52
October 2010

I&O MANUAL 10-18-10

Embed Size (px)

Citation preview

Page 1: I&O MANUAL 10-18-10

October 2010

Page 2: I&O MANUAL 10-18-10
Page 3: I&O MANUAL 10-18-10

i October 2010

TABLE OF CONTENTS

Section Page

Section 1. INTRODUCTION

1-1 Refcon Refrigerated Cases ……………………………………….1

1-2 Self-Contained Models ……………………………………………..1

1-3 Remote Models ………………………………………………………….1

1-4 Case Location …………………………………………………………….1

1-5 Proper Care ……………………………………………………………….1

1-6 Assistance ………………………………………………………………….1

1-7 Safety ………………………………………………………………………..2

Section 2. INSTALLATION

2-1 Introduction ………………………………………………………………3

2-2 Shipping Damages ……………………………………………………3

2-3 Shortages …………………………………………………………………3

2-4 Prior to Installation …………………………………………………..3

2-5 Uncrating Instructions ……………………………………………..4

2-6 Unpacking Instructions …………………………………………….4

2-7 Excessive External Loads ………………………………………….5

2-8 Leveling Cases ………………………………………………………….5

2-9 Pocket Doors ……………………………………………………………..6

2-10 Case Line-up ……………………………………………………………..6

2-11 Case Drains ……………………………………………………………….7

2-12 Electrical ……………………………………………………………………8

2-13 Refrigerant Piping …………………………………………………...8

2-14 Shelving …………………………………………………………………….8

2-15 Doors …………………………………………………………………………8

2-16 Lift-Up Glass ……………………………………………………………..9

2-17 Drop-In and HMR Units ……………………...................11

2-18 Installation Checklist ….……………………...................14

Page 4: I&O MANUAL 10-18-10

ii October 2010

TABLE OF CONTENTS (Continued)

Section

Page

Section 3. OPERATION

3-1 Refrigeration System ………………………………………………15

3-2 Refrigeration Controls …..……………………………………….17

3-3 Lift-Up Glass ……………………………………………………… ….18

3-4 Load Limits.……………………………………………………………..19

3-5 Operational Checklist…………………………………….…..……21

3-6 Heated Cases ………………………………………………………… 22

3-7 Gelato Cases …………………………………………………………. 24

Section 4. MAINTENANCE

4-1 Case Cleaning ….………………………………….…….……………27

4-1a Glass ……………………….………………………………….27

4-1b Stainless Steel ……………………………..……………….27

4-1c Lexan…………….……………………………………………….28

4-1d Acrylic ………….…………………………………………………29

4-1e DuPont™Corian® ……………….……………………………29

4-1f CaesarStone…….……………………………………..…….31

4-1g Granite …..…………………………………………………..31

4-1h Richlite (cutting Boards) ………………………………32

4-2 Evaporator Coil .…..…………………………………………………33

4-3 Condenser Coil ………………………………………………………..33

Section 5. ELECTRICAL WIRING DIAGRAMS …………….………………………35

Section 6. WARRANTY & WARRANTY PROCEDURES ………………………..39

Section 7 WEBSITE ………………………………..…………………………………………43

Page 5: I&O MANUAL 10-18-10

Page 1 October 2010

1.0 INTRODUCTION

1-1. REFCON REFRIGERATED CASES: Refcon cases; refrigerated and heated; are distinctively designed to accommodate a wide variety of food display

applications and products. Refcon refrigerated cases are offered in either self-contained or remote models.

1.1A SELF-CONTAINED MODELS: Self-contained cases include a factory installed compressor/condensing unit to provide the designed refrigeration requirements. Self-contained models typically are built

with a factory installed electric condensate evaporator, or in some instances, the case may be built for use with a plumbing floor sink, or

drain (Provided by others).

1.1B REMOTE MODELS: Remote Cases are constructed to utilize a

refrigeration source that is external to the case. It is important that the

external refrigeration source(s) have the correct refrigerant type for the fixture(s) purchased, and the refrigeration capacity is sufficient to

maintain the case(s) temperature. Remote cases are typically built for use with a plumbing floor sink, or drain (Provided by others).

1-2. CASE LOCATION: For proper case operation, installation in an air-conditioned space maintained at a maximum ambient temperature of 75° F and a relative humidity of 55% is mandatory. Do not install the refrigerated

case(s):

• In an area that has excessive air movement; i.e. close to external doors or

from air-conditioning vents.

• In a location that may have excessive heat, such as near windows that get direct sun.

• Near any other heat producing equipment or lighting.

• Self-contained cases must be installed such that airflow is not obstructed to

the condenser air intake and exhaust sections. Ensure the area of free airspace openings is equal to, or greater than, the louvered condenser section of the self-contained case.

1-3. PROPER CARE: As with any display fixture, Refcon refrigerated cases require routine care and maintenance. Requirements for the maintenance and cleaning

are contained in the manual and must become a regular part of the operation of the unit at all times.

1-4. ASSISTANCE: Should there be the need for additional, or service related assistance, please feel free to contact Refcon at (201) 750-5060.

Page 6: I&O MANUAL 10-18-10

Page 2 October 2010

1.0 INTRODUCTION (continued)

1-5. SAFETY: Refcon refrigerated fixtures are constructed to comply with the latest

industry safety standards. However, the only way to ensure a safe operation is

to fully understand the proper installation, operation, and maintenance procedures. The instructions in this manual have been prepared to aid in learning these proper procedures. Where information is of particular importance

or safety related, the words WARNING, CAUTION, and NOTICE are used. Their usage is described below:

NOTICE is used to highlight especially

important information.

CAUTION indicates a potentially hazardous

situation, which if not avoided, may result in property damage and/or minor to moderate injury.

WARNING Indicates a potentially

hazardous situation, which if not avoided, could result in serious injury or death.

Page 7: I&O MANUAL 10-18-10

Page 3 October 2010

2.0 INSTALLATION

2-1. INTRODUCTION: This section provides the installation and unpacking instructions for Refcon refrigerated display cases.

