Upload
donga
View
242
Download
1
Embed Size (px)
Citation preview
Čisti prostoripo sistemu
kljuČ u ruke
Klimaoprema d.d.
Gradna 78A, HR-10430 Samobor, Hrvatska | T. +385 (0)1 33 62 513 | F. +385 (0)1 33 62 905
[email protected] | www.klimaoprema.hr
11/2014.
ČISTI PROSTORI | FILTRACIJA I VENTILACIJA | ZAŠTITNE KABINE I KABINETI | NAMJEŠTAJ ZA ČISTE PROSTORE
inženjering proizVoDnjA instAlirAnje VAliDACije
Čist
i pro
stor
i po
sist
emu
klju
Č u
ruk
e
SADRŽAJKlimaoprema Cleanroom Solutions ............................................................3
Inženjering i projektiranje ................................................................................4
Čisti prostori po sistemu „ključ u ruke“....................................................6
Čisti prostori – sastavni dijelovi...............................................................................8Zidni paneli ...........................................................................................................10Antibakterijski paneli .............................................................................................12Stropni paneli ........................................................................................................14Cleanroom prozori ................................................................................................16Cleanroom vrata ...................................................................................................18Cleanroom podovi.................................................................................................20Cleanroom lampe .................................................................................................21Klima komore........................................................................................................22HVAC sustavi ........................................................................................................24BMS (Building Management System)...................................................................25
Filtracija zraka .....................................................................................................26
Klasifikacija filtera prema normama......................................................................27Izvedbe filtera .......................................................................................................28Orijentacijski podaci za grube i fine filtere ............................................................29Apsolutni stropni filter FAC ...................................................................................30Apsolutni kanalski filter FAK .................................................................................32Apsolutni kanalski filter sa rešetkom FAR.............................................................33Vrećasti kanalski filter FKV-P................................................................................34Vrećasti kanalski filter FKV-C................................................................................35Apsolutni filter sa aktivnim ugljenom FKU ............................................................36Kanalski filter FKK ................................................................................................37Propusnik/Prolazna komora - Pass box................................................................38Zračni tuš TKA ......................................................................................................39Validacije i servisi..................................................................................................40Oznake za narudžbu.............................................................................................41
Zaštitne kabine i kabineti ...............................................................................42
Prijenosni laminarni kabinet KTP-A ......................................................................44Horizontalni laminarni kabinet KTH-S...................................................................45Vertikalni laminarni kabinet KTV-S........................................................................46Vertikalni laminarni kabinet KTV-A........................................................................47Mikrobiološki zaštitni kabinet KTB-NS (Klasa II)...................................................48Mikrobiološki zaštitni kabinet KTB-VS (Klasa II) ...................................................49IVF kabinet............................................................................................................50UV kabinet za sterilizaciju.....................................................................................51Laminarna kabina KA ...........................................................................................52Komora za vaganje/otprašivanje VKA ..................................................................53Komora za vaganje/otprašivanje VKO..................................................................54Komora za vaganje/otprašivanje VKL...................................................................55Specijalni uređaji...................................................................................................56Validacije i servisi..................................................................................................57
Namještaj za čiste prostore...........................................................................58
Cleanroom stolovi .................................................................................................60Cleanroom ladičari ................................................................................................61Cleanroom ormari .................................................................................................62Cleanroom police i žičane stalaže ........................................................................63Klupice za presvlačenje ........................................................................................64Vješalice za odjeću ...............................................................................................65Cleanroom sudoperi .............................................................................................66Cleanroom kolica ..................................................................................................68Kirurški držač instrumenata ..................................................................................69Ostali namještaj i dodaci .......................................................................................70
Više od 35 godina iskustva
Više od 220zaposlenih
Proizvodnja
Inženjering
Opremanje
Servis
Validacije
Montaža
10.000 m² proizvodno,skladišnih,
uredskih prostora
Tisuće izvedenihkvadrata čistih
prostora
Klimaoprema d.d. je vodeći Hrvatski proizvođač čistih prostora te opreme za klima-tizaciju i ventilaciju.
Nudimo kompletna rješenja po sistemu „ključ u ruke“, što uključuje izradu projekata,inženjering, proizvodnju, montažu, validacije (GMP klase A, B, C, D), servis, sustavventilacije i klimatizacije te automatiku. Cjelokupni „know-how“ u ovom sektoru rezul-tat je vlastitog istraživanja i razvoja.
Iskustvo stječemo od osnutka 1975.g. do danas, kada je Klimaoprema moderno or-ganizirana proizvodna tvrtka sa vrhunskim stručnjacima, inženjerima i projektantima,kvalitetnim strojnim parkom, ispitnim laboratorijem, ERP informatičkim sustavom zaupravljanje poslovnim procesima, certificiranim sustavom upravljanja kvalitetom ISO9001, programima za odabir proizvoda te novim tehnologijama.
Klimaoprema zapošljava više od 220 djelatnika na centralnoj lokaciji i sjedištu uSamoboru te raspolaže sa 10.000 m² proizvodno-skladišnih i uredskih prostora.
Tvrtka smo u koju ljudi žele doći raditi, gdje su djelatnici zadovoljni, a poslovni partneridobivaju svu potrebnu pomoć pri realizaciji projekata.
Naše aplikacije su potvrđene u praksi i zadovoljavaju najstrože propise koji seodnose na farmaceutsku, kemijsku i prehrambenu industriju.
Ovaj katalog je samo put do nas. Osobni kontakt i ispunjavanje korisnikovih speci-fičnih zahtjeva su naša misija, a naši djelatnici, svojim znanjem, inženjerskimiskustvom i energijom, u djelo će provesti Vašu ideju.
Projektiramo čiste prostore u farmaceutskoj, medicinskoj, prehrambenoj, elektron-ičkoj i drugim industrijama osjetljivima na onečišćenja iz okoliša.
Prva faza projektiranja je izrada idejnog projekta (Conceptual design), a izvodi se usvrhu dobivanja lokacijske dozvole za građevinu. Zatim se izvodi glavni projekt (Basicdesign) i dobiva se građevinska dozvola. Slijedi izrada izvedbenog projekta (Detaileddesign) i počinje se sa gradnjom. Na kraju slijedi izvedeno stanje (As-built) koje služiza dobivanje uporabne dozvole.
Svako kvalitetno proizvodno postrojenje niknulo je iz dobrih temelja, zbog čega jevažna početna faza izrade idejnog projekta. Ovdje se vrši procjena investicije. Defini-raju se dimenzije objekta te opseg projekta kojeg čine proizvodni procesi, listaopreme, energenti koji će biti korišteni te potrebna infrastruktura. Idejni projektdefinira i vrijeme realizacije.
Proizvodni procesi odvijaju se na brojnim visokoproduktivnim linijama i CNC stroje-vima koji garantiraju najkraće vrijeme izrade i svjetsku kvalitetu proizvoda. Kompletanproizvodni proces upravljan je ERP informatičkim sustavom koji garantira efikasantijek informacija potrebnih za brzu reakciju.
Kao tvrtka usmjerena budućnosti konstantno težimo novim mogućnostima i inova-tivnim rješenjima. Potičemo originalnost i kreativnost pojedinaca i timova kako bi ko-risnicima ponudili opremu za čiste prostore, klimatizaciju i ventilaciju koja osiguravazdrav i ugodan boravak u prostoru te energetsku učinkovitost postrojenja.
Instaliranje cleanroom prostora izvršiti će naši iskusni monteri, spretni i brzi, ukratkom roku prostor će postati čista cleanroom zona koja zadovoljava sve smjernicei standarde.
Servis u čistom prostoru znači održavanje objekta te validaciju uređaja i kompletnihcleanroom prostora. Riječ je o održavanju novo izgrađenih ili rekonstruiranih čistihprostora te pripadajućih postrojenja. Redovito servisiranje, održavanje i validiranjeopreme ili objekta osigurava sigurnost pri uporabi te duži životni vijek uređaja.
KLIMAOPREMA CLEANROOMSOLUTIONS
INŽE
NJERING
VALIDACIJE INSTALIR
AN
JE
PROIZVODNJA
Cleanroom dizajn & inženjeringu farmaceutskoj, medicinskoj,prehrambenoj, elektronskoj idrugim industrijama
Proizvodnja čistih prostora, operacijskihdvorana, laminar flow kabina i kabineta,mikrobioloških kabineta, komora za va-ganje, specijalnih uređaja, namještaja
Instalacija čistih prostora,opremanjeValidacije & Servis
KLIMAOPREMA CLEANROOM SOLUTIONS 3
4 INŽENJERING I PROJEKTIRANJE
INŽENJERING I PROJEKTIRANJE
Izvedeno stanje
Projektiramo čiste prostore u farmaceutskoj, medicinskoj,prehrambenoj, elektroničkoj i drugim industrijama osjetljivimana onečišćenja iz okoliša i drugih izvora.
• Tehnološka rješenja
• Arhitektonska rješenja
• HVAC projekt
• Elektroinstalacije
• DDC & BMS
Projektiranje u skladu sa državnim propisima i normama teGMP i FDA smjernicama.
Izrada prihvatljivog projekta s aspekta visine investicije. Svakomkorisniku pristupamo zasebno, slušajući njegove potrebe i želje,predlažemo rješenja te projektiramo, razvijamo i realiziramo ko-risnikovu viziju.
IZVEDBENI PROJEKT
GLAVNI PROJEKT
IDEJNI PROJEKT
INŽENJERING I PROJEKTIRANJE 5
ČISTI PROSTORI PO SISTEMU„ključ u ruke“Čiste sobe su prostori u kojima se izvode operacije, vršeznanstvena istraživanja i radnje koje ne smiju doći u doticaj sazagađivačima kao što su prašina, zračni mikrobi i česticeaerosola. Bez čistih prostora danas je nemoguće zamislitiproizvodne pogone farmaceutske, biotehnološke, kemijske,prehrambene, mljekarske i drugih industrija koje su osjetljivena onečišćenja iz okoliša.
Čisti prostor - Cleanroom je definirani i kontrolirani prostor pro-jektiran na način da je unos, generiranje, sakupljanje i zadrža-vanje čestica (kontaminanata) minimiziran i kontroliran. Prostoru koji se ubacuje filtrirani zrak ima pozitivan tlak u odnosu na
okolne prostore u svim radnim uvjetima te zrak efikasno ispireprostor. Prostor u kojemu su svi relevantni parametri strogokontrolirani: temperatura, relativna vlaga, buka, osvjetljenje iostali parametri.Klimaoprema Cleanroom Solutions projektira čiste prostorekoji udovoljavaju zahtjevima za brojem čestica: u mirovanju(at-rest) i u radu (in operation). Zahtjevi su definirani za svakuprostoriju (klasu) zasebno. Čisti prostori klasificiraju se prema broju i veličini dopuštenihčestica po volumenu zraka. Norme definiraju čistoću zraka. Ve-liki brojevi kao što su "klasa 100" ili "klasa 1000" odnose se naUS FED STD 209E i označavaju broj čestica veličine 0,5 μmili većih po kubičnoj stopi zraka. Dakle, klasom 100 prema USFED 209E standardu propisano je da broj čestica veličine 0,5μm ili većih ne smije prijeći vrijednost od 100 čestica na 1 ft³.Mali brojevi odnose se na ISO 14644-1 standarde koji određujudecimalni logaritam broja čestica veličine 0,1 μm ili većih pokubičnom metru zraka. Prema tome, na primjer, čisti prostorISO klase 5 ima najviše 105 = 100,000 čestica po m³. Budućida je 1 m³ približno jednak 35 ft³, ta dva standarda približno sujednaka kad se mjere čestice od 0,5 μm, iako se standardi te-stiranja razlikuju. Običan zrak u prostorijama približno je klase1.000.000 ili ISO 14644-9.
Neophodne smjernice pri projektiranju čistih prostora su GMP(Good Manufacturing Practice) smjernice prema čijim se nače-lima i uputama treba odvijati i dokumentirati proizvodna orga-nizacija u farmaceutskoj industriji. GMP osigurava trenutnu idosljednu kontrolu kvalitete. Naši djelatnici kontinuirano usva-jaju nove tehnologije čime pospješujemo kvalitetu proizvoda iudovoljavamo strogim zahtjevima i normama koje se primjen-juju pri izvođenju čistih prostora.
Poznavajući dizajn i tehniku izrade čistih prostora, izrađujemocijele projekte te vršimo opremanje čistih prostora. Trajno smoorijentirani prema klijentima čije potrebe pratimo i analiziramosa posebnom pažnjom izvodeći čiste prostore u farmaceutskimpogonima, bolnicama, ljekarnama, pogonima za proizvodnjuprehrambenih artikala, inženjering pogonima, pogonima elek-tronske industrije i drugim.
Kao vodeći proizvođač opreme za čiste prostore u Hrvatskoj iregiji, Klimaoprema Cleanroom Solutions dokazuje svojukvalitetu ne samo kroz finalni proizvod, već znanjem i profe-sionalnošću osoblja koje vodi isporuke, montažu, proizvodnjute komunikaciju sa poslovnim partnerima. Obratite nam se spovjerenjem i Klimaoprema Cleanroom Solutions će Vašuzamisao ili ideju koja je tek u nastanku, projektirati,proizvesti, montirati, opremiti čisti prostor, validirati te ueksploataciji servisirati.
ČISTI PROSTORI 7
8 ČISTI PROSTORI
ČISTI PROSTORI Sastavni dijelovi
Kao što se projektira kuća, projektira se i čisti prostor - Clean-room. Svi elementi koji čine kuću; zidovi, stropovi, prozori, vrata,podovi i drugi elementi, čine i čisti prostor. Kuća je siguran domnjegovom vlasniku, a čisti prostor je sigurno mjesto za operatera,farmaceuta, kirurga i drugo osoblje.
Čisti prostori moraju biti projektirani, konstruirani i prilagođeni takoda odgovaraju radnjama koje se u njima izvode. Projekt se izvodina način da je rizik od kontaminacije, nakupljanja prašine i drugihnečistoća sveden na minimalnu vjerojatnost.Osvjetljenje, temperatura, vlaga i ventilacija moraju odgovaratizahtjevima radnji i ne smiju utjecati na kvalitetu radnja niti na radopreme.
Tijek ljudi, materijala i opreme mora biti jednosmjeran u najvećojmogućoj mjeri, kako bi se izbjegla mogućnost miješanja i konta-minacije.
Raspored radnih prostora mora omogućiti uredan i logičan ras-pored materijala i opreme kako bi se izbjegla mogućnost kros-kontaminacije i isključio rizik ispuštanja ili zamjene bilo koje fazeoperacije ili kontrole.
Zidovi, stropovi i podovi čistih prostora trebaju biti od nepro-pusnog materijala, glatki, bez pukotina i lako perivi, a završnaobrada zidova, stropova i podova mora biti zaobljena.
Osnovni procesni energenti sastavni su dio postrojenja, a njihovrazvod do mjesta potrošnje treba izvesti što kraćim trasama tespajanje na potrošače izvesti sa stropa.
Pri projektiranju vodova i instalacija treba izbjeći udubljenja i os-igurati njihovo održavanje izvan čistih prostora.Odvodi moraju biti odgovarajuće veličine i bez mogućnosti izlije-vanja tj. povratnog toka.
Potrebno je osigurati adekvatan odsisni sustav za kontrolu kont-aminanata u slučaju eventualnog zagađenja prostora, kao i zaodržavanje propisane čistoće prostorije.Potrebno je osigurati adekvatne elektroinstalacije i električno na-pajanje.Pristup pogonu mora biti kontroliran i limitiran na ovlaštene osobepomoću kontroliranog pristupa ili čitača kartica.
