Gdb-glb181.1e3 Vav Compact

Embed Size (px)

Citation preview

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    1/14

    Siemens Building Technologies CM2N3544E / 06.1999

    Landis & Staefa Division 1/14

    3544

    OpenAir

    VAV compact controllersGDB181.1E/3GLB181.1E/3

    Compact controllers for plants with variable and constant air volume with the air

    volume as an auxiliary variable. Comprised of pressure difference sensors, digital

    air volume controller and actuator;

    Operating voltage AC 24 V;

    P-response, nominal torque 5/10 Nm, air damper working range mechanically

    adjustable between 0 and 90, prewired with 0.9 m long connecting cable;

    Fully compatible to RCE84.1... and SQE92.1....

    Used primarily to control the room temperature in individual rooms and zones of

    ventilation and air conditioning plants working with variable or constant air volume, in

    cases where n o mechanical (direct acting) constant air volume controller1)

    is planned

    and where the air volume is required as an auxiliary variable1)

    .

    1) To keep constant the air volume on pressure fluctuations in a system

    The unit can be used for:Supply air control

    Extract air control

    Supply / extract air cascade control with

    proportional control 1 : 1

    proportional control 1 1 (over- / underpressure)differential control 1 1 (over- / underpressure)

    Air damper nominal torque up to 5 or 10 Nm

    For air throttles with mechanic (direct acting) constant air volume controller, use the

    TEC controllers.

    AC 24 V operating voltage

    Torque Pressure range

    0..300 Pa

    5 Nm GDB181.1E/310 Nm GLB181.1E/3

    Use

    Note

    Type summary

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    2/14

    CM2N3544E / 06.1999 Siemens Building Technologies

    2/14 Landis & Staefa Division

    Description Type/Order Number

    Air filter 4 287 1088 0

    When ordering, indicate the type designation or the order number of the unit or the

    accessories, e.g.: GDB181.1E/3

    The following parts are not mounted on delivery:

    a mounting bracket with two fixing screws

    one centring element for shaft diameters 8...10 mm (only forGLB181.1E/3).The VAV compact controllers are supplied with a 0.9 m long, fully wired connecting

    cable.

    Unit Type Data sheet

    Room temperature controller RCE84.21, RCE84.22 3542, 3543

    POLYGYR product range 3400

    TEC product range 3601

    DESIGO RX product range: 38xx

    Setting unit AST10 5851

    The VAV compact controller GDB181.1E/3or GLB181.1E/3can be used with or without

    an internal VAV/CAV controller.

    The following parameter are available in the unit:

    Parameters Range Factory setting

    Function type VAV+CAV / 3pt+sensor VAV+CAV

    minV 1...2.55 1

    minV1)

    20...+60 % 0 %

    maxV1)

    40...120 % 100 %

    Motor rotational direction Left rotation/ right rotation Right rotation

    Address (only for DESIGORX) 9 / 10 / 11 / 12 9

    1) If the function type "3pt+sensor" has been selected for the VAV compact controller, a value can be

    set, but does not have any influence

    The setting of parameters "Motor direction" and "Address" (only in connection with

    DESIGORX...) is made at the DIL switches.

    Adjustment of all other parameters occurs by means of the setting unit AST10via

    terminal UC with digital communication.

    The VAV controllers GDB181.1E/3or GLB181.1E/3together with the RCE84.21forms

    a room temperature cascade controller with the room temperature as the main control

    variable and with the air volume as the auxiliary control variable.

    In this control type, the deviation of the room temperature defines the setpoint for the air

    volume. The air volume is then kept at this setpoint by the auxiliary control, i.e., the

    pressure fluctuations in the duct, which appear as a fault variable, have no influence on

    the air volume and thus no influence on the room temperature.

    The control response for the "Air volume" auxiliary variable is P (proportional).

    The air volume actual value in the air duct is acquired via the differential pressure p by

    means of a membrane pressure sensor. The differential pressure is converted

    electronically to an air volume signal, which is made available at terminal UC (core 9) as

    a DC 0...10 V output signal (e.g. for air volume indication).