2-2. SHIPPING DAMAGES: Thoroughly check the received Refcon

equipment for possible transportation damages. If such damage is established, a claim must be filed with the carrier immediately and any

apparent damage must be stated on the freight bill or carrier may refuse the claim. Retain all packaging for carrier’s inspection.

If the damage is established only after equipment is uncrated, the

purchaser must file an immediate claim with the carrier and request in writing an immediate inspection. All packaging must be retained for

inspection. Request for inspection must be made within 10 days after shipment is received.

2-3. SHORTAGES: Received equipment should be checked for possible shortages. Should such shortages exist, contact Refcon and/or the carrier

immediately. Refcon will only consider all shortage reports within 10 days after equipment was received at destination.

2-4. PRIOR TO INSTALLATION: Verify the intended final case location is suitable for proper operation. As mentioned it section 1, it is imperative

that the placement of Refcon equipment is not located where there is excessive heat from sunlight, heating units and/or there is excessive air

movement nearby since this will impair the intended performance of the

case(s).

Only qualified Electrical, Mechanical, and Refrigeration Technicians should perform the installation of the

refrigerated cases in accordance with all applicable National and Local codes.

Examine Fixture For Any Shipping Damage. Report Any Such Damage to the Carrier for Adjustment. All

Equipment is Shipped FOB from the factory and filing claims for damages, which occur during transit, is the

responsibility of the Purchaser.

For proper case operation, installation in an air-conditioned space maintained at a maximum ambient

temperature of 75° F and a relative humidity of 55% is mandatory.

Page 8: I&O MANUAL 10-18-10

Page 4 October 2010

2.0 INSTALLATION (Continued)

2-5. UNCRATING INSTUCTIONS: Move the fixture as close as possible to

its permanent location. When ready to uncrate, carefully remove all crating above the pallet. Loosen the plastic dust cover from the pallet

but leave cover over the case in order to protect it while removing the

case from the pallet. Carefully slide it off the pallet.

2-6. UNPACKING INSTRUCTIONS: Carefully remove all separately packed

accessories such as lights, shelves, etc. from the fixture and place them in area where damage will not occur.

Cases are TOP HEAVY. Take special care in lifting and/or moving cases, or personal injury could

result.

Page 9: I&O MANUAL 10-18-10

Page 5 October 2010

2.0 INSTALLATION (Continued)

2-7. EXCESSIVE EXTERNAL LOADS: Do not place any heavy objects or walk on top of the cases. Refcon displays are not designed to support

excessive external loads.

2-8. LEVELING CASES: After locating the case in position, level the case by

adjusting leveling feet or shimming as required.

Use of 4’-5’ level is recommended. Level both left to right and front to

back.

Standing or walking on top of cases may cause personal

injury or property damage to the case.

For Cases equipped with lift up glass, it is extremely

important the fixture is set perfectly level.

To ensure proper operation of the refrigeration system

and the correct drainage of condensate, make sure that

all cases are installed level.

Standing or walking on top of cases may cause personal

injury or property damage to the case.

Page 10: I&O MANUAL 10-18-10

Page 6 October 2010

2.0 INSTALLATION (Continued)

2-9. POCKET DOORS: Cases with pocket doors must be set properly in order for pocket doors to operate properly. Some adjustment to doors maybe

required after installation. (This is the installers’ responsibility).

2-10. CASE LINE-UP: All cases are set up in the factory in order to assure proper alignment in the field. In order to properly line-up and level

2-10a. Find the highest part of the floor under the cases.

2-10b. Start leveling from the high point and continue through the rest

of the lineup.

2-10c. Fasten the cases together with the connection hardware

included.

For Cases equipped with pocket doors, case must be square and level for pocket doors to operate properly.

Page 11: I&O MANUAL 10-18-10

Page 7 October 2010

Condensate Evaporators Operate At A Very High Temperatures and Should Never Be Touched While

Operating. Personal Injury or Burns May Occur.

2.0 INSTALLATION (Continued)

2-11. CASE DRAINS: Remote refrigerated cases are typically shipped with a P-trap drain. Field extensions need to be connected and routed to the

nearest floor sink, or floor drain. Ensure the trap is installed correctly and the extended condensate line is pitched towards the floor drain.

For self-contained cases utilizing a floor drain, follow the same directions as for a remote case.

For cases equipped with a condensate evaporator, the condensate trap and drain is factory installed.

Ensure all national and local codes are followed for the condensate drain piping materials used and the final

indirect waste connection at the floor drains has the correct air gap distance.

Page 12: I&O MANUAL 10-18-10

Page 8 October 2010

Remote are shipped with a Nitrogen holding charge. Be sure to relieve pressure carefully.

2.0 INSTALLATION (Continued)

2-12. ELECTRICAL: Electrical connections can be made within the power supply

junction box at the case. Voltage requirements can be verified by checking the

data tag of the case. ONLY qualified electrical contractors should do electrical installation work. In all instances, the case electrical power supply must comply with all NEC and local codes. It is imperative all cases are properly grounded.

Verify all case electrical terminations are secure, connections can sometimes loosen during shipment.

2-13. REFRIGERANT PIPING: Remote refrigerated cases have stubbed

connections (liquid and suction) for refrigerant piping. Review case fact sheet to determine the appropriate location to install refrigerant piping. Remote cases

are shipped with a Nitrogen holding charge. Be sure to relieve pressure carefully. Use care when brazing, as damage can occur to valves and controls if overheated. While brazing piping always use nitrogen to keep contaminants

from forming inside the refrigeration piping. Ensure all refrigerant piping is properly sized for the associated load and temperature conditions required.

Properly insulate suction lines to prevent sweating. Keep refrigerant piping away from condensate evaporators (if equipped).

2-14. SHELVING:

2-14a. Glass Shelves: Glass shelves are protectively wrapped and shipped within the case.

2-14b. Non-Glass Shelves: Stainless steel shelves are shipped in place with padding and blocking to avoid damage during shipping. Verify

padding and blocking is removed prior to loading shelves.

