ETAP PowerStation Load Flow EE 533 Fall Quarter 2011 California State University Los Angeles

ETAP Presentation

Embed Size (px)

DESCRIPTION

ETAP PowerStation • ETAP is a multi study tool and it has several modules which includes: load flow AC  and DC, short circuit, transient stability, optimal load flow, cable pulling, grounding,  etc. The program can be set on edit and study mode In the EDIT MODE you could add the different components from the library (caution  there are two libraries which are displayed on the right hand side bars a D

Citation preview

Page 1: ETAP Presentation

ETAP PowerStationLoad FlowEE 533 

Fall Quarter 2011

California State University Los Angeles

Page 2: ETAP Presentation

• ETAP is a multi study tool and it has several modules which includes: load flow AC and DC, short circuit, transient stability, optimal load flow, cable pulling, grounding, etc.

• The program can be set on edit and study mode• In the EDIT MODE you could add the different components from the library (caution 

there are two libraries which are displayed on the right hand side bars a DC and AC components

• Once you chose a study to run in this mode the components library will disappear and you cannot add new components from here only from the EDIT model. In this mode you also have access to the crystal reports 

• Case selector allows you to setup variations from your base case

ETAP PowerStation 

EDIT MODE STUDY MODES

CASE SELECTOR

Page 3: ETAP Presentation

BUS (AC)• To enter a bus drag and drop from the AC components library

• You only need to fill the Info tab section, if you are running a load flow study

• Different from PSLF the bus type is determined by what is connected to it ,e.g., if a generator is connected to it based on the generator page setting it will be identified as swing or PV bus. When a load and not generator is connected it will automatically classify it as PQ bus 

Data Required

Bus Name

In service/ Out of Service

Type of connection

Initial voltage

Page 4: ETAP Presentation

TRANSFORMER (info tab)• To enter a bus drag and drop from the AC components library

• You need to enter data on the Info and rating tab only if running a load flow 

• Different from PSLF the bus type is determined by what is connected to it ,e.g., if a generator is connected to it based on the generator page setting it will be identified as swing or PV bus. When a load and not generator is connected it will automatically classify it as PQ bus 

Data Required

ID

In Service /Out of Service

Connection

Standard (by default ANSI always chooseit unless running a study based on European standard)

Page 5: ETAP Presentation

• If the X/R ratio is not given choose typical if left as zero you will get an error message  as this ration cannot be infinite. In PSLF you could leave it as zero by not entering the real losses

• If you are not given the transformer impedance the a typical value may also be chosen

TRANSFORMER (rating  tab)

Required Data

MVA base 

%Z (if X/R not given use typical)

Page 6: ETAP Presentation

TRANSMISSION LINE (info tab)• To enter a transmission line drag and drop from the AC components library

• You need to enter data on the Info and impedance tab only, if running a load flow 

Data Required

ID

In Service / Out of Service

Connection

Length (if you user defined impedance is chosen leave default values)

Page 7: ETAP Presentation

TRANSMISSION LINE (impedance tab)• Chose the User‐Defined option (notice that the impedance entry table is not 

available to edit)

• You need to enter data on the Info and impedance tab only, if running a load flow 

Data Required

Positive Sequence Impedance (enter R‐T1 and R‐T2 equal)

Choose user defined 

Units (leave as default)

Page 8: ETAP Presentation

Synchronous Generator(info  tab)

• To enter a generator drag and drop from the AC components library

• You need to enter data on the Info and rating  tab only, if running a load flow

• The rating library entry mode changes based on the configuration mode chosen (Swing or Voltage Control) 

Data Required

ID

In Service / Out of Service

Operation Mode (Swing , Voltage Control)

Page 9: ETAP Presentation

Synchronous Generator(rating tab – voltage control)

• If the generator is set to work in voltage control mode, under the generator category table you may only modify the % voltage, Real Power output (MW), Qmax and Qmin; (therefore known as PV bus)

• Under rating section only need to enter the MVA, kV and %pf all other fields are self populated

Data Required

kV base

MVA base

%pf

%V (schedule voltage)

P (schedule MW)

Qmax (+MVAR)

Qmin (‐MVAR)

Page 10: ETAP Presentation

Synchronous Generator(rating tab – swing)

• If the generator is set to work in swing mode, under the generator category table you may only modify the % voltage, angle , Qmax and Qmin

• Under rating section only need to enter the MVA, kV and %pf all other fields are self populated

Data Required

kV base

MVA base

%pf

%V (schedule voltage)

Angle (set at zero)

Page 11: ETAP Presentation

Lumped Load  (info tab)

• For fix load (no voltage dependent) used the lump load

Required Data

ID

In Service / Out of Service

Connection (3phase)

Page 12: ETAP Presentation

Lumped Load  (info nameplate)

• Move the adjuster on the load type setting to 100% constant kVA

Required Data

MW

Mvar

Rated kV

Load Type

Page 13: ETAP Presentation

AC Load Flow Mode

• You could run the load flow solution from here• Check the display model• Check the crystal report• Set the alarm

Run Load Flow

Chose load flow display options

Choose Components Data Display options

Page 14: ETAP Presentation