    Accessories (optional)

    Ordering anddelivery

    Equipmentcombinations

    Technical design

    .

    .

    .

    .

    .

    .

    Effect with VAV/CAV

    controller

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    3/14

    Siemens Building Technologies CM2N3544E / 06.1999

    Landis & Staefa Division 3/14

    Legend1 Air volume actual value

    2 Flow resistance duct (schematic)

    3 Measuring l ine

    4 Static (membrane) differential pressure sensor

    Switching terminal input Y defines the type of air volume control.

    The following table shows the influence of switching terminal inputs Y on both controltype and air damper control.

    VAV control CAV control

    Y (core 8) DC 0...10 V1)

    DC 0...10 V DC 0...10 V1)

    DC 0...10 V open open open open

    Y1 (core 6) open G0 G0 Open open G0 G0 open

    Y2 (core 7) open open G0 G0 open open G0 G0

    Effect VAV Right rotation2)

    complete

    opening

    VAV Left rotation2)

    complete

    closure

    minV Right rotation2)

    complete

    opening

    maxV Left rotation2)

    complete

    opening

    1) Complete closure in the VAV range occurs on Y = DC 1.5 ... 0.5 V

    2) Applies when parameter "Air damper direction" at the DIL switches is set to "Right rotation";

    otherwise, the contrary applies

    The DC 010 V signal at terminal Y serves as the setpoint for the air cascade control

    loop. The setpoint, in dependence of the pressure situation in the supply air duct and

    within the limits of maxV and minV , determines the required air volume.

    Depending on the input switch setting (open/close) of inputs Y1 and Y2, control occurs

    to the desired CAV value. With an open input, the GDB181.1E/3or GLB181.1E/3

    controls to minV , and with a closed input to maxV .

    With the aid of parameter Vn , the measuring range of the GDB181.1E/3or

    GLB181.1E/3can be adjusted at the factory (box manufacturer) to the respective

    nominal volume of the unit for the air boxes. This ensures that the maximum permissible

    nominal volume of the unit is not exceeded.

    100 % nominal air volume of the air box then corresponds to DC 10 V of the measuring

    range of the GDB181.1E/3or GLB181.1E/3. This setting can be checked at terminal

    UC.

    With the aid of the setting parameters minV and maxV , the air volume can be limited by a

    minimum and maximum air volume.

    With supply/extract air control, a room over- or underpressure up to 20 % max. at equal

    duct cross sections and pressure ranges with the aid of parameters maxV and minV of

    the cascade controller.

    For supply and extract air control, parameters maxV and minV allow for duct

    compensation of max. 20 %.

    By switching signal inputs Y1 and Y2, the air dampers can be completely opened or

    closed, independent of maxV and minV .

    Full closure of the air volume occurs via the digital signal input Y2. If this input is

    connected to ground (G0) and if signal input Y1 is open, full closure occurs without

    consideration of minV .

    The signal is triggered by an external switching contact (e.g. window contact) or theRCE84.21room temperature controller.

    3544Z01

    1 12

    3

    4

    3

    Variable (VAV) or constant

    (CAV) air volume control

    .

    .

    .

    .

    .

    .

    .

    .

    .

    VAV control

    CAV control

    Nominal air volume

    setting ( Vn )

    Minimum and maximum

    limitation of the air volume

    Overpressure /

    underpressure setting

    Compensation of different

    duct cross sections

    Complete closure of air

    dampers

    Full closure of the air

    volume

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    4/14

    CM2N3544E / 06.1999 Siemens Building Technologies

    4/14 Landis & Staefa Division

    In order to utilise the VAV compact controller GDB181.1E/3or GLB181.1E/3without the

    VAV/CAV controller, reset the "Function type" parameter of "VAV+CAV" to "3pt+sensor".

    This can be done with the aid of setting unit AST10.

    In order for the parameter change to become effective, voltage supply (AC 24 V) must

    be interrupted.