2-15. DOORS: Some cases are equipped with rear sliding doors. If the doors are

shipped inside the case, remove the protective coverings from the doors and then push the top edge of the doors up into the top track so that the bottom of

the doors can clear the bottom track. Push the bottom door section onto the bottom track. Verify doors slide easily side to side.

Cases Must Be Properly Grounded. Failure to Properly Ground the Electrical Case May Result in

Personal Injury Or Death.

DO NOT modify plugs in any way to fit into outlet

receptacles.

Page 13: I&O MANUAL 10-18-10

Page 9 October 2010

2.0 INSTALLATION (Continued)

2-16. LIFT-UP GLASS: Some cases are fitted with front lift up glass. Extreme care

should be used when opening and closing the lift-up glass assemblies. Do not

force, or quickly open/close the glass, as damage can be done to the lifting support arms. The glass is installed at the factory with the case set level but some field adjustments maybe required. (This is the installers’ responsibility).

2-16a. To avoid any damage, please do the following prior to completely raising the glass:

i. Case must be square and level

ii. Slowly raise and lower the glass 6 times to a height of 6 inches.

iii. Slowly raise and lower the glass 6 times to a height of 12 inches

iv. Slowly raise and lower the glass 6 times to the fully open position

2-16b. If further adjustment is required after verifying the cases are level,

please follow the instructions below:

i. Ensure two people are available to make glass adjustments. One

person must always be holding the glass.

ii. Lift up the glass to the highest position.

iii. Loosen the set screws on the glass clamping mechanism.

It is especially important that cases fitted with lift-up glass be installed completely level.

Page 14: I&O MANUAL 10-18-10

Page 10 October 2010

2.0 INSTALLATION (Continued)

iv. Slide the glass, left or right, until the glass is even. Ensure the glass is correctly recessed in the clamping mechanism.

v. Tighten the set screw first at either the left or right sides. Ensure the glass is held firmly at the opposite end of where the tightening is started.

vi. Securely tighten all remaining set screws.

vii. Lower the glass into position and check alignment.

viii. If necessary, repeat this process until the glass is completely level.

Necessary adjustments to glass require 2 persons.

The glass must be securely held at all times during adjustment.

Page 15: I&O MANUAL 10-18-10

Page 11 October 2010

2.0 INSTALLATION (Continued)

2-17. DROP-IN AND HMR (COUNTERTOP) INSTALLATION:

2-17a. DROP-IN UNITS

i. Refcon HMR’s and DROP-IN UNITS should be installed by mechanics familiar with the installation of refrigeration equipment.

ii. If standard air flow pattern shown below cannot be followed, Refcon must be advised about that to suggest an alternative.

iii. Intake and exhaust louvers; as shown on the following drawings; must have a minimum of 4 in. (102 mm) unobstructed outside space for air cooling to function properly.

iv. It is recommended that access to the condensing unit be provided as indicated on the Plan View for maintenance and service.

A B C MODEL

NUMBER Size

in mm in mm in mm

M/GMAJDS ALL 10 254 24 610

M/SLEGDS ALL

036-060 23 584

29 737

M/SLEGDS-HB 072

9 229

25 635 43 1092

M/SMASDS ALL 10 254 24 610 29 737

030 27 686

043-082 27 686

29 737 M & MA/SPREDS

95

13 330

29 737

036-060 25 635 35 889

M/SWINDS 072

9 229 27 686 43 1092

Page 16: I&O MANUAL 10-18-10

Page 12 October 2010

2.0 INSTALLATION (Continued)

2-17. DROP-IN AND HMR (COUNTERTOP) INSTALLATION:

2-17a. DROP-IN UNITS

Page 17: I&O MANUAL 10-18-10

Page 13 October 2010

2.0 INSTALLATION (Continued)

2-17. DROP-IN AND HMR (COUNTERTOP) INSTALLATION:

2-17b. HMR (COUNTERTOP) UNITS

Page 18: I&O MANUAL 10-18-10

Page 14 October 2010

2.0 INSTALLATION (Continued)

2-18. INSTALLATION CHECKLIST:

Case General

1. Verify case is installed in an appropriate location.

2. On self-contained cases, verify the proper airflow

area exists at the condenser inlet and outlet and no obstructions are present.

3. Ensure fixtures are installed level.

4. Verify case drains are installed properly (Cases

without condensate evaporators)

5. If equipped with a condensate evaporator, Ensure

the drain line is secure and properly aligned into the condensate pan area.

6. Verify shelving is properly installed and ready to

accept the weight of product.

7. Check shelf lighting connections are secure.

Electrical

1. Verify the proper quantity and size of wiring has been installed.

2. Ensure the case has been properly grounded.

3. Verify all electrical connections are properly

tightened. Connections can loosen during shipping.

Refrigeration Piping (Remote)

1. Ensure there are no leaks in piping connections to remote cases.

2. Verify the piping to remote cases is properly sized.

3. Verify all refrigerant piping is properly supported

and that copper lines are not touching any metal, or other abrasive surfaces.

Evaporator Area

1. Verify all debris is removed from this area and that

the drains are clear.

2. Properly install all cover pans (if equipped). Ensure

there are no large gaps between the cover pans where airflow leakage could occur.

Compressor Area

(Self-Contained)

1. Verify any compressor shipping supports, or blocks, are removed.

Lift-up Glass

1. Ensure glass raises and lowers easily and there are no obstructions.

2. If glass adjustment is necessary, make sure to carefully follow the instructions for this procedure.

Page 19: I&O MANUAL 10-18-10

Page 15 October 2010

3.0 OPERATION

3-1. REFRIGERATION SYSTEM: Refcon’s remote and self-contained cases use

either forced or gravity air circulation systems for cooling (depending on model).

The refrigeration system consists of an all copper tubing evaporator coil with aluminum fins and a thermostatic expansion valve designed for the specific case application. Self-contained models include a matched hermetic condensing unit

for long life and operating efficiency.

