/45
25*/30* 31.4/37.7 47.9/55.8 50/60
12.2 20
5 6.3 20.1 25
7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30
10*/12* 12.6/15.1 27.9/31.1 30/35
15*/20* 18.8/25.1 35.7/43.6 40/45
25*/30* 31.4/37.7 51.4/59.3 60/70
POWER
SUPPLY
(V-Ph-Hz)
VOLTAGE
RANGE
BLOWER
MOTORELECTRIC HEATER
MCA MOCP
MODEL No.: BY14
(STD.)
(ALT.)
(STD.)
(ALT.)
(STD.)
(ALT.)
(4 WIRE)
18
MIN. MAX. HP FLA kW FLA
17.3 305 12.6 33 40
208/230-3-60 187 253
5 13.8 6/7.5 15.1/18.8 36.1/40.8 45/45
10*/12* 25.1/30.1 48.6/54.9 50/60
15*/20* 37.7/50.2 64.4/80 70/90
25*/30* 62.8/75.3 95.8/111.4 100/125
35*/40* 87.9/100.4 127.1/142.8 150/150
24.4 40
5 12.6 40.1 50
7.5 19.5 6/7.5 15.1/18.8 43.3/47.9 50/60
10*/12* 25.1/30.1 55.8/62 60/70
15*/20* 37.7/50.2 71.5/87.1 80/90
25*/30* 62.8/75.3 102.9/118.5 110/125
35*/40* 87.9/100.4 134.3/149.9 150/175
11.3 20
5 7.6 20.8 25
380-3-60 342 418
5 9 6/7.5 9.1/11.4 22.6/25.5 25/30
10*/12* 15.2/18.2 30.3/34 35/35
15*/20* 22.8/30.4 39.8/49.3 45/50
25*/30* 38/45.6 58.8/68.3 60/70
35*/40* 53.2/60.8 77.8/87.3 80/90
15.6 25
5 7.6 25.1 35
7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35
10*/12* 15.2/18.2 34.6/38.4 40/45
15*/20* 22.8/30.4 44.1/53.6 50/60
25*/30* 38/45.6 63.1/72.6 70/80
35*/40* 53.2/60.8 82.1/91.6 90/100
8.6 15
5 6.3 16.5 20
460-3-60 414 506
5 6.9 6/7.5 7.5/9.4 18/20.4 20/25
10*/12* 12.6/15.1 24.4/27.5 30/30
15*/20* 18.8/25.1 32.1/40 35/45
25*/30* 31.4/37.7 47.9/55.8 50/60
35*/40* 43.9/50.2 63.5/71.4 70/80
12.2 20
5 6.3 20.1 25
7.5 9.75 6/7.5 7.5/9.4 21.6/23.9 25/30
10*/12* 12.6/15.1 27.9/31.1 30/35
15*/20* 18.8/25.1 35.7/43.6 40/45
25*/30* 31.4/37.7 51.4/59.3 60/70
35*/40* 43.9/50.2 67.1/74.9 70/80
POWER
SUPPLY
(V-Ph-Hz)
VOLTAGE
RANGE
BLOWER
MOTORELECTRIC HEATER
MCA MOCP
MODEL No.: BY18
(STD.)
(ALT.)
(STD.)
(ALT.)
(STD.)
(ALT.)