    With this function type setting, the VAV compact controller records the actual value for

    the air volume in the air duct via the differential pressure p with static pressure sensor.

    The differential pressure is converted electronically into an air volume signal which is

    available at terminal UC as a DC 0..10 V output signal (air volume actual value).

    Switching the terminal inputs Y1 and Y2 defines the direction of rotation of air dampers(3-position control).

    The following table shows the influence of terminal switching on air damper control for

    function type "3pt+sensor".

    3pt+sensor

    Y (core 8) open open open open

    Y1 (core 6) open G0 G0 open

    Y2 (core 7) open open G0 G0

    Effect none Right

    rotation1)

    Left rotation1)

    Left rotation1)

    1) Applies when parameter "Air damper direction" at the DIL switches is set to "Right rotation";

    otherwise, the contrary applies

    The VAV compact controller is designed for attachment on damper shafts that are at

    least 30 mm long. It consists of a base group and a two-part housing.

    The base group consists of:

    a base plate made from steel with air damper attachment mechanism for varying shaftcross sections and diameters (see "Dimensions") and a rotary angle limiter

    maintenance-free, noise-free spur gearing

    magnetic hysteresis coupling with low contact power transmission and an actuator

    that is thus protected against locking and overload, even during continuous operation

    The housing is made from hard plastic. Do not remove its cover. The following is located

    below the cover:

    the controller electronics

    the membrane pressure sensor with electronic circuit

    the synchronous motor for damper actuation.

    For manual adjustment of the air dampers, the gearing can be decoupled via the

    gearing attachment mechanism on the side of the housing.A centring element made from hardened, sintered steel is available for the VAV compact

    controller GLB181.1E/3(10 Nm) (separately supplied accessory). This ensures a proper

    connection between damper shafts of smaller diameters (810 mm) and the connector

    plug and the longitudinal movement of the VAV compact controller is reduced by means

    of excentric movement.

    The flows in the measured line are sufficiently low so that no contamination of the flow

    sensor must be expected. In severely contaminated environments, we recommend

    using the 4 287 1088 0air filter.

    The mounting accessories (mounting bracket) as part of the delivery ensures full

    adoption of the reaction torque to maximum load.

    Electrical connection occurs via a fixed connecting cable at the bottom of the housing.

    The cable ends are equipped with ferrules.

    Effect without

    VAV/CAV controller

    Mechanicaldesign

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    5/14

    Siemens Building Technologies CM2N3544E / 06.1999

    Landis & Staefa Division 5/14

    90

    90

    45

    address1 1

    0 0

    S3 S2 S1

    11

    12

    13

    14

    7

    8

    109

    1

    6

    32 4 5

    35

    44Z02

    1 Shaft f ixing screw

    2 Measuring element for the connecting line to the 'cable gland for lower pressure' of the measuring

    cross on the box

    3 Measuring element connection (+) for the connecting line to the 'cable gland for higher pressure' of

    the measuring cross on the box

    4 6-core connecting cable

    5 Gearing attachment mechanism

    6 Connector plug (shaft opening)

    7 Adjustment lever with shaft fastening screw

    8 Rotational angle scales (0...90/ 90...0)

    9 DIL switch cover

    10 DIL switch block

    Switch no. 1: Motor direction for complete closure

    Switch no. 2 and 3: Address (only for DESIGORX)

    Meaning of coloured switch settings:

    DIL switch no. 1

    (S1)

    Motor rotational

    direction

    1) Right rotation

    Left rotation

    DIL switch no. 3

    (S3)

    DIL switch no. 2

    (S2)

    Device address

    (Decimal)

    0 1) 0 1) 9

    0 1 10

    1 0 11

    1 1 12

    1) Factory setting

    11 Rotational angle limiter (M4 cylinder screw, 3 mm internal hexagon),

    stepless adjustment between 0 and 90

    12 Rotational angle position indicator

    13 Centring element for GLB...1E, for 810 mm shaft diameter

    14 Mounting bracket

    The DIL switches can be sealed.