1
2
3
4
5 6
7
8 10 11 12
13
14
9
ČISTI PROSTORI 9
27
15
16
17
18
19
21
22
23
2425
26
20
1. Stropni paneli2. Zidni paneli3. Ovalni profili4. Stol5. Ladičar6. Kolica7. Police8. Umivaonik9. Okretna vrata
10. Klupica11. Laminarni zaštitni kabinet12. Komora za vaganje13. Mikrobiološki zaštitni kabinet14. Staklena stijena15. Odbojnik16. Laminarna kabina17. Odsisna rešetka18. Kućište za sigurnu izmjenu19. Ormar20. Sudoper21. Propusnik (Pass box)22. Apsolutni filter FAC23. Klima komora24. Pod25. Klizna vrata26. Lampe27. Prozor
10
Zidni paneliTEHNIČKE KARAKTERISTIKE
• Panel kao segment zida izrađen iz dvije stjenke limapresavijene oko rubova (sendvič paneli), ojačan okvi-rom
• Stjenke panela mogu biti izrađene iz:- pocinčanog čeličnog lima plastificiranog u boju debljine
25 μm- aluminijskog lima plastificiranog u boju debljine 60 μm- pocinčanog čeličnog lima plastificiranog u antibakterijsku
boju debljine 110 μm- aluminijskog lima plastificiranog u antibakterijsku boju
debljine 110 μm- nehrđajućeg lima (opcija: plastifikacija u antibakterijsku
boju debljine 110 μm)• Između stjenka panela je ispuna ekspandiranim poliesterom
(EPS – stiropor) ili kamenom vunom koja panelu daju iz-vrsna mehanička, termodinamička i prigušna svojstva
• Paneli izvedeni kao vodotjesni – svi žljebovi izmeđupanela zapunjeni cleanroom silikonom
• Unutar panelnog sistema predviđeni kanali za razvodelektroinstalacija
• Standardna boja zidova RAL 9002, ostale boje dostupnena zahtjev
• Debljine panela: 42, 62, 82 mm• Opcija: zidovi sa olovnom zaštitom, zaštita od zračenja
Opcija 1. Podni aluminijski profili montirani na građevinskinivelirani pod, slijedi instalacija PVC ili EPOXY poda
Opcija 2. Profilirani podni aluminijski profilimontirani na gotov pod (PVC ili EPOXY)
SVOJSTVA
• Čvrstoća• Glatka površina, bez izbočina• Lako čišćenje i održavanje• Neporoznost, ne upija vodu• Otpornost na habanje, kemikalije• Toplinska i zvučna izolacija• Zaštita od korozije• Dugotrajnost
MONTAŽA
• Paneli se montiraju u čvrsti aluminijski podni profil• Učvršćivanje putem aluminijskih „H“ profila (prije postavljanja
poda) ili „U“ profila (na postavljen pod)• Spajanje panela pomoću aluminijskih profila, spojevi zapu-
njeni cleanroom silikonom• Dio panela predviđen kao montažno-demontažni radi uno-
šenja/iznošenja krupne opreme• Jednostavna montaža i demontaža u slučaju izmjena• U panelima se predviđaju otvori za ugradnju istrujnih rešetki
ČISTI PROSTORI
ZIDNI PANEL - SASTAVNI DIJELOVI
Spojni profil
Podna vodilica
Ispuna
Okvir
Lim
ČISTI PROSTORI 11
PVC ovalni profil Aluminijski ovalni profil
OVALNI PROFILI
• Svi spojevi stropova i zidova izvedeni sa zaobljenjima • Svi spojevi podova i zidova izvedeni sa zaobljenjima• Ovalnim profilima se prekrivaju aluminijski profili koji ver-
tikalno spajaju zidove ili horizontalno spajaju zidove sastropovima
• Izrađeni iz PVC-a ili aluminija
TEHNIČKI PODACI
Zidni paneli
OZNAKE Eng. Hrv.
CRWPAN Cleanroom Wall Panel Cleanroom zidni panel
GS Galvanized steel sheet Pocinčani čelični lim
AL Aluminium sheet Aluminijski lim
ST Stainless steel Nehrđajući lim
RW Rockwool Kamena vuna
PS Styrofoam Stiropor
CRWAB Cleanroom Wall Panel Antibacterial Antibakterijski zidni panel
Moguće izvedbe drugih dimenzija prema zahtjevu.
ZIDNI PANELI 42/62/82 mm
Tip CRWPANGS RW
CRWPANAL RW
CRWPANST RW
CRWPANGS PS
CRWPANAL PS
CRWPANST PS
42 ili 82 mm
CRWABPS ili RW
Opis Modularni Cleanroom OBLOŽNI paneli bez vidljive podkonstrukcije - 42 mmModularni Cleanroom OBLOŽNI i PREGRADNI paneli bez vidljive podkonstrukcije - 62, 82 mm
Debljina 42 mm ILI 62 mm ILI 82 mm (± 1 mm)
Dimenzije Ovisno o zahtjevima projekataMax.dimenzije panela iz jednog komada 1200 x 4000 mm (širina x visina)
Stjenke/obloga Pocinčani čelični lim0,8 mm
Aluminijski lim1,0 mm
Nehrđajući lim0,8 mm
Pocinčani čelični lim0,8 mm
Aluminijski lim1,0 mm
Nehrđajući lim0,8 mm
Antibakterijskialuminijski lim
1,0 mm
Fina obradaPoliester lakirani 25mikrona sa odvojenim zaštitnim filmom
Plastifikacija 60mikrona sa odvojenimzaštitnim filmom
Razni površinskizavršeci dostupni
Poliester lakirani 25mikrona sa odvojenimzaštitnim filmom
Plastifikacija 60mikrona sa odvojenimzaštitnim filmom
Razni površinskizavršeci dostupni
Plastifikacija PVC sloj debljine110 mikrona
BojaRAL 9002
Ostale boje iz RAL karte dostupne na zahtjev
-RAL 9002
Ostale boje iz RAL karte dostupne na zahtjev
-
RAL 9002Ostale boje iz
RAL kartedostupne na zahtjev
IspunaKamena vuna (100 kg/m³), klasa A1
Reakcija panela na požar sukladno standardu: EN 13501-1+A1:2009, A2-s1, d0
Stiropor (30 kg/m³) Kamena vuna ilistiropor
Težina/m²42 mm - 15 kg62 mm - 17 kg82 mm - 19 kg
42 mm - 9 kg62 mm - 11 kg82 mm - 13 kg
42 mm - 5 kg62 mm - 17 kg82 mm - 19 kg
42 mm - 13 kg62 mm - 14 kg82 mm - 14 kg
42 mm - 7 kg62 mm - 8 kg82 mm - 8 kg
42 mm - 13 kg62 mm - ------82 mm - 14 kg
42 mm - 13 kg62 mm - 14 kg82 mm - 14 kg
Spoj Spojni profil
Podni profil Aluminijski bazni profil h=100 mm ili U profil
12 ČISTI PROSTORI
ANTIBAKTERIJSKE KARAKTERISTIKE
• Antibakterijski premaz debljine 110 μm• Antibakterijske karakteristike djeluju u prisutnosti
okolišnih uvjeta koji pogoduju širenju bakterija, glji-vica i algi
• Dvostruko djelovanje: sprječava nastanak bakterijai eliminira postojeće
• Dugotrajna zaštita, čak i kada standardno čišćenjenije moguće
• Širok raspon boja, sa naglaskom na pastelne boje,najčešće korištene u farmaceutici
PODRUČJA PRIMJENE
• Farmaceutika• Laboratoriji• Mikroelektronika• Prehrambena industrija• Bolnice• Zdravstvene i zubne ordinacije• Istraživački instituti
SVOJSTVA• Izdržljivost i trajnost• Glatka površina, bez izbočina• Lako čišćenje i održavanje• Neporoznost, ne upija vodu• Kemijska otpornost• Toplinska otpornost• Otpornost na mikroorganizme• Otpornost na koroziju i ogrebotine
Bakterije
Ioni srebraAntibakterijski
premaz
Otpuštanje iona srebra
Okoliš
Antimikrobnapovršina
Površinski sloj
Specijalna nano tehnologija
Antibakterijski premaz sadrži ione srebra
Ioni srebra sprječavaju nastanak bakterija
Eliminacija bakterija prisutnih na površini
Nano čestice u boji
Osigurana jaka antibakterijska zaštita
Zaštitni film
Antibakterijski film
Ljepilo
Površinska zaštita
Površinska zaštita
Temeljninanos
Cink
Cink
Metalik zaštita
ANTIBAKTERIJSKI PREMAZ
DJELOVANJE ANTIBAKTERIJSKIH KARAKTERISTIKA
Testiranja potvrđuju antibakterijska svojstva u sprječavanju nastanka navedenih bakterija, uz efikasnost preko 99%
Escherichia Coli Klebisella pneumoniae Staphylococcus aureus Salmonella typhimurim Listeria monocytogenes Legionella pneumophila Pseudomonas aeruginosa
Antibakterijski paneli
Širok raspon boja
ČISTI PROSTORI 13
Antibakterijski paneli
14 ČISTI PROSTORI
TEHNIČKE KARAKTERISTIKE
• Panel kao segment stropa izrađen iz dvije stjenke limapresavijene oko rubova (sendvič paneli), ojačan okvirom
• Stjenke panela mogu biti izrađene iz:- pocinčanog čeličnog lima plastificiranog u boju debljine
25 μm- aluminijskog lima plastificiranog u boju debljine 60 μm- pocinčanog čeličnog lima plastificiranog u antibakterij-
sku boju debljine 110 μm- aluminijskog lima plastificiranog u antibakterijsku boju
debljine 110 μm- nehrđajućeg lima (opcija: plastifikacija u antibakterijsku
boju debljine 110 μm)• Između stjenka panela je ispuna ekspandiranim polieste-
rom (EPS – stiropor) ili kamenom vunom koja panelu dajuizvrsna mehanička, termodinamička i prigušna svojstva
• Paneli izvedeni kao vodotjesni – svi žljebovi između pa-nela zapunjeni cleanroom silikonom
• Unutar panelnog sistema predviđeni kanali za razvodelektroinstalacija
• Standardna boja stropova RAL 9002, ostale boje do-stupne na zahtjev
• Debljine panela: 42, 62, 82 mm• Stropovi su prohodni (do 100 kg), neprohodni stropovi
dostupni na zahtjev• Opcija: Stropovi sa olovnom zaštitom, zaštita od zra-čenja
MONTAŽA
• U stropnim panelnim sistemima nalazi se ovjes za montažuna betonsku ili čeličnu konstrukciju, neprimjetno ovješenstrop
• Ugradnja spuštenog stropa standardnih dimenzija 1,2 x 2,4 m(ovisno o obliku i veličini prostorije)
• U stropu se ostavljaju otvori za ugradnju anemostata, lampii svjetlarnika, spojevi zapunjeni cleanroom silikonom
• Jednostavna montaža i demontaža u slučaju izmjena
SVOJSTVA
• Čvrstoća• Glatka površina, bez izbočina• Lako čišćenje i održavanje• Neporoznost, ne upija vodu• Otpornost na habanje, kemikalije• Prohodnost• Toplinska i zvučna izolacija• Zaštita od korozije• Dugotrajnost
Stropni paneliSTROPNI PANEL - SASTAVNI DIJELOVI
Stropni paneli Razvod elektroinstalacija
Lim
Okvir
Ispuna
ČISTI PROSTORI 15
Stropni paneli
TEHNIČKI PODACI
OZNAKE Eng. Hrv.
CRCPAN Cleanroom Ceiling Panel Cleanroom stropni panel
GS Galvanized steel sheet Pocinčani čelični lim
AL Aluminium sheet Aluminijski lim
ST Stainless steel Nehrđajući lim
RW Rockwool Kamena vuna
PS Styrofoam Stiropor
CRCAB Cleanroom Ceiling Panel Antibacterial Antibakterijski stropni panel
STROPNI PANELI 42/62/82 mm
Tip CRCPANGS RW
CRCPANAL RW
CRCPANST RW
CRCPANGS PS
CRCPANAL PS
CRCPANST PS
CRCABPS ili RW
Opis Modularni Cleanroom OBLOŽNI paneli bez vidljive podkonstrukcije
Debljina 42 mm ILI 62 mm ILI 82 mm (± 1 mm)
Dimenzije Ovisno o zahtjevima projekataMax.dimenzije panela iz jednog komada 1200 x 4000 mm (širina x visina)
Stjenke/obloga Pocinčani čelični lim0,8 mm
Aluminijski lim1,0 mm
Nehrđajući lim0,8 mm
Pocinčani čelični lim0,8 mm
Aluminijski lim1,0 mm
Nehrđajući lim0,8 mm
Antibakterijskialuminijski lim
1,0 mm
Fina obradaPoliester lakirani 25mikrona sa odvojenim zaštitnim filmom
Plastifikacija 60mikrona sa odvojenimzaštitnim filmom
Razni površinskizavršeci dostupni
Poliester lakirani 25mikrona sa odvojenimzaštitnim filmom
Plastifikacija 60mikrona sa odvojenimzaštitnim filmom
Razni površinskizavršeci dostupni
Plastifikacija PVC sloj debljine110 mikrona
BojaRAL 9002
Ostale boje iz RAL karte dostupne na zahtjev
-RAL 9002
Ostale boje iz RAL karte dostupne na zahtjev
-
RAL 9002Ostale boje iz
RAL kartedostupne na zahtjev
IspunaKamena vuna (100 kg/m³), klasa A1
Reakcija panela na požar sukladno standardu: EN 13501-1+A1:2009, A2-s1, d0
Stiropor (30 kg/m³) Kamena vuna ilistiropor
Težina/m²42 mm - 15 kg62 mm - 17 kg82 mm - 19 kg
42 mm - 9 kg62 mm - 11 kg82 mm - 13 kg
42 mm - 5 kg62 mm - 17 kg82 mm - 19 kg
42 mm - 13 kg62 mm - 14 kg82 mm - 14 kg
42 mm - 7 kg62 mm - 8 kg82 mm - 8 kg
42 mm - 13 kg62 mm - 14 kg82 mm - 14 kg
42 mm - 13 kg62 mm - 14 kg82 mm - 14 kg
Spoj Spojni profil
Ovjes Nevidljivi ovjes, montaža na betonsku ili čeličnu konstrukciju
Moguće izvedbe drugih dimenzija prema zahtjevu.
16 ČISTI PROSTORI
OZNAKE Eng. Hrv.
CRW Cleanroom Window Cleanroom prozor
AL Aluminium frame Aluminijski okvir
TEHNIČKE KARAKTERISTIKE
• Prozor je sastavni dio zidnog panela• Debljina prozora jednaka debljini zidnog panela• Prozor izrađen iz dvostrukog stakla 6+6 mm• U okvir prozora umetnut silica gel koji upija vlagu, sprje-čavanje nastanka kondenzata u prostoru između dvastakla
• Staklene stijene – prozor izveden kao staklena stijena izspecijalnih profila i jednostrukog stakla debljine 10 mm
• Cleanroom prozori i staklene stijene u dimenzijamaprema zahtjevima projekata
• Opcija: ugrađene rolete za zaštitu od sunca ili pogleda,automatsko podešavanje (daljinski upravljač)
• Opcija: samozatamnjivanje stakla, automatsko podeša-vanje (prekidač osjetljiv na dodir, daljinski upravljač)
Cleanroom prozori
MONTAŽA
• Prozori se u aluminijskom profilu ugrađuju u panele• Spojevi zapunjeni cleanroom silikonom
SVOJSTVA
• Čvrstoća• Glatka površina, bez izbočina• Lako čišćenje i održavanje• Neporoznost, ne upija vodu• Zaštita od kondenzacije
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
PROZOR - SASTAVNI DIJELOVI
Profil prozora
Dvostruko staklo
Panel
CLEANROOM PROZORI
Tip CRW 42 AL900 mm
CRW 42 AL1200 mm
CRW 62 AL900 mm
CRW 62 AL1200 mm
CRW 82 AL900 mm
CRW 82 AL1200 mm
Opis Cleanroom prozor, dvostruko staklo 6+6 mm, punjen silica gelom
Debljina 42 42 62 62 82 82
Visina 900 1200 900 1200 900 1200
Dimenzije
600 x 900900 x 900
1200 x 9001500 x 9001800 x 900
600 x 1200900 x 1200
1200 x 12001500 x 12001800 x 1200
600 x 900900 x 900
1200 x 9001500 x 9001800 x 900
600 x 1200900 x 1200
1200 x 12001500 x 12001800 x 1200
600 x 900900 x 900
1200 x 9001500 x 9001800 x 900
600 x 1200900 x 1200
1200 x 12001500 x 12001800 x 1200
ČISTI PROSTORI 17
Cleanroom prozori
18 ČISTI PROSTORI
Cleanroom vrataTEHNIČKE KARAKTERISTIKE
• Vrata izrađena iz cleanroom panela i aluminija, ispunaiz kamene vune, tvrdog stiropora ili aluminijskih saća
• Moguća izvedba sa prozorom ili bez prozora (dimenzijeprema zahtjevu)
• Ostakljenja unutar vratnih krila izvedena bez fuga, utorai sl.