(4 WIRE)
8/10/2019 By CY Series
21/36
ELECTRICAL DATA
LEGEND
FLA Full Load Amps
HP Horse Power
MCA Minimum Circuit Amps
MOCP Maximum Over Current Protection
*Combination of 2 heater modules
MIN. MAX. HP FLA kW FLA
25.5 455 12.6 41.2 50
208/230-3-60 187 253
7.5 20.4 6/7.5 15.1/18.8 44.3/49 60/60
10*/12* 25.1/30.1 56.9/63.2 70/70
15*/20* 37.7/50.2 72.6/88.3 80/90
25*/30* 62.8/75.3 103.9/119.6 110/125
35*/40* 87.9/100.4 135.3/151 150/175
32.6 50
5 12.6 48.3 70
10 26.1 6/7.5 15.1/18.8 51.5/56.2 70/70
10*/12* 25.1/30.1 64/70.3 80/80
15*/20* 37.7/50.2 79.7/95.4 90/100
25*/30* 62.8/75.3 111.1/126.8 125/150
35*/40* 87.9/100.4 142.4/158.1 150/175
15.6 25
5 7.6 25.1 35
380-3-60 342 418
7.5 12.5 6/7.5 9.1/11.4 27/29.9 35/35
10*/12* 15.2/18.2 34.6/38.4 40/45
15*/20* 22.8/30.4 44.1/53.6 50/60
25*/30* 38/45.6 63.1/72.6 70/80
35*/40* 53.2/60.8 82.1/91.6 90/100
20 35
5 7.6 29.5 40
10 16 6/7.5 9.1/11.4 31.4/34.2 45/45
10*/12* 15.2/18.2 39/42.8 50/50
15*/20* 22.8/30.4 48.5/58 50/60
25*/30* 38/45.6 67.5/77 70/80
35*/40* 53.2/60.8 86.5/96 90/100
12.8 20
5 6.3 20.6 25
460-3-60 414 506
7.5 10.2 6/7.5 7.5/9.4 22.2/24.5 30/30
10*/12* 12.6/15.1 28.4/31.6 35/35
15*/20* 18.8/25.1 36.3/44.1 40/45
25*/30* 31.4/37.7 52/59.8 60/60
35*/40* 43.9/50.2 67.7/75.5 70/80
16.3 25
5 6.3 24.1 35
10 13 6/7.5 7.5/9.4 25.7/28 35/35
10*/12* 12.6/15.1 31.9/35.1 40/40
15*/20* 18.8/25.1 39.8/47.6 45/50
25*/30* 31.4/37.7 55.5/63.3 60/70
35*/40* 43.9/50.2 71.2/79 80/80
POWER
SUPPLY
(V-Ph-Hz)
VOLTAGE
RANGE
BLOWER
MOTORELECTRIC HEATER
MCA MOCP
MODEL No.: BY25
(STD.)
(ALT.)
(STD.)
(ALT.)
(STD.)
(ALT.)
(4 WIRE)
19
8/10/2019 By CY Series
22/36
DIMENSIONS
BY07 - BY14 (HORIZONTAL DISCHARGE)
A B C D E F G H J K L M
BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 182(7.16) 406(15.98) 66(2.6) 995(39.17) 550(21.65) 378(14.88) 721(28.38) 123(4.84)
BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 332(13.1) 406(15.98) 42(1.65) 1295(51) 625(24.61) 378(14.88) 721(28.38) 198(7.8)
BY14 1625(64) 1600(63) 705(27.75) 1321(52) 187(7.36) 406(15.98) 55(2.16) 1495(58.86) 655(25.8) 471(18.54) 791(31.14) 153(6.02)
MODEL
DIMENSIONS
NOTE: All dimensions are in mm (dimensions in brackets are in inches).
20
8/10/2019 By CY Series
23/36
DIMENSIONS
BY07 - BY14 (VERTICAL DISCHARGE)
A B C D E F G H J K L M
BY07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 213(8.4) 406(15.98) 85(3.34) 991(39) 504(19.83) 302(11.87) 697(27.53) 110(4.33)
BY10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 365(14.38) 406(15.98) 35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 123(4.84)
BY14 1625(64) 1600(63) 705(27.75) 1321(52) 224(8.82) 406(15.98) 49(1.92) 1497(58.95) 607(23.91) 370(14.59) 929(36.56) 110(4.33)
MODELDIMENSIONS
NOTE: All dimensions are in mm (dimensions in brackets are in inches).
21
8/10/2019 By CY Series
24/36
DIMENSIONS
BY18 - BY25 (HORIZONTAL DISCHARGE)
A B C D E F G H J K L M
BY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 382(15.04) 483(19.02) 35(1.38) 1965(77.36) 655(25.79) 471(18.54) 791(31.14) 153(6.02)
BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 590(23.23) 483(19.02) 50(1.97) 2257(88.86) 790(31.1) 503(19.8) 913(35.94) 288(11.34)
MODEL
DIMENSIONS
NOTE: All dimensions are in mm (dimensions in brackets are in inches).