3-2. REFRIGERATION CONTROL:

• Remote cases: Can be controlled through several methods:

o With No Controls. This version is intended for installation with a parallel

compressor rack (Supplied by others) or single compressor system. In this instance, the necessary temperature and defrost controls need to come from the associated compressor system equipment.

o Optional Thermostat This version controls the case through an optional thermostat and liquid line solenoid valve. Defrost is controlled by other

means. (Supplied by others)

o Remote Refrigeration Control Package These cases are controlled through a micro-processor based controller tied to a liquid line solenoid valve. The

controller controls case temperature, timed defrost initiation and temperature defrost termination

• Self-Contained cases: These cases are controlled through a micro-processor based controller tied to the condensing unit. The controller controls case temperature, timed defrost initiation and temperature defrost termination.

• Two different controllers have been used in Refcon cases. Check the unit and verify the controller installed in the case.

Page 20: I&O MANUAL 10-18-10

Page 16 October 2010

3.0 OPERATION (continued)

o REFRIGERATION CONTROLLER: (Dixell XR02CX)

To display target set point, in

programming mode it selects a parameter

or confirms an operation

To start a manual defrost

In programming mode it browses the

parameter codes or increases the

displayed value

AUX

In programming mode it browses the

parameter codes or decreases the

displayed value

LED MODE CONDITION

On Compressor enabled

Flashing Anti short cycle delay enabled (AC parameter)

On Defrost in progress

Flashing Dripping in progress

On Measurement unit

Flashing Programming mode

On Measurement unit

Flashing Programming mode

XR02CX DEFAULT PARAMETERS

LABEL SETTING Units DEFAULT LEVEL

DEFINITION

SEt 26 °F -- Set point

AC 2 min Pr1 Anti-short cycle delay

dE 45 °F Pr1 Defrost termination temperature

Hy 3 °F Pr1 Differential

id 3 h Pr1 Interval between defrost cycles

Md 60 min Pr1 Maximum length for defrost

rE in Pr1 Resolution (only for C)

To change the case temperature set point; press and hold

for 3 seconds. Use and AUX keys to change the case temperature set point. Press to store the new set

point.

Page 21: I&O MANUAL 10-18-10

Page 17 October 2010

3.0 OPERATION (continued)

o REFRIGERATION CONTROLLER: (Sporlan Unistat)

COMPONENT FUNCTION FACTORY

SETTING

Manual Defrost Button Pressing the button, starts a defrost cycle N/A

Defrost Interval Dial The time between defrosts (hrs) 6

Defrost Sensor Input The connection for the DEFROST SENSOR. The

DEFROST SENSOR is used to terminate the defrost. N/A

Air Sensor Input This connection is for temperature probe.

Display Input This connection is for the temperature display. N/A

Temperature Dial This is the dial for setting the case temperature.

(The numbers are not the temperature.) 3.5 =27ºF

Dip Switches SEE TABLE

TEMPERATURE DIAL

DIP SWITCHES

AIR SENSOR INPUT DISPLAY INPUT

DEFROST SENSOR INPUT

DEFROST INTERVAL DIAL

MANUAL DEFROST BUTTON

Page 22: I&O MANUAL 10-18-10

Page 18 October 2010

3.0 OPERATION (continued)

3-3. LIFT UP GLASS: Be careful when opening lift up glass.

COMPONENT FUNCTION FACTORY SETTING

1-2 Temperature Differential 1-UP, 2-DN; 5.5ºF

3 Compressor Delay 3-DN; Off

4 Temperature Units 4-UP; Fahrenheit

5,6,7,8 Defrost Termination 5-UP, 6-UP, 7-DN, 8-DN; 42ºf

9 Defrost Type 9-DN; Air Over

Dip Switches

10 Not Used 10-DN; Off

Never open the lift up glass partially. The lift-up glass

must be fully opened or closed.

For corner and curved cases, avoid opening more

than one piece of glass at a time as the pieces of glass may interfere and contact another piece of

glass.

Page 23: I&O MANUAL 10-18-10

Page 19 October 2010

3.0 OPERATION (continued)

3-4. AIRFLOW/LOAD LIMITS: For proper case performance, airflow must not

be obstructed. Ensure discharge and return air grills are free from any airflow

obstructions from product, signs, or other items.

3-4a CLOSED CASE

3-4b SALAD/COLD PAN CASE

Do not place or load product in a manner that blocks or

impacts the air flow of the case.

DO NOT allow product to extend

into the REAR airflow area.

Blocking this area will impact case performance.

2”

DO NOT allow

product to extend into the TOP airflow

area. Blocking this area will impact case performance.

Page 24: I&O MANUAL 10-18-10

Page 20 October 2010

3.0 OPERATION (continued)

3-4c AIR SCREEN CASE

3-4d DELI CASE

DO NOT allow

product to extend into the FRONT

airflow area. Blocking this area

will impact case performance.

DO NOT allow product to extend

into the FRONT airflow area.

Blocking this area will impact case performance.

Page 25: I&O MANUAL 10-18-10

Page 21 October 2010

3.0 OPERATION (continued)

3-5. OPERATIONAL CHECKLIST:

Case or Product

Temperature is Warm

1. Case may be in defrost. Check controller or time clock.

2. Thermostat or Controller may be set too high.

3. Ensure product is cold prior to stocking in the case.

4. Ensure room temperature <75ºF and humidity <55%.

5. Ensure there are no external vents or grilles discharging into

the case.

6. Check for Proper Airflow.

7. Ensure product is not above load limits.

8. Verify the return or discharge grills are not blocked.

9. Ensure the condensing unit or remote compressor is operating

and there is no obstruction for condensing unit discharge air.

10. Ensure shelves are properly located and not blocking the

intended air flow.

Case Temperature Too Cold 1. Thermostat or Controller may be set too low.

Poor, or No Airflow

1. Check for obstructions.

2. Verify fans are operating.

3. Ensure that evaporator coil is free from ice build-up.

Water Under Cases with

Floor Drains

1. Check if floor drain (If equipped) is plugged.

2. Inspect PVC condensate line for leaks and proper placement

over floor drain.

