Upload
payolin77
View
217
Download
0
Embed Size (px)
Citation preview
8/17/2019 Il 04209003 e
1/2
Instructional Leaflet IL04209003E Effective July 2010
C4411 Remote Display Installation Guide
Type 1 and 12 Applications
Step 1 — Enclosure Preparation
Drill or punch two 30mm pilot device holes on1.75-inch centers a minimum of 1.60 inches (40.6 mm)from every door gasket.
Step 2 — Mounting the Remote Display
• Insert remote display through the door andadd two gaskets provided behind the door (seeFigure 2).
• Orient strain relief bracket with respect to yourchosen cable routing.
• Add two jam nuts provided and tighten 30mmpilot device tool (E22CW recommended) until thestrain relief bracket is flush with the enclosure
door, tighten an additional 1/2 of a turn. Step 3 — Connecting the Remote Display
• Select cable up to 10 feet long from Table 1below and route cable to Motor Insight™, installingcommunications filter provided with C4411following the instructions in Figure 3.
TABLE 1.
CATALOG LENGHT LENGHT
NUMBER INCHES METER
D77E-QPIP25 9.8 0.25
D77E-QPIP100 39.4 1.0
D77E-QPIP200 78.7 2.0
D77E-QPIP300 118.1 3.0
• Secure cable to the strain relief bracket using any
suitable tie wrap.
Locate the common mode communication filter. Othe shell and insert (1) complete loop. Close and sthe shell shut. See Figure 3. The filter is to be locatedclose to the Motor Insight overload relay as possibl
8/17/2019 Il 04209003 e
2/2
C4411 Remote Display Installation Guide
Eaton CorporationElectrical Sector1000 Cherrington ParkwayMoon Township, PA 15108United States877-ETN-CARE (877-386-2273)Eaton.com
© 2008 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. IL04209003EJuly 2010 Rev.002
PowerChain Management is a registeredtrademark of Eaton Corporation.
All other trademarks are property of theirrespective owners.
Type 1/12 Remote Display Conversion to 3R Applications
For 3R applications, install 3R kit C4413 as follows:
1. Loosen the captive screw in C4413 enclosure assembly and remove
cover.
2. Insert User Interface into the base of the 3R enclosure provided
and through the holes as prepared in Step 1 above for Type 1/12
installations (Figure 4).
3. Follow Steps 2 and 3 from Type 1/12 installation instructions above.4. Insert cover into cam slots Figure 5 and pull cover forward and down,
(Figure 6) torque screw 12-15 in-lb
Note: Provisions are made for two 3/8” shackle locks to prevent tampering
from unauthorized personnel.