• Ugrađena brava sa ključem i kvaka od nehrđajućeg limaili kugla
• Na podnoj strani vrata ugrađena automatska pomičnagumena brtva koja sprječava prestrujavanje zraka ispodvrata (održavanje razlike tlaka u prostoru)
• Standardna boja RAL 9002, ostale boje dostupne nazahtjev
• Vrata u prostorima sa klasama (režimima tlaka) osiguranasamozatvarajućim mehanizmima, osigurana maksimalnaprionjivost, magnet
• Vrata svojom konstrukcijom osiguravaju održavanje na-dtlaka u prostoriji
• Opcija: otvor za istrujnu rešetku• Upravljanje: ručno ili automatsko
TIPOVI CLEANROOM VRATA
• Ručna/Automatska okretna jednokrilna• Ručna/Automatska klizna jednokrilna• Ručna okretna dvokrilna simetrična/asimetrična• Automatska okretna dvokrilna simetrična• Ručna/Automatska klizna dvokrilna simetrična
HIDRAULIČNE PUMPE
• Slabija, za vrata širine krila do 1100 mm• Jača, za vrata širine krila do 1400 mm• Podesiva sila zatvaranja, ovisno o tlakovima u
prostorima• Mogućnost podešavanja brzine zatvaranja i
zaustavljanja vrata• Za desnu ili lijevu stranu (potezanje ili guranje)• Optički indikator snage zatvaranja• Zupčasti zatvarač sa kliznom vodilicom, za kli-
zna vrata
VRATA - SASTAVNI DIJELOVI
Okretna vrata
Klizna vrata
Jednokrilna klizna vrata Dvokrilna klizna vrata
SVOJSTVA
• Čvrstoća• Glatka površina, bez izbočina• Lako čišćenje i održavanje• Neporoznost, ne upija vodu• Otpornost na habanje, kemikalije• Toplinska i zvučna izolacija• Zaštita od korozije• Dugotrajnost
Magnetski kontakt
Semafor za interlock
Elektromagnetskablokada
Brava
Padajuća brtva
Automatika
Prozor
Ukopna ručka
Krilo - panel
Sporedno krilo
Pant
Kvaka
Prozor
Dovratnik
Jednokrilna okretna vrata Dvokrilna okretna vrata
ČISTI PROSTORI 19
Cleanroom vrata
INTERLOCK SISTEMI
• Mogućnost raznih načina programiranja sustava• Kada su vrata unutar sistema zatvorena, LED lampica signalizira ze-
leno svijetlo, kada se jedna vrata otvore, ostala se automatski zaklju-čavaju i LED lampica signalizira crveno svijetlo
• Kada je više vrata otvoreno, javljaju se alarm i svjetlosna indikacija• Tipkalo za paniku u slučaju uzbune automatski otključava sva vrata• Mogućnost autoriziranog ulaza, pomoću sigurnosne kartice
DIMENZIJE CLEANROOM VRATA
Tip Dimenzije(širina x visina) Ispuna Brava sa
ključem Prozor
Jednokrilna okretna vrataCRDAB ili CRD 62 AL
Jednokrilna okretna vrata sa prozorom
CRDWAB AL ili CRDW 62 AL
800 x 2200/82/62 mm900 x 2200/82/62 mm
1000 x 2200/82/62 mm1100 x 2200/82/62 mm1200 x 2200/82/62 mm
Tvrdi stiropor ilikamena vunadebljine 82/60 mm ilial. saće (62)
Da
Obostrano 6+6 mm uravnini krila 400 x 700 mm
Dvokrilna okretna vrataCRDAB AL ili CRD 62 AL
Dvokrilna okretna vrata sa prozorom
CRDWAB AL ili CRDW 62 AL
1300 x 2200/82/62 mm1400 x 2200/82/62 mm1500 x 2200/82/62 mm1600 x 2200/82/62 mm1700 x 2200/82/62 mm1800 x 2200/82/62 mm1900 x 2200/82/62 mm2000 x 2200/82/62 mm2100 x 2200/82/62 mm2200 x 2200/82/62 mm
Tvrdi stiropor ilikamena vunadebljine 82/60 mm ilial. saće (62)
Da Obostrano 6+6 mm uravnini krila 400 x 700 mm
Klizna jednokrilna vrata sa ili bez prozora CRDSAB AL
800 x 2200/42 mm900 x 2200/42 mm
1000 x 2200/42 mm1100 x 2200/42 mm1200 x 2200/42 mm1300 x 2200/42 mm
Tvrdi stiropor ilikamena vunaili al. saće(62)
Ne
Obostrano 6+6 mm uravnini krila 400 x 700 mm
Klizna dvokrilna vrata sa ili bez prozora CRDSAB AL
1300 x 2200/42 mm1400 x 2200/42 mm1500 x 2200/42 mm1600 x 2200/42 mm1700 x 2200/42 mm1800 x 2200/42 mm1900 x 2200/42 mm2000 x 2200/42 mm2100 x 2200/42 mm2200 x 2200/42 mm
Tvrdi stiropor ilikamena vunaili al. saće(62)
Ne
Obostrano 6+6 mm uravnini krila 400 x 700 mm
OZNAKE Eng. Hrv.
CRD Cleanroom door Cleanroom vrata
CRDS Cleanroom door sliding Cleanroom vrata klizna
CRDW Cleanroom door window Cleanroom vrata sa prozorom
CRDAB Cleanroom door antibacterial Cleanroom vrata antibakterijska
CRDSAB Cleanroom door sliding antibacterial
Cleanroom vrata klizna antibakterijska
CRDWAB Cleanroom door window antibacterial
Cleanroom vrata sa prozorom antibakterijska
AL Aluminium sheet Aluminijski lim
AL-HC Aluminium honeycomb Aluminijske saće
Moguće izvedbe drugih dimenzija prema zahtjevu.
Jednokrilna okretna vrata
Dvokrilna klizna vrata Ključanica Pomična gumena brtva Hidraulična pumpa Interlock
TEHNIČKI PODACI
20 ČISTI PROSTORI
Cleanroom podoviTEHNIČKE KARAKTERISTIKE
• Elektroprovodljivi, zrnata struktura• Antistatički• Otpornost na kemikalije, mehaničke mrlje i toplinu• Nema vidljivih tragova habanja• Bez fuga, zatvoreni spojevi• Vodonepropusni• Protuklizni• Površina otporna na trošenje, pogodna za često čišćenje
• Širok izbor boja i dezena• Trajnost: od 15-40 godina
SIGURNOSNA SVOJSTVA
• Otpornost na požar EN 13501-1: Bfl-S1(DIN 4102 B1), više tipova
• Protukliznost BGR 181: grupa R10, višeopcija
• Prigušenje topota koraka ISO 140-8: 3 dB
VRSTE CLEANROOM PODOVA
• EPOXY- kompaktna glatka površina, bez pora, izrađena od
epo xy smole praškastih granula na PU osnovi- izvodi se na podlozi od zaglađenog betona ili cementnog
estriha- pogodni za farmaceutsku industriju
• PVC- visoko impregnirani PVC, polivinilklorid- najčešće se izvodi na podlozi od cementnog estriha
MINIMALNI ZAHTJEVI PODNE PODLOGE
• Prolazni otpor EN 1081: ≤1 x 106 Ω, za elektro-provodljive podove
• Debljina EN 428: 2,2 mm• Otpornost na habanje EN 685: 31/43• Toplinska vodljivost EN 12524: 0,25 W/mK• Zaostalo utisnuće EN 433: 0,04• Plošna masa EN 430: 2900 g/m²• Tlačna čvrstoća: 80N/mm²• Prionjivost: >3N/mm²• Mehanička elastičnost: 15'000N/mm²• Tvrdoća: Sh.75• Visoka kemijska otpornost: DIN 53454, 53452,
53750, ISO 868
EPOXY
PVC
Širok raspon bojai uzoraka
Širok raspon bojai uzoraka
ČISTI PROSTORI 21
Cleanroom lampeTEHNIČKE KARAKTERISTIKE
• Metalno kućište, plastificirano u bijelu boju, druge bojena zahtjev
• U svjetiljke se ugrađuju lampe 14W, 24W, 28W, 54W iTC-L 55W, adekvatne temperature svjetla i visoke ene-rgetske učinkovitosti
• Kao cjelina u panelnom sistemu osiguravaju zrakone-propusnost tj. nadtlak u čistom prostoru
• Prozirno ili mat kaljeno staklo, u kombinaciji sa adekvatnimodsijaćima
• Za čiste prostore, operacijske dvorane, odjele intenzivnenjege, laboratorije
MONTAŽA
• Ugradnja u stropni panel• Zamjena cijevi u lampama iz tehničke zone ili iz čistog
prostora
Florescentne cijevi Zaštita
Cleanroom lampe
4 x 14W
IP 54, IP 65, IP 664 x 24W
2 x 28W
2 x 54W
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
22
STROJARSKE INSTALACIJE
KLIMA KOMORE - uređaji za pripremuzrakaTEHNIČKE KARAKTERISTIKE
• Stjenke glatke, bez izbočina• Unutarnja površina panela izrađena iz plastificiranog
pocinčanog čeličnog lima, nehrđajućeg lima ili lima ot-pornog na morsku vodu (AIMg)
• Svi dijelovi uređaja neporozni, ne upijaju vlagu• Svi dijelovi uređaja otporni na sredstva za čišćenje i de-
zinfekciju• Jednostavan pristup dijelovima radi čišćenja i dezinfekcije• Uređaji opremljeni žaluzijama u zrakotijesnoj izvedbi
(prema DIN 1946 dio 4)• Sustav za sigurno otjecanje kondenzata• Parni ovlaživači• Rekuperatori topline za iskorištavanje energije otpadnog
zraka• Ventilatori i motori zaštićeni od korozije, na pokretnom
okviru radi lakšeg čišćenja i dezinfekcije• Prigušne kulise lako dostupne• Opcija: Klima komore u Ex izvedbi
FUNKCIJSKE JEDINICE
KONSTRUKCIJSKI ZAHTJEVI
• Upotreba materijala koji ne ugrožavaju zdravlje i nisupogodna podloga za stvaranje štetnih mikroorganizama
• Unutarnje površine uređaja izraditi iz materijala otpornihna trošenje, čišćenje i dezinfekciju
• Osigurati dostupnost za pregled, čišćenje i dezinfekcijusvih dijelova koji provode zrak
FILTERI
• Vrećasti filteri u 1. stupnju filtracije, klase F5 ili više, u 2.stupnju filtracije klase F7 ili više
• Filteri klase G4 i F5 za zaštitu izmjenjivača topline• Filteri klase F7 ili više za smanjenje onečišćenja zraka u
distributivnim kanalima i zaštitu HEPA filtera na distribu-tivnim elementima
• Ventilatorska jedinica
S visokoučinskim radijalnim dvousisnim ventilatorima,elektromotorom i klinastim remenskim prijenosom, klasazaštite IP 55. Centrifugalni ventilator bez kućišta direktnopogonjen elektromotorom. Postolje s protuvibrirajućimumetcima.
• Ovlaživačka jedinicaParni ovlaživač sa električnim generatorom pare ili za cen-tralnu pripremu pare.
• Jedinica s rekuperatorom toplineKV lamelni rekuperator s dva izmjenjivača topline.
• Prigušivač zvukaAkustična ispuna kulisa negoriva, klase A2 prema DIN4102, presvučena materijalom otpornim na habanje.
• Usisna/Istrujna miješajuća jedinicaKlima uređaj sa ili bez regulacijske žaluzije, za regulacijutlaka ili protoka zraka, s elastičnim spojem ili usisnimkanalom.
• Filterska jedinicaKlima uređaj s filterskim umetcima sukladno DIN24185. Klasa filtera prema EN 779: G1-G2, G3-G4,F5-F9 i H10-H14. Panelni, vrećasti, kompaktni, HEPAfilteri.
• Ogrjevna jedinicaIzmjenjivač topline za toplu vodu, mješavinu glikola,paru ili freon. Električni grijač s elementima regulacijei zaštite.
• Rashladna jedinicaIzmjenjivač topline za hladnu vodu, mješavinu glikolaili direktnu ekspanziju freona. Tava za nakupljanjekondenzata na dnu jedinice. Eliminator kapljica izPVC-a i okvirom iz nehrđajućeg čelika.
ČISTI PROSTORI
23
NORME I SMJERNICE
• HRN EN 1886:2003 – Ventilacija u zgradama – Cen-tralne jedinice za pripremu zraka – Tehničke značajke(EN 1886:1998)
• HRN EN 13053:2004 – Ventilacija u zgradama – Cen-tralne jedinice za pripremu zraka – Podjela i značajkeza jedinice, dijelove i sekcije (EN 13053:2001+AC:2002)
• VDI 3803 – Temeljni tehnički zahtjevi za ventilacijske iklimatizacijske sustave
• VDI 6022, dio 1 – Higijenski zahtjevi za projektiranje,ugradnju, pogon i održavanje sustava ventilacije –Uredski prostori i prostori za okupljanje
• VDI 6022, dio 3 – Higijenski zahtjevi za projektiranje,ugradnju, pogon i održavanje sustava ventilacije uproizvodnim pogonima
• DIN 1946, dio 2 – Zdravstveni zahtjevi za ventilacijskei klimatizacijske sustave
• DIN 1946, dio 4 – Ventilacijski i klimatizacijski sustaviu bolnicama
ČISTI PROSTORI
24
STROJARSKE INSTALACIJE
HVAC sustavi
ČISTI PROSTORI
TEHNIČKE KARAKTERISTIKE
• Rešetke iz eloksiranog aluminija ili čelika
• Rešetke sa podesivim, nepomičnim ili neprovidnim la-melama, sa/bez zaklopki
• Anemostati iz eloksiranog aluminija ili čelika
• Anemostati sa podesivim, fiksnim ili neprovidnim lamelama,krilasti, perforirani, vrtložni varijabilni, stropni raspori, sahorizontalno-vertikalnim istrujavanjem, krilasti zakretni,sa pojedinačno podesivim istrujnim elementima, sa/bezzaklopki, sa/bez priključne kutije
• Rešetke i anemostati za razne visine ugradnje, podeša-vanje smjera istrujavanja, plastifikacija u standardnubijelu boju RAL 9010, ostale boje na zahtjev
• Specijalni distributeri: sapnice, zračni ventili, rešetke zaprozračivanje, istrujne rozete, stubišni distributeri vrtložnii krilasti, vrtložni distributeri, podni istrujni difuzori
• Žaluzine i zaklopke iz pocinčanog čeličnog lima, alumi-nijskog lima ili ekstrudiranih aluminijskih profila, sa/bezugradne rame
• Regulatori varijabilnog i konstantnog protoka zraka, ci-lindrični ili pravokutni, tvorničko namještanje prema zah-tjevima, bez održavanja, elektromotorni ili ručni pogon,regulatori tlaka
• Prigušivači zvuka sa aerodinamički oblikovanom kulisom,kulisa iz negorivog, apsorpcijskog materijala – kamenevune, u skladu s klasom A2 prema HRN i DIN 4102, dio1. Zadovoljeni higijenski zahtjevi prema VDI 6022, part 1i part 3, DIN 1946 part 2 i part 4, VDI 3803
• Protupožarne zaklopke, cilindrične ili pravokutne, motornipogon ili ručni pogon sa taljivom vezom, ispitane premanormi HRN EN 1366-2 na 300 Pa, klasificirane premanormi HRN EN 13501-3
• Opcija: Sustavi u Ex izvedbi
ZAHTJEVI PRI PROJEKTIRANJU
• Zrak u prostoru treba biti čist - bez mirisa, prašine iostalih nečistoća
• Temperatura i relativna vlažnost u unutarnjem prostorutrebaju zadovoljiti definirane uvjete prema namjeni i ak-tivnostima u prostoru
• Ukupna dobavna struja zraka mora sadržavati higijenskipropisani minimalni udio svježeg vanjskog zraka
VENTILACIJSKE REŠETKE
STROPNI DISTRIBUTERI
SPECIJALNIDISTRIBUTERI
REGULATORIPROTOKA
PRIGUŠIVAČI
PROTUPOŽARNEI DIMOODVODNEZAKLOPKE
PROIZVODNI PROGRAM
25
AUTOMATIKA
BMS (Building Management System)
ČISTI PROSTORI
TEHNIČKE KARAKTERISTIKE
• Automatizacija u čistim prostorima i zgradama
• Kontrola i nadzor mehaničke i električne opreme: ventilacija,rasvjeta, elektroenergetski sustavi, požarni sustavi, si-gurnosni sustavi i dr.
• Internetski protokoli: DeviceNet, BACnet, LONWorks,Modbus
• Pravilno konfiguriran ostvaruje značajnu uštedu energije
• Bilježenje svih pojava u skladu sa GMP smjernicama
PREDNOSTI
• Kontrola unutarnjih uvjeta udobnosti• Mogućnost individualne regulacije• Povećana produktivnost osoblja• Učinkovito praćenje potrošnje energije• Veća pouzdanost postrojenja• Uštede pri održavanju• Nadzor HVAC sustava (klima komore, protupožarne za-
klopke, regulatori protoka zraka, prigušivači buke)• Centralno ili daljinsko upravljanje• Jednostavno, sigurno i brzo otkrivanje problema
• Rasvjeta
• Temperatura, rel. vlaga
• Električna energija
• Tlačni profil
• Količine zraka
• Upravljanje interlocksistemima
• HVAC sustav pripremeenergenata
• Sigurnost i nadzor• Kontrola pristupa• Protupožarni sustav• Dizala, liftovi• Ostali sustavi koji traže
kontinuirani nadzor
REGULACIJA I NADZOR PARAMETARA
26 FILTRACIJA I VENTILACIJA
FILTRACIJA ZRAKA
Okolišni zrak, kako vanjski, tako i u zatvorenim prostorima po-dložan je kontaminaciji krutim ili tekućim česticama mineralnogili organskog podrijetla koje zovemo aerosolima. Veličina ovih če-stica je od 0,0001 μm do 100 μm. Čestice veće od 10 μm redo-vito se talože na tlo, dok čestice manje od 1 μm, a naročito onemanje od 0,3 μm, ostaju lebdjeti u zraku. Prosječna koncentracijaovih čestica u atmosferi iznad europskog kontinenta mjeri se umilijunima po 1 litri zraka, a dijele se u donje kategorije:
• Prašina - male čvrste čestice
• Dim - sitne čvrste čestice
• Magla - sitne kapljice
• Sumaglica - vrlo sitne kapljice
• Para - plinovita supstanca
Uzorci nastanka navedenih čestica su:
• Prirodni procesi koji se odvijaju na površini Zemlje
• Raslinje na Zemlji
• Organizmi koji nastanjuju Zemlju, uključujući ljudska bića
• Tehnološki procesi stvoreni od strane čovjeka
Pomoću apsolutnih1 filtera ta se koncentracija može smanjiti načak 3,5 čestice po 1 litri zraka, pa i na manje. Osim prašine, oko-lišni i ambijentalni zrak sadrži još i žive mikroorganizme, mikrobe,fermente, gljivice, bakterije, viruse itd. Zrak koji je sasvim čist odživih organizama zovemo sterilnim. Takav se zrak može dobitisamo korištenjem apsolutnih filtera.Iskustva nekih istraživača pokazuju da postoji odnos izmeđubroja živih čestica i broja inertnih (organskih i neorganskih) če-stica i da se taj odnos kreće od 1:500 do 1:12000, a najčešće je1:1000.Nakon prolaza kroz apsolutni filter zrak je praktički čist i sterilan.Ako se traži još veća sigurnost u pogledu sterilnosti, tada se izaapsolutnog filtera ugrađuju UV svjetiljke koje ubijaju eventualnepreostale mikroorganizme koje nije uspio zaustaviti apsolutni filter.