Water Under Cases with

Condensate Evaporators

1. Inspect PVC condensate line for leaks and proper placement

into the condensate evaporator.

2. Check the operation of the condensate evaporator float, switch,

and heating element.

High Discharge Pressures

(Self-Contained Models)

1. Check for airflow obstructions at the intake and discharge

panels to the condensing unit.

2. Ensure that the condenser coil is clean.

3. Verify the condenser fan is operating when the compressor is

on.

Condensation on Glass

1. Verify ambient conditions (temperature and humidity) are in

acceptable ranges.

2. Check for airflow obstructions at the intake and discharge

panels to the condensing unit.

3. Verify unit temperature set point is not set too low

Page 26: I&O MANUAL 10-18-10

Page 22 October 2010

THIS

PAGE

IS

INTENTIONLY

BLANK

Page 27: I&O MANUAL 10-18-10

Page 23 October 2010

3.0 OPERATION (continued)

3.6 HEATED CASES:

3.6a. Operation Control (Overhead Food Warmer)

SPREHD Model

i. A lighted master switch controls all Heaters. Individual on/off and

adjustable dial switches for the temperature adjustment are used to control each shelf heater. The pilot light on the switch will be lit when

the heater power is on.

ii. A single light switch controls all of the shelf lights. A circuit breaker with a reset button is installed on the light circuit.

SPREHD Model

SQUBHD Model

iii. Individual on/off switches are used to control each shelf heater. The

pilot light on the switch will be lit when the heater power is on.

iv. A single light switch controls all of the shelf lights.

SQUBHD Model

Page 28: I&O MANUAL 10-18-10

Page 24 October 2010

Only plug a power cord into an outlet receptacle with the identical configuration as the plug used to prevent

electrical shock or injury.

3.0 OPERATION (continued)

3.6 HEATED CASES:

3.6b. Operating Procedure

i. Verify the power cord has been correctly plugged into the proper power outlet. Only plug a power cord into an outlet receptacle with the identical configuration as the plug used.

ii. Turn the lighted master switch to the “on” position. Put the toggle switch for the shelf in the on position. Turn the dial for the overhead heater to the desired setting. Turn the adjustable dial switch

(Overhead food warmer to the desired setting. Further adjustments maybe required after the unit has running for a whie.

NOTE

3.6c. Putting product in the food shelves

i. Gently fill up the shelves with products and be caution not to overload shelf. Keep at least 2” space between the product and the heater surface (proper load line).

Typical temperatures holding requirements for HOT FOODS are 150°F or higher. It is recommended the internal temperature of

food product be checked to verify the proper temperatures are

being maintained.

Page 29: I&O MANUAL 10-18-10

Page 25 October 2010

3.0 OPERATION (continued)

3.7 GELATO CASES:

Gelato cases are low temperature units which utilize a hot gas defrost to reduce the

defrost time. In addition, hot gas is used eliminate condensation forming on the glass.

o REFRIGERATION CONTROLLER: (Dixell XR04CX)

Similar to the standard refrigerated cxase controller, the XR04CX

has an additional output for the hot gas solenoid.

To display target set point, in

programming mode it selects a parameter

or confirms an operation

To start a manual defrost

In programming mode it browses the

parameter codes or increases the

displayed value

AUX

In programming mode it browses the

parameter codes or decreases the

displayed value

LED MODE CONDITION

On Compressor enabled

Flashing Anti short cycle delay enabled (AC parameter)

On Defrost in progress

Flashing Dripping in progress

On Measurement unit

Flashing Programming mode

On Measurement unit

Flashing Programming mode

Page 30: I&O MANUAL 10-18-10

Page 26 October 2010

3.0 OPERATION (continued)

3.7 GELATO CASES:

XR04CX DEFAULT PARAMETERS

LABEL SETTING Units DEFAULT

LEVEL DEFINITION

SEt -15 °F -- Set point

AC 1 min Pr1 Anti-short cycle delay

dE 45 °F Pr1 Defrost termination temperature

Hy 5 °F Pr1 Differential

id 3 h Pr1 Interval between defrost cycles

Md 30 min Pr1 Maximum length for defrost

rE in Pr1 Resolution (only for C)

To change the case temperature set point; press and hold

for 3 seconds. Use and AUX keys to change the case temperature set point. Press to store the new set

point.

DO NOT allow

product to extend into the FRONT

airflow area. Blocking this area

will impact case performance.

Page 31: I&O MANUAL 10-18-10

Page 27 October 2010

4.0 MAINTENANCE

4-1. CLEANING: Frequently clean ALL surfaces.

4-1a. GLASS

In cleaning windows to remove soil and grease use an alkali, such as ammonia

or baking soda or washing soda.

To remove hard water deposits and some soils, use a weak acid such as vinegar (a strong acid would etch the glass).

Never combine an acid and an alkali to clean glass. One partially neutralizes the

other and you waste these neutralized materials. Thus do not mix vinegar and ammonia; use one or the other in your water solution to get the full effectiveness of the one product used.

Be careful not to drip alkaline or alcohol solutions on painted or varnished

woodwork as it can damage the finish. Wring out a cloth, sponge, or chamois almost dry before wiping the glass

surface. Dry the wet surface with paper towels, window wipes, or a chamois. Try not to drip cleaning solution on woodwork.

4-1b. STAINLESS STEEL

Known for its ability to be a clean surface that resists corrosion and rust. Dirt, dust and grime, however, put stainless steel at risk for corrosion and rust.

Routine cleaning can be accomplished by using warm water and a cloth. Dry

with a towel or cloth to prevent water spots. Wipe in the directions of the polish lines.

For cleaning that needs more power, mild detergent(dish washing liquid) and warm water can do a great job without damaging the stainless steel. Rinse the surface thoroughly to prevent staining and spotting. Towel dry to prevent water

spots which can be caused by minerals in water.