    For environmentally compatible disposal, the larger plastic parts have been labelled as

    per ISO/DIS 11 469.

    Setting, operating and

    connecting elements

    Legend

    Disposal

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    6/14

    CM2N3544E / 06.1999 Siemens Building Technologies

    6/14 Landis & Staefa Division

    AC 24 V operating voltage is necessary for supplying the VAV compact controller.

    The operating voltage must comply with the requirements for safety extra-low voltage

    (SELV) as per EN 60 730.

    Use safety insulating transformers with double insulation in accordance with

    EN 60 742; The transformers must be made for 100% runtime.

    Observe all local safety rules and regulations pertaining to sizing and protecting

    transformers.

    Electric connection in parallel of the VAV compact controllers GDB181.1E/3 withGLB181.1/3 is permissible only if the operating voltage is within the required tolerance.

    Voltage drops at the feed lines must be considered.

    Do not mechanically couple the actuators.

    Selection of the VAV compact controller type depends on several torque factors. After

    obtaining the damper torque rating (Nm/m2) from the manufacturer and determining the

    damper area, calculate the total torque required to move the damper as follows:

    Total Torque = Torque Rating Damper Area

    Determine the required type of VAV compact controller from the table below:

    If [ ])1SF

    NmtorqueTotal then use type

    5 Nm GDB181.1E/3(5 Nm)

    10 Nm GLB181.1E/3(10 Nm)

    1) Safety factor SF: When calculating, non-definable variables such as slight misalignment, damper

    age, etc. must be included as a safety factor.

    We recommend a safety factor of 0.80 (or 80 % of the torque characteristic).

    Do not open the actuator!

    The unit is maintenance-free. Any repair work must be conducted by the manufacturer

    only.

    The setting values for Vn , maxV , minV and the selected function type ('VAV+CAV' or

    '3pt+sensor') must be entered in the plant papers.

    There are no limits to the mounting position, however, the housing must remain

    accessible (gearing attachment mechanism!). The cable connection for UC must be

    accessible for the AST10 setting unit (e.g. terminal in the control cabinet).

    Observe the permissible ambient temperature and humidity (refer to "Technical data").

    The mounting brackets must be installed so that the pivot's insertion in the base plate of

    the VAV compact controller's base group is sufficient and enough play is ensured

    toward the shaft centre; this is necessary especially for small shaft diameters which

    cause bigger excentric movements.

    Use the centring element at shaft diameters of 810 mm to ensure a clean connection.

    Mount this element between the damper shaft and the connector plug as per the

    mounting instructions.

    Manually adjust the actuator only when no voltage is applied.

    Where required, you can set the rotational angle range by positioning the adjusting

    screw accordingly.

    The VAV compact controller is delivered with mounting instructions.

    Engineering notes

    Electric parallel switchingof varying VAV compact

    controller types

    Note

    Selection of the VAV

    compact controller type

    Caution, maintenance

    Setting values

    Mounting notes

    Mounting position

    Ambient conditions

    Mounting bracket

    Centring element

    GLB181.1E/3(10 Nm)

    Manual adjustment

    Mechanical limitation of

    rotational angle

    Mounting instructions

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    7/14

    Siemens Building Technologies CM2N3544E / 06.1999

    Landis & Staefa Division 7/14

    Check the mechanical settings as per the plant-specific requirements and especially

    to ensure that the dampers close tight

    Check the rotational direction

    Use the red slider (while no voltage is supplied) to manually adjust the dampers or the

    actuator.

    Fasten the actuator securely to avoid side load and blocking of the actuator

    Check lines for differential pressure measurement for correct connection

    Check the settings at the DIL switches as per the plant documentation and seal them,

    where required

    The setting unit AST 10 is needed for checking or setting the setting values for Vn ,

    maxV , minV and for the function type ('VAV+CAV' or '3pt+sensor'). After separating the

    AST10 from the VAV compact controller, wait for one minute before Y, Y1 and Y2

    work as per the specifications

    The sensor signal is correct after a maximum of two minutes following application of

    AC 24 V operating voltage or after interruption of the voltage supply. During this time,

    the VAV compact controller conducts zero point calibration of the differential pressure

    sensor

    If the AST10 setting unit is connected, no analogue voltage can be measured at

    output UC.