1 Slobodniji izraz za filtere za lebdeće čestice, zbog njihove vrlo velike efikasnosti.
FILTRACIJA I VENTILACIJA 27
Klasifikacija filtera prema normamaOsnovni činilac u filtraciji zraka su filterski materijali tj. filterski ulo-šci, ili kraće, filteri: grubi, fini i apsolutni (filteri za lebdeće čestice).Grubi, fini i apsolutni filteri ugrađeni u finalni proizvod (okvir ililimeno kućište) redovito dobivaju proširene nazive, npr.
• Panelni filter• Kanalski filter• Stropni distributer s apsolutnim filterom
Filter kao finalni proizvod sastoji se od jednog, dva ili tri filterskauloška, pri čemu zadnji ugrađen u nizu zovemo filterom, a pret-hodne predfilterima.
Godine 1993. Europski komitet za normizaciju, Tehnički komitet195, Radna grupa 1 (CEN/TC195-WG1) donio je nove norme
za grube i fine filtere za opću ventilaciju. Uvođenjem ove norme,pod imenom EN 779, zemlje članice Europske unije obveznesu izdati svoje vlastite nacionalne verzije normi unutar postav-ljenog okvira (npr. BS EN 779 u Velikoj Britaniji, DIN EN 779 uNjemačkoj). Norma EN 779 zasnovana je na postojećim doku-mentima kao što su EUROVENT 4/5 i ASHRAE 52.1:1992, ali jeu stvari mnogo stroža od njih. Ona obuhvaća i novi sustav klasi-fikacije za grube i fine filtere, zasnovan na prosječnoj efikasnostiizdvajanja prašine pri određenom konačnom padu tlaka. Filteri spočetnim stupnjem efikasnosti Eo < 20% su klasificirani kao grubifilteri u rasponu G1-G4. Konačni pad tlaka kod certifikacije jeodređen s ≤ 250 Pa. Filteri s početnim stupnjem efikasnosti Eo ≥20% su klasificirani kao filteri u rasponu E5-F9. Konačni pad tlakakod certifikacije je određen s ≤ 450 Pa.
StFDIN
24185, dio 100
DIN 24185, dio 2 EN 779
GRUB
I
A A EU 1 Am < 65 - G1
B
B1 EU 2 65 ≤ Am ≤ 80 - G2
B2EU 3 80 ≤ Am ≤ 90 - G3
EU 4 90 ≤ Am - G4
FINI C
C1EU 5 - 40 ≤ Em ≤ 60 M5
EU 6 - 60 ≤ Em ≤ 80 M6
C2 EU 7 - 80 ≤ Em ≤ 90 F7
C3EU 8 - 90 ≤ Em ≤ 95 F8
EU 9 - 95 ≤ Em F9
StFDIN
24185, dio 100
DIN 24185, T1, E, dodatak A
E % 0,3 μm E % MPPS
EN 1822
HE
PA
Filteri za
lebdeće čestice
Q EU 10
1
> 95 - E10
3
R EU 11 > 98 - E11
SEU 12 > 99,99 - E12
EU 13 > 99,997 - H13
EU 14 > 99,999 - H14
UL
PA
- E % 0,12 μm
EU 15
2
- > 99,9995 U15
4EU 16 - > 99,99995 U16
EU 17 - > 99,999995 U17
KLASIFIKACIJA FILTERA ZA ZRAK PREMA RAZLIČITIM NORMAMA
Oznaka Objašnjenje
1 Uobičajeni apsolutni filteri
2 Visokoefikasni apsolutni filteri
3 Visokoefikasni filteri za lebdeće čestice (HEPA)
4 Filteri za lebdeće čestice s ultra niskim propuštanjem (ULPA)
StF Institut za istraživanje prašine Saveza zanatskih stručnih grupa u Bonnu, Njem.
DIN 24185, dio 100DIN 24185, dio 2 Odgovara europskoj klasifikaciji EUROVENT-a
EUROVENT Europski odbor proizvođača postrojenja za tehnički zrak i sušenje u Frankfurtu, Njem.
EN 779EN 1822 Europske norme
Am Prosječni stupanj izdvajanja za GRUBE filtere (u odnosu na umjetnu prašinu)
Em Prosječna efikasnost za FINE filtere (u odnosu na umjetnu prašinu)
E % Srednja (minimalna) efikasnost za HEPA i ULPA filtere
MPPS Veličina čestica koje najviše prolaze kroz filter (Most Penetrating Particle Size)
HEPA Visokoučinski filter za lebdeće čestice (High Efficiency Particulate Air Filter)
ULPA Ultra nisko propusni filter za lebdeće čestice (Ultra Low Penetration Air Filter). U ovu grupu ubrajaju se i apsolutni filteri s komercijalnim nazivimaVHSI, MEGA, SUPER MEGA i dr.
LEGENDA
28 FILTRACIJA I VENTILACIJA
• Filteri od staklenih vlakana u roli
• Filteri od sintetičkih vlakana u roli
• Filteri od sintetičkih vlakana otpornih na temperaturudo 200°C
• Filteri od sintetičkih vlakana za lakirnice
• Filteri od papira
• Vrećasti filteri od sintetičkih vlakana
• Vrećasti filteri od sintetičkih i staklenih vlakana
• Spaljivi vrećasti filteri
• Perivi metalni filteri
• Kompaktni visokokapacitetni filteri
• Apsolutni HEPA i ULPA filteri
• Apsolutni filteri za čiste prostore i operacijskedvorane
• Filteri otporni na visoke temperature (do 480°C)
• Filteri s aktivnim ugljenom
• Filteri u roli s automatskim pogonom
• Filteri za otprašivanje
• Elektrostatski filteri
Osim efikasnosti apsolutnog filtera, koja je definirana klasom urasponu E10-U17, korisniku može biti od značaja podatak o ve-ličini čestice koja najviše prolazi (penetrira) kroz filterski medijkod određene brzine strujanja zraka. U tu svrhu provodi se ispi-tivanje opisano u nastavku.
Veličina čestice koja najviše prodire kroz filtracijski medij(MPPS), utvrđena je za danu brzinu zraka (smjer strujanja jeokomit na filtersku površinu).
Kroz filter struje aerosol i MPPS čestice. Mjesna i ukupna efi-kasnost definira se brojačem čestica (CNC) ili laserskim spek-trometrom.Filter se klasificira u skladu s rezultatima ispitivanja u klaseE10-H14 za HEPA, odnosno U15-U17 za ULPA filtere.Propuštanje (penetracija) je definirano kao maksimalno dozvo-ljeno mjesno (lokalno) prodiranje MPPS-a, koje izraženo u po-stocima, ne smije prijeći peterostruku vrijednost ukupnogpropuštanja.
PROPUŠTANJE ČESTICA ODREĐENE VELIČINE (PREMA CEN TC/WG2 NO22 DRAFT)
Klasa filtera
Efikasnost u odnosu na MPPS Propuštanje (penetracija) uodnosu na MPPS
Ukupna Mjesna Ukupno Mjesno
E10 ≥ 85 - 15 -
E11 ≥ 95 - 5 -
E12 ≥ 99,5 97,5 0,5 2,5
H13 ≥ 99,95 99,75 0,05 0,25
H14 ≥ 99,995 99,975 0,005 0,025
U15 ≥ 99,9995 99,9975 0,0005 0,0025
U16 ≥ 99,99995 99,99975 0,00005 0,00025
U17 ≥ 99,999995 99,999975 0,000005 0,0001
OPASKA:
• Za filtere klase E10 i E11 nije potrebna potvrda o lokalnom prop-uštanju (penetraciji)
• Filteri u klasi E12, H13 i H14 mogu se ispitati pomoću testa suljnom maglom, u skladu sa normom EN 1822 što je općenitoprihvaćeno i mnogo poznatije od navedenog mjesnog propuš-tanja
• Filter klase U17 predstavlja izuzetak od pravila; u ovom slučajuvrijednost mjesnog propuštanja izražena u postocima, ne smijebiti veća od dvadesetorostruke vrijednosti ukupnog propuštanja
Izvedbe filtera
FILTRACIJA I VENTILACIJA 29
Orijentacijski podaci za grube i fine filtereGrubi filteri prostorne filtracije najčešće se koriste u klimatiza-ciji proizvodnih hala, kompresorskih stanica, za zaštitu električ-nih uređaja ili kao predfilteri u zahtjevnijim klima komorama(lakirnice, poslovne zgrade…).
Fini filteri prostorne filtracije prisutni su u bolnicama, laborato-rijima, elektranama, lakirnicama i drugdje.
Apsolutni filteri najčešće se koriste u operacijskim dvora-nama, medicinskoj i farmaceutskoj industriji, sterilnim punioni-cama, pogonima za mikrotehnologiju i mikro elek troniku, uprehrambenoj industriji i drugim pogonima u kojima je potrebnoispuniti najviše zahtjeve za čistoću zraka.
Klasa G1* G2* G3* G4*
Preporučljiva brzina strujanja m/s 2,5 2,0 2,0 2,0
Jedinični kapacitet m³/h m² 9000 7200 7200 7200
Početni otpor Pa 40 40 45 60
Preporučljivi konačni otpor Pa 100-200 150-200 160-200 160-200
Prosječno izdvajanje Am % do 100 75-80 80-85 87-92
Dozvoljena radna temperatura °C -30 do 120 do 100 do 100 do 100
Debljina mm 10÷20 13÷25 15÷20 20
GRUBI FILTERI
Klasa M5** M6** F7** F8** F9**
Preporučljiva brzina strujanja m/s 0,9 2,5 2,0 2,5 3,5
Jedinični kapacitetm³/h m² 3240 9000 7200 7200 12600
Početni otpor Pa 90 80 100 120 120-140
Preporučljivi konačni otpor Pa 200-400 250 350 350 450
Prosječna efikasnost Em % 40÷50 60÷80 80÷90 90÷95 više od 95
Dozvoljena radnatemperatura °C do 100 -30 do +90 -30 do +90 -30 do +90 -30 do +90
Debljina mm 20 100 78 100 292
FINI FILTERI
Klase čistoće po ISO 14644-1 standardu 8 7 6 5 4 3
Klase čistoće po U.S.Federal standardu 209 E 100 000 10 000 1 000 100 10 1
Klase čistoće po EU GMP standardu D C B A
Maksimalan dozvoljen broj čestica (čestica/m³) jednak ili veći od
5.0 μm 29 300 2 930 293 29 - -
1.0 μm 832 000 83 200 8 320 832 83 8
0.5 μm 3 520 000 352 000 35 200 3 520 352 35
0.3 μm - - 102 000 10 200 1 020 102
0.2 μm - - 237 000 23 700 2 370 237
0.1 μm - - 1 000 000 100 000 10 000 1 000
Tip strujanja turbulentno turbulentno prijelazno jednosmjerno jednosmjerno jednosmjerno
Maksimalan broj izmjena zraka i/h 36-90 60-100 180-300 300-480 420-600 500-640
Minimalna brzina strujanja m/s 0.08-0.10 0.10-0.15 0.15-0.25 0.26-0.36 0.36-0.41 0.38-0.46
Minimalna pokrivenost stropa filterima % 15 30 40 75 100 100
Tip filtera H12 H12 H13 H14 U16 U16
Otvori za ubacivanje zraka Stropni zakretni distributeri
Stropni zakretni distributeri
Filterski istrujnistrop
Filterski istrujnistrop
Filterski istrujnistrop
Filterski istrujnistrop
Otvori za odsis zraka Postranični zidni
Nisko postavljeni
postranični zidni
Nisko postavljeni postranični
Podni ili niskopostavljeni postranični
Podni Podni
Nadtlak čistog prostora Pa 10-15 10-15 10-15 10-15 1.5 1.5
Temperatura °C
22°C±1°C,ne više od 2°C
varijacije tijekom 4 sata
22°C±1°C,ne više od 2°C
varijacije tijekom 4 sata
22°C±1°C,ne više od 2°C
varijacije tijekom 4 sata
22°C±0.5°C,ne više od 1°C
varijacije tijekom 4 sata
22°C±0.25°C,ne više od 0.5°C
varijacije tijekom 4 sata
22°C±0.25°C,ne više od 0.5°C
varijacije tijekom 4 sata
Vlažnost %
45%RH±5%ne više od 5%
varijacije tijekom 4 sata
45%RH±5%ne više od 5%
varijacije tijekom 4 sata
45%RH±5%ne više od 5%
varijacije tijekom 4 sata
45%RH±5%ne više od 3%
varijacije tijekom 4 sata
45%RH±5%ne više od 3%
varijacije tijekom 4 sata
45%RH±5%ne više od 3%
varijacije tijekom 4 sata
Brojenje čestica 12 mjeseci 12 mjeseci 12 mjeseci 6 mjeseci 6 mjeseci 6 mjeseci
Volumenski protok ili brzina zračne struje 12 mjeseci 12 mjeseci 12 mjeseci 12 mjeseci 12 mjeseci 12 mjeseci
Integritet filtera i kućišta 24 mjeseca 24 mjeseca 24 mjeseca 24 mjeseca 24 mjeseca 24 mjeseca
Vizualizacija strujanja 24 mjeseca 24 mjeseca 24 mjeseca 24 mjeseca 24 mjeseca 24 mjeseca
Klasifikacija različitih klasa čistoće prostora po ISO 14644-1, U.S.F.S. 209 E i EU GMP smjernicama
* Ravni filterski uložak, u svitku (roli) ili sašiven u oblik vreće ** Plisirani filterski uložak, ugrađen u različite okvire
30 FILTRACIJA I VENTILACIJA
Apsolutni stropni filter FACTEHNIČKE KARAKTERISTIKE
• Apsolutni stropni filter s istrujnom pločom namijenjen zadovod visoko filtriranog zraka u čiste prostore klase 7 i 8prema ISO 14644 standardu (laboratoriji, operacijskedvorane, sobe za intenzivnu njegu)
• Kućište se sastoji od gornjeg modula sa priključkom zazrak i donjeg modula sa apsolutnim filterom klase E10;E11; E12, H13 ili H14 prema EN 1822. Moduli iz nehr-đajućeg čeličnog lima
• Moduli nepropusno izvedeni, svi spojevi zrakonepropu-sni
• Na gornjem modulu priključak za kontrolu propusnostifiltera i kućišta, priključak za DOP test
• Na zahtjev, priključak za kontrolu zapunjenosti filtera • Istrujna ploča izrađena iz čeličnog lima, plastificirana u
bijelu boju RAL 9010, ostale boje ili izrada iz nehrđajućeglima na zahtjev
• Vanjske dimenzije istrujne ploče tvornički prilagođenedimenzijama priključne kutije
• Zamjena filtera sa donje (čiste) strane kućišta, po skidanjuistrujne ploče
PRIKLJUČAK ZA DOVOD ZRAKA NA KUĆIŠTU
• Horizontalni cilindrični priključak FAC-HO• Vertikalni cilindrični priključak FAC-V• Horizontalni pravokutni priključak FAC-H• Horizontalni pravokutni priključak sa zrakotjesnom za-
klopkom, ručni pogon. Opcija elektromotorni pogonFAC-HZ
DODATNA OPREMA
• Priključak za DOP test za ugradnju na panel (zid ili strop)• Priključak za tlak, kontrolu zapunjenosti filtera za ugradnju
na panel (zid ili strop)• Diferencijalni manometar (0-500 Pa)
Gornji modul
HEPA filter
Donji modul
Istrujna ploča
Priključak za zrak
ANK ANP DEK-K DEU DEV-K DVS-K
Za: FAC-HO, FAC-V, FAC-H, FAC-HZ ANEMOSTATI (ISTRUJNE PLOČE)
FAC
DEV-K DEK-K DEU ANK ANP DVS-K
319 x H DEV-K 355/12 DEK-K 355 DEU 355 ANK 3 (CR) 358 ANP 355 -
471 x H DEV-K 510/24 DEK-K 510 DEU 510 ANK 6 (CR) 500 ANP 510 DVS-K 510
549 x H DEV-K 580/24 DEK-K 580 DEU 580 ANK 580 (CR) ANP 580 DVS-K 580
589 x H DEV-K 625/54 DEK-K 625 DEU 625 ANK 8 (CR) 625 ANP 625 DVS-K 625
624 x H DEV-K 660/54 DEK-K 660 DEU 660 ANK 660 (CR) ANP 660 DVS-K 660
Za: FAC-HO, FAC-V, FAC-H, FAC-HZ ANEMOSTATI (ISTRUJNE PLOČE) Efektivne površine Aef (m2)
FAC
DEV-K DEK-K DEU ANK ANP DVS-K
319 x H 0,0149 m2 0,0150 m2 0,0192 m2 0,0295 m2 0,0380 m2 -
471 x H 0,0298 m2 0,0376 m2 0,0517 m2 0,0728 m2 0,0836 m2 0,0180 m2
549 x H 0,0436m2 0,0408 m2 0,0517 m2 0,1080 m2 0,1117 m2 0,0295 m2
589 x H 0,0671 m2 0,0616 m2 0,0718 m2 0,1280 m2 0,1117 m2 0,0295 m2
624 x H 0,0671 m2 0,0616 m2 0,0718 m2 0,1440 m2 0,1451 m2 0,0295 m2
ISTRUJNE PLOČE
DIMENZIJE ISTRUJNIH PLOČA
FAC - SASTAVI DIJELOVI
FILTRACIJA I VENTILACIJA 31
LEGENDA
Nazivna dimenzijaFAC-HO
Dimenzije FAC-HO Dimenzije apsolutnog filtera
b x h x t
Qmax(H13)m³/h
pp(H13)
Pa
Qmax(H14)m³/h
pp(H14)
Pa
pkPaB
(mm)H
(mm)ɸD
(mm)A
(mm)
FAC-
HO
319 x 380 319 380 158 355 305 305 78 250 175 250 220 400
471 x 470 471 470 248 510 457 457 78 570 175 570 220 400
549 x 470 549 470 248 580 535 535 78 770 175 770 220 400
589 x 520 589 535 313 625 575 575 78 890 175 890 220 400
624 x 535 624 535 313 660 610 610 78 1000 175 1000 220 400
Nazivna dimenzija
FAC-V
Dimenzije FAC-V Dimenzije apsolutnog filtera
b x h x t
Qmax(H13)m³/h
pp(H13)
Pa
Qmax(H14)m³/h
pp(H14)
Pa
pkPaB
(mm)H
(mm)ɸD
(mm)A
(mm)
FAC-
V
319 x 328 319 328 158 355 305 305 78 250 175 250 220 400
471 x 328 471 328 248 510 457 457 78 570 175 570 220 400
549 x 328 549 328 248 580 535 535 78 770 175 770 220 400
589 x 328 589 328 313 625 575 575 78 890 175 890 220 400
624 x 328 624 328 313 660 610 610 78 1000 175 1000 220 400
Nazivna dimenzija
FAC-H
Dimenzije FAC-H Dimenzije apsolutnog filtera
b x h x t
Qmax(H13)m³/h
pp(H13)
Pa
Qmax(H14)m³/h
pp(H14)
Pa
pkPaB
(mm)H
(mm)C
(mm)D
(mm)A
(mm)
FAC-
H
319 x 360 319 360 250 120 355 305 305 78 250 175 250 220 400
471 x 360 471 360 400 120 510 457 457 78 570 175 570 220 400
549 x 360 549 360 475 120 580 535 535 78 770 175 770 220 400
589 x 360 589 360 520 120 625 575 575 78 890 175 890 220 400
624 x 360 624 360 550 120 660 610 610 78 1000 175 1000 220 400
Nazivna dimenzijaFAC-HZ
Dimenzije FAC-HZ Dimenzije apsolutnog filtera
b x h x t
Qmax(H13)m³/h
pp(H13)
Pa
Qmax(H14)m³/h
pp(H14)
Pa
pkPaB
(mm)H
(mm)C
(mm)D
(mm)A
(mm)
FAC-
HZ
319 x 360 319 360 250 120 355 305 305 78 250 175 250 220 400
471 x 360 471 360 400 120 510 457 457 78 570 175 570 220 400
549 x 360 549 360 475 120 580 535 535 78 770 175 770 220 400
589 x 360 589 360 520 120 625 575 575 78 890 175 890 220 400
624 x 360 624 360 550 120 660 610 610 78 1000 175 1000 220 400
B [mm] Nazivna dimenzija FAC-a (širina)
H [mm] Visina FAC-a
ΦD [mm] Promjer cilindričnog priključka
A [mm] Dimenzija istrujne ploče
b [mm] Širina apsolutnog filtera
h [mm] Duljina apsolutnog filtera
t [mm] Dubina apsolutnog filtera
C [mm] Duljina pravokutnog priključka
D [mm] Visina pravokutnog priključka
Qmax [m3/h] Protok zraka (maksimalni)
Δpp [Pa] Pad tlaka na filtru početni
Δpk [Pa] Pad tlaka na filtru krajnji
TEHNIČKI PODACI
OP: Oznake za narudžbu, vidi strana 41.