Fingerprints are one of the biggest complaints about stainless steel, but can be

taken care by using glass cleaner or household ammonia. Rinse thoroughly and towel dry.

Turn off all power witches prior to cleaning the case to

prevent electrical shock.

Page 32: I&O MANUAL 10-18-10

Page 28 October 2010

4.0 MAINTENANCE (continued)

For staining or scratching, or to polish stainless steel, a stainless steel cleaner may be a good option. Some of these cleaners and polishes can help minimize scratching and remove stains and can polish stainless steel surfaces nicely.

Read the directions on the stainless steel cleaner and test in an inconspicuous spot. Rinse thoroughly and towel dry.

� Painless Stainless

4-1c. LEXAN™

Cleaning Instructions

Wash using a mild soap or detergent and lukewarm water, using a clean sponge or a soft cloth. Rinse well with clean water. Dry thoroughly with a chamois or moist cellulose sponge to prevent water spots. Do not scrub or use brushes on

this product. The following cleaning agents have been found compatible with LEXAN™:

� Joy* � VM&P grade Naphtha

� Top Job* � Palmolive Liquid** � Windex with Ammonia D***

*Registered Trademarks of Procter & Gamble.

**Registered Trademark of Colgate Palmolive.

***Registered Trademark of the JohnsonDiversey Consumer Branded Professional Products.

Minimizing Hairline Scratches Scratches and minor abrasions can be minimized by using a mild automobile

polish. It is recommended that a small area be tested with the product selected following the manufacturer’s recommended instructions prior to use on a

complete window. Listed below are three products marketed to polish and fill scratches:

� Johnson Paste Wax

� Novus Plastic Polish #1 & #2 � (Novus, Inc., Minneapolis, MN)

� Mirror Glaze Plastic Polish (M.G. M10)

� (Mirror Bright Polish Co., Pasadena, CA)

DO NOT use abrasive or highly alkaline cleaners

NEVER scrape LEXAN™ with squeegees, razor blades or other sharp instruments

Benzene, gasoline, acetone or carbon tetrachloride should never be used

DO NOT clean LEXAN™ in hot sun or at elevated

temperatures

Page 33: I&O MANUAL 10-18-10

Page 29 October 2010

4.0 MAINTENANCE (continued)

4-1d. ACRYLIC (Plexiglas)

Cleaning Instructions

The Number 1 Problem with acrylic is the use of incorrect cleaners. Do not use cleaners containing ammonia. Cleaners such as Windex or 409 will harm your

new piece of acrylic. Use only products specifically recommended for cleaning acrylic such as Novus #1, or Brillianize, and a soft cloth. Never use a dry cloth

or your hand to clean your acrylic! This rubs the dirt and dust INTO the acrylic as much as it rubs it OFF. First, blow the dust or dirt off, or use water and a soft

cloth to float the dirt off. Then use a recommended cleaner to complete the job. Note: a mild solution of dish detergent and warm water takes off stubborn dirt easily without harming the acrylic if you've run out of Novus #1 or Brillianize.

4-1e. DuPont™ Corian®

Routine Care of Your Corian® Countertop

There are three types of Corian® countertop finishes: matte/satin, semi-gloss

and high-gloss*. Most countertops are finished with a matte/satin finish. All Corian® sinks have a matte/satin finish. (*Contact your local Corian® sales expert if you are uncertain what type of finish is on your countertop.)

A KEY TO KEEPING YOUR COUNTERTOPS LOOKING GOOD IS TO THOROUGHLY RINSE AND WIPE COMPLETELY DRY AFTER CLEANING

Preventing Heat Damage

While Corian® is heat resistant, as with all countertop materials, it is important

to minimize direct heat exposure to protect your surface and investment.

DO NOT PLACE HOT POTS, PANS, ETC. DIRECTLY ON THE COUNTERTOP

SURFACE.

Always use heat trivets or hot pads when placing hot objects on any surface. Always use a trivet under portable heat generating appliances such as a toaster

oven. Allow cookware to cool before placing it into a Corian® sink.

Page 34: I&O MANUAL 10-18-10

Page 30 October 2010

4.0 MAINTENANCE (Continued)

To enhance the gloss level on semi-gloss and high-gloss finishes, use a

countertop polish such as Countertop Magic®, Hope's Countertop Polish® or

Enhance Countertop Polish®.

Scotch Brite® is a registered trademark of 3M Company

Soft Scrub® is a registered trademark of The Dial Corporation

Countertop Magic® is a registered trademark of The Hope Co.

Enhance Countertop Polish® is a registered of Eastern Marble Co.

Cleaning All Finishes

Most dirt &

residue

Use soapy water, ammonia based cleaner (not window cleaner),

rinse and wipe completely dry. Commercially available solid surface

cleaners, such as Clean EnCounters® will also work well.

Preventing

hard water

marks

Rinse and wipe completely dry after cleaning; clean up spills before

they dry.

Removing

hard water

marks

Use a cleaner formulated for removing hard water marks such as

CLR or Lime-A-Way.

Difficult

residue

Spray residue with Deep Cleaner for DuPont Corian® from Stone

Care International. Follow instructions on the bottle. Wash area

with soapy water, rinse and wipe completely dry. If residue

persists, follow steps below for removing dulling film.

Disinfecting Occasionally, wipe surface with diluted household bleach (1 part

water/1 part bleach). Rinse top thoroughly with water and wipe

completely dry.

Avoid getting the bleach solution in your eyes or

bare skin. Always follow the bleach manufacturer's

safety instructions when working with bleach.

Page 35: I&O MANUAL 10-18-10

Page 31 October 2010

4.0 MAINTENANCE (Continued)

4-1f. CAESARSTONE

Its hard, nonporous surface makes it simple to clean. In most cases, soap and

water or a mild detergent is all that is required to maintain its luster. If necessary, a non-abrasive cleanser such as Soft Scrub Liquid Gel with Bleach or Comet Soft Cleanser Cream With Bleach can be used along with a non-scratch or

delicate scrub pad such as blue Scotch-Brite sponge. Adhered materials like food, gum, or nail polish can be scraped away with a plastic putty knife; any

marks left by the blade can be removed with Soft Scrub Liquid Gel and a blue Scotch-Brite pad. Thoroughly rinse the surface with clean water to remove residue.