    Operating voltage AC 24 V 20 %

    Safety extra-low voltage (SELV) or protection by extra-low

    voltage (PELV) as per HD 384

    Requirements of external safety insulating transformer (100% ED) as per EN 60 742

    Frequency 50 / 60 Hz

    Supply line fuse Max. 10 A

    Power consumption for transformer sizing 6 VA/3.5 W

    Consumption on

    Holding

    RunningCompensation mode

    Running + compensation mode

    2 VA/1 W

    3 VA/3 W6 VA/3.5 W

    7.5 VA/5.5 W

    Input voltage DC 010 V

    Max. permissible input voltage DC 35 V

    Limited to DC 11 V

    for complete closure in VAV range DC 1.5 . . . 0.5 V

    Input resistance

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    8/14

    CM2N3544E / 06.1999 Siemens Building Technologies

    8/14 Landis & Staefa Division

    Operation IEC 721-3-3

    Climatic conditions Class 3K5

    Mounting location interior, weather-protected

    Temperature 0....50 C

    Humidity (non-condensing) 10 Nm

    Maximum torque < 14 Nm

    Nominal rotational angle (with position indication) 90

    Maximum rotational angle (mechanic limitation) 952Runtime for nominal rot. angle 90, motor operation at 50/60 Hz 150 s / 125 s

    Periodic switch-on time of the motor on damper blocking after 24 h each

    Rotational movement direction (defined by DIL switch setting) clockwise / counterclockwise

    Mechanical life 105cycles

    Shaft cross section

    Round 8...16 mm

    Round, with centring element (only for GLB181.1E/3) 810 mm

    Square 6...12 mm

    Min. shaft length 30 mm

    Max. shaft hardness < 300 HV

    3-position controller with hysteresis

    Max. air volume maxV , adjustable 40...120 %

    Min. air volume minV , adjustable 20...+60 %

    Nominal air volume Vn corrective factor 1.00...2.55

    Measuring range see Type summary

    Accuracy across 2...100 % of the pressure range

    at 25 C, 990 hPa, Vn = 1 and any mounting position 2.5 % of measuring range

    Time constant 1 s

    Max. permissible operating pressure 3000 Pa

    Max. permissible side load 3000 Pa

    Environmental conditions

    Standards

    Product safety

    Electromagnetic

    compatibility

    conformity as per

    Dimensions

    Weight

    Actuator

    Mechanical data

    Suitable damper shafts

    Controller

    Sensors

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    9/14

    Siemens Building Technologies CM2N3544E / 06.1999

    Landis & Staefa Division 9/14

    The illustrations show only principal connections of signal lines. Switch-off functions and

    manipulations are not part of the illustrations as they differ from plant to plant.

    If a window contact, that was switched via terminal Y2 (core 7) of the GDB.../GLB...or

    E1 of the RCE84.21, is open: Window closed, i.e., comfort mode. If this is not the case,

    we must assume that the window is closed. For applications with complete closure of

    the air volume, the terminals Y2 (core 7) of the reference controller and of the cascade

    controller must be connected.