22
8/10/2019 By CY Series
25/36
DIMENSIONS
BY18 - BY25 (VERTICAL DISCHARGE)
A B C D E F G H J K L M
BY18 1625(64) 2070(81.5) 705(27.75) 1575(62) 422(16.61) 483(19.02) 46(1.81) 1969(77.52) 596(23.46) 354(13.94) 878(34.57) 110(4.33)
BY25 1825(71.85) 2362(93) 840(33.1) 1575(62) 625(24.61) 483(19.02) 74(2.91) 2217(87.28) 596(23.46) 704(27.72) 878(34.57) 110(4.33)
MODEL
DIMENSIONS
NOTE: All dimensions are in mm (dimensions in brackets are in inches).
23
8/10/2019 By CY Series
26/36
DIMENSIONS - HEATER BOX
24
205(8.1
")
412
(16.2")
25.4(1
")TYP
HEATER CONTROLS MTGCOVER
HEATER CONTROLS MTG
HEATER ACCESS COVER
PLATE
BY07 - BY14
A
BY07 818 (32.2)
BY10 818 (32.2)
BY14 1326(52.2)
MODELDIMENSIONS
1581(62.3")
205(8.1
")
492(19
.4")
25.4(1
")TYP
HEATER CONTROLS MTGCOVER
HEATER CONTROLS MTG
HEATER ACCESS COVER
PLATE
(BOTH SIDES)
BY18 - BY25
NOTES: 1. All dimensions are in mm (dimensions in brackets are in inches).2. Heater box is an optional feature.
8/10/2019 By CY Series
27/36
DIMENSIONSMATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY075 - CY120
25
NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Dual system units will have 2 set of service valves.
3. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units forproper airflow.
82 [3.228"]
1061
[41.
771"]
571 [22.480"]
966 [38.031"]
1161
[45.
708"]
1123
[44.
212"]
115
[4.
527"]
190
[7.
480"]
1016
[40"]
8/10/2019 By CY Series
28/36
DIMENSIONSMATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY150 - CY300
26
NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Single system units will have 1 set of service valves.3. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.
MODEL NUMBER A B C D E F G
CY150 - CY220 1900 (74.8) 1120 (44.09) 1145 (45.07) 1071 (42.16) 150 (5.9) 800 (31.5) 800 (31.5)
CY240 - CY300 2200 (86.61) 1225 (48.23) 1300 (51.18) 1179 (46.41) 300 (11.81) 800 (31.5) 800 (31.5)
8/10/2019 By CY Series
29/36
DIMENSIONSMATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY360
27
195
[7.
677"]
NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.
8/10/2019 By CY Series
30/36
TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with single compressor units)
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
28
REFER TO UNITNAMEPLATE FOR
POWER SUPPLY
LUG
HVTB OR BMC
BM
L2
L3
L1
68
69
BMC
70
G
LVTB OLR18 19BMC ATB
2
OLR
BMC
68
BM
70
69
APPLICABLE FOR BM WITH
TO HVTB
L1
L3
L2
BM
CONNECTION APPLICABLE FOR 1PH BM
SEC
PRI
ON
DIP SWITCH
J_PROG
POWER(GRN)
DIP
LOCK2(RED)
SYSTEM2(ORG)
FUSE
SYSTEM1(YEL)
P3_##
LOCK1(RED) ECB
BMC
TRANS
TO CONDENSING UNIT ATB
TO CONDENSING UNIT ATB
30
29
230V
W1W2 Y1 G RC
28HC1
HC2
CNC
NO
AFS
(by others)
24Vac
STG2 HEATING
STG1 HEATING
STG1 COOLING
BM CONTROL
W2
W1
Y1
R
G
C
LVTB
W2
W1
Y1
G
C
R
THERMOSTAT / DDC CONTROLLER
TO CONDENSING UNIT ATB
EXTERNAL OLR (OPTION)
8/10/2019 By CY Series
31/36
TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with single compressor units)
LEGEND
AI ANTI ICE THERMOSTAT
AFS AIRFLOW SWITCH
ATB AUXILIARY TERMINAL BLOCK
AR AUXILIARY RELAY
BM BLOWER MOTOR
BMC BLOWER MOTOR CONTACTOR
CAP CAPACITOR
ECB ELECTRONIC CONTROL BOARD
FL FUSE LINK
HC HEATER CONTACTOR
HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR HEATER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LVTB LOW VOLTAGE TERMINAL BLOCK
LUG LUG GROUND
MOHT MANUAL RESET OHT
NTB NEUTRAL TERMINAL BLOCK
OHT OVERHEAT THERMOSTAT
OLR OVER LOAD RELAY
SM SYSTEMIZER
VFC VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
FL OR MOHT
_ _ _
+
29
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
THERMOSTAT CONTROL VOLTAGE - 24VAC.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE
900C OR ITS EQUIVALENT.
