Upload
abhijit-mandal
View
18
Download
0
Embed Size (px)
DESCRIPTION
Current Transformer
Citation preview
Worked Example
Equipment Selection:
Relay: Siemens 7SS5
CT: 600/1 5P10 15 VA Ri = 4 Ω
CT Leads: 6 mm2 50 m (r=0.0179
Wmm2/m)
Iscc.max = 30 kA
CT Calculation:
From Siemens relay data:
Current Transformer Dimensioning
Posted @ 3/26/2012 6:54 AM by Steven | Files in Power Systems
Correct dimensioning of current transformers is required to ensure satisfactory operation of measuring
instruments and protection relays.
Measuring CTs
Measuring current transformers are normally class 0.5 or 1 for general use. Class 0.1 or 0.2 for precision and
tariff measurements. Typical accuracy limiting factors of 10 and burdens of 5, 10 and 15 VA are common. A
typical specification may be 0.5M10 15 VA.
Protection CTs
Protection CTs provide signals to protective relays to
enable correct operation under steady state and transient
conditions.
IEC 60044 & 60185
IEC 60044 specifies the requirements for protection CTs (in
addition to measuring CT's, VTs and electronic sensors).
Generally accuracy class 5P (1%) is specified with rated
accuracy limiting factors of 10 or 20 being common.
Typically burdens would be 5, 10, 15 or 20 VA. A typical
specification would be 5P10 15 VA.
To correctly select a CT the following dimensioning
formulae can be used:
with
where:
KALF is the rated CT accuracy factor •
K*ALF is the effective CT accuracy limiting
factor
•
RBN is the rated burden resistance •
RBC is the connected burden •
Ri is the internal CT resistance
(secondary winding)
•
Iscc.mzx is the maximum short circuit current •
IN is the rated primary CT current •
Page 1 of 3Print Entry Option
7/15/2012http://myelectrical.com/DesktopModules/SunBlog/Handlers/Print.aspx?id=151
The rated KALF of 10 is greater than 7.6,
therefore stability of the relay is
confirmed.
KOF is an over dimensioning factor •
The over dimensioning factor KOF is dependant on the type
of protection
relay and primary DC time constant. These values are
normally
available in the protection relay manual.
BS 3838
CTs can be defined by the knee point voltage UKN and the
internal secondary resistance Ri. To convert an IEC design
the following can be used:
where:
I2N is the nominal secondary current •
ANSI/IEEE C 57.13
Class C of the ANSI standard defines CTs by their secondary terminal voltage at 20 times nominal current (for
which the ratio error shall not exceed 10%). Standard classes are C100, C200, C400 and C800 for 5 A nominal
secondary current. This terminal voltage can be calculated from the IEC data as follows:
with
and
Connection Leads
The burden of connection leads can be estimated from:
where:
l is the connection lead length in m •
ρ is the resistivity in Ω mm2 m
-1 (=0.0179 for copper) •
Page 2 of 3Print Entry Option
7/15/2012http://myelectrical.com/DesktopModules/SunBlog/Handlers/Print.aspx?id=151
A is the cross sectional area in mm2 •
Related
For an introduction and guidance on how to apply CT sizing, refer the following post:
How to Size Current Transformers
Page 3 of 3Print Entry Option
7/15/2012http://myelectrical.com/DesktopModules/SunBlog/Handlers/Print.aspx?id=151