    RCE84.21

    p MY2

    Y

    Y

    Z1

    Y20

    Y10

    E1

    T P

    P

    M

    G0

    Y2p M

    UC

    GDB181.1E/3GLB181.1E/3

    GDB181.1E/3GLB181.1E/3

    Window contact

    Outside temperaturecompensation

    3544S01E

    RCE92.1RCE93.1

    QAA12

    AO1...4

    RS1...4

    T

    3544S02

    p MY

    Y

    p M

    UC

    GDB181.1E/3GLB181.1E/3

    GDB181.1E/3GLB181.1E/3

    p M

    GDB181.1E/3GLB181.1E/3

    p M

    T

    QAA11...14

    RCE92.1/RCE93.1

    3544S03

    GDB181.1E/3GLB181.1E/3

    Y1 Y1

    Y2

    UC UC

    Y2

    Plant examples

    Note

    Plant example 1

    function type "VVS/KVS":

    Control loop without

    communication

    Plant example 2

    function type "VVS/KVS":

    Control loop with

    communication

    Plant example 3

    function type "3pt+sensor"

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    10/14

    CM2N3544E / 06.1999 Siemens Building Technologies

    10/14 Landis & Staefa Division

    VAV differential pressure control 1 : 1

    Master (supply air): minV = 20 %, maxV = 80 %, Vn = 1

    Slave (extract air): minV = 0 %, = maxV 100 %, Vn = 1

    Reference signal: Y20 = 2.5 V

    Result: Vmaster = 35 %, Vslave = 35 %

    Vmin [%]Vmin [%] Vmax [%]

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    120

    110

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    120

    110

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    00

    V [%] Vmax [%] V [%] UC [V]

    0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10Y [V] Y [V]

    UC [V]

    Master controller(Supply air)

    Slave controller(Extract air)

    Control range Controlrange

    Reference signal DC 0...10 VY20 (RCE84.21 room controller) 35

    44D01E

    VAV differential pressure control 1 1, with 20 % room overpressure

    Master (supply air): minV = 20 %, maxV = 80 %, Vn = 1

    Slave (extract air): minV = 20 %, maxV = 80 %, Vn = 1

    Reference signal: Y20 = 2.5 V

    Result: Vmaster = 35 %, Vslave = 15 %

    V [%]Vmin [%]

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    120

    110

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    120

    110

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    0 1 2 3 4 5 6 7 8 9 10Y [V] Y [V]

    1090 1 2 3 4 5 6 7 8

    Vmax [%] UC [V] UC [V]V [%]Vmax [%]Vmin [%]

    Master controller(Supply air)

    Slave controller(Extract air)

    Control range Controlrange

    Reference signal DV 0...10 VY20 (RCE84.21 room controller)

    3544D02E

    VAV differential pressure control 1 1, with 20 % room underpressure

    Master (supply air): minV = 20 %, maxV = 80 %, Vn = 1

    Slave (extract air): minV = 20 %, maxV = 120 %, Vn = 1

    Reference signal: Y20 = 2.5 V

    Result: Vmaster = 35 %, Vslave = 55 %

    V [%]Vmax [%]

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    120

    110

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    0

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    120

    110

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    0 1 2 3 4 5 6 7 8 9 10Y [V]Y [V]

    0 1 2 3 4 5 6 7 8 9 10

    Vmin [%] UC [V] V [%]Vmax [%]Vmin [%] UC [V]

    Master controller(Supply air)

    Slave controller(Extract air)

    Control range Controlrange

    Reference signal DC 0...10 VY20 (RCE84.21 room controller) 35

    44D03E

    Setting examples

    Setting example 1

    Setting example 2

    Setting example 3

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    11/14

    Siemens Building Technologies CM2N3544E / 06.1999

    Landis & Staefa Division 11/14

    VAV relational control 1 1,

    with increasing room overpressure in proportion to the supply air volume

    Master (supply air): minV = 20 %, maxV = 80 %, Vn = 1

    Slave (extract air): minV = 0 %, maxV = 80 %, Vn = 1

    Reference signal: Y20 = 2.5 V

    Result: Vmaster = 35 %, Vslave = 28 %

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    120110

    100

    9080

    70

    60

    50

    40

    30

    20

    10

    100

    9080

    70

    60

    50

    40

    30

    20

    10

    10

    98

    7

    6

    5

    4

    3

    2

    1

    0

    10

    98

    7

    6

    5

    4

    3

    2

    1

    0

    100

    9080

    70

    60

    50

    40

    30

    20

    10

    120110

    100

    9080

    70

    60

    50

    40

    30

    20

    10

    60

    50

    40

    30

    20

    10

    0

    -10

    -20

    0 1 2 3 4 5 6 7 8 9 10 0Y [V] Y [V]