While CaesarStone does not require sealants or waxes to maintain its luster,

occasional polishing with Soft Scrub Bleach Gel or Comet Gel will keep the quartz surfacing looking its best.

HONED finishes will require more daily maintenance than polished finishes. Since there is more exposed surface area with honed finishes, metal marks,

finger prints and other signs of daily living will show on honed material. Most of these marks can be easily removed with little effort and non-abrasive cleaning products such as Soft Scrub Liquid Gel. For tough stains, work the area with a

blue Scotch Brite pad.

4-1g. GRANITE

Soap and water will clean up most stains but leave a soap film behind over time

that the granite cleaner will easily remove.

i. Spray a light mist of stone cleaner over the area to be cleaned.

ii. Let the product sit for approximately 30 seconds.

iii. Scrub with a sponge.

iv. Buff the surface dry with a clean white cloth or paper towel.

Granite stains! Clean up spills promptly, before they soak into the granite and become permanent.

Granite can be sealed so it is maintenance free and you don’t have to wipe up

spills.

Page 36: I&O MANUAL 10-18-10

Page 32 October 2010

4.0 MAINTENANCE (Continued)

4-1h. RICHLITE

Richlite surface is a durable, attractive material designed to stay beautiful for

the lifetime of your kitchen, bath or office space. A simple wipe up with a damp

sponge on a regular basis will maintain its beauty. Alkaline soap such as regular

dish soap will gradually dull the surface. Howards’s Naturals Wood Cleaner and

Polish will lightly renew the luster if used on a regular basis. Richlite

recommends finishing the surface with Richlite Enhancer to provide a rich,

polished finish that requires minimum care.

Removing Stains

Generally speaking, Richlite resists stains quite well. As with most any material,

there is a potential for some staining. With stubborn stains, try a nonabrasive

household cleaner.

Repairing Scratches and Burn Marks

Richlite is extremely dense and durable. The material resists scratches and

burns but, like most surfaces, can potentially be damaged by cutting directly on

the surface or setting a hot frying pan on the surface. Richlite recommends the

use of cutting boards, hot pads and trivets to protect the surface from potential

damage.

Before refinishing their countertop, please seek the advice of the dealer or

fabricator who installed the counter. In most cases, it is preferable if the

installer refinishes the surface. Light scratch marks and burn marks can be

refinished using a Scotch-Brite® pad (#7447/Red Color). It is important to

note, the refinished area will noticeably lighten compared to the surrounding

surface area. Richlite surfaces are made of paper which, like wood, patinas – or

darkens – over time, especially in the lighter colors such as Baguette. The area

will eventually patina and match the remainder of the counter surrounding it. In

order to avoid affecting one spot, lightly refinish the entire section of the

counter.

• Scotch-Brite is a registered trademark of 3M Company

• Howards Naturals can be purchased at many paint stores nationally.

It is also available at: ww.howardnaturals.com/wood_cleaner_and_polish.asp

General Precautions

Richlite countertops are stain resistant to nearly all kitchen related substances

with the exception of some raw meat juice (such as liver), high-alkaline fruit or

vegetables (such as papaya and red beet), and high-alkaline soaps (such as

automatic dishwasher powder and oven cleaners) when left in contact for a

prolonged time.

Page 37: I&O MANUAL 10-18-10

Page 33 October 2010

4.0 MAINTENANCE (Continued)

The lighter colors in the Richlite color range will show stains more than the darker colors. Additionally, grout (which is a high alkaline product) will lighten darker-colored Richlite counters and darken the lighter tones. Cover the surface with a protective sheet when installing tile around countertop areas. Avoid using bleach products or abrasive powdered cleaners. It is good to avoid using the abrasive side of sponges as this may also scratch the surface of a Richlite countertop.

4-2. EVAPORATOR COIL (Always use a qualified technician/mechanic)

� Inspect coil every month

� Clean coil at least every three (3) months; more often if necessary

� Wash coil with warm water

4-3. CONDENSER COIL: (Always use a qualified technician/mechanic)

� Inspect coil every month

� Clean coil at least every three (3) months; more often if necessary

� Vacuum debris off the coil

� Use caution to avoid blowing debris into the surrounding environment

Do not use large quantities of water when washing

the coil on units with a condensate evaporator

Page 38: I&O MANUAL 10-18-10

Page 34 October 2010

THIS

PAGE

IS

INTENTIONLY

BLANK

Page 39: I&O MANUAL 10-18-10

Page 35 October 2010

5.0 WIRING DIAGRAMS

5-1. Refrigerated - 120V Remote Case with Microprocessor Controller

5-2. Refrigerated - 120V Self Contained Case with Microprocessor Control

Page 40: I&O MANUAL 10-18-10

Page 36 October 2010

5.0 WIRING DIAGRAMS (continued)

5-3. Refrigerated - 208-120V Self Contained Case with Microprocessor Control

NOTES:

� ** Power Contactor is required for condensing units > 16A

� Disconnect All power before servicing unit � The actual number of light fixtures and fan motors could vary

depending on actual design

� All wiring is to be done per NEC and local codes � Use copper conductors for power supply connections

OR

USE THIS DETAIL WHEN LPS IS

SEPATRATE FROM CONDENSING UNIT

USE THIS DETAIL WHEN LPS IS

INTEGRATED IN CONDENSING UNIT

Page 41: I&O MANUAL 10-18-10

Page 37 October 2010

5.0 WIRING DIAGRAMS (continued)

5-5. Heated – 208-120V 3Ø Case

5-4. Heated –208-120V 1Ø Case

Page 42: I&O MANUAL 10-18-10

Page 38 October 2010

5.0 WIRING DIAGRAMS (continued)

NOTES:

� ** Power Contactor is required for condensing units > 16A � Disconnect All power before servicing unit

� The actual number of light fixtures and fan motors could vary depending on actual design

� All wiring is to be done per NEC and local codes � Use copper conductors for power supply connections

5-6. Gelato - 120V Self Contained Case with Microprocessor Control

OR

USE THIS DETAIL WHEN LPS IS

SEPATRATE FROM CONDENSING

UNIT

USE THIS DETAIL WHEN LPS IS

INTEGRATED IN CONDENSING

UNIT

Page 43: I&O MANUAL 10-18-10

Page 39 October 2010

6-0 WARRANTIES AND WARRANTY PROCEDURES

6-1 WARRANTY PROCEDURE

In order for your Refcon warranty to be in full effect, the

following information must be completed and returned to Refcon within 10 days of start-up.