USE COPPER CONDUCTOR WIRES ONLY.
3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORTCYCLE PROTECTION FOR COMPRESSOR IS AVAIL-ABLE IN ZAMIL ELECTRONIC THERMOSTAT.
4. IF HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
5. FUSED DISCONNECT SWITCH OR CIRCUIT
BREAKER TO BE PROVIDED BY CONSUMER WITH
RATING AS RECOMMENDED BY ZAMIL.
6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLT-
AGE ACROSS TERMINAL X1, X2 & 2 IS 230 VAC.
7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASE
BLOWER MOTOR ONLY. ALSO APPLICABLE FOR
UNITS WITH 380 VOLT.
T1G
HEATER OPTION-3HEATER OPTION-1
HC2
HC1
T1G
71A
T1F
HEATER1
T3F
29
T2F
73A
72A
F11
F12
HC1
F13
71A
HEATER OPTION-2(SEE TABLE)
HC2
HEATER2
T3G
T2G
28
73B
72B
71B
F14
F15
F16
30
HEATER3
T1H
T2H
T3H
F17
74A
76A
75A
F18
F19
HC4
76B
HEATER4
28
T3I
T1I
HC3
T2I
74B
HC3
75B
F20
F21
29
HC4
F22
HEATER3
(SEE TABLE)
F19
HC1
28
HEATER1
HC1
T3F
T1F
T2F
73A
72A
F11
F12
F13
T1H
30 HC3
T2H
T3H
74A
76A
75A
F18
F17
HC129
72A
HEATER1
T2F
28
T1F
HC3
71A
F11
T3F
HC1
73A
F12
F13
L1 L2 L3 L3
TO HVTB
L2L1 L3 L1 L2 L2L1 L3 L3
TO HVTB
L1L2 L3 L2L1
TO HVTB
L1 L3L2
(SEE TABLE)
HC2
HC2
28 30
HEATER2
T3G
T2G
HEATER3
T3H
T2H
T1H
76A
74A
75A
F17
F18
F19
28
T2I
HEATER4
T1I
T3I
TO HVTB
L2L1 L3
NOTES: HTR-35 & 40KW IS APPLICABLE FOR
5 K.W
20 K.W
25 K.W
35 K.W
30 K.W
10 K.W
15 K.W
12 K.W
7.5 K.W
40 K.W
6 K.W
HTR
**
H2
2 1 6 K.W
7.5 K.W
12.5 K.W
2*10 K.W
7.5+10 K.W2*
BY 18 MODEL ONLY.
USE OPTION 1 FOR 230V-3PH UNIT MODELUSE OPTION 3 FOR 380V/460V-3PH UNIT MODEL
* 2 2*10 K.W
2
2
2
2
2
2
2
2
2
2
2
2
2
1
7.5 K.W
7.5+10 K.W
12.5 K.W
15 K.W
10 K.W
15 K.W
10 K.W
5 K.W
6 K.W
7.5 K.W
5 K.W
6 K.W
OHT
FL
FL
HEATER DATA TABLE
HEATER DATA TABLE
2
OPT# STG
1
I STG
5 K.W
II STG
H4 FL
FL
FL
H3
(#2)
OHT
OHT
FL
(#1)OHT
HEATER TYPES
H1
OHT
FL
OHT
OHT
FL
OHT
FACTORY SETTINGS OF DIP SWITCHES
ON
DIP SWITCH #
OFF
S1 S2 S3 S4
S4
ON= TEST MODE ENABLE
ON= COMPRESSOR 1 LEAD
OFF=TEST MODE DISABLE
LOAD BALANCES2
S1
(Comp1&2 Auto Lead Lag)OFF=
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION
on-board programming function (always set to on)
LED INDICATORS
Green power on/off indicator
Red system lock-out due to system fault
Yellow
system 1 fault diagnostic
Orange
system 2 fault diagnosticnote:
Set dip switch # 3 according to unit's option(pump down or no pump down)
ECB DIP SWITCH SETTINGS & LED INDICATORSDIP SWITCH FUCTIONS
blinking slow - LPS1/ HPS1/ SSPS1/