    1 2 3 4 5 6 7 8 9 10

    Vmin [%] Vmax [%] V [%] UC [V] Vmin [%] Vmax [%] V [%] UC [V]

    Master controller(Supply air)

    Slave controller(Extract air)

    Control range Controlrange

    Reference signal DC 0...10 VY20 (RCE84.21 room controller) 35

    44D04E

    VAV relational control 1 1,with increasing room underpressure in proportion to the supply air volume

    Master (supply air): minV = 20 %, maxV = 80 %, Vn = 1

    Slave (extract air): minV = 0 %, maxV = 120 %, Vn = 1

    Reference signal: Y20 = 2.5 V

    Result: Vmaster = 35 %, Vslave = 42 %

    Vmax [%]

    60

    5040

    30

    20

    10

    0

    -10

    -20

    120

    110

    100

    90

    80

    70

    60

    504030

    20

    10

    100

    90

    80

    70

    60

    504030

    20

    10

    10

    9

    8

    7

    6

    543

    2

    1

    0

    10

    9

    8

    7

    6

    543

    2

    1

    0

    100

    90

    80

    70

    60

    504030

    20

    10

    120

    110

    100

    90

    80

    70

    60

    504030

    20

    10

    60

    5040

    30

    20

    10

    0

    -10

    -20

    0 1 2 3 4 5 6 7 8 9 10Y [V] Y [V]

    0 1 2 3 4 5 6 7 8 9 10

    Vmin [%] V [%] UC [V] Vmax [%]Vmin [%] V [%] UC [V]

    Master controller(Supply air)

    Slave controller(Extract air)

    Control range Controlrange

    Reference signal DC 0...10 VY20 (RCE84.21 room controller) 35

    44D05E

    V Air volumeVn Nominal air volume

    minV Minimal air volume

    maxV Maximum air volumeVmaster Air volume of the supply air controller (master)

    Vslave Air volume of the extract air controller (slave)

    Y DC 0...10 V input signal (air volume setpoint)

    UC DC 0...10 V output signal (air volume actual value)

    Actual value [%] =Setpoint [%] x (Vmax Vmin ) [%]

    + Vmin[%]

    Actual value [V] =

    Setpoint [V] x (Vmax Vmin ) [V]

    + Vmin[V]

    100 [%]

    10 [V]

    Setting example 4 .

    .

    Setting example 5 ..

    Legend for setting

    examples 1 to 5

    Actual value formula

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    12/14

    CM2N3544E / 06.1999 Siemens Building Technologies

    12/14 Landis & Staefa Division

    The VAV compact controllers are supplied with a fixed connecting cable. The connected

    units must galvanically be applied to the same G0.

    ( )

    p

    (G) (Y2) (Y1) (Y)

    1 7 6 8

    (G0) (UC)

    2 93544G01

    All connecting wire cores are colour-coded and labelled.

    Wirelabelling

    Core colour Landis & Staefa-terminal code

    Meaning

    1 Red G Phase AC 24 V

    2 Black G0 System neutral AC 24 V

    6 Purple Y1 Positioning signal "Motor direction" (switched G0),dependent of the settings at DIL switch 1 (for factorysetting = right rotation)

    7 Orange Y2 Positioning signal "Motor direction" (switched G0),dependent of the settings at DIL switch 1 (for factorysetting = left rotation)

    8 Grey Y Air volume positioning signalDC 0 ... 10 V(setpoint)

    9 Pink UC Air volume measuring signalDC 0 ... 10 V (actualvalue) or communication signal for connected settingunit

    Control loop without communication

    G

    G Y2 Y1 YG E1

    G0G0 Y10 Y20

    G0

    b)a)

    AC2

    4V

    N1N2

    3544A01

    UC

    Control loop with communication

    3544A02G

    RS1...4

    GG RS1...4

    G0 AO1...3

    G Y2 Y1 Y

    G0

    G0

    b)