This form is in the back of this manual and also available online at our website:

www.refconcase.com

Page 44: I&O MANUAL 10-18-10

Page 40 October 2010

6-0 WARRANTIES AND WARRANTY PROCEDURES

WARRANTY PARTS and SERVICE PROCEDURE

In the unlikely event your Refcon case requires warranty service work, please follow the procedure listed below.

1. Contact Refcon at 201-750-5060, x-29 to verify that the factory warranty is in effect. You may wish to contact the dealer from which you purchased the equipment to see if the dealers provide their own warranties.

2. Customers are free to choose any competent refrigeration service company. The Yellow Pages or Internet may be good sources. You may wish to contact the service company who installed your equipment for follow-up service. Prior to any warranty service being performed, the technician must contact Refcon to obtain a work authorization number for the anticipated service. No payments will be made without this prior authorization.

3. Service contractor must contact Refcon Technical Service at 201-750-5060 X-29 and provide: • Display Model Number (located on the data plate of the case) • Display Serial Number (located on the data plate of the case) • Nature of the failure • Service Company information

4. A Work Authorization Number will be given to the contractor if the work is covered by the Optional One Year Labor Warranty*(see below). Note: Refcon does not authorize any warranty overtime labor.

5. Replacement parts identified as being required for the service by the contractor will be sent at no charge during the Parts Warranty**period.

6. Refcon may ask that certain original parts, replaced under warranty, be returned to Refcon. An invoice for replacements parts will be sent. After receipt of the parts replaced, a credit memo for the invoice will be issued.

7. Service contractor is to submit a service report, detailing the work done, and an invoice with Refcon’s work authorization number to Refcon for processing.

8. Warranty does not cover initial installation, start-up, normal adjustments, refrigerant recovery or repairs due to abuse, misapplication, improper installation, or any fragile items such as glass or granite.

* The Optional One Year Labor Warranty is available at an additional charge at the time of

initial purchase of equipment.

**The Parts Warranty period is any time within one year from the shipment date of the

equipment from the factory.

Refcon does not authorize any warranty overtime labor or

travel time to and from job site.

Page 45: I&O MANUAL 10-18-10

Page 41 October 2010

6-0 WARRANTIES AND WARRANTY PROCEDURES

6-2 WARRANTY POLICY

WARRANTYWARRANTYWARRANTYWARRANTY

Page 46: I&O MANUAL 10-18-10

Page 42 October 2010

THIS

PAGE

IS

INTENTIONLY

BLANK

Page 47: I&O MANUAL 10-18-10

Page 43 October 2010

7-0 WEBSITE

www.refconcase.com

7-1 CASE SPECIFICATIONS

Page 48: I&O MANUAL 10-18-10

Page 44 October 2010

7-0 WEBSITE

7-2 ON-LINE PARTS ORDERING

7-3 ON-LINE WARRANTY REGISTRATION

Page 49: I&O MANUAL 10-18-10

Page 45 October 2010

7-0 WEBSITE

7-4 CONTACT INFORMATION

Page 50: I&O MANUAL 10-18-10

Page 46 October 2010

THIS

PAGE

IS

INTENTIONLY

BLANK

Page 51: I&O MANUAL 10-18-10

Page 47 October 2010

REMOTE CONDENSING UNIT

START UP and WARRANTY REGISTRATION

If this form is not completed and returned to REFCON the standard warranty is not in effect.

FAX TO: (201)750-5066 Attn: WARRANTY

Job Name:______________________________________ Date:________

Job Address:__________________________________

Model # _______________________ S/N# ______________________

Installation Contractor ______________________

Address _____________________________ Town/City ___________________ Zip Code _________

Contact Name _________________________ Phone # _____________

REQUIRED START UP INFORMATION:

(1) Outdoor Ambient temp. ______ºF (2) Outdoor Relative Humidity ______% or wet bulb ______ ºF

(3) Indoor Ambient temp. ______ ºF (4) Indoor Relative humidity ______% or wet bulb ______ ºF

REFRIGERATION INFORMATION:

(1) Condensing Unit Model # ____________________

(2) Manufacturer________________________ (3) Condensing Unit S/N # ______________________

(4) Voltage __________ (5) Refrigerant Type ________

(6) Common Loop Suction Pressure ________ psi

(7) Liquid Line Temp. ______ ºF (8) Type of Loop ________

(9) Type of EPR Valve_______________ Model________________ Range _______________

(10) How is case controlled? ______________________

(11) Low pressure control Cut-in ______ psi diff. ______ psi

(12) Supply Air Set Point _____ ºF diff. ______ ºF (13) Defrost Termination Set Point _____ ºF

Readings after Refrigerated Case Stabilizes in Temperature:

(13) Superheat ___ ºF at evap. coil

(14) Suction pressure ______ psi (15) Discharge pressure ______ psi

(16) Discharge air temp. ____ ºF (17) Velocity _______FPM

(18) Top shelf temp. _____ ºF (19) E.P.R. Valve Setting _____ psi

E-mail: [email protected] Website:www.refconcase.com

Page 52: I&O MANUAL 10-18-10

Page 48 October 2010

REFCON, LLC

335 Chestnut Street

Norwood, NJ 07648

(201) 750-5060