32 FILTRACIJA I VENTILACIJA
Apsolutni kanalski filter FAKTEHNIČKE KARAKTERISTIKE
• Apsolutni kanalski filter namijenjen za apsolutnu filtracijuzraka prije same prostorije u kojoj se zahtjeva visokaklasa čistoće zraka (farmaceutska, prehrambena, elek-tronska industrija, bolnice)
• Filterski uložak je apsolutni HEPA filter klase H13 ili H14za lebdeće čestice 0,3 μm efikasnosti 99,95÷99,995%prema EN 1822
• Priključci za kontrolu zapunjenosti filtera na kućištu• Kućište izrađeno iz nehrđajućeg lima, plastificirano u
bijelu boju RAL 9010, ostale boje na zahtjev• Zamjena filterskog uloška sa bočne strane, po skidanju
poklopca
FAK - DIMENZIJE
TEHNIČKI PODACI
Nazivna dimenzija Apsolutni kanalski filter FAK
Dimenzije FAK Dimenzije apsolutnog filtera
b x h x t
Qmaxm³/h
pp (H13)Pa
pp (H14)Pa
pkPaB
(mm)H
(mm)L
(mm)
FAK
309 x 309 x 450 309 309 450 305 305 78 250 250 280 500
461 x 461 x 450 461 461 450 457 457 78 570 250 280 500
309 x 614 x 450 309 614 450 305 610 78 500 250 280 500
614 x614 x 450 614 614 450 610 610 78 1000 250 280 500
309 x 309 x 600 309 309 600 305 305 292 500 250 280 500
461 x 461 x 600 461 461 600 457 457 292 1140 250 280 500
309 x 614 x 600 309 614 600 305 610 292 1000 250 280 500
614 x 614 x 600 614 614 600 610 610 292 2000 250 280 500
309 x 614 x 600 -max 309 614 600 305 610 292 1500 250 280 500
614 x 614 x 600 -max 614 614 600 610 610 292 3400 250 280 500
OZNAKE
Qmax Maksimalni protok zraka
Δpp (H13) Početni pad tlaka na filteru za klasu H13
Δpp (H14) Početni pad tlaka na filteru za klasu H14
Δpk Konačni pad tlaka na filteru (zapunjen filter)
B, b Širina
H, h Visina
L Duljina
t Dubina
Moguće izvedbe drugih dimenzija prema zahtjevu.
OP: Oznake za narudžbu, vidi strana 41.
FILTRACIJA I VENTILACIJA 33
Apsolutni kanalski filter sa rešetkom FARTEHNIČKE KARAKTERISTIKE
• Apsolutni kanalski filter sa rešetkom namijenjen za dovodvisoko filtriranog zraka u čiste prostore (mikrobiološki la-boratoriji, operacijske dvorane, sobe za intenzivnu njegu,farmaceutska, prehrambena, elektronska industrija)
• Filterski uložak je apsolutni HEPA filter klase H13 ili H14za lebdeće čestice 0,3 μm efikasnosti 99,95÷99,995%prema EN 1822
• Aluminijska rešetka od ekstrudiranih Al-profila zaštićenaanodnom oksidacijom (eloksiranjem) u prirodnoj bojialuminija
• Kućište izrađeno iz nehrđajućeg lima, plastificirano ubijelu boju RAL 9010, ostale boje na zahtjev
• Ugradnja na kraj ventilacijskog kanala• Zamjena filterskog uloška sa čiste strane tj. sa strane
rešetke
FAR - DIMENZIJE
TEHNIČKI PODACI
Nazivna dimenzija Apsolutni kanalski filter FAR
Dimenzije FAR Dimenzije apsolutnog filtera
b x h x t
Qmaxm³/h
pp (H13)Pa
pp (H14)Pa
pkPaB
(mm)H
(mm)L
(mm)
FAR
309 x 309 x 450 309 309 450 305 305 78 250 250 280 500
461 x 461 x 450 461 461 450 457 457 78 570 250 280 500
309 x 614 x 450 309 614 450 305 610 78 500 250 280 500
614 x614 x 450 614 614 450 610 610 78 1000 250 280 500
309 x 309 x 600 309 309 600 305 305 292 500 250 280 500
461 x 461 x 600 461 461 600 457 457 292 1140 250 280 500
309 x 614 x 600 309 614 600 305 610 292 1000 250 280 500
614 x 614 x 600 614 614 600 610 610 292 2000 250 280 500
309 x 614 x 600 -max 309 614 600 305 610 292 1500 250 280 500
614 x 614 x 600 -max 614 614 600 610 610 292 3400 250 280 500
OZNAKE
Qmax Maksimalni protok zraka
Δpp (H13) Početni pad tlaka na filteru za klasu H13
Δpp (H14) Početni pad tlaka na filteru za klasu H14
Δpk Konačni pad tlaka na filteru (zapunjen filter)
B, b Širina
H, h Visina
L Duljina
t Dubina
Moguće izvedbe drugih dimenzija prema zahtjevu.
OP: Oznake za narudžbu, vidi strana 41.
34 FILTRACIJA I VENTILACIJA
Vrećasti kanalski filter FKV-PTEHNIČKE KARAKTERISTIKE
• Vrećasti kanalski filter za pravokutni kanal namijenjenza filtraciju zraka u sustavima ventilacije i klimatizacijegdje se zahtjeva veća čistoća zraka (laboratoriji, farma-ceutska, prehrambena, elektronska industrija, bolnice)
• Ugradnja vrećastog kanalskog filtera produljuje vijek tra-janja HEPA filtera, krupnije čestice se uklanjaju vrećastimfilterom ugrađenim prije HEPA filtera
• Kućište izrađeno iz pocinčanog lima, na zahtjev mogućaizvedba iz čeličnog lima plastificiranog u željenu RALboju ili kompletno iz nehrđajućeg lima
• U kućište ugrađen vrećasti filter klase M5 do F7 premaEN 779
• Zamjena filterskog uloška sa bočne strane kućišta, poskidanju poklopca. Kod većih dimenzija (B >18 mm) po-klopci ugrađeni sa dvije bočne strane radi lakše izmjenefilterskog uloška
FKV-P - DIMENZIJE
TEHNIČKI PODACI
Nazivna dimenzija Vrećasti kanalski filter
FKV-P(za pravokutni kanal)
Dimenzije FKV-P Dimenzije vrećastih filtera b x h x 630 Qmax
m3 / h
Δpp(M5)
Pa
Δpp(M6)
Pa
Δpp(F7)Pa
Δpp(F8)Pa
Δpp(F9)Pa
ΔpkPa
B (mm) H (mm) L (mm)(1; 2; 3; 4; 6 broj komada filtera)
592 x 592 287 x 592 287 x 287
FKV-
P
613 x 613 x 750 613 613 750 1 0 0 3 400 60 68 83 86 86 450
918 x 613 x 750 918 613 750 1 1 0 5 100 60 68 83 86 86 450
1223 x 613 x 750 1223 613 750 2 0 0 6 800 60 68 83 86 86 450
1528 x 613 x 750 1528 613 750 2 1 0 8 500 60 68 83 86 86 450
1833 x 613 x 750 1833 613 750 3 0 0 10 200 60 68 83 86 86 450
613 x 918 x 750 613 918 750 1 1 0 5 100 60 68 83 86 86 450
918 x 918 x 750 918 918 750 1 2 1 7 650 60 68 83 86 86 450
1223 x 918 x 750 1223 918 750 2 2 0 10 200 60 68 83 86 86 450
1528 x 918 x 750 1528 918 750 2 2 1 12 750 60 68 83 86 86 450
1833 x 918 x 750 1833 918 750 3 3 0 15 300 60 68 83 86 86 450
613 x 1223 x 750 613 1223 750 2 0 0 6 800 60 68 83 86 86 450
918 x 1223 x 750 918 1223 750 2 1 0 10 200 60 68 83 86 86 450
1223 x 1223 x 750 1223 1223 750 4 0 0 13 600 60 68 83 86 86 450
1528 x 1223 x 750 1528 1223 750 4 2 0 17 000 60 68 83 86 86 450
1833 x 1223 x 750 1833 1223 750 6 0 0 20 400 60 68 83 86 86 450
Moguće izvedbe drugih dimenzija prema zahtjevu.
OP: Oznake za narudžbu, vidi strana 41.
OZNAKE
Qmax Maksimalni protok zraka
Δpp (M5) Početni pad tlaka na filteru za klasu M5
Δpp (M6) Početni pad tlaka na filteru za klasu M6
Δpp (F7) Početni pad tlaka na filteru za klasu F7
Δpp (F8) Početni pad tlaka na filteru za klasu F8
Δpp (F9) Početni pad tlaka na filteru za klasu F9
Δpk Konačni pad tlaka na filteru (zapunjen filter)
B, b ŠirinaH, h Visina
L Duljina
FILTRACIJA I VENTILACIJA 35
Vrećasti kanalski filter FKV-CTEHNIČKE KARAKTERISTIKE
• Vrećasti kanalski filtar za cilindrični kanal namijenjen zafiltraciju zraka u sustavima ventilacije i klimatizacije gdjese zahtjeva veća čistoća zraka (laboratoriji, farmaceutska,prehrambena, elektronska industrija, bolnice)
• Ugradnja vrećastog kanalskog filtera produljuje vijek tra-janja HEPA filtera, grijača, hladnjaka i sličnih elemenata,krupnije čestice se uklanjaju vrećastim filterom ugrađenimprije HEPA filtera
• Kućište izrađeno iz pocinčanog lima, na zahtjev mogućaizvedba iz čeličnog lima plastificiranog u željenu RALboju ili kompletno iz nehrđajućeg lima
• U kućište ugrađen vrećasti filter klase M5 do F7 premaEN 779
• Zamjena filtarskog uloška sa gornje ili donje stranekućišta, po skidanju gornjeg poklopca
FKV-C - DIMENZIJE
TEHNIČKI PODACI
OP: Oznake za narudžbu, vidi strana 41.
Moguće izvedbe drugih dimenzija prema zahtjevu.
Nazivna dimenzija Vrećasti kanalski filter
FKV-C (za cilindrični kanal)
Dimenzije FKV-C Dimenzije vrećastih filtera b x h x d Qmax
m3 / h
Δpp(M5)Pa
Δpp(M6)
Pa
Δpp(F7)Pa
Δpp(F8)Pa
Δpp(F9)Pa
ΔpkPa
Ø (mm) B (mm) H (mm) C (mm) L (mm) b h d
FKV-
C
100 98 210 170 430 528 204 155 260 200 60 68 83 86 86 450
125 123 210 170 430 534 214 190 260 320 60 68 83 86 86 450
160 158 270 235 450 554 264 220 260 500 60 68 83 86 86 450
200 198 320 245 500 620 312 260 260 720 60 68 83 86 86 450
250 248 370 325 560 680 362 310 360 1100 60 68 83 86 86 450
315 313 430 395 625 745 423 372 360 1500 60 68 83 86 86 450
355 353 520 496 635 765 512 480 360 2100 60 68 83 86 86 450
400 398 520 496 635 765 512 480 360 2400 60 68 83 86 86 450
500 498 620 596 635 765 612 580 360 3600 60 68 83 86 86 450
OZNAKE
Ø Promjer
B, b Širina
H, h Visina
C Promjer priključka
L Duljina
d Dubina
Qmax Maksimalni protok zraka
Δpp (M5) Početni pad tlaka na filteru za klasu M5
Δpp (M6) Početni pad tlaka na filteru za klasu M6
Δpp (F7) Početni pad tlaka na filteru za klasu F7
Δpp (F8) Početni pad tlaka na filteru za klasu F8
Δpp (F9) Početni pad tlaka na filteru za klasu F9
Δpk Konačni pad tlaka na filteru (zapunjen filter)
36 FILTRACIJA I VENTILACIJA
Apsolutni filter sa aktivnim ugljenom FKUTEHNIČKE KARAKTERISTIKE
• Kanalski filter sa aktivnim ugljenom namijenjen za filtracijuzraka i odstranjivanje neugodnih mirisa iz kuhinja, javnihzgrada, ureda i industrijskih postrojenja
• Mogućnost isporuke filtera sa aktivnim ugljenom za ap-sorpciju plinova (kemikalije) u farmaceutskoj i kemijskojindustriji, rafinerijama
• Kućište izrađeno iz pocinčanog lima, na zahtjev mogućaizvedba iz čeličnog lima plastificiranog u željenu RALboju ili kompletno iz nehrđajućeg lima
• U kućištu brtvenica na koju se pričvršćuje filter saaktivnim ugljenom
• Zamjena filterskog uloška sa bočne strane kućišta, poskidanju poklopca
• Maksimalna radna temperatura kontinuirano 50°C• Maksimalna relativna vlažnost zraka 70%
FKU - DIMENZIJE
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
OZNAKE
B Širina
H Visina
L Duljina
Qmax Maksimalni protok zraka
Qnom Nominalni protok zraka
Δp Pad tlaka
Nazivna dimenzija FKUDimenzije FKU Broj
cilindričnih uložaka sa aktivnimugljenom
Qmax Qnom
Pad tlaka za Qnom/ Qmax
Δp (Pa)Δp= constB (mm) H (mm) L (mm)
FKU
309 x 309 x 600 309 309 600 4 840 660 200/280
380 x 380 x 600 380 380 600 5 1050 825 200/280
464 x 309 x 600 464 309 600 6 1260 990 200/280
309 x 614 x 600 309 614 600 8 1680 1320 200/280
760 x 309 x 600 760 309 600 10 2100 1650 200/280
614 x 614 x 600 614 614 600 16 3360 2640 200/280
910 x 1060 x 600 910 1060 600 42 8820 6930 200/280
OP: Oznake za narudžbu, vidi strana 41.