    AC2

    4V

    B1

    N3 N1UC

    Diagrams

    Internal diagram

    (applies to all types)

    Legend

    Connection diagram 1

    Connection diagram 2

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    13/14

    Siemens Building Technologies CM2N3544E / 06.1999

    Landis & Staefa Division 13/14

    VAV supply air or extract air control

    3a:modulating control 3b: modulating control between 3c: modulating control between

    minV and minV maxV and minV and complete closure minV and maxV and complete opening

    G

    G0

    DC 0...10 V

    G Y2 Y1 Y

    G0

    3544A03

    N1AC2

    4

    V

    S1

    UC

    G

    G0

    DC 0...10 V

    G Y2 Y1 Y

    G0

    3544A04

    N1AC2

    4

    V

    S1

    UC

    G

    G0

    DC 0...10 V

    G Y2 Y1 Y

    G0

    3544A10

    N1AC2

    4

    V

    UC

    CAV supply air or extract air control

    4a:control to minV value 4b: control to maxV value

    G

    G Y2 Y1 Y

    G0

    G0

    AC2

    4V

    N1

    3544A0

    5

    UC

    G

    G Y2 Y1 Y

    G0

    G0

    AC2

    4V

    N1

    3544A0

    6

    UC

    4c: Complete closure 4d:Complete openingG

    G Y2 Y1 Y

    G0

    G0

    AC2

    4V

    N1

    3544A07

    UC

    G

    G Y2 Y1 Y

    G0

    G0

    AC2

    4V

    N1

    3544A08

    UC

    B1 Room unit QAA12

    N1 VAV compact controllers GDB181.1/3 or GLB181.1/3

    N2 Room temperature controller RCE84.21

    N3 Room temperature controllers RCE92.1 or RCE93.1

    S1 Window contact (window closed = open contact)

    a) For control unit "Heating"

    b) For slave controller

    The operating voltage on terminals G and G0 must comply with the requirements forsafety extra-low voltage (SELV) as per EN 60 730.

    Use safety insulating transformers with double insulation in accordance withEN 60 742; The transformers must be made for 100% runtime.

    Connection diagrams

    3a to 3c

    Connection diagrams

    4a to 4c

    Legend for connecting

    diagrams 1 to 4

  • 8/10/2019 Gdb-glb181.1e3 Vav Compact

    14/14

    CM2N3544E / 06 1999 Siemens Building Technologies

    Supply air / extract air control with TEC controller and GDB181.1/E3 or GLB181.1/E3

    function type "3pt+sensor"

    AC

    24V

    RS4

    TxD RxD G0 PPS

    G Y1 Y2

    N1

    G Y1 Y2

    N3

    RS3 RS2 RS1

    G BO5 BO6BO4BO3G

    B1

    N2

    G

    G0

    G0 G0

    G

    G0 3544A09

    AI1 AI2M M

    UC UC

    N1, N2 VAV compact controllers GDB181.1E/3 or GLB181.1E/3

    N3 TEC controllers RCE92.1 or RCE93.1

    B1 TEC room unit, e.g. QAA11

    The operating voltage on terminals G and G0 must comply with the requirements forsafety extra-low voltage (SELV) as per EN 60 730.

    Use safety insulating transformers with double insulation in accordance withEN 60 742; The transformers must be made for 100% runtime.

    59,5 43,5 87

    137

    90

    34,1

    2,3

    68

    min. 100

    min.

    200

    min. 60

    4

    min.

    6

    12 20

    4

    d

    2

    5

    180

    10 - 16 mm

    X

    12 mm15 mm

    8 - 16 mm

    12 mm15 mm

    3544M01

    X =GLB181.1E/3 X =GDB181.1E/3

    Connection diagram 5

    Legend for connection

    diagram 5

    Dimensions

    Dimensions in mm 1999 Siemens Building Technologies AG

    d = Mounting bracket