blinking slow - LPS2/ HPS2/ SSPS2/
OLR1/CB1 ckt fault
OLR2/ CB2 ckt fault
2) VFC OPTION FOR BM RUN &TRIP INDICATION
OPTIONS1) ANTI ICE OPTION
CONNECTION APPLICABLE FOR ANTI ICE
COMP
21A AI-1 23A
LPS
BM TRIP CONNECTION FOR BM WITH OLR
5251
BM TRIP
BM ON
4948 BMCA-1A
5251
BM TRIP
BMCA-2A
48A
51A
OLR-2
8/10/2019 By CY Series
32/36
TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with dual compressor units)
NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
30
REFER TO UNITNAMEPLATE FORPOWER SUPPLY
G
LVTB OLR18 19BMC ATB
2
OLR
BMC
68
BM
70
69
APPLICABLE FOR BM WITH EXTERNAL OLR
TO HVTB
L1
L3
L2
L1 68
LUG
L3
L2 BM70
69
HVTB BMC
APPLICABLE FOR 1PH BM
HEATER1
HEATER2
OUTFAN1
OUTFAN2
NEUTRAL
12v-0-12v
SEC
240v
PRI
LIVE
DIP SWITCH
J_PROG
POWER(GRN)
X2
LOCK2(RED)
SYSTEM2(ORG)
FUSE
SYSTEM1(YEL)
LOCK1(RED)
X1
INFAN
41A
41B
30
29
14
HP2
(LP2)
LP1
LP2
(LP1)
(HP2)
23B
22B
23A
26A
ECB
(HP1)
HP1
COMP2
P2
P1
COMP1
28
3B
4B
4A
3A
HC1
BMC
HC2
TRANS
15
16
13
14
CNC
NO
TO CONDENSING UNIT ATB
TO CU ATB
TO CU ATB
30
29
LVTB
THERMOSTAT / DDC CONTROLLER
TO CONDENSING UNIT ATB
230V
8/10/2019 By CY Series
33/36
TYPICAL SCHEMATIC WIRING DIAGRAM(Matching with dual compressor units)
LEGEND
AI ANTI ICE THERMOSTAT
AFS AIRFLOW SWITCH
ATB AUXILIARY TERMINAL BLOCK
AR AUXILIARY RELAY
BM BLOWER MOTOR
BMC BLOWER MOTOR CONTACTOR
ECB ELECTRONIC CONTROL BOARD
FL FUSE LINK
HC HEATER CONTACTOR
HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR HEATER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LVTB LOW VOLTAGE TERMINAL BLOCK
LUG LUG GROUND
LLS LEAD LAG SWITCH
MOHT MANUAL RESET OHT
NTB NEUTRAL TERMINAL BLOCK
OHT OVERHEAT THERMOSTAT
OLR OVER LOAD RELAY
SM SYSTEMIZER
VFC VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
FL OR MOHT
_ _ _
+
31
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
THERMOSTAT CONTROL VOLTAGE - 24VAC.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE
900C OR ITS EQUIVALENT.
USE COPPER CONDUCTOR WIRES ONLY.
3. IF HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORTCYCLE PROTECTION FOR COMPRESSOR IS AVAIL-ABLE IN ZAMIL ELECTRONIC THERMOSTAT.
5. FUSED DISCONNECT SWITCH OR CIRCUIT
BREAKER TO BE PROVIDED BY CONSUMER WITH
RATING AS RECOMMENDED BY ZAMIL.
6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLT-
AGE ACROSS TERMINAL X1, X2 & 2 IS 230 VAC.
7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASE
BLOWER MOTOR ONLY. ALSO APPLICABLE FOR
UNITS WITH 380 VOLT.