FILTRACIJA I VENTILACIJA 37
Kanalski filter FKKTEHNIČKE KARAKTERISTIKE
• Kanalski filtar za cilindrični kanal namijenjen za filtracijuzraka u sustavima ventilacije i klimatizacije gdje sezahtjeva ugradnja predfiltara radi zaštite elementaunutar ventilacijskog sustava
• Ugradnja vrećastog filtera produljuje vijek trajanja HEPAfiltera, grijača, hladnjaka i sličnih elemenata
• Kućište izrađeno iz pocinčanog lima, na zahtjev mogućaizvedba iz čeličnog lima plastificiranog u željenu RALboju ili kompletno iz nehrđajućeg lima
• U kućište ugrađen vrećasti filter klase G4 ili M5 premaEN 779
• Zamjena filtarskog uloška sa gornje strane kućišta, poskidanju gornjeg poklopca
FKK - DIMENZIJE
Moguće izvedbe drugih dimenzija prema zahtjevu.
OP: Oznake za narudžbu, vidi strana 41.
TIP FKK 100 FKK 125 FKK 160 FKK 200 FKK 250 FKK 315 FKK 355 FKK 400
Qn (m3/h) 170 230 330 470 700 1160 1570 2040
Δpp G4 (Pa) 50 50 50 50 50 50 50 50
Δpp M5 (Pa) 70 70 70 70 70 70 70 70
Δpk (Pa) 250 250 250 250 250 250 250 250
ØD (mm) 98 123 158 198 248 313 353 398
B (mm) 205 215 265 315 365 425 472 515
H (mm) 170 205 235 275 325 390 435 495
C (mm) 120 140 155 180 230 330 400 455
L (mm) 220 252 267 302 352 452 512 574
TEHNIČKI PODACI
OZNAKE
Qn Nazivni protok zraka
Δpp (G4) Početni pad tlaka na filteru za klasu G4
Δpp (M5) Početni pad tlaka na filteru za klasu M5
Δpk Konačni pad tlaka na filteru (zapunjen filter)
38 FILTRACIJA I VENTILACIJA
Propusnik/Prolazna komora - Pass boxTEHNIČKE KARAKTERISTIKE
• Prolazna komora za prijenos materijala iz jedne u druguprostoriju različitih klasa čistoće
• Ugrađen mehanički sistem interlock sustava blokadevrata, opcija bez blokade vrata
• Izrada iz poliranog nehrđajućeg lima AISI 304• Vrata sa termički ojačanim staklom debljine 10 mm• Opcija ugradnje priključaka za dovod i odsis zraka iz ko-
more• Opcija ugradnje UV-C sterilizacijske rasvjete. Na uprav-
ljačkoj ploči određuje se vrijeme rada UV lampe, po ot-varanju vrata propusnika UV lampa se automatski gasi.Ugradnja dodatnog UV filtera na vratima za zaštitu kori-snika
• Mogućnost izvedbe bez blokade vrata
PROPUSNIK
TEHNIČKI PODACI
TipDimenzije radnog prostora (mm)
visina x širina x dubinaod ručke do ručke
Vanjske dimenzije (mm)visina x širina x dubina
od ručke do ručke
PB 666 600 x 600 x 600 700 x 700 x 770
PB 444 400 x 400 x 400 500 x 500 x 570
Moguće izvedbe drugih dimenzija prema zahtjevu.
FILTRACIJA I VENTILACIJA 39
Zračni tuš TKATEHNIČKE KARAKTERISTIKE
• Dimenzije uređaja sukladno prostoru u koji se uređajugrađuje
• Dimenzije radnog prostora sukladno potrebama naru-čioca
• Zračni tuš izrađen iz cleanroom panelnih sistema• Stjenke panela mogu biti izrađene iz:
- pocinčanog čeličnog lima plastificiranog u boju debljine25 μm
- aluminijskog lima plastificiranog u boju debljine 60 μm- pocinčanog čeličnog lima plastificiranog u antibakterijsku
boju debljine 110 μm- aluminijskog lima plastificiranog u antibakterijsku boju
debljine 110 μm- nehrđajućeg lima (opcija: plastifikacija u antibakterijsku
boju debljine 110 μm)• Jednokrilna ili dvokrilna vrata• Automatsko zaključavanje vrata tokom rada (20 sek.),
tipkalo za paniku u slučaju uzbune• Tlačni ventilator• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi. Dodatno ugrađeni HEPA predfil-teri
• Upravljanje: mikroprocesorski kontrolirani parametri skontrolnog panela, ekran osjetljiv na dodir
• Istrujne rešetke
PRINCIP RADA
Ventilator povlači zrak kroz set predfiltera koji filtrirajukrupnije čestice. Zatim ventilator potiskuje zrak premasetu HEPA apsolutnih filtera. Apsolutno čisti zrak krozsapnice struji u radni prostor brzinom 25-30 m/s. Samakinetička energija osigurava otklanjanje čestica sa osobljakoje ulazi u čisti prostor. Ovaj proces je izveden na način100 postotne recirkulacije zraka ili izbacivanjem određenogdijela zraka i nadomještanje novim, apsolutno čistimzrakom, stvarajući podtlak u radnom prostoru zračnogtuša.
TEHNIČKI PODACI
Moguće izvedbe raznih dimenzija prema zahtjevu.
ZRAČNI TUŠ
Validacije i servisiTEHNIČKE KARAKTERISTIKE
• Servisiranje, održavanje i validiranje opreme ili objektaosigurava sigurnost pri upotrebi i duži vijek trajanja
• Održavanje novo izgrađenih ili rekonstruiranih čistih pro-stora i pripadajućih postrojenja
• Validacije prema svjetskim pravilnicima i normama,norma EN 12469 za mikrobiološke zaštitne kabinete,GMP i ISO standardi za čiste prostore
• HVAC balansiranje• CNUS/BMS• Električni ormari• Kalibriranje mjernih uređaja• Ispitivanje integriteta filtera• Brojenje čestica u radnom prostoru• Test oporavka prostora• Vizualizacijski test• Monitoring• Test buke i vibracija• Razina i jednolikost osvjetljenja• Ispitivanje dokumentacije
USLUGE
• Cjelokupna briga o postrojenju, sustavu ili uređaju• Parcijalni servisi• Validacije na zahtjev klijenata
FILTRACIJA I VENTILACIJA 41
Apsolutni stropni filter FAC:
FAC-V 471x328/ F 313/ H13/ ANK
FAC-V - tip priključka za dovod zraka na kućištu
471 - veličina kućišta B (mm)
328 - visina kućišta H (mm)
F 313 - promjer priključka D (mm)
H13 - klasa HEPA filtera prema EN 1822
ANK - tip istrujne ploče
Apsolutni kanalski filter FAK:
FAK 309x614x450/ H14
FAK - oznaka proizvoda
309 - širina kućišta B (mm)
614 - visina kućišta H (mm)
450 - duljina kućišta L (mm)
H14 - klasa HEPA filtera prema EN 1822
Apsolutni kanalski filter sa rešetkom FAR:
FAR 665x630x200/ H13
FAR - oznaka proizvoda
665 - širina kućišta B (mm)
630 - visina kućišta H (mm)
200 - duljina kućišta L (mm)
H13 - klasa HEPA filtera prema EN 1822
OZNAKE ZA NARUDŽBU
Vrećasti kanalski filter pravokutni FKV-P:
FKV-P 1223x613x750-F7
FKV-P - oznaka proizvoda1223 - širina kućišta B (mm)613 - visina kućišta H (mm)750 - duljina kućišta L (mm)F7 - klasa vrećastog filtra prema EN 779
Vrećasti kanalski filter cilindrični FKV-C:
FKV-C 315-F8
FKV-C - oznaka proizvoda315 - nazivni promjerF8 - klasa vrećastog filtra prema EN 779
Apsolutni filter sa aktivnim ugljenom FKU:
FKU 309x614x600 (dodatna oznaka)
FKU - oznaka proizvoda309 - širina kućišta B (mm)614 - visina kućišta H (mm)600 - duljina kućišta L (mm)( ) - dodatna oznaka neorganskih tvari u struji zraka
Kanalski filter FKK:
FKK 250-M5
FKK - oznaka proizvoda250 - nazivni promjerM5 - klasa kanalskog filtra prema EN 779
42 LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
LAMINARNI UREĐAJI ZAŠTITNE KABINE I KABINETIZaštitne kabine i kabineti sastavni su dio svakog laboratorija isuvremenog farmaceutskog pogona. Proizvodnja lijekovaobuhvaća cjeloviti postupak farmaceutsko tehnološkog ob-likovanja gotovog lijeka, uključujući proizvodnju ili zaprimanjetvari i materijala, tehnološku obradu i opremanje te provjerukakvoće, skladištenje i isporuku.Proizvodnja lijekova se odvija u skladu sa jasno definiranimpostupcima, regulativama i zahtjevima - Zakon o lijekovima imedicinskim proizvodima RH, PIC preporuke, GMP smjer-nice, ISO standardi, FDA i PDA tehnička izvješća, a sve u svrhusmanjivanja rizika mikrobiološke kontaminacije, kao i kontami-nacije čestica na najmanju moguću mjeru.Klimaoprema Cleanroom Solutions proizvodi laminarne kabinei kabinete, mikrobiološke zaštitne kabinete, komore za va-ganje/otprašivanje te brojne specijalne uređaje koji su projekti-rani u skladu sa EU GMP smjernicama što kupcima osiguravareputaciju proizvođača lijekova najviših standarda kvalitete.Projektiramo cijele proizvodne prostore te vršimo validacije is-poručene opreme potvrđujući da je oprema ispravna, u skladusa pravilnicima, odgovarajuća za primjenu i sukladna potre-bama naručioca.Projektiramo čiste prostore za proizvodnju sterilnih lijekova ukojima se zrak dobavlja preko filtera odgovarajuće učinkovi-tosti (HEPA) te je nužno održavanje razlike u tlakovima izmeđupojedinih zona. Prostori moraju biti projektirani tako da udovol-javaju zahtjevima za brojem čestica: u mirovanju (at-rest) i uradu (in operation), a ti uvjeti moraju biti definirani za svakuprostoriju (klasu) zasebno. Filtrirani zrak mora imati pozitivantlak u odnosu na okolne prostore u svim radnim uvjetima i moraefikasno ispirati prostor.Zaštitne kabine i kabineti projektirani su na način da sepopravci i zamjene filtera obavljaju u čistom prostoru. Dijelovi
proizvodne opreme koja dolazi u kontakt s proizvodom nesmiju biti reaktivni, aditivni ili apsorptivni do granice koja možeutjecati na kvalitetu proizvoda. Oprema treba biti projektiranaza laku promjenu veličine serije, čišćenje i dezinfekciju.Zaštitne kabine i kabineti štite operatera, predmet rada te radniokoliš od moguće kontaminacije ili biološki opasnog materijala(biohazard) za vrijeme proučavanja i rada sa mikroorga-nizmima i mikrobima. Infektivne čestice, bakterije i virusi, jed-nostanični i višestanični heterotrofni i aklorotrofni organizmisu opasne tvari sa kojima se radi isključivo u laminar flow za-štitnim uređajima.Laminarno strujanje zraka je mirno, jednolično strujanje fluida(kapljevina i plinova) u paralelnim slojevima, bez miješanjameđu njima i bez turbulencija.Važno je odabrati optimalno rješenje, uz optimalne troškove.Prilikom narudžbe ne dobiva se samo „goli“ proizvod već iedukacija za rad na uređaju te su osigurani servis i održavanješto će učiniti naši inženjeri i tehničari.Često je potrebno osigurati sterilno čiste uvjete tamo gdje jeprostor ograničen kao i uređaji u njemu. Ljekarne i maliproizvodni pogoni nemaju razloga za brigu, jer nudimo speci-jalne uređaje koji su „krojeni“ prema korisnikovim zahtjevima iograničenjima koja onemogućuju primjenu standardnih ure-đaja. Ovisno o svojoj funkciji specijalni uređaji osiguravaju za-štitu predmeta rada, otvorenih farmaceutskih supstanci, radnuokolinu sigurnu za operatera te hlađenje recirkulirajućeg zraka.Trajno smo orijentirani prema kupcima čije potrebe pratimo ianaliziramo sa posebnom pažnjom proizvodeći i isporučujućizaštitne kabine i kabinete za proizvodnju lijekova u obliku am-pula, tableta, film tableta, kapsula, masti, gelova, emulzija, sus-penzija i sirupa.
LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI 43
44 LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Prijenosni laminarni kabinet KTP-ATEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada• Tip strujanja zraka: laminarno, vertikalno• Brzina strujanja zraka: 0.25-0.45 m/s, sa mogućnosti
podešavanja• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Upravljanje kabinetom: ručno kontrolirani parametri• Konstrukcija: plastificirani čelik i specijalni cleanroom
profili• Radna površina: nehrđajući perforirani čelik• Radni prostor: zaštićen staklenim stijenama• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Zamjena filtera: promjena se vrši sa gornje strane, bez
zadiranja u radni prostor• Buka: niska razina buke• Osvjetljenje: FLUO lampa, > 750 lux-a• Zauzima malo prostora
OPCIONALNA UGRADNJA
• Priključci za razne medije (plin, zrak, vakum, voda)• Električna utičnica (230 V)• UV baktericidna lampa• Diferencijalni manometar za kontrolu zapunjenosti HEPA
filtera• Brojač radnih sati kabineta• Brojač radnih sati UV lampe• Moguća izvedba iz nehrđajućeg čelika
PRINCIP RADA
Kabinet uzima zrak kroz predfilter koji filtrira krupniječestice. Zatim ventilator potiskuje zrak prema HEPA ap-solutnom filteru. Zahvaljujući posebnom sustavu distribucije,zrak laminarno struji u radni prostor i osigurava visokistupanj čistoće radnog prostora.
HEPA filtrirani zrak
okolni zrakrecirkulirajući zrak
LEGENDA:
TEHNIČKI PODACI
Tip KTP-A II KTP-A IV
Vanjske dimenzije (mm)širina x dubina x visina 494 x 556 x 950 645 x 710 x 950
Radni prostor (mm)širina x dubina x visina 459 x 459 x 470 610 x 610 x 470
Max. snaga (W) 130 180
HEPA filter H14 (EN1822) mm 457 x 457 x 69 610 x 610 x 69
Izmjene zraka (m³/h) 450 600
Napon/frekvencija (V/Hz) 230/50 230/50
Težina (kg) 40 50
Moguće izvedbe drugih dimenzija prema zahtjevu.
LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI 45
Horizontalni laminarni kabinet KTH-S
OPCIONALNA UGRADNJA
• Priključci za razne medije (plin, zrak, vakum, voda)• Električna utičnica u radnom prostoru (230 V)• UV baktericidna lampa• Diferencijalni manometar za kontrolu zapunjenosti HEPA
filtera• Postolje (visina: sjedeća 750 mm, stojeća 950 mm)• Moguća izvedba iz nehrđajućeg čelika• UV baktericidna lampa• Brojač radnih sati UV lampe
TEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada• Tip strujanja zraka: laminarno, horizontalno• Brzina strujanja zraka: 0.25-0.45 m/s, sa mogućnosti
podešavanja• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Upravljanje kabinetom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Konstrukcija: plastificirani čelik• Radna površina: nehrđajući polirani čelik• Radni prostor: nehrđajući čelik AISI 304• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Osvjetljenje: FLUO lampa, >750 lux-a• Sigurnost: vizualni alarmi nepovoljnih stanja• Buka: niska razina buke• Brojač radnih sati kabineta
PRINCIP RADA
Kabinet uzima zrak kroz predfilter koji filtrira krupniječestice. Zatim ventilator potiskuje zrak prema HEPA ap-solutnom filteru. Zahvaljujući posebnom sustavu distribucije,zrak laminarno struji u radni prostor i osigurava visokistupanj čistoće radnog prostora.
HEPA filtrirani zrak
okolni zrakrecirkulirajući zrak
LEGENDA:
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
Tip KTH-S I KTH-S II KTH-S III KTH-S IV
Vanjske dimenzije (mm)širina x dubina x visina 970 x 1025 x 880 1275 x 1025 x 880 1580 x 1025 x 880 1885 x 1025 x 880
Radni prostor (mm)širina x dubina x visina 940 x 500 x 610 1245 x 500 x 610 1550 x 500 x 610 1855 x 500 x 610
Max. priključna snaga(W) 1600 1600 1650 1650
Max. priključna snagana utičnici (W) 550 550 550 550
Napon/frekvencija(V/Hz) 230/50 230/50 230/50 230/50
Težina (kg) 200 255 285 315
46 LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Vertikalni laminarni kabinet KTV-STEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada• Tip strujanja zraka: laminarno, vertikalno• Brzina strujanja zraka: 0.25-0.45 m/s, sa mogućnosti
podešavanja• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Upravljanje kabinetom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Konstrukcija: plastificirani čelik i specijalni cleanroom
profili• Radna površina: nehrđajući polirani čelik• Radni prostor: nehrđajući čelik AISI 304, električni podizač
prednjeg zaštitnog stakla• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Osvjetljenje: FLUO lampa, >750 lux-a• Sigurnost: vizualni alarmi nepovoljnih stanja• Buka: niska razina buke• Brojač radnih sati kabineta• UV baktericidna lampa• Električna utičnica u radnom prostoru (230 V)
OPCIONALNA UGRADNJA
• Priključci za razne medije (plin, zrak, vakum, voda)• Diferencijalni manometar za kontrolu zapunjenosti HEPA
filtera• Postolje (visina: sjedeća 750 mm, stojeća 950 mm)• Moguća izvedba iz nehrđajućeg čelika
PRINCIP RADA
Ventilator potiskuje zrak kroz HEPA filter. Apsolutni filtriranizrak laminarno struji u radni prostor. Jedan dio zraka (25-30%) izlazi u okolni prostor prema operateru, a drugi diozraka (70-75%) se kroz radnu površinu recirkulira prekoapsolutnog HEPA filtera. Zrak koji se ispuhao u okolinunadomješta se novim koji ulazi u sistem recirkulacije krozpredfilter klase G4.