T1G
HEATER OPTION-3HEATER OPTION-1
HC2
HC1
T1G
71A
T1F
HEATER1
T3F
29
T2F
73A
72A
F11
F12
HC1
F13
71A
HEATER OPTION-2(SEE TABLE)
HC2
HEATER2
T3G
T2G
28
73B
72B
71B
F14
F15
F16
30
HEATER3
T1H
T2H
T3H
F17
74A
76A
75A
F18
F19
HC4
76B
HEATER4
28
T3I
T1I
HC3
T2I
74B
HC3
75B
F20
F21
29
HC4
F22
HEATER3
(SEE TABLE)
F19
HC1
28
HEATER1
HC1
T3F
T1F
T2F
73A
72A
F11
F12
F13
T1H
30 HC3
T2H
T3H
74A
76A
75A
F18
F17
HC129
72A
HEATER1
T2F
28
T1F
HC3
71A
F11
T3F
HC1
73A
F12
F13
L1 L2 L3 L3
TO HVTB
L2L1 L3 L1 L2 L2L1 L3 L3
TO HVTB
L1 L2 L3 L2L1
TO HVTB
L1 L3L2
(SEE TABLE)
HC2
HC2
28 30
HEATER2
T3G
T2G
HEATER3
T3H
T2H
T1H
76A
74A
75A
F17
F18
F19
28
T2I
HEATER4
T1I
T3I
TO HVTB
L2L1 L3
NOTES: HTR-35 & 40KW IS APPLICABLE FOR
5 K.W
20 K.W
25 K.W
35 K.W
30 K.W
10 K.W
15 K.W
12 K.W
7.5 K.W
40 K.W
6 K.W
HTR
**
H2
2 1 6 K.W
7.5 K.W
12.5 K.W
2*10 K.W
7.5+10 K.W2*
BY 18 & 25 MODELS ONLY.
USE OPTION 1 FOR 230V-3PH UNIT MODELUSE OPTION 3 FOR 380V /460V-3PH UNIT MODEL
* 2 2*10 K.W
2
2
2
2
2
2
2
2
2
2
2
2
2
1
7.5 K.W
7.5+10 K.W
12.5 K.W
15 K.W
10 K.W
15 K.W
10 K.W
5 K.W
6 K.W
7.5 K.W
5 K.W
6 K.W
OHT
FL
FL
HEATER DATA TABLE
HEATER DATA TABLE
2
OPT# STG
1
I STG
5 K.W
II STG
H4 FL
FL
FL
H3
(#2)
OHT
OHT
FL
(#1)OHT
HEATER TYPES
H1
OHT
FL
OHT
OHT
FL
OHT
FACTORY SETTINGS OF DIP SWITCHES
ON
DIP SWITCH #
OFF
S1 S2 S3 S4
S4
ON= TEST MODE ENABLE
ON= COMPRESSOR 1 LEAD
OFF=TEST MODE DISABLE
LOAD BALANCES2
S1
(Comp1&2 Auto Lead Lag)OFF=
S3 OFF= WITHOUT PUMP DOWN ON= WITH PUMP DOWN OPTION
on-board programming function (always set to on)
LED INDICATORS
Green power on/off indicator
Red system lock-out due to system fault
Yellow
system 1 fault diagnostic
Orange
system 2 fault diagnosticnote:
Set dip switch # 3 ac cording to unit's option(pump down or no pump down)
ECB DIP SWITCH SETTINGS & LED INDICATORS
DIP SWITCH FUCTIONS
2) VFC OPTION FOR BM RUN &TRIP INDICATION
OPTIONS1) ANTI ICE OPTION
BM TRIP CONNECTION FOR BM WITH OLR
5251
BM TRIP
COMP1
21A AI-1 23A
LPS1
COMP221B AI-2 23B
LPS2
BM ON
4948
5251
BM TRIP
48A
51A
blinking slow - LPS1/ HPS1/ SSPS1/
OLR1/CB1 ckt fault
blinking slow - LPS2/ HPS2/ SSPS2/
OLR2/ CB2 ckt fault
OLR-2
8/10/2019 By CY Series
34/36
32
Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct
rotation when the system is operated. Verification of correct rotation is by observing that the suction pressure drops and
discharge pressure rises when compressor run. Reverse rotation results in abnormal sound, as well as, substantially low
current draw and by interchanging power supply wire L1 & L3 will correct this problem.
The operation of the air conditioning unit is controlled by a 24VAC electronic control board.
GENERAL
The thermostat normally displays room temperature and mode of operation. The five buttons on the front of the unit
allow complete control of the thermostat. The thermostat also allows to select continuous fan operation (useful whenusing an air cleaner) or have the fan come on with the compressor.
SWITCH FUNCTION
- On/Off Key : Switch the system On or Off.- Up Key : To increases the set temperature.
- Down Key : To decreases the set temperature.- Mode Key : Changes the mode to Fan, Cool, Heat or Auto.
- Fan Key : Changes the Fan Operation to Auto or Continuous.- C/F selection : By pressing Mode & UP key together, toggles between C to F or vice versa.
USER CONTROLS
Mode:
Select the desired mode of operation by pressing of the mode button:
Fan: In this mode of operation, the compressor will be in inactive state. Display shows room temperature. Fan will be running.
Cool: In this mode of operation, the compressor will be ON after a delay depending on the differential of room
temperature & Set temperature.
Heat: In this mode of operation, Fan is ON.
Auto : In auto mode, thermostat provide automatic changeover from heating to cooling mode & vice versa. Ther-
mostat automatically switches to maintain the desired temperature.
DIP SWITCH OPTIONS AND FUNCTIONS
There are 4 small DIP (Dual in line package) switches on the back of the circuit board which must be configured by
the installer.
CONTROLS & SEQUENCE OF OPERATION
SWITCH ON OFF
1 N. A. -
2 N. A. -
3 N. A. -
4 INDOOR SENSOR REMOTE SENSOR
DIP SWITCH SELECTION
Note:
Keep DIP SWITCH 1, 2 & 3 in OFFposition only.
FAN COOL HEAT AUTO
SUPPLY FAN CONTROL
STG1 COOLING
STG1 HEATER
STG2 HEATER
STG2 COOLING
W2
R
C
G
W1
Y2
Y1
LVTB
THERMOSTAT
Y2
W1
Y1
G
24V(R)
24V(C)W2
REMOTESENSOR
FAULT 1
FAULT 2
SENSOR
OPTIONAL CONNECTION:
IF REMOTE TEMPERATURESENSING
FUNCTION ISREQUIRED.
NOTE:
(ZAC P/N 80065261)
ATBCOMPRESSORFAULT SIGNAL
(VOLT-FREECONTACT)
COMP1
COMP2
(COMMON)
24V ac
( OPTIONAL CONNECTION )
HOOK-UP WIRING DIAGRAM
ACCU CONTROL PANEL
LEGEND:
ATB
LVTB
AUXILIARY TERMINAL BLOCK
LOW VOLTAGE TERMINAL BLOCK
( THERMOSTAT CONTROLLER TO AIR HANDLING UNIT )
AHU CONTROL PANEL
8/10/2019 By CY Series
35/36
INSTALLATION INSTRUCTIONSA. GENERAL
Blower units are shipped completely wired. Only external power, interconnecting control wiring between outdoor andindoor units and refrigerant pipe connections are needed to complete the installation. For detailed instructions/informa-
tions, please refer to corresponding IOM manual.
B. UNIT LOCATION & ACCESS SPACEThe placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must be
kept on the service access side and return air side.When making tubing connections, be sure to provide clearance for electrical connections.
C. TUBING INSTALLATION
Do not remove plugs from the compression fittings until tubing has been run and is ready for connection.
a. Make sure the tubing is round, without dent or burrs.
b. Cut tubing to the length required with a tube cutter carefully. Do not use a hacksaw.
c. Remove burr from inside and outside using file or deburring tool.
NOTE: Always use a gear type tube bender when making bends in suction line.
When installing tubing through walls or along side of any structural members, be sure the tubing is isolated from thesemembers or walls to avoid any transmission of vibration that may occur, while unit is running.
ELECTRICALSTEP 1: INSTALLATION
A)Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.NOTE:Use copper wires of proper rating for all field wiring.
Warning
Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one discon-nect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wires
Connect power wires to terminal block per wiring diagram.
Connect ground wire to the ground lug inside the control box.
C) Control wiring between outdoor & indoor unit
Use 16 gauge color-coded wire between the indoor and outdoor units (control wiring).
STEP 2: START-UPRefer to outdoor unit installation instructions for system start-up instructions and refrigerant charging method details.
STEP 3: SEQUENCE OF OPERATIONWith power supplied to indoor and outdoor units, the unit starts responding to the thermostat mode requirement.
Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on. The compressorcontactor is energized to start the compressor and condenser fan.As the conditioned space approaches the thermostat cooling set point, the unit cycles off.
Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor forelectric h