HEPA filtrirani zrak
okolni zrakrecirkulirajući zrak
LEGENDA:
Tip KTV-S I KTV-S II KTV-S III KTV-S IV
Vanjske dimenzije (mm)širina x dubina x visina 1030 x 825 x 2200 1335 x 825 x 2200 1640 x 825 x 2200 1945 x 825 x 2200
Radni prostor (mm)širina x dubina x visina 885 x 610 x 660 1190 x 610 x 660 1495 x 610 x 660 1800 x 610 x 660
Max. priključna snaga(W) 1800 1800 1850 1850
Max. priključna snagana utičnici (W) 550 550 550 550
Napon/frekvencija(V/Hz) 230/50 230/50 230/50 230/50
Težina (kg) 270 300 320 350
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI 47
Tip KTV-A I KTV-A II KTV-A III KTV-A IV
Vanjske dimenzije (mm)širina x dubina x visina 970 x 750 x 2020 1275 x 750 x 2020 1580 x 750 x 2020 1885 x 750 x 2020
Radni prostor (mm)širina x dubina x visina 925 x 600 x 650 1230 x 600 x 650 1535 x 600 x 650 1840 x 600 x 650
Max. priključna snagana utičnici (W) 450 520 650 750
Napon/frekvencija(V/Hz) 230/50 230/50 230/50 230/50
Težina (kg) 74 85 102 120
Moguće izvedbe drugih dimenzija prema zahtjevu.
Vertikalni laminarni kabinet KTV-ATEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada• Tip strujanja zraka: laminarno, vertikalno• Brzina strujanja zraka: 0.25-0.45 m/s, sa mogućnosti
podešavanja• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Upravljanje kabinetom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Konstrukcija: plastificirani čelik i specijalni cleanroom
profili• Radna površina: nehrđajući polirani čelik• Radni prostor: zaštićen staklenim stijenama• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Osvjetljenje: FLUO lampa, >750 lux-a• Sigurnost: vizualni alarmi nepovoljnih stanja• Buka: niska razina buke• Brojač radnih sati kabineta
OPCIONALNA UGRADNJA
• Priključci za razne medije (plin, zrak, vakum, voda)• Električna utičnica u radnom prostoru (230 V)• UV baktericidna lampa• Brojač radnih sati UV lampe• Diferencijalni manometar za kontrolu zapunjenosti HEPA
filtera• Postolje (visina: sjedeća 750 mm, stojeća 950 mm)• Moguća izvedba iz nehrđajućeg čelika
PRINCIP RADA
Kabinet uzima zrak kroz predfilter koji filtrira krupniječestice. Zatim ventilator potiskuje zrak prema HEPA ap-solutnom filteru. Zahvaljujući posebnom sustavu distribucijezrak laminarno struji u radni prostor i osigurava visokistupanj čistoće radnog prostora.
HEPA filtrirani zrak
okolni zrakrecirkulirajući zrak
LEGENDA:
TEHNIČKI PODACI
48
Mikrobiološki zaštitni kabinetKTB-NS (Klasa II)TEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada, operatera i okoline• Tip strujanja zraka: laminarno, vertikalno• Brzina strujanja zraka: 0.25-0.45 m/s, sa mogućnosti
podešavanja• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Upravljanje kabinetom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Konstrukcija: plastificirani čelik i specijalni cleanroom
profili• Radna površina: nehrđajući polirani čelik• Radni prostor: nehrđajući čelik AISI 304, električni podizač
prednjeg zaštitnog stakla• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Osvjetljenje: FLUO lampa, > 750 lux-a• Baktericidno UV svjetlo za sterilizaciju• Sigurnost: vizualni alarmi nepovoljnih stanja• Buka: niska razina buke• Brojač radnih sati kabineta• Brojač radnih sati UV lampe• Električna utičnica u radnom prostoru (230 V)
OPCIONALNA UGRADNJA
• Priključci za razne medije (plin, zrak, vakum, voda)• Diferencijalni manometar za kontrolu zapunjenosti HEPA
filtera i izlaznog HEPA filtera• Postolje (visina: sjedeća 750 mm, stojeća 950 mm)• Moguća izvedba iz nehrđajućeg čelika
PRINCIP RADA
Mikrobiološki zaštitni kabinet recirkulira 70% kontaminiranogzraka kroz jedan HEPA filter i ispuhuje preostalih 30%preko drugog HEPA filtera. Nadolazeći zrak laminarnostruji brzinom 0.45 m/s u radni prostor, osiguravajući ap-solutno čistu radnu zonu.Ovakva izvedba strujanja zraka čini sistem sukladnimrazinama 1, 2 i 3 biokontaminacije.
LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Tip KTB-NS I KTB-NS II KTB-NS III KTB-NS IV
Vanjske dimenzije (mm)širina x dubina x visina 1030 x 825 x 2200 1335 x 825 x 2200 1640 x 825 x 2200 1945 x 825 x 2200
Radni prostor (mm)širina x dubina x visina 885 x 610 x 660 1190 x 610 x 660 1495 x 610 x 660 1800 x 610 x 660
Max. priključna snaga(W) 1800 1800 1850 1850
Max. priključna snagana utičnici (W) 550 550 550 550
Napon/frekvencija(V/Hz) 230/50 230/50 230/50 230/50
Težina (kg) 270 300 320 350
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
kontaminirani zrakHEPA filtrirani zrakokolni zrak
LEGENDA:
49
Mikrobiološki zaštitni kabinet KTB-VS (Klasa II)Specijalni model s apsolutnim predfilterom za visoko rizične laboratorije
TEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada, operatera i okoline• Tip strujanja zraka: laminarno, vertikalno• Brzina strujanja zraka: 0.25-0.45 m/s, sa mogućnosti
podešavanja• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Upravljanje kabinetom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Konstrukcija: plastificirani čelik i specijalni cleanroom
profili• Radna površina: nehrđajući polirani čelik• Radni prostor: nehrđajući čelik AISI 304, električni podizač
prednjeg zaštitnog stakla• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS prema
EN 1822 normi. Dodatno ugrađeni HEPA predfilteri• Osvjetljenje: FLUO lampa, > 750 lux-a• Baktericidno UV svjetlo za sterilizaciju• Sigurnost: vizualni alarmi nepovoljnih stanja, vizualni i
zvučni alarm stanja filtera• Buka: niska razina buke• Brojač radnih sati kabineta• Brojač radnih sati UV lampe• Električna utičnica u radnom prostoru (230 V)
OPCIONALNA UGRADNJA
• Priključci za razne medije (plin, zrak, vakum, voda)• Diferencijalni manometar za kontrolu zapunjenosti HEPA
filtera i izlaznog HEPA filtera• Postolje (visina: sjedeća 750 mm, stojeća 950 mm)• Moguća izvedba iz nehrđajućeg čelika
LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Tip KTB-VS I KTB-VS II KTB-VS III KTB-VS IV
Vanjske dimenzije (mm)širina x dubina x visina 1030 x 825 x 2200 1335 x 825 x 2200 1640 x 825 x 2200 1945 x 825 x 2200
Radni prostor (mm)širina x dubina x visina 885 x 610 x 660 1190 x 610 x 660 1495 x 610 x 660 1800 x 610 x 660
Max. priključna snaga(W) 1800 1800 1850 1850
Max. priključna snagana utičnici (W) 550 550 550 550
Napon/frekvencija(V/Hz) 230/50 230/50 230/50 230/50
Težina (kg) 270 300 320 350
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
kontaminirani zrakHEPA filtrirani zrakokolni zrak
LEGENDA:
PRINCIP RADA
Mikrobiološki zaštitni kabinet recirkulira 70% kontaminiranogzraka kroz jedan HEPA filter i ispuhuje preostalih 30%preko drugog HEPA filtera. Razlika u odnosu na klasični mi-krobiološki kabinet su HEPA predfilteri s velikom površinom,ugrađeni ispod radnog pulta. Sav ulazni i recirkulacijskizrak pročisti se kroz HEPA predfiltere, tako da su izlazni iradni filter izloženi kontaminiranom zraku tek pri zamjeni.Mijenjanje HEPA predfiltera izvodi se pri normalnom radukabineta. Segmenti filtera se demontiraju u radnomprostoru, u zaštitnoj atmosferi, a zatim hermetički zatvarajuu PVC vreće. Na ovaj način osigurana je potpuna zaštitapri servisiranju kabineta u kojima se radi sa opasnimagensima.
50 LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
IVF kabinetTEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada• Tip strujanja zraka: laminarno, vertikalno• Brzina strujanja zraka: 0.25-0.45 m/s, sa mogućnosti
podešavanja• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Upravljanje kabinetom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Konstrukcija: nehrđajući čelik i specijalni cleanroom profili• Radna površina: nehrđajući polirani čelik• Temperatura radne površine: grijaća ploča 22ºC-45ºC,
podesiva• Radni prostor: zaštićen staklenim stijenama• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Osvjetljenje: FLUO lampa, > 750 lux-a• Sigurnost: vizualni alarmi nepovoljnih stanja, vizualni i
zvučni alarm stanja filtera• Napajanje: 230 V, 50 Hz• Postolje (visina: sjedeća 750 mm, stojeća 950 mm)• Buka: niska razina buke• Brojač radnih sati kabineta
OPCIONALNA UGRADNJA
• LCD monitor 19“• CO2 inkubator zapremnine 14-16 litara• Priključci za razne medije (plin, zrak, vakum, voda)• Električna utičnica u radnom prostoru (230 V)• Stereomikroskop: povećanje min. 120 puta, adapter za
kameru• UV baktericidna lampa• Brojač radnih sati UV lampe• Diferencijalni manometar za kontrolu zapunjenosti HEPA
filtera
PRINCIP RADA
Kabinet uzima zrak kroz predfilter koji filtrira krupniječestice. Zatim ventilator potiskuje zrak prema HEPA ap-solutnom filteru. Zahvaljujući posebnom sustavu distribucije,zrak laminarno struji u radni prostor i osigurava visokistupanj čistoće radnog prostora.
Tip IVF I IVF II IVF III IVF IV
Vanjske dimenzije (mm)širina x dubina x visina 970 x 750 x 2120 1275 x 750 x 2120 1580 x 750 x 2120 1885 x 750 x 2120
Radni prostor (mm)širina x dubina x visina 925 x 600 x 750 1230 x 600 x 750 1535 x 600 x 750 1840 x 600 x 750
Max. priključna snaga(W) 450 520 650 750
Max. priključna snagana utičnici (W) 230/50 230/50 230/50 230/50
Napon/frekvencija(V/Hz) 84 95 112 130
Težina (kg) 270 300 320 350
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
HEPA filtrirani zrak
okolni zrakrecirkulirajući zrak
LEGENDA:
51LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
UV kabinet za sterilizacijuTEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada, zaštita operatera odUV zraka. Konstantna dekontaminacija unutar radnogprostora
• Tip strujanja zraka: kružno recirkulacijsko strujanje• Broj izmjena zraka u radnom prostoru: 50 izmjena/h• Konstrukcija: nehrđajući čelik AISI 304• Staklo: dvoslojno, UV nepropusno (lamistal)• Recirkulacijski sklop: unutar maske kabineta, sastoji se
od ventilatora, UV lampe i filtera G4 (EN 779) za prašinu• UV lampa: 8.000 radnih sati, ugrađena u gornjem dijelu
radnog prostora, UV zračenje dezinficira radni prostoruništavanjem DNA/RNA fragmenata tijekom 15-30 minutneizloženosti. Druga UV lampa unutar regulacijskog sklopa
• Automatsko isključivanje UV lampe po otvaranju zaštitnogstakla, vremenski brojač rada UV lampe 30 min
• Osvjetljenje: FLUO lampa 15W• Brojač radnih sati kabineta• Brojač radnih sati UV lampe• Buka: niska razina buke• Za vrijeme rada operatera UV lampa unutar radnog
prostora ne smije biti u funkciji
PRINCIP RADA
UV kabinet pokreće se pomoću ključa te automatskipokreće ventilator i uključuje UV lampu unutar recirkula-cijskog sklopa. Ventilator povlači zrak iz radnog prostorakroz filter klase G4 koji eliminira krupnije kontaminante iusmjerava ga prema UV recirkulacijskom sklopu u kojemuUV lampa sterilizira struju zraka. Sterilizirana struja zrakase kroz izlaznu perforaciju na stropu UV kabineta vraćanatrag u radni prostor te se ciklus ponavlja. Tijekom radaodređena količina zraka iz radnog prostora izlazi ispodstakla u prostoriju dok ista količina zraka iz prostorijeulazi u radni prostor kabineta.
sterilizirani zrak
okolni zrakdjelomično filtrirani zrak
LEGENDA:Tip IVF
Vanjske dimenzije (mm)širina x dubina x visina 690 x 515 x 555
Radni prostor (mm)širina x dubina x visina 675 x 500 x 405
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
52 LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Laminarna kabina KATEHNIČKE KARAKTERISTIKE
• Tip zaštite: zaštita predmeta rada u velikim radnim pro-storima
• Tip strujanja zraka: laminarno, vertikalno• Brzina strujanja zraka: 0.45 m/s ± 20%• Radna brzina: 0.30, 0.35, 0.40, 0.45 m/s • Pripremni (stand-by) mod: 0.25 m/s• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Radni prostor: zaštićen UV stabilnim PVC trakama• Konstrukcija: nehrđajući satinirani lim AISI 304 (DIN 1.4301)• Upravljanje kabinom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Predfilteri: klase G4 do F9 (EN 779)• Sigurnost: automatska kontrola filtera i kvara uređaja
(vizualni i zvučni alarmi) • Osvjetljenje: integrirano osvjetljenje, 500 lux-a na radnoj
visini• Brojač radnih sati kabine
OPCIONALNA UGRADNJA
• Diferencijalni manometar za kontrolu zapunjenosti HEPAfiltera
• Baktericidno UV svijetlo za sterilizaciju• Brojač radnih sati UV lampe• Ex protueksplozijska izvedba, certifikati za ugrađene
komponente
PRINCIP RADA
Kabina uzima zrak kroz predfiltere koji filtriraju krupniječestice. Ventilatori usmjeravaju zrak kroz HEPA apsolutnefiltere. Zahvaljujući posebnom sustavu distribucije, zraklaminarno struji u radni prostor i osigurava apsolutnočistu atmosferu.
MONTAŽA
• Ovješena o strop• Postavljena na fiksne noseće stupove• Postavljena na stupove sa kotačima
TEHNIČKI PODACI
Moguće izvedbe raznih dimenzija prema zahtjevu.
HEPA filtrirani zrak
okolni zrakrecirkulirajući zrak
LEGENDA:
53LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Komora za vaganje/otprašivanje VKATEHNIČKE KARAKTERISTIKE
• Tip zaštite: radna okolina sigurna za operatera sprječavaudisaj opasnih čestica, zaštita okoline komore sprječavada čestice generirane unutar komore budu distribuiraneizvan nje, zaštita otvorenih farmaceutskih supstanci odkontaminacije održavanjem laminarne zračne strujeunutar komore i pomoću zračne zavjese na ulazu (PVC)
• Tip strujanja zraka: laminarno, vertikalno• Radna brzina: 0.30, 0.35, 0.40, 0.45 m/s• Pripremni (stand-by) mod: 0.25 m/s• Klasa čistoće: ISO klasa 5(4), 100(10) klasa po
U.S.F.S.209 E, GMP klasa A• Konstrukcija: nehrđajući satinirani lim AISI 304 (DIN 1.4301)• Upravljanje komorom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Predfilteri: klase G4 do F9 (EN 779)• Sigurnost: automatska kontrola filtera i kvara uređaja
(vizualni i zvučni alarmi) • Osvjetljenje: integrirano osvjetljenje, 500 lux-a na radnoj
visini• Uređaj konstruiran za rad u tri smjene• PVC zaštitna zavjesa• Brojač radnih sati komore
PRINCIP RADA
Ventilatori usmjeravaju zračnu struju kroz paket sigurnosnihHEPA filtera i zrak ulazi u radni prostor u laminarnoj verti-kalnoj struji. Od ukupne količine zraka 10-15% istrujava uokolinu, povečavajući čistoću prostora. Na dnu radnogprostora zrak se povlači kroz predfiltere i zajedno sazrakom iz okoline čini upravo onu količinu zraka koja jeprethodno ispuhana. Zračna struja se filtrira preko HEPAfiltera i ciklus se ponavlja.
OPCIONALNA UGRADNJA
• Dodatna vizualna kontrola filtera (analogni diferencijalniumjereni manometar)
• Zračna zavjesa: sprječava kontaminaciju radnog prostora,ugrađena na ulazu u kabinu
• Hladnjak• Baktericidno UV svjetlo za sterilizaciju• Brojač radnih sati UV lampe• Safe change• Ex protueksplozijska izvedba, certifikati za ugrađene
komponente
TEHNIČKI PODACI
Moguće izvedbe raznih dimenzija prema zahtjevu.
HEPA filtrirani zrak
djelomično kontaminirani zrak
okolni zrakdjelomično filtrirani zrak
LEGENDA:
54 LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Komora za vaganje/otprašivanje VKOTEHNIČKE KARAKTERISTIKE
• Tip zaštite: radna okolina sigurna za operatera sprječavaudisaj opasnih čestica, zaštita okoline komore sprječavada čestice generirane unutar komore budu distribuiraneizvan nje, zaštita otvorenih farmaceutskih supstanci odkontaminacije održavanjem laminarne zračne strujeunutar komore
• Razina izloženosti operatera - 100 μg/m³• Tip strujanja zraka: laminarno, vertikalno• Radna brzina: 0.30, 0.35, 0.40, 0.45 m/s• Pripremni (stand-by) mod: 0.25 m/s• Klasa čistoće: ISO klasa 6(5), 1000(100) klasa po
U.S.F.S.209 E, GMP klasa A• Konstrukcija: nehrđajući satinirani lim AISI 304 (DIN 1.4301)• Upravljanje komorom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Hlađenje recirkulirajućeg zraka, hladnjak za recirkulacijski
zrak• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Dva stupnja predfiltracije• Sigurnost: automatska kontrola filtera i kvara uređaja
(vizualni i zvučni alarmi) • Osvjetljenje: integrirano osvjetljenje, 500 lux-a na radnoj
visini• Uređaj konstruiran za rad u tri smjene
PRINCIP RADA
Ventilatori povlače zrak kroz perforaciju na donjem dijeluradnog prostora. Zračna struja prolazi kroz dva stupnjapredfiltracije i komplet HEPA filtera. Prolazom kroz hladnjakzrak ulazi u distribucijski plenum. Od ukupne količinezraka dio ulazi u radni prostor preko poliesterskih kaseta,a ostatak istrujava u okolni prostor. Ova količina zraka na-doknađuje se povlačenjem zraka iz okoline.
OPCIONALNA UGRADNJA
• Dodatna vizualna kontrola filtera (analogni diferencijalniumjereni manometar)
• Safe change• Ex protueksplozijska izvedba, certifikati za ugrađene
komponente
TEHNIČKI PODACI
Moguće izvedbe raznih dimenzija prema zahtjevu.
HEPA filtrirani zrak
djelomično kontaminirani zrak
okolni zrak
LEGENDA:
55LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Komora za vaganje/otprašivanje VKLTEHNIČKE KARAKTERISTIKE
• Tip zaštite: radna okolina sigurna za operatera sprječavaudisaj opasnih čestica, zaštita okoline komore sprječavada čestice generirane unutar komore budu distribuiraneizvan nje, zaštita otvorenih farmaceutskih supstanci odkontaminacije održavanjem laminarne zračne strujeunutar komore
• Razina izloženosti operatera - 100 μg/m³• Tip strujanja zraka: laminarno, vertikalno• Radna brzina: 0.30, 0.35, 0.40, 0.45 m/s• Pripremni (stand-by) mod: 0.25 m/s• Klasa čistoće: ISO klasa 6(5), 1000(100) klasa po
U.S.F.S.209 E, GMP klasa A• Konstrukcija: nehrđajući satinirani lim AISI 304 (DIN 1.4301) • Upravljanje komorom: mikroprocesorski kontrolirani pa-
rametri s kontrolnog panela, ekran osjetljiv na dodir• Glavni filter: HEPA H14, efikasnosti 99,995% MPPS
prema EN 1822 normi• Prvi stupanj filtracije preko G4-F9 filtera (EN 779)• Sigurnost: automatska kontrola filtera i kvara uređaja
(vizualni i zvučni alarmi) • Osvjetljenje: integrirano osvjetljenje, 500 lux-a na radnoj
visini• Zaštitno staklo: podizanje zaštitnog stakla elektromotornim
pogonom• Postolje za vagu• Ugrađeni priključci za DOP (DEHS) test za svaku filtersku
jedinicu• Uređaj konstruiran za rad u 3 smjene• Prilagođen sjedećem položaju• Brojač radnih sati komore
PRINCIP RADA
Ventilatori usmjeravaju zračnu struju kroz predfiltere. Diofiltriranog zraka (70%) zajedno sa zrakom iz okoline (30%)prolazi kroz predfilter. Radni prostor komore zaštićen jepomičnim staklom koje sprječava kontaminaciju farma-ceutskih supstanci.
OPCIONALNA UGRADNJA
• Dodatna vizualna kontrola filtera (analogni diferencijalniumjereni manometar)
• UV lampa za sterilizaciju radnih površina• Električna utičnica u radnom prostoru (230 V)• Priključci za razne medije (plin, zrak, vakum, voda)• Postolje za bačvu na kotačima• Ex protueksplozijska izvedba, certifikati za ugrađene
komponente
TEHNIČKI PODACI
Moguće izvedbe raznih dimenzija prema zahtjevu.HEPA filtrirani zrak
djelomično kontaminirani zrak
okolni zrakdjelomično filtrirani zrak
LEGENDA:
56 LAMINARNI UREĐAJI - ZAŠTITNE KABINE I KABINETI
Specijalni uređaji
TEHNIČKE KARAKTERISTIKE
• Dimenzije radnog prostora prema zahtjevima• Horizontalna ili vertikalna zračna struja• Mogućnost izbora radne brzine• Pripremni (stand-by) mod • Mikroprocesorski kontrolirani parametri s kontrolnog pa-
nela• Automatska kontrola filtera i kvara uređaja (vizualni i
zvučni alarmi)• Dodatna vizualna kontrola filtera (analogni diferencijalni
manometar)• Apsolutna filtracija preko HEPA i ULPA filtera• Hladnjak za recirkulacijski zrak• Oprema konstruirana za rad u 3 smjene• Integrirano osvjetljenje 500 lux-a na radnoj visini• Izrada prema međunarodno priznatim GMP smjernicama
i EN normama• Opcija: Ex protueksplozijska izvedba
Često je potrebno osigurati sterilno čiste uvjete tamo gdjeje prostor ograničen kao i uređaji u njemu. Proizvodimospecijalne uređaje koji su „krojeni“ prema korisnikovimzahtjevima i ograničenjima koja onemogućavaju primjenustandardnih uređaja.
Prilikom rada u zaštitnom uređaju važno je da se operaterosjeća udobno. Neudobnost i tjeskoba prethode nezgodi.Operater mora biti u mogućnosti sjediti ili stajati tako da sumu ruke u prirodnom položaju za rad na radnoj plohiuređaja i mora biti u mogućnosti dosegnuti sve predmetebez istezanja. Operater mora moći vidjeti kroz radni prostor,ne ispod njega, i njegovo vidno polje ne smije biti smetanodržačima stakla.Radni prostor kabineta ne smije biti prenatrpan, previšepreparata i pribora smeta protoku zraka. Kada je sav posaou kabinetu obavljen, ventilator mora raditi još nekolikominuta prije gašenja i namještanja prednjeg poklopca.
PREDMET ZAŠTITE
• Zaštita okoline komore, sprječavajući da čestice generiraneunutar komore budu distribuirane izvan nje
• Zaštita predmeta rada od kontaminacije u velikim radnimprostorima, održavanjem adekvatne, laminarne, apsolutnočiste zračne struje unutar kabine/kabineta/komore
• Radnu okolinu sigurnu za operatera, sprječavajući operateraunutar komore da udiše po zdravlje opasne čestice
• Hlađenje recirkulirajućeg zraka
Validacije i servisiTEHNIČKE KARAKTERISTIKE
• Servisiranje, održavanje i validiranje opreme ili objektaosigurava sigurnost pri upotrebi i duži vijek trajanja
• Održavanje novo izgrađenih ili rekonstruiranih čistih pro-stora i pripadajućih postrojenja
• Validacije prema svjetskim pravilnicima i normama,norma EN 12469 za mikrobiološke zaštitne kabinete,GMP i ISO standardi za čiste prostore
• HVAC balansiranje• CNUS/BMS• Električni ormari• Kalibriranje mjernih uređaja• Ispitivanje integriteta filtera• Brojenje čestica u radnom prostoru• Test oporavka prostora• Vizualizacijski test• Monitoring• Test buke i vibracija• Razina i jednolikost osvjetljenja• Ispitivanje dokumentacije
USLUGE
• Cjelokupna briga o postrojenju, sustavu ili uređaju• Parcijalni servisi• Validacije na zahtjev klijenata
NAMJEŠTAJ ZA ČISTE PROSTORECleanroom namještaj se koristi u raznim industrijama gdjeje nužno spriječiti kontaminaciju te širenje bakterija, virusai drugih nečistoća. Koristi se u farmaceutskoj i medicinskojindustriji, kao i u elektronici, inženjerstvu, automobilskojindustriji, optičkoj, prehrambenoj i drugim industrijama.Svaki kvadratni metar cleanroom zone je bitan, iskoristiv ičesto ograničen prostor, zbog čega standardan namještajnije uvijek optimalno rješenje. Klimaoprema CleanroomSolutions projektira i proizvodi cleanroom namještaj premazahtjevima prostora i potrebama korisnika. Informacijekoje slijede odnose se na standardan namještaj, no spe-cijaliziramo u izradi namještaja specifičnih i posebnih di-menzija i karakteristika, prema zahtjevima korisnika.Cleanroom namještaj je izrađen od nehrđajućeg lima(inox-a), a čine ga okomiti držači i perforirane ili izrađeneiz drugog materijala radne površine. Namještajem se jed-nostavno rukuje, lako se održava te je pogodan za svevrste čistih prostora.
NAMJEŠTAJ ZA ČISTE PROSTORE 59
60 NAMJEŠTAJ ZA ČISTE PROSTORE
Cleanroom stoloviTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Razni materijali radne plohe: perforirana ploča, Kerrock,
staklo, mramor, nehrđajući lim ili drugi metal• Ispuna stiroporom ili kamenom vunom• Dizajniran za siguran rad sa kemikalijama i prijenosnim
laboratorijskim instrumentima• Koriste se u različitim vrstama laboratorija, u kemijskoj
proizvodnji, u školama, u medicinskoj industriji, elektronici,u prehrambenoj industriji
• Razne veličine i dimenzije ovisno o veličini prostora izahtjevima korisnika
• Podesive visine• Razni modeli: kutni stolovi, dupli stolovi, konferencijski
stolovi, sa ladičarem ispod stola, fiksni stolovi, mobilnistolovi (sa kotačima) i dr.
TEHNIČKI PODACI
Dužina (mm) Širina (mm) Visina (mm)
1000 700 900
1200 700 900
1600 700 900
Moguće izvedbe drugih dimenzija prema zahtjevu.
NAMJEŠTAJ ZA ČISTE PROSTORE 61
Cleanroom ladičariTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Razne veličine i dimenzije ovisno o veličini prostora i zahtjevima
korisnika• Razni modeli: sa ladicama, sa vratima, sa ladicama i vratima,
sa policama, na zaključavanje, fiksni ladičari, mobilni (sa ko-tačima) ladičari, za ispod stola i dr.
Dužina (mm) Širina (mm) Visina (mm)
500 600 600
500 650 600
500 700 600
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
62 NAMJEŠTAJ ZA ČISTE PROSTORE
Cleanroom ormariTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Glatke ili perforirane police• Jednostavno čišćenje i dezinfekcija površina• Prikladni za sva postrojenja unutar laboratorijskog i me-
dicinskog sektora, prehrambene i drugih industrija• Razne veličine i dimenzije ovisno o veličini prostora
i zahtjevima korisnika• Razni modeli: sa ladicama, sa vratima, sa ladicama
i vratima, sa policama, na zaključavanje, fiksni ormari,mobilni (sa kotačima) ormari, sa visećim ili kliznimvratima i dr.
NAMJEŠTAJ ZA ČISTE PROSTORE 63
Cleanroom police i žičane stalažeTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Glatke ili perforirane police• Jednostavno čišćenje i dezinfekcija površina• Žičane stalaže i police osiguravaju troškovno učinkovitu
i efikasnu pohranu materijala za proizvodnju• Razne veličine i dimenzije ovisno o veličini prostora i
zahtjevima korisnika• Razni modeli: samostojeće police, zidne police, mobilne
(sa kotačima) police i dr.
Dužina (mm) Širina (mm) Visina (mm)
1000 250 400
1200 500 400
1600 600 400
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
64 NAMJEŠTAJ ZA ČISTE PROSTORE
Klupice za presvlačenjeTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Jednostavno čišćenje i dezinfekcija površina• Funkcionalna barijera za odvajanje različitih područja• Cleanroom sjedeće površine• Sa ili bez odjeljaka za cipele• Prikladne za sva postrojenja unutar laboratorijskog
i medicinskog sektora, prehrambene i drugih industrija• Razne veličine i dimenzije ovisno o veličini prostora
i zahtjevima korisnika
Dužina (mm) Širina (mm) Visina (mm)
1000 400 450
1200 400 450
1600 400 450
TEHNIČKI PODACI
Moguće izvedbe drugih dimenzija prema zahtjevu.
NAMJEŠTAJ ZA ČISTE PROSTORE 65
Vješalice za odjećuTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Stabilne, visoko otporne, jednostavne za rukovanje• Jednostavno čišćenje i dezinfekcija površina• Prikladne za sva postrojenje unutar laboratorijskog
i medicinskog sektora, prehrambene i drugih industrija• Razne veličine i dimenzije ovisno o veličini prostora
i zahtjevima korisnika• Razni modeli: prijenosni, fiksni, dvostruki
66 NAMJEŠTAJ ZA ČISTE PROSTORE
Cleanroom sudoperiTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Jednostavno čišćenje i dezinfekcija površina• Prikladni za sva postrojenja unutar laboratorijskog i me-
dicinskog sektora, prehrambene i drugih industrija• Razne veličine i dimenzije ovisno o veličini prostora i
zahtjevima korisnika• Razni modeli: zidni sudoperi, samostojeći sudoperi,
viseći sudoperi, toaletni umivaonici, kirurški sudoperi,dvostruki sudoperi i dr.
• Dodaci: pipe, cjedila, košare, čepovi
NAMJEŠTAJ ZA ČISTE PROSTORE 67
68 NAMJEŠTAJ ZA ČISTE PROSTORE
Cleanroom kolicaTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Namijenjena za transport raznog materijala• Stabilna, visoko otporna, jednostavna za rukovanje• Jednostavno čišćenje i dezinfekcija površina• Prikladna za sva postrojenja unutar laboratorijskog
i medicinskog sektora, prehrambene i drugih industrija• Razne veličine i dimenzije ovisno o veličini prostora
i zahtjevima korisnika• Razni modeli: sa ili bez kočnica na kotačima, otvorena
ili sa vratima, zaključavanje, police i dr.
NAMJEŠTAJ ZA ČISTE PROSTORE 69
Kirurški držač instrumenataTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Namijenjena za transport raznog materijala• Stabilna, visoko otporna, jednostavna za rukovanje• Jednostavno čišćenje i dezinfekcija površina• Prikladna za sva postrojenja unutar laboratorijskog i
medicinskog sektora, prehrambene i drugih industrija• Razne veličine i dimenzije ovisno o veličini prostora i
zahtjevima korisnika
70 NAMJEŠTAJ ZA ČISTE PROSTORE
Ostali namještaj i dodaciTEHNIČKE KARAKTERISTIKE
• Nehrđajući lim - Inox, brušeni ili polirani• Ispuna stiroporom ili kamenom vunom• Stabilan, visoko otporan, jednostavan za rukovanje• Jednostavno čišćenje i dezinfekcija površina• Moderan dizajn• Prikladan za sva postrojenja unutar laboratorijskog i
medicinskog sektora, prehrambene i drugih industrija• Razne veličine i dimenzije ovisno o veličini prostora i
zahtjevima korisnika• Razni modeli: elektronsko pokretanje, ručno pokretanje,
pokretanje stopalom i dr.
KOŠEVI ZA OTPAD
DRŽAČI RUČNIKA
SUŠILA ZA RUKE
DRŽAČI PAPIRA
POSUDE ZA SAPUN
ČISTI PROSTORI 71
72 ČISTI PROSTORI
ČISTI PROSTORI 73
74 ČISTI PROSTORI
Napomene:
ČISTI PROSTORI 75
Napomene:
U više od 35 godina iskustva Klimaoprema Cleanroom Solutions je izvela tisućekvadrata farmaceutskih i medicinskih postrojenja.
Mnogi projekti su izvedeni po sistemu „ključ u ruke“, što uključuje: izraduidejnog, glavnog i izvedbenog projekta, proizvodnju, montažu, opremanje,
validacije i servis.
Obratite nam se s povjerenjem i mi ćemo Vašu viziju ili idejukoja je tek u nastanku učiniti stvarnom.
Čisti prostoripo sistemu
kljuČ u ruke
Klimaoprema d.d.
Gradna 78A, HR-10430 Samobor, Hrvatska | T. +385 (0)1 33 62 513 | F. +385 (0)1 33 62 905
[email protected] | www.klimaoprema.hr
11/2014.
ČISTI PROSTORI | FILTRACIJA I VENTILACIJA | ZAŠTITNE KABINE I KABINETI | NAMJEŠTAJ ZA ČISTE PROSTORE
inženjering proizVoDnjA instAlirAnje VAliDACije
Čist
i pro
stor
i po
sist
emu
klju
Č u